CONTAINMENTSYSTEHSCONTAINMENTLEAKAGELIMITINGCONDITIONFOROPERATION3.6.1.2Containmentleakageratesshallbelimitedto:a.Anoverallintegratedleakagerateof:=l.<La,0.50percentbyweightofthecontainmentairper24hoursatP,(39.6psig),or2.<Lt,0.32percentbyweightofthecontainmentairper24hoursatareducedpressureofPt,(19.8psig).b.Acombinedleakagerateof<0.60LaforallpenetrationsandvalvessubjecttoTypeBandCtestsasidentifiedinTable3.6-1whenpressurizedtoPa.c.Acombinedleakagerateof<0.27LaforallpenetrationsidentifiedinTable3.6-1assecondarycontainmentbypassleakagepathswhenpressurizedtoPa.APPLICABILITY:NODES1,2,3and4.ACTION:Witheither(a)themeasuredoverallintegratedcontainmentleakagerateexceeding0.75Laor0.75Lt,asapplicable,or(b)withthemeasuredcombinedleakagerateforaTlpenetrationsandvalvessubjecttoTypesBandCtestsexceeding0.60La~or(c)withthecombinedbypassleakagerateexceeding0.27La,restoretheleakagerate(s)towithinthelimit(s)priortoincreasingtheReactorCoolantSystemtemperatureabove200'F.SURVEILLANCEREUIREMENTS4.6.1.2ThecontainmentleakageratesshallbedemonstratedatthefollowingtestscheduleandshallbedeterminedinconformancewiththecriteriaspecifiedinAppendixJof10CFR50usingthemethodsandprovisionsofANSIN45.4-1972:a.ThreeTypeAtests(OverallintegratedContainmentLeakageRate)shallbeconductedat40+10monthintervalsduringshutdownateitherPa(39.6psig)oratPt(19.8psig)duringeach10-yearST.LUCIE-UNIT13/46-24/18/80 CONTAINMENTSYSTBiSSUR'lEILLANCEREQUIRB1ENTSContinued)serviceperiod.Thethirdtestofeachsetshallbeconductedduringtheshutdownforthe10-yearplant.inserviceinspection..b.IfanyperiodicTypeAtestfailstomeeteither.75Lor.75L,thetestscheduleforsubsequentTypeAtestsshallbreviewedandapprovedbytheCommission.IftwoconsecutiveTypeAtestsfailtomeeteither.75Lor.75L,a=-TypeAtestshallbeperformdatleastevery18mont~isuntiltwocon-secutiveTypeAtestsmeteither.75Lor.75Latwhichtimetheabovetestschedulemayberesumed.c.TheaccuracyofeachTypeAtestshallbeverifiedbyasupplementaltestwhich:l.ConfirmstheaccuracyoftheTypeAtestbyverifyingthatthedifferencebetweensupplementalandTypeAtestdataiswithin0.25Lor0.25Lt,a2..HasadurationsufficienttoestablishaccuratelythechangeinleakagebetweentheTypeAtestandthesupplementaltestd.e.3.Requiresthequantityofgasinjectedintothcontainmentorbledfromthecontainmentduringthesupplementa'1testtobeequivalenttoatleast25percent,ofthetotalmeasuredleakagerateatP-(39.6psig)orPt(19.8psig).aTypeBand'CtestsshallbeconductedwithgasatP'39;6psig)atintervalsnogreaterthan24monthsexceptfortestsin-volvingairlocks..Thecombinedbypassleakagerateshallbedeterminedtobe<0.27LbyapplicableTypeBandCtestsatleastonceper24monthsexceptforpenetrationswhichare.notindividuallytestable;penetrationsnotindividuallytestableshallbedeterminedtohavenodetectableleakagewhentestedwithsoapbubbleswhilethecontainmentispressurizedtoP(39.6psig)duringeachTypeAtest.AirlocksshallbetestedanddemonstratedOPERABLEperSurveillanceRequirement4.6.1.3.ST.LUCIE-UNIT13/46-34/18/80 0V PLANTSYSTEHSSURVEILLANCEREUIREHENTSContinued)e.At.leastonceper18monthsby:l.'erifyingthatthepressuredropacrossthecombinedHEPAfiltersandcharcoaladsorberbanksis<4.15inchesHaterGaugewhileoperatingtheventilationsystema.taflowrate.of2000cfm+10/..A2.'erifyingthatonacontainmenti'solationsignalorchlorineaccidentdetectionsignal,thesystemautomaticallyisolatesthecontrolroomwithin35secondsandswi"tchesintoarecirculationmode.ofoperationwithflowthroughtheHEPAfiltersandcharcoaladsorberbanks.3.'eri,yingthatthesystemmaintainsthecontrolroomatapositivepressureof>1/8inchH.G.relativetotheoutsideatmosphereduringsystemoperationwith<450'cfmoutsideairintake.f.""Aftereachcompleteorpartialreplacementof.aHEPAfilterbankbyverifyingthattheHEPAfilterbanksremove>99iloftheDQPwhentheyaretestedin-p'laceinaccordancewithANSI.N510-1975whileoperatingtheventilationsystemataflowrateof2000cfm+10!..,-.'