| Title | Failure to Evaluate the Adequacy of Voltage for Safety-Related Equipment |
| Description | The inspectors identified a finding having very low safety significance and an associated NCV of 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Action, for the failure to consider design basis accident temperature and voltage variations when performing an operability evaluation of safety-related equipment with very low voltage margin. Specifically, during the 2010 CDBI self-assessment, a licensees reviewer identified concerns regarding an operability evaluation that failed to consider the design basis accident temperatures and voltage. Although the licensee placed this issue in their corrective action program, the licensee failed to assess operability. After identification by the team, the licensee determined the associated equipment were operable or operable but non-conforming
The inspectors determined that this finding was more than minor because it was associated with Barrier Integrity cornerstone attribute of design control and affected the cornerstone objective of providing reasonable assurance that physical design barriers protect the public from radionuclide releases caused by accidents or events. This finding was of very low safety significance (Green) because the finding was a not degradation of a boundary, was not an open pathway and did not impact the hydrogen igniters. This finding had a cross-cutting aspect in the area of problem identification and resolution in the component of self assessment because the 2010 CDBI self-assessment concerns were not evaluated and corrected. |
| Site: | Prairie Island |
|---|---|
| Report | IR 05000282/2010006 Section 1R21 |
| Date counted | Sep 30, 2010 (2010Q3) |
| Type: | NCV: Green |
| cornerstone | Barrier Integrity |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | J Chiloyan D Betancourt M Munir A Dahbur D Szwarc C Brown B Sherbin |
| CCA | P.6, Self-Assessment |
| INPO aspect | CL.2 |
| ' | |