p-r APPENDIX A NOTICE OF VIOLATION Philadelphia Electric Company Docket No. 50-277 Peach Bottom Units 2 and 3 50-278 License No.DPR-44 DPR-56 As a result of the inspection conducted on May 10 - June 17,1986, and in accordance with the NRC Enforcement Policy (10 CFR 2,-Appendix C) the following violation was identified:

10 CFR 50, Appendix B, Criterion XVI and the Peach Bottom Atomic Power Station Quality Assurance Plan, Volume III, paragraphs PR16.1 and S016.1, require measures to be established to assure that conditions adverse to quality are promptly identified and corrected.

Contrary to the above, on May 16, 1986, the Unit 2 and 3 safety related 4KV/480V gas filled and sealed emergency load center transformers were determined to be in a potentially degraded condition in that gas pressure was_ low in transformers E-234, E-434, E-334, E-424, E-13A, E-23A, and E-43A.

The degraded condition was not identified nor corrected.

This is a Severity Level IV Violation (Supplement 1) applicable to DPR-44 and DPR-56.

8607310062 860725 PDR ADOCK 05000277 G