ML17340A906

From kanterella
Revision as of 10:58, 22 October 2019 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Proposed Tech Specs 6.13 Re Environ Qualifications,Sys Integrity,Iodine Monitoring & Backup Methods for Determining Subcooling Margin
ML17340A906
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 03/10/1981
From:
FLORIDA POWER & LIGHT CO.
To:
Shared Package
ML17340A905 List:
References
NUDOCS 8103310380
Download: ML17340A906 (2)


Text

6.13 ENVIRONMENTAL UALIFICATIONS 6.13.1'y no later than June 30, 1982 all safety-related electrical equipment in the facility shall be qualified in accordance with the provisions of: Division of Operating Reactors "Guidelines for Evaluating Environmental Qualification of Class lE Electrical Equipment in Operating Reactors" (DOR Guidelines): or, NUREG-0588 "Interim Staff Position on Environmental Qualifcation of Safety-Related Electrical Equipment," December 1979. Copies of these documents are attached to the Order of Modification of License Nos.

DPR-31 and DPR-41 dated October 24, 1980.

6. 13. 2 By no later than December 1, 1980, complete and auditible records must be available and maintained at a central location which describe the environmental qualification methods used for all safety-related electrical equipment in sufficient detail to document the degree of compliance with the DOR Guidelines or NUREG-0588. Thereafter, such records should be updated and maintained current as equipment is replaced, further tested, or otherwise further qualified.

6.14 SYSTEMS INTEGRITY The licensee shall implement a program to reduce leakage from systems outside containment that would or could contain highly radioactive fluids during a serious transient or accident to as low as practical levels. This program shall include the following:

1. Provisions establishing preventative maintenance and periodic visual inspection requirements, and
2. Integrated leak test requirements for each system at a frequency not to exceed refueling cycle intervals.
6. 15 IODINE MONITORING The licensee shall implement a program which will ensure the capability to accurately determine the airborne iodine concentration in vital areas under accident conditions. This program shall include the following:
1. Training of personnel
2. Procedures for monitoring, and
3. Provisions for maintenance of sampling and analysis equipment.

6.16 BACKUP METHODS FOR DETERMINING SUBCOOLING MARGIN The licensee shall implement a program which will ensure the capability to accurately monitor the Reactor Coolant System subcooling margin. This program shall include the following:

1. Training of personnel, and
2. Procedures for monitoring.

6-30

>108 ~y 0 P~ 3/10/81