Semantic search
Jump to navigation
Jump to search
Issue date | Title | Topic | |
---|---|---|---|
ML19296A704 | 8 February 1980 | LER 80-003/03L-0:on 800110,repairs to Number 21 Diesel Generator Jacket Coolant Sys Required Diesel Be Out of Svc. Caused by Leaking Gasket on Jacket Cooling Water Discharge Header.Leak Located & Repaired | |
ML19296C253 | 12 February 1980 | LER 80-007/01T-0:on 800129,during Core Flush W/Rcs at 258 Psig,Relief Valve RC-404-ERV Opened.Apparently Caused by Spurious High Pressure Signal from Transmitter PT-103-1 When Technician Removed Cover of Transmitter During Review | |
ML19296C829 | 27 February 1980 | LER 80-009/03L-0:on 800201,during Surveillance Testing, Discovered Hose for One of Two Containment Elevator Hose Stations Missing.Caused by Work Group Using Fire Sys for Cleaning Purposes on Elevation of Containment | |
ML19296D117 | 19 February 1980 | LER 80-004/03L-0:on 800121,during Steady State Operation, Received Indication of Several Spurious Loss of Load Trips on Channel B.Cause of Event Unknown.Troubleshooting Revealed Electrical Noise on Input Leads | |
ML19296D129 | 22 February 1980 | LER 80-005/03L-0:on 800122,five Channel B Trip Units Were Bypassed Due to Spurious High Power Levels.Caused by Noise from Excore Nuclear Instrument Upper Subchannel Detector. Troubleshooting Planned for Next Cold Shutdown | |
ML19296D134 | 22 February 1980 | LER 80-006/03L-0:on 800126,during Steady State Operation, Reactor Protective Sys Channel a High Power,Low Flow,Axial Flux Offset & Thermal Margin/Low Pressure Trip Units Bypassed for Corrective Maint.Meter Input Jacks Cleaned | |
ML19296D306 | 25 February 1980 | LER 80-008/03L-0:on 800126,while Cooling Down for Scheduled Outage,Survey Technician Discovered Steam Blowing from 11A Reactor Coolant Pump.Sensing Line lPDT-123A Had through-wall Leak.Caused by Friction of Sensing Line W/Another Pipe | Through-Wall Leak |
ML19296D522 | 26 February 1980 | Notifies That LER Number 50-317/79-78 Was Not Used for 1979 | |
ML19305B325 | 12 March 1980 | LER 80-011/01T-0:on 800227,while Testing Diesel Generator 21,unit Failed to Reach Rated Speed in 10-s or Less.Caused by Slow Response of Diesel Generator Governor.Governor Replaced & Will Be Inspected & Overhauled by Manufacturer | |
ML19305C368 | 19 March 1980 | LER 80-012/03L-0:on 800219,during Routine Surveillance,Small Leak Discovered on Charging Pump Common Suction Header Relief Valve.Caused by Vibration Induced Metal Fatigue in heat-affected Zone of Welded Penetration in Header | |
ML19305D759 | 10 April 1980 | LER 80-017/03L-0:on 800316,saltwater Svc Water Heat Exchanger 22 Was Taken Out of Svc.Caused by Need to Repair Tube Leak.Tube Leak Found & Plugged | |
ML19305D850 | 10 April 1980 | LER 80-014/03L-0:on 800310,during Surveillance Testing, Reactor Core Drain Tank & Quench Tank Oxygen Sample Valves Failed to Shut on Safety Injection Actuation Signal.Caused by Corrosion on Output Relay Terminals | |
ML19305D859 | 10 April 1980 | LER 80-018/03L-0:on 800311,during Routine Insp Tour,Watch Stander Noticed Leak Weld on 23 Charging Pump Suction Relief Valve Causing Degradation of Sys Designed to Contain Radioactive Fluid.Caused by vibration-induced Metal Fatigue | |
ML19305E797 | 16 May 1980 | LER 80-026/03L-0:on 800428,pressurizer Level Control Channels LT-110X & LT-110Y Were Removed from Svc After Erratic Changes in Pressurizer Level Occurred.Caused by Leaking Drain Valves in Transmitter 2-LT-110Y.Valves Shut | |
ML19305E820 | 16 May 1980 | LER 80-023/03L-0:on 800416,while 21 Diesel Generator Was Being Taken Off 24 4 Kv Bus Following Test,Two 15 Vdc Power Supplies Had No Output.Caused by Tripped Overvoltage Protection Modules | |
ML19305E875 | 16 May 1980 | LER 80-025/03L-0:on 800428,during Steady State Operation, Channel a Trip Functions Were Bypassed in Accordance W/Tech Specs.Bypass Necessary to Determine Cause of Erratic Channel a Computer Flow Alarms.Caused by Defective Thermocouple | |
