W3F1-2002-0046, Ses, Annual Radiological Environmental Operating Report

From kanterella
Jump to navigation Jump to search
Ses, Annual Radiological Environmental Operating Report
ML021210087
Person / Time
Site: Waterford Entergy icon.png
Issue date: 04/23/2002
From: Peters R
Entergy Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
A4.05, W3F1-2002-0046
Download: ML021210087 (80)


Text

Entergy Operations, Inc.

En 17265 River Road Killona, LA 70066 Tel 504 739 6650 W3Ffl-2002-0046 A4.05 PR April 23, 2002 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555

Subject:

Waterford 3 SES Docket No. 50-382 License No. NPF-38 Annual Radilogical Environmental Operating Report Gentlemen:

Attached is the Annual Radiological Environmental Operating Report for the period of January 1 through December 31, 2001. This report is submitted pursuant to the requirements of Waterford 3 Technical Specification Section 6.9.1.7.

If there are any questions please contact T.M. Manzella at (504) 739-6882. This submittal does not contain commitments.

Very truly yours, R.D. Peters Acting, Director Nuclear Safety Assurance RDPITMM/cbh Attachment cc: E.W. Merschoff (NRC Region IV), N. Kalyanam (NRC-NRR), J. Smith, N.S. Reynolds, NRC Resident Inspectors Office SL*55

m Entergy Anua I

Iý January 1, 2001 - December 31, 2001 1 Waterford 3S m E le

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Originator:

Ann V. Dubois, Chemistry Technician Date Reviewed By: D/

a S p e r ine n Date n L . Pi er c e , C h e m is try Jonh

,t/-/-7.--T__

Approved By:

Glenn M. Pierce, Chemistry Superintendent Date

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station TABLE OF CONTENTS

SUMMARY

1

1.0 INTRODUCTION

6 1.1 Radiological Environmental Monitoring Program 6 1.2 Pathways Monitored 6 1.3 Land Use Census 6 2.0 INTERPRETATION AND TRENDS OF RESULTS 21 2.1 Air Particulate and Radiolodine Sample Results 21 2.2 Thermoluminescent Dosimetry Sample Results 21 2.3 Water Sample Results 22 2.4 Sediment Sample Results 23 2.5 Milk Sample Results 23 2.6 Fish Sample Results 23 2.7 Broad Leaf Vegetation Sample Results 24 2.8 Land Use Census Results 24 2.9 Interlaboratory Comparison Results 24 3.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM

SUMMARY

27 3.1 2001 Program Results Summary 27

- i-

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station LIST OF TABLES TABLE 1.1 RADIOLOGICAL ENVIRONMENTAL SAMPLING PROGRAM 7 TABLE 2.1 BIANNUAL LAND USE CENSUS RESULTS 25 TABLE 3.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM

SUMMARY

28

-ii-

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station LIST OF FIGURES FIGURE 1-1 REMP SAMPLES WITHIN 2 MILES OF WATERFORD 3 18 FIGURE 1-2 REMP SAMPLES WITHIN 10 MILES OF WATERFORD 3 19 FIGURE 1-3 REMP SAMPLES WITHIN 50 MILES OF WATERFORD 3 20 FIGURE 2-1 TLD RADIATION DOSE COMPARISON (BY YEAR) 26

- iii -

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station LIST OF ATTACHMENTS ATTACHMENT 1 2001 RADIOLOGICAL MONITORING REPORT

SUMMARY

OF MONITORING RESULTS 32 ATTACHMENT 2 STATISTICAL COMPARISONS 51 ATTACHMENT 3 2002 REVISED ODCM TABLES 59

- iv -

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Summary The Annual Radiological Environmental Operating Report presents data obtained through analyses of environmental samples collected for Waterford 3's (W3) Radiological Environmental Monitoring Program (REMP) for the period January 1 through December 31, 2001. This report fulfills the requirements of W3 Technical Specification 6.9.1.7.

During 2001, gross beta radioactivity was detected in all air and drinking water/surface water locations. Results obtained at the indicator locations were similar to those obtained at the control location. Therefore, levels continue to remain at background.

Cesium-137, a man-made nuclide, was detected once during 2001 at an indicator sediment location (SHWE-3). This is consistent with results obtained from the preoperational program and previous years of operation. Studies in Louisiana indicate that Cesium-137 is commonly found in soils and sediments as a result of atmospheric weapons testing. Because the Cesium-137 levels are consistent with preoperational values, the Cesium-137 level detected in 2001 is more than likely attributable to weapons testing fallout.

