LER 79-010/03X-1 on 790223:diesel Essential Svc Water Check Valves 1-ESW-111 & 1-ESW-114 Not Functioning Properly.Caused by Excessive Wear at Split Disc Hinge Points.Discs Replaced
ML17317B171
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 05/07/1979
From: Michael Brown
INDIANA MICHIGAN POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML17317B170 List:
References
LER-79-010-03X, LER-79-10-3X, NUDOCS 7905110124