ML19309A796 | 25 March 1980 | LER 80-001/03L-0:on 800225,although Low Pressure Safety Injection Pump 21 Was Placed Out of Svc for Maint, Containment Spray Pump 21 Was Disassembled.Caused by Verbal Communication Error | |
ML19309A809 | 28 March 1980 | LER 80-016/03L-0:on 800303,emergency Diesel Generator 21 Was Placed Out of Svc After It Failed to Reach Rated Speed During Start Test.Caused by Diesel Generator Governor Slow Response.Governor Replaced,All Governors Inspected | |
ML19309A822 | 25 March 1980 | LER 80-019/02L-0:on 800312,while Performing QC Insp,Cable A2Y0929P Was Found Incorrectly Routed,Which Violated Cable Separation Criteria.Caused by Personnel Not Following Designed Routing of Cable.Temporary Cable Installed | |
ML19309A829 | 25 March 1980 | LER 80-015/03L-0:on 800227,during Maint,Control Element Assembly 44 Dropped Into Core.Caused by Electrician Accidentally Grounding Prime 15 Volt Power Supply.Faulty Backup Power Supply Was Changed | |
ML19309A866 | 25 March 1980 | LER 80-013/03L-0:on 800225,while Performing Surveillance Test,Channel D Containment High Pressure Trip Setpoint Was Less Conservative than Value Given in Tech Specs.Caused by Failed Signal Isolator 1-E/E-5313D | |
ML19309A873 | 24 March 1980 | LER 80-010/03L-0:on 800224,during Surveillance Testing, Control Element Assemblies 31 & 34 Dropped Into Core.Caused by Fault in Timer Module.Module Replaced | |
ML19309C350 | 2 April 1980 | LER 80-013/03L-0:on 800303,channel Zf Pressure Input Signal for Steam Generator Isolation 22 Was Bypassed.Caused by Signal Isolater 2-E/E-1023C Being Out of Calibr Due to Nonlinear Response | |
ML19309C370 | 3 April 1980 | LER 80-002/04T-0:on 800322,instantaneous Hourly Average for Condenser Temp Rise Observed in Excess of Tech Spec Limit. Caused by Operator Inattention to Temp Rise Across Condenser & Environ Conditions | |
ML19309E548 | 17 April 1980 | LER 80-015/03L-0:on 800317,steam Generator Auxiliary Feed Pump 11 Was Taken Out of Operation.Caused by Sightglass Being Broken by Operator Taking Oil Sample for Analysis. Broken Glass Replaced | |
ML19309E626 | 16 April 1980 | LER 80-021/04T-0:on 800404,during Preventive Maint for Draining Condensate from Fuel Oil Storage Tank,Operator Drained Oil Instead of Water.Caused by Operator Inability to Discern Difference Between Oil & Water Through Bullseye | |
ML19309E664 | 18 April 1980 | LER 80-021/03L-0:on 800318,during Performance of Surveillance Test 23,saltwater Pump Did Not Start Upon Receipt of Safety Actuation Signal.Caused by Faulty Pin. Pin Replaced | |
ML19309F363 | 25 April 1980 | Updated LER 79-001/03X-1:on 790106,RCS Had Unidentified Leakage of 1.546 Gpm,Exceeding Tech Spec.Caused by Cracked Weld Located on Socket Weld Downstream of Second Isolation Valve.Weld Repaired | |
ML19309F377 | 25 April 1980 | LER 80-005/03L-0:on 800325,during Normal Operation,Control Room Air Conditioning Unit 12 Tripped.Caused by Failure of Diaphragm on Unipressure Valve.Valve Replaced & Unit Returned to Svc | |
ML19309F384 | 25 April 1980 | LER 80-016/03L-0:on 800325,during Surveillance Testing, Channel a Wide Range Nuclear Instrument Did Not Respond in Calibr Mode.Apparently Caused by Failure of Channel Preamplifier.Power Supply Replaced W/Spare | |
ML19309F400 | 25 April 1980 | Updated LER 79-003/01X-2:on 790120,reactor Coolant Pump 22A Lower Seal Temp Alarm Activated & 2 Gpm Increase in Leak Rate Noted.Reactor Manually Tripped.Caused by Cracked Weld on Seal Pressure Sensing Line.Seal Assembly Replaced | |
ML19309F418 | 25 April 1980 | Updated LER 79-052/03X-1:on 790928,containment Gaseous & Particulate Radioactivity Monitoring Sys Failed Due to Loss of Sampling Pump.Caused by Normal end-of-life Failure of Graphite Particles Depositing on Bearings | |
ML19309F423 | 25 April 1980 | Updated LER 80-011/03X-1:on 800208,w/RCS at 130 Degrees & 250 Psia,Shutdown Cooling Suction Header Relief Lifted & Failed to Reset.Caused by Personnel Error.Valve Reset | |
ML19309F449 | 25 April 1980 | LER 80-019/03L-0:on 800327,during Normal Operation,Channel B Loss of Load Trip Occurred Intermittently.Caused by Auxiliary Master Trip Relay end-of-life Type Failure | |
