| Title | Failure to Ensure Compliance with TS SR 3.8.1.10c |
| Description | The inspectors identified a finding of very low safety significance and an NCV of Technical Specification (TS) 3.8.1 in October 2010 due to the failure to demonstrate that the D2 EDG would energize the 12 battery charger within 60 seconds of an actual or simulated LOOP/LOCA event. Specifically, the licensee failed to comply with TS surveillance requirement 3.8.1.10c. Corrective actions for this issue included declaring the D2 EDG inoperable; requesting an exigent TS change from the NRC to address the issues associated with TS Surveillance Requirement 3.8.1.10c; receiving approval of the exigent TS change; and implementing actions to address a long-standing issue with the 12 battery charger. The inspectors determined that this issue was more than minor because, if left uncorrected, long-standing noncompliance with TS requirements would become a more significant safety concern. The inspectors completed a Phase 1 SDP evaluation and determined that this finding was of very low safety significance because it was not due to an EDG design deficiency; did not result in a loss of safety function for the Unit 1 EDGs; and did not screen as potentially risk significant due to a seismic, flooding or severe weather initiating event. No cross-cutting aspect was assigned to this finding because the decisions which led to the non-compliance were made several years ago and were not reflective of current performance. |
| Site: | Prairie Island |
|---|---|
| Report | IR 05000282/2010005 Section 1R15 |
| Date counted | Dec 31, 2010 (2010Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.15 |
| Inspectors (proximate) | C Brown D Mcneil J Dalzell J Giessner K Stoedter L Kozak P Zurawski R Lerch |
| INPO aspect | |
| ' | |
Finding - Prairie Island - IR 05000282/2010005 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Prairie Island) @ 2010Q4
Self-Identified List (Prairie Island)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||