ML20054D275: Difference between revisions

From kanterella
Jump to navigation Jump to search
(StriderTol Bot insert)
 
(StriderTol Bot change)
 
Line 12: Line 12:
| case reference number = CON-NRC-82-57
| case reference number = CON-NRC-82-57
| document report number = NUDOCS 8204220508
| document report number = NUDOCS 8204220508
| document type = REPORTABLE OCCURRENCE REPORT (SEE ALSO AO,LER), TEXT-SAFETY REPORT
| document type = REPORTABLE OCCURRENCE REPORT (SEE ALSO AO LER), TEXT-SAFETY REPORT
| page count = 1
| page count = 1
}}
}}

Latest revision as of 14:59, 15 March 2020

RO Re Failure of Control Room Area Monitor (Channel R-1) of Radiation Monitoring Sys & Immediate & long-term Corrective Actions.Portable Radiation Monitor Placed in Control Room. Monthly Testing Performed
ML20054D275
Person / Time
Site: Kewaunee Dominion icon.png
Issue date: 04/15/1982
From: Mathews E
WISCONSIN PUBLIC SERVICE CORP.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
CON-NRC-82-57 NUDOCS 8204220508
Download: ML20054D275 (1)


Text

NRC-82-59 WISCONSIN P U B LIC S ERVICE CORPORATIO N P.O. Box 1200, Green Bay, Wisconsin 54305

,,c.P_R_INCIPAL STA L V M k_((2%TS 352 __ O. I 3/D l h s.o

, ,,g I 4- ~ L DTI April 55, 1982 DFP/4E File jv (Te Mr. J. G. Keppler, Reg Adm Office of Inspection & Enforcement m Region III 4 g U. S. Nuclear Regulatory Commission 799 Roosevelt Road &s 1 Glen Ellyn, IL 60137 , NECElVED:

~

Dear Sir:

APR 22198A -

a smst ra;uist numer DEasE BWiouf M ,

Docket 50-305 \ T100 /

Operating License DPR-43 Kewaunee Nuclear Power Plant 'D' Radiation Monitoring System - R-1 Failure This is to inform you of the failure of the Control Room Area Monitor (Channel R-1) of our radiation monitoring system and our immediate 'and long-term corrective actions. We consider the equipment failure significant, however, it is not reportable per Technical Specifications.

Upon indication of Channel R-1 failure, the Operations Staf f placed a portable radiation monitor in service in the Control Room. A check of this monitor was performed daily. Monthly testing was not performed as required by Technical Specifications (Table 4.1-1 Item 19) since no alarms were available on the portable instrument to test.

Replacement parts for R-1 were ordered and delivery is expected within six to nine months. Due to the long delivery time, an off-the-shelf area monitor (Dosimeter Corporation AM-2) with visibic and audible alarms was purchased, i calibrated, and placed in the Control Room. This monitor will be checked daily and tested monthly in accordance with Technical Specifications Table 4.1-1 until R-1 is repaired and placed in service.

l l Very truly yours ,

$.k. Yo.u W E. R. Mathews, Senior Vice President Power Supply and Engineering d3:

snf Z~~E ,7 2, cc - Mr. Robert Nelson, US NRC (ip 8204220508 920415 gDRADOCK05000 gpgig g ,