ML19309F469 | 25 April 1980 | LER 80-022/01T-0:on 800415,util Informed of Possible Deficiency in FSAR Section 14.3,boron Dilution Incident,For Case When RCS Is Drained to Hot Leg w/1% Shutdown Margin. Cause Not Stated.Procedures Changed | Shutdown Margin |
ML19309F490 | 25 April 1980 | LER 80-017/03L-0:on 800326,results of Surveillance Test Indicated That ECCS Exhaust Filter Train Charcoal Did Not Demonstrate Removal Efficiency of 90% or Higher for Radioactive Methyl Iodide.Caused by Age of Filters | |
ML19309G422 | 30 April 1980 | LER 80-018/03L-0:on 800401,Number 11 Control Room Air Conditioning Unit Taken Out of Operation for Maint.Caused by Need to Calibr Outside Air Temp Transmitter 0-TT-5350. Transmitter Calibr & Placed Back in Svc | |
ML19309G436 | 30 April 1980 | Updated LER 80-013/03X-1:on 800225,during Surveillance Test, Channel D Containment High Pressure Setpoint Less Conservative than Tech Specs.Caused by Failed Signal Isolator 1-E/E-5313D.Instrument Returned for Repair | |
ML19309G445 | 30 April 1980 | LER 80-022/03L-0:on 800412,charging Pump 23 Removed from Svc to Repair Weld on Suction Relief Valve.Leak Caused by Vibration Induced Metal Fatigue in Heat Affected Zone of Weld.Leak Repaired & Mods Approved for Charging Pumps | |
ML19312E384 | 2 June 1980 | LER 80-027/03L-0:on 800506,during Performance of Surveillance Testing,Discovered Channel B Axial Flux Offset Not Indicating Properly.Caused by Dirty Connector on Deviation Card A-5.Connector Cleaned | |
ML19312E503 | 30 May 1980 | LER 80-024/03L:on 800430,while Making Containment Insp, Discovered Cracked Weld on 11B Reactor Coolant Pump Control Bleedoff Line.Caused by Metal Fatigue Induced by Vibration. Pipe Replaced & Weld Repair Performed | |
ML19312E511 | 2 June 1980 | LER 80-028/03L-0:on 800512,during Steady State Operation, Discovered Plant Computer Had Failed.Caused by I/O Power Failure Due to Generation of Noise Spike | |
ML19318A091 | 13 June 1980 | LER 80-028/03L-0:on 800515,during Performance of Routine Test,Diesel Generator 12 Failed to Reach Rated Speed in Less than 10-s Until Third Attempt.Caused by Intermittent Female Pin & Crack in Bakelite Spacer of Anphenol Connector | |
ML19318A124 | 13 June 1980 | LER 80-031/03L-0:on 800522,containment Gaseous & Particulate Radiation Monitors Failed.Caused by Electrician Accidently Grounding Motor Phase,Causing Pumps to Trip.Control Circuit Failed Due to Armature Not Being Replaced in Solenoid Valve | |
ML19318A131 | 13 June 1980 | LER 80-029/03L-0:on 800515,during Routine Surveillance Test, Reactor Coolant Hot Leg Sample Valve Indicated Intermediate Position.Valve Position Could Not Be Verified.Cause Not Determined | |
ML19318A148 | 13 June 1980 | LER 80-030/03L-0:on 800517,containment Gaseous & Particulate Monitors Failed Due to Ground in Instrument Control Power. Caused by Water in Plant Page Unit.Monitor Pumps Bridged to Keep Pumps Running While Trouble Shooting Continued | |
ML19321A759 | 18 July 1980 | LER 80-030/03L-0:on 800618,primary Sample Valve 1.CV-5467 Indicated Intermediate Position & Fully Shut Position Could Not Be Verified.Cause Cannot Be Determined by Remote Means. Corrective Action to Be Performed During Shutdown | |
ML19322A075 | 22 December 1978 | LER 78-057/04T-0 on 781216:during Normal Operation While Regenerating 11 make-up Water Demineralizers,Approximately 172 Gal of Caustic Solution Were Discharged Via Outfall 001. Caused by Inadvertent Operator Action | |
ML19323A095 | 14 April 1980 | LER 80-020/03L-0:on 800314,while Operating at 98% Power,Fire Marshall Discovered Fire Barrier Penetration Between Cable Spreading Room & Turbine Bldg Not Sealed W/Flamastic Fire Retardant Matl.Caused by Inaccessible Location | Fire Barrier Fire Protection Program Fire Watch |
ML19323C016 | 7 May 1980 | LER 80-025/04T-0:on 800307,environ Samples Collected & Analyzed in Accordance W/Ets,Confirmed Measured Levels of Radioactivity in Excess of Ten Times Background Value.Caused by Use of More Sensitive Background Value |