...~Afg.Aftereachcompleteorpartialreplacementofacharcoa1adsorberbankbyverifyingthatthcharcoaladsorbersremove>99;ofahalogenatedhydrocarbonrefrigranttestgaswhentheyaretestedin-placeinaccordancewithANSIN510-1975whileoperatingtheventilationsystemataflowrateof2000'fm+10/.ST.LUCIE-UNIT13/47-234/18/80 SAFETYEVALUATIOH0Re."St.LucieUnit.l;,'ocketNo50-335ProposedAmendmentContainment&ControlRoomLeakageI.IntroductionThisevaluationsupportsaproposalto(1)increasethecombinedleakagerateallowedforallpenetrationsidentifiedassecondarycontainmentby-passleakaqepaths,and(2)increasethelimitonoutsideairintakeintothecontrolroomduringtherecirculationmodeofoperation.Thesoughtafterbypassleakagerateof27'AwaspreviouslyevaluatedinAppendix6BoftheFSAR.Thereevaluationdiscussedhereinisbasedonamoreconser-vativecontainmentmodelingtechnique.Thecurrentlimitoncontrolroomoutsideairintakeisbasedontheoriginalcontrolroompost-LOCAhabit-abilityevaluationthatispresentedinFSARsection15.4.1.2.5(d).Theevaluationdidnottakecreditfortheoperationofthe"backfitted"IodineRemovalSystem(IRS)andShieldBuildingVentilationSystem(SBVS)heaters.ThereevaluationdiscussedbelowusesthesamecontrolroommodelsandassumptionspresentedintheFSARinadditiontotheoperationofthe"backfitted"systems.II.DiscussionTheSt.LucieUnit1calculationsestimatingwholebodyandthyroiddosesfromapostulatedlossofcoolantaccident(LOCA)havebeenrevised.Therevisedanalysisusesamoreconservativecontainmentreleasemodel.TheanalysiswaspreviouslypresentedinAppendix6BoftheFSAP,andwasbasedonasinglevolumewell-mixedcontainmentactivityreleasemodelaswellasthe"backfit",containmentbypassfractionof27K.ThedifferencebetweentheFSARanalysisandtheanalysisdescribedhereinisthatamoreconser-vativetwocompartmentcontainmentmodelisusedthattakesintoaccountthedifferenceiniodinescrubbingeffectivenessbetweentheregionsofthecon-tainmentthatreceiveordonotreceivespraycoverage.Thevolumeofthecontainmentatmospherethatissprayedisconservativelyassumedtobe86/.i'lixingisassumedtooccurbetweenthesprayedandunsprayedregionsatarateof4volumesofunsprayedregionperhour.TheonlyotherchangeinassumptionsfromthosepresentedinAppendix6BoftheFSARisthatittakes44minutesforthespraystoreducetheelementaliodineconcentrationinthecontainmentbytheallowablefactorof100ratherthanthepreviousperiodof28minutes.Theremovalofparticulateiodinebythespraysisterminatedat1hour.ThepHofthesodiumhydroxidesolutionatthespraynozzlewillbebetween8.5andll.TherevisedoffsiteLOCAdosesarepre-sentedinTablel.Althoughtherevisedthyroiddosesforboththeexclu-sionzoneboundaryandlowpopulationzonearesomewhathigherbecauseamoreconservativemodelwasused,theyarestillwellwithinthe300remlimitsetby10CFR100forthereactorsitingcriteria.IntheprocessofdevelopingrevisedoffsiteLOCAdosecalculations,itwasdeterminedthatTechnicalSpecificationleaktestingcriteriacouldbemadelessstringent.ThecurrentSpecificationsseta12"limitonunfiltered

