05000282/FIN-2010006-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Fuel Oil Storage Design Did Not Support EDGs 7-Day Supply |
| Description | The inspectors identified a finding having very low safety significance and an associated NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for the licensees failure to ensure that the fuel oil storage capability for emergency diesel generators (EDGs) D5 and D6 maintained the minimum volume required to run under accident conditions for seven days as specified in Regulatory Guide 1.137 Fuel Oil Systems for Standby Diesel Generators. Specifically, with one tank out-of-service, as allowed per procedure, the licensee would not have enough fuel to meet the mission time for one diesel following a single failure of the opposite diesel during an accident conditions. This finding was entered into the licensees corrective action program and a Temporary Change Request was initiated by the licensee to update the procedure until all issues associated with EDGs fuel oil storage capabilities (i.e., common mode failure, single failure, etc.), are resolved
The inspectors determined that this finding was more than minor because it was associated with the Mitigating Systems cornerstone attribute of equipment performance and affected the cornerstone objective of ensuring availability of the EDG to respond to initiating events to prevent undesirable consequences. This finding was of very low safety significance (Green) because a single storage tank provided sufficient fuel for EDG operation under accident loads for a period greater than the 24-hour probabilistic risk assessment (PRA) mission time. This finding had a cross-cutting aspect in the area of Human Performance, Decision Making, because the licensee failed to thoroughly evaluate the impact of downgrading the interconnection between the tanks to non-safety-related and the scenarios and existing practices that it would affect. |
| Site: | Prairie Island |
|---|---|
| Report | IR 05000282/2010006 Section 1R21 |
| Date counted | Sep 30, 2010 (2010Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | J Chiloyan D Betancourt M Munir A Dahbur D Szwarc C Brown B Sherbin |
| CCA | H.14, Conservative Bias |
| INPO aspect | DM.2 |
| ' | |