{{#Wiki_filter:}}
{{#Wiki_filter:TABLE 4.8-2 BATTERY SURVEILLANCE RE UIREMENTS CATEGORY A (1)CATEGORY B (2)PARAMETER LIMITS FOR EACH designated pilot cell LIMITS FOR EACH connected cell ALLOWABLE (3)value for connected cell Electrolyte Level Greater than minimum level indication mark, and less than 4 inch above maximum level indication mark Greater than minimum level indication mark, and less than 4 inch above maximum level indication mark Above top of plates and not overflowing Float Voltage Greater than or equal to 2.13 volts Greater than or equal to 2.13 volts (6)Greater than or equal to 2.07 volts Specific Gravity (4)Greater than or equal to 1.200 (5)Greater than or equal to 1.195 Average of all connected cells greater than 1.205 Not more than 0.020 below the average of all connected cells Average of all connected cells greater than or equal to 1.195 (5)TABLE NOTATIONS (2)(3)(4)(5)(6)For any Category A parameter(s) outside the limit(s)shown, the battery may be considered OPERABLE provided that within 24 hours all the Category B measurements are taken and found to be within their allowable values, and equalizing charge is started.All Category A and B parameter(s) must be restored to within limits within the next 6 days.For any Category B parameter(s) outside the limit(s)shown, the battery may be considered OPERABLE provided that the Category B parameters are within their allowable values, and equalizing charge is started.All Category B parameter(s) must be restored to within limits within 7 days.Any Category B parameter not within its allowable value indicates an inoperable battery.Corrected for electrolyte temperature and level.Or battery charging current is less than 2 amps when on charge.Corrected for average electrolyte temperature.
803i7 eaos>>Docs, o oooo 8~oooo>>p99.Amendment Nos.and 0 ,~~~}}

Revision as of 08:38, 14 September 2018

Revised Proposed Tech Spec Table 4.8-2, Battery Surveillance Requirements.
ML17347A698
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 03/17/1988
From:
FLORIDA POWER & LIGHT CO.
To:
Shared Package
ML17347A697 List:
References
NUDOCS 8803230055
Download: ML17347A698 (2)


Text

TABLE 4.8-2 BATTERY SURVEILLANCE RE UIREMENTS CATEGORY A (1)CATEGORY B (2)PARAMETER LIMITS FOR EACH designated pilot cell LIMITS FOR EACH connected cell ALLOWABLE (3)value for connected cell Electrolyte Level Greater than minimum level indication mark, and less than 4 inch above maximum level indication mark Greater than minimum level indication mark, and less than 4 inch above maximum level indication mark Above top of plates and not overflowing Float Voltage Greater than or equal to 2.13 volts Greater than or equal to 2.13 volts (6)Greater than or equal to 2.07 volts Specific Gravity (4)Greater than or equal to 1.200 (5)Greater than or equal to 1.195 Average of all connected cells greater than 1.205 Not more than 0.020 below the average of all connected cells Average of all connected cells greater than or equal to 1.195 (5)TABLE NOTATIONS (2)(3)(4)(5)(6)For any Category A parameter(s) outside the limit(s)shown, the battery may be considered OPERABLE provided that within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> all the Category B measurements are taken and found to be within their allowable values, and equalizing charge is started.All Category A and B parameter(s) must be restored to within limits within the next 6 days.For any Category B parameter(s) outside the limit(s)shown, the battery may be considered OPERABLE provided that the Category B parameters are within their allowable values, and equalizing charge is started.All Category B parameter(s) must be restored to within limits within 7 days.Any Category B parameter not within its allowable value indicates an inoperable battery.Corrected for electrolyte temperature and level.Or battery charging current is less than 2 amps when on charge.Corrected for average electrolyte temperature.

803i7 eaos>>Docs, o oooo 8~oooo>>p99.Amendment Nos.and 0 ,~~~