Proposed Tech Specs Re Safety Limits & Limiting Safety Sys Settings
ML17229A183
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 12/20/1996
From:
FLORIDA POWER & LIGHT CO.
To:
Shared Package
ML17229A182 List:
References
NUDOCS 9612270074
Download: ML17229A183 (3)


Text

L-96-333 Attachment 3 ATTACHMENT 3 ST.LUCIE UNIT 1 MARKED-UP TECHNICAL SPECIFICATION PAGE Page,2-1 9612270074 96i220 VDR aDOCX OS000SS5 P PDR

~~I I 2.0 SAFETY LIMITS ANO LIMITING SAFETY SYSTEN SETTINGS 2.1 SAFETY LIMITS REACTOR CORE~gL.f I p$gE g as&2.1.1 The combfnatfon of THERMAL PNER, pressurfzer pressure, and maxf-axan cold leg coolant temperature shall not exceed the lfmfts shown on Ff gure 2.1-1.APPLICABILITY:

MODES 1 and 2.ACTION: Whenever the point defined by the combfnatfon of maxfnam cold leg tetnper-ature and THERMAL POWER has exceeded the appropriate pressurizer pressure line, be in HOT STANDBY within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.REACTOR COOLANT SYSTEM PRESSURE 2.1.2 The Reactor Coolant System pressure shall not exceed 2750 psfa.APPLICABILITY:

MODES 1, 2, 3, 4 and 5.ACTION: MODES 1 and 2 Whenever the Reactor Coolant System pressure has exceeded 2750 psfa, be in HOT STANDBY with the Reactor Coolant System pressure within its limit within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.MODES 3, 4 and 5 Whenever the Reactor Coolant System pressure has exceeded 2750 psfa, reduce the Reactor Coolant System pressure to within its limit within 5 minutes.Qt" L]=lE Amendment No.ST.LUCIE-UNIT 1 2-1 L-96-333 Enclosure ENCLOSURE Siemens Power Corporation-Nuclear Division Report EMF-96-176, Revision 1 St.Lucie Unit 1 Small Break LOCA Analysis with 30%Steam Generator Tube Plugging December 1996