,0SAFETYEVALUATION(Continued)0secondarycontainmentbypassleakageanda100CFHlimitonControlRoomin-leakage.TherevisedLOCAanalysisdiscussedabovejustifiesacontainmentbypassleakageofupto27%andacontrolroominleakageofupto450CFH.TheLOCAdosespresentedinTable1arebasedonabypassleakageof27'Aandthemoreconservativecontainmentmodel.AllotherFSARassumptionshavebeenretained,Therevised30daypost-LOCAcontrolroomdosesarepresentedinTable2andarecomparedtothosepresentedintheFSAR.Thecontrolroomdosemodelusedinthereelevationisidenticaltothemodeldescribedinchap-.ter15oftheFSAR.TheonlychangeinassumptionsisthattheIRSandSBVSheat"backfits"havebeenincorporatedandthecontainmentbypassleakagein-creasedto27~value.Controlroominleakageisconservativelylimitedto450CFH.Thismaximumvalueofinleakage,plustheControlRoomairconditioningSystem,assuresthattherelativehumidityoftheairattheinletofthecon-trolroom'scharcoalfiltersislessthan70/,Relativehumiditymustbemain-tainedbelowthisvalueinorderthattheassumedcharcoalefficienciespresen-tedonFSARpage15.4.1-20dcanbeobtained..Theeffectofapostulatedchlo-rinereleaseonthecontrolroomhabitabilitywasalsoreevaluated.Thechlorinereleaseevaluationillustratedavalueforinleakageof568CFtlwhichisabovethelimitationimposedbytherelativehumidityrequirements.III.ConclusionMehaveconcluded,basedontheconsiderationsdiscussedabove,that:(1)theamendmentdoesnotinvolveasignificantincreaseintheprobabilityorcon-sequencesofaccidentspreviouslyconsideredanddoesnotinvolveasignificantdecreaseinasafetymargin,(2)thereisreasonableassurancethatthehealthandsafetyofthepublicwillnotbeendangeredbyoperationintheproposedmanner,and(3)suchactivitieswillbeconductedincompliancewiththeCom-mission'sregulationsandtheissuanceofthisamendmentwillnotbeinimicaltothecommondefenseandsecurityortothehealthandsafetyofthepublic, TABLEIREEYALUATIONOFFSAROFFSITELOCADOSESFOR27'ASHIELDBUILDINGBYPASSLEAKAGE2HourThyroid-Doseat1555Meters(EZB)2HourMholeBodyDoseat1555fleters(EZB)30DayThyroidDoseat1609tIeters(LPZ)30Dayi<holeBodyDoseat1609Meters(LPZ)~FSAR66rem4rem150rem5.5rem*~ANENDt1ENT75rem4rem167rem6rem*PostiodineremovalsystemsbackfitcaseperFSARAppendix6Batpage68-17.**PostIodineremovalsystemsbackfitcaseperFSARAppendix6Bwithaddition-alcalculationalconservatismsasnotedintext.

TABLEIIREEVALUATIONOFFSARCONTROLROOMLOCADOSESFORTHEPOSTIODINEREMOVAL'YSTEMSBACKFI'TCASELIITH450CFMINLEAKAGEControlRoomThyroidDoseControlRoom(!holeBodyDoseControlRoomSkinDose"FSAR'0rem1.7rem17.8rem**At1EIIDMENT12.5rem3.0rem27.0rem*FSARcaseatpage15.4.1-20dwithnocreditforiodineremovalsystembackfitsand100CFMcontrolroominleakage.~*Postiodineremovalsystemsbackfitcasewithadditionalcalculationalconservatismsasnotedintextand450CFMcontrolroominleakage.

STATEOFFLORIDA))COUNTYOFDADE)ssRobertE.Uhrig,beingfirstdulysworn,deposesandsays:ThatheisaVicePresidentofFlorid'aPower5LightCompany,theLicenseeherein;Thathehasexecutedtheforegoingdocument;thatthestate-mentsmadeinthissaiddocumentaretrueandcorrecttothebestofhisknowledge,information,andbelief,andthatheisauthorizedtoexecutethedocument-onbehalfofsaidLicensee.RobertE.Uhrig~SCIBQOrASubscribedandsworntobeforemethistil~NOTARYPUBLX,inandforthecountyofDade,StateofFloridaNotaryPubgc,StateotFloridaatLargoMyCommis"'onExpiresOctober30,>>1983loryCOmmiSSiOneXpireS:~endedtbruMaynardEondingAgency kg"w.PIIQY(