ML20203F412: Difference between revisions

From kanterella
Jump to navigation Jump to search
(StriderTol Bot insert)
 
(StriderTol Bot change)
 
Line 17: Line 17:


=Text=
=Text=
{{#Wiki_filter:}}
{{#Wiki_filter:p-r APPENDIX A NOTICE OF VIOLATION Philadelphia Electric Company                        Docket No. 50-277 Peach Bottom Units 2 and 3                                        50-278 License No.DPR-44 DPR-56 As a result of the inspection conducted on May 10 - June 17,1986, and in accordance with the NRC Enforcement Policy (10 CFR 2,-Appendix C) the following violation was identified:
10 CFR 50, Appendix B, Criterion XVI and the Peach Bottom Atomic Power Station Quality Assurance Plan, Volume III, paragraphs PR16.1 and S016.1, require measures to be established to assure that conditions adverse to quality are promptly identified and corrected.
Contrary to the above, on May 16, 1986, the Unit 2 and 3 safety related 4KV/480V gas filled and sealed emergency load center transformers were determined to be in a potentially degraded condition in that gas pressure was_ low in transformers E-234, E-434, E-334, E-424, E-13A, E-23A, and E-43A.
The degraded condition was not identified nor corrected.
This is a Severity Level IV Violation (Supplement 1) applicable to DPR-44 and DPR-56.
8607310062 860725 PDR  ADOCK 05000277 G                  PDR OFFICIAL RECORD COPY    CIR PB 86-09/12 - 0004.0.0 07/15/86
                                                                                      ..- .. __.}}

Latest revision as of 20:55, 31 December 2020

Notice of Violation from Insp on 860510-0617
ML20203F412
Person / Time
Site: Peach Bottom  Constellation icon.png
Issue date: 07/25/1986
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20203F398 List:
References
50-277-86-09, 50-277-86-9, 50-278-86-12, NUDOCS 8607310062
Download: ML20203F412 (1)


Text

p-r APPENDIX A NOTICE OF VIOLATION Philadelphia Electric Company Docket No. 50-277 Peach Bottom Units 2 and 3 50-278 License No.DPR-44 DPR-56 As a result of the inspection conducted on May 10 - June 17,1986, and in accordance with the NRC Enforcement Policy (10 CFR 2,-Appendix C) the following violation was identified:

10 CFR 50, Appendix B, Criterion XVI and the Peach Bottom Atomic Power Station Quality Assurance Plan, Volume III, paragraphs PR16.1 and S016.1, require measures to be established to assure that conditions adverse to quality are promptly identified and corrected.

Contrary to the above, on May 16, 1986, the Unit 2 and 3 safety related 4KV/480V gas filled and sealed emergency load center transformers were determined to be in a potentially degraded condition in that gas pressure was_ low in transformers E-234, E-434, E-334, E-424, E-13A, E-23A, and E-43A.

The degraded condition was not identified nor corrected.

This is a Severity Level IV Violation (Supplement 1) applicable to DPR-44 and DPR-56.

8607310062 860725 PDR ADOCK 05000277 G PDR OFFICIAL RECORD COPY CIR PB 86-09/12 - 0004.0.0 07/15/86

..- .. __.