| document type = LICENSEE EVENT REPORT (SEE ALSO AO,RO), TEXT-SAFETY REPORT
| document type = LICENSEE EVENT REPORT (SEE ALSO AO,RO), TEXT-SAFETY REPORT
| page count = 8
| page count = 8
| revision = 0
}}
}}

Revision as of 07:49, 26 February 2018

LER 86-011-01:on 860709,Emergency Diesel Generator 2A Taken Out of Svc Due to Failure to Meet Required Start Time.Caused by Excessive Tightening of Friction Clutch Locknut.Cooling Fan Shroud Removed & Fan Repositioned.W/871216 Ltr
ML17221A549
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 12/16/1987
From: POWELL J M, WOODY C O
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
L-87-513, LER-86-011, LER-86-11, NUDOCS 8712220118
Download: ML17221A549 (8)