ML17317B374

From kanterella
Revision as of 05:21, 24 October 2019 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Jump to navigation Jump to search
LER 79-022/03L-0 on 790706:bistable 2PB-934B Tripped at Value Exceeding Tech Spec Limit by 0.104 Psi During Surveillance Test on Containment Pressure Protection.Caused by Drifting of Bistable Trip Set Point.Bistable Replaced
ML17317B374
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 07/25/1979
From: Rischling J
INDIANA MICHIGAN POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML17317B373 List:
References
LER-79-022-03L-01, LER-79-22-3L-1, NUDOCS 7907300337
Download: ML17317B374 (4)


Text