ML17354A374

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs,Modifying TSs to Change SR for TS 4.4.10 Re Reactor Coolant Pump Flywheel Insp
ML17354A374
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 12/17/1996
From:
FLORIDA POWER & LIGHT CO.
To:
Shared Package
ML17354A373 List:
References
NUDOCS 9612240269
Download: ML17354A374 (2)


Text

REACTOR COOLANT SYSTEM 3/4.4. 10 STRUCTURAL INTEGRITY LIMITING CONDITION FOR OPERATION 3.4.10 The structural integrity of ASME Code Class 1,

2 and 3 components shall be maintained in accordance with Specification 4.4. 10.

APPLICABILITY:

Al 1 MODES ACTION:

C.

With the structural integrity of any ASME Code Class 1 component(s) not conforming to the above requirements, restore the structural integrity of the affected component(s) to within its limit or isolate the affected component(s) prior to increasing the Reactor Coolant System temperature more than 50'F above the minimum temperature required by NDT considerations.

With the structural integrity of any ASME Code Class 2 component(s) not conforming to the above requirements; restore the structural integrity of the affected component(s) to within its limit or isolate the affected component(s) prior to increasing the Reactor Coolant System temperature above 200'F.

With the structural integrity of any ASME Code Class 3 component(s) not conforming to the above requirements, restore the structural integrity of the affected component(s) to within its limit or isolate the affected component(s) from service.

SURVEILLANCE RE UIREMENTS

4. 4. 10 iti to e re ire ts Spe 'ca 4..5, ch ac c

p p f he sh be 'e d pe he corn dat's Re ~y o ti C.4 of egu ory uid

. 14, evis n

1 ug 19 In addition to the requirements of Specification 4.0.5, each reactor coolant pump flywheel shall be inspected at least once every 10 years, by either conducting an in-place ultrasonic examination over the volume from the inner bore of the flywheel to the circle of one-half the outer

radius, or conduct a surface examination (magnetic particle and/or liquid penetrant) of exposed surfaces of the dissassembled flywheel.

TURKEY POINT - UNITS 3 8c 4 3/4 4-38 AMENDMENT NOS. 137AND 132 965,2240269 96i2i7 PDR ADQCK 05000250 P

PDR

'4

~

~

4 I

t