LER#78-016/03L-0 on 781109:during Mode 3 Oper,Emergency Diesel Generator B Tripped from 100% Load.Caused by Damage to Rod & Main Bearings,Crankshaft & Pistons,Perhaps Due to Loose Baseplate Mounting Screw
ML20064J174
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 12/07/1978
From: Shively C
ARKANSAS POWER & LIGHT CO.
To:
Shared Package
ML20064J170 List:
References
LER-78-016-03L, LER-78-16-3L, NUDOCS 7812290164