LER 90-002-00:on 900108,two MSIVs Exhibited Closing Time in Excess of Tech Spec 3.7.1.5 Limit of 5 S.On 900109 & 10, Confirmed That Excessive Condensation Collected on Vent Side.Caused by Inadequate insulation.W/900209 Ltr
ML17328A584
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 02/09/1990
From: Blind A, Droste J
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
LER-90-002, LER-90-2, NUDOCS 9002280017
Download: ML17328A584 (12)