Finding | |
|---|---|
| Title | No Full Flow Testing of PORV Air Supply Check Valves |
| Description | A finding of very low safety significance and an associated NCV of 10 CFR Part 50, Appendix B, Criterion XI, Test Control, was identified by the inspectors for the failure to assure that all testing required to demonstrate the check valves installed as part of a temporary modification for low temperature over pressure (LTOP) protection would perform satisfactory in service was identified and performed. Specifically, the licensee failed to verify the check valves would pass the necessary air flow to support the required number of valve strokes assumed in the LTOP analysis. The licensee performed a subsequent test and determined that the check valves would allow adequate air flow rate. The issue was entered into the CAP as CAP 1242980. The inspectors determined this finding was more than minor because, if left uncorrected, the failure to demonstrate that the check valves would perform satisfactorily in service could result in installing an inadequately designed LTOP system each refueling outage. This finding impacted the Barrier Integrity Cornerstone. The inspectors used IMC 0609, Appendix G, Shutdown Operations Significance Determination Process, and determined that the issue screened out in Phase 1 and did not require a quantitative assessment, because the failure to perform the test did not result in a non-compliance with the LTOP TSs as listed in the various Attachment 1 checklists. Therefore, the finding was of very low safety significance, Green. The inspectors did not identify a cross-cutting aspect associated with this finding because decisions regarding the check valve testing were made several years ago and were not reflective of current performance. |
| Site: | Prairie Island |
|---|---|
| Report | IR 05000282/2011003 Section 4OA5 |
| Date counted | Jun 30, 2011 (2011Q2) |
| Type: | NCV: Green |
| cornerstone | Barrier Integrity |
| Identified by: | NRC identified |
| Inspection Procedure: | |
| Inspectors (proximate) | J Jandovitz M Mitchell C Brown M Phalen K Stoedter D Betancourt J Corujo-Sandin E Sanchez N Feliz-Adorno S Lynch S Shah |
| INPO aspect | |
| ' | |
Finding - Prairie Island - IR 05000282/2011003 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Prairie Island) @ 2011Q2
Self-Identified List (Prairie Island)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||