Even though tritium was detected in three groundwater samples, the values observed were less than the required LLD in all three samples. Tritium is routinely released as measured in effluent sampling analysis via this pathway. Those levels observed are consistent with effluent sampling and analysis results.

Radiological Environmental Monitoring Program W3 established the REMP prior to the station becoming operational (1985) to provide data on background radiation and radioactivity normally present in the area. W3 has continued to monitor the environment by sampling air, water, sediment, milk, fish and broadleaf vegetation, as well as measuring radiation directly.

The REMP includes sampling indicator and control locations within a 50-mile radius of the plant. The REMP utilizes indicator locations near the site to show any increases or buildup of radioactivity that might occur due to station operation, and control locations farther away from the site to indicate the presence of only naturally occurring radioactivity. W3 compares indicator results with control, preoperational, and previous years operational results to assess any impact W3 might have on the surrounding environment.

In 2001, W3 collected environmental samples for radiological analysis. Based on the comparison results of indicator locations with control locations and previous studies, it was concluded that overall W3 operations had no significant impact on plant environs with the exception of groundwater tritium where a direct correlation from plant operations exists well below the reporting level. The review of 2001 data, in many cases, showed undetectable radiation levels in the environment and near background level in significant pathways associated with W3.

Harmful Effects or Irreversible Damage The REMP did not detect any harmful effects or evidence of irreversible damage in 2001. Therefore, no analysis or planned course of action to alleviate problems was necessary.

1

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Reporting Levels W3's review indicates that no samples equaled or exceeded reporting levels for radioactivity concentration in environmental samples, as outlined in Technical Requirements Manual (TRM)

Table 3.12-2 when averaged over any calendar quarter, due to W3 effluents. Therefore, 2001 results did not trigger any Radiological Monitoring Program Special Reports.

Radioactivitv Not Attributable to W3 The W3 REMP detected radioactivity attributable to other sources twice. These include the 25th Chinese nuclear test explosion in 1980, and the radioactivity plume release due to reactor core degradation at the Chernobyl Nuclear Power Plant in 1986.

Comparison to State Program W3 compared REMP data to the monitoring program of the Environmental Radiological Laboratory Department of Environmental Quality Laboratory Services Division (ERL-DEQLSD). The ERL-DEQLSD and the W3 REMP entail similar radiological environmental monitoring program requirements. Both programs have obtained similar results over previous years.

Sample Deviations

  • Milk Samples Two milk samples were unavailable from indicator location MKQ-5 due to cows not producing enough milk. Milk samples were not available during the 2001 reporting period from location MKQ-1 since the cows are not currently producing milk for human consumption. With the absence of milk samples at these locations, broadleaf vegetation sampling was performed as required by TRM Table 3.12-1.

+ Air Samples The air sample locations listed below failed to meet the requirement for sample continuity.

However, required LLDs were achieved in all cases. As described in footnote (1) of TRM Table 3.12-1, deviations are permitted from the required sampling schedule due to malfunction of sampling equipment and other legitimate reasons.

Location Sample period Explanation of Deviation APP-1 01/16/01 - 01/29/01 Sample pump tripped APP-1 09/10/01 - 09/24/01 Calibration check unsatisfactory 2

Annual Radiological 2001 Environmental Operatinq Report Waterford 3 Steam Electric Station

  • Water Samples The drinking/surface water sample locations listed below failed to meet the requirement for sample continuity. However, required LLDs were achieved in all cases. As described in footnote (1) of TRM Table 3.12-1, deviations are permitted from the required sampling schedule due to malfunction of sampling equipment and other legitimate reasons.

Location Sample period Explanation of Deviation DWP-7 09/10/01 - 10/08/01 Calibration check unsatisfactory DWE-5 09/10/01 - 10/08/01 Low battery

+ TLDs Station K-1 was missing one TLD during the third quarter monthly inspection. The remaining TLD was left in place and read at the end of the quarter.

  • Missed Samples TLD station D-2 was missing during the fourth quarter monthly inspection due to vandalism.

Another set of TLDs was placed at this location on 11-13-01.

  • Required Lower Limit of Detection (LLD) Values All LLDs during this reporting period were within the acceptable limits required by the W3 TRM.
  • Unavailable Results W3 received analytical results in adequate time for inclusion in this report. In addition, W3's review identified no missing results.

Program Modifications W3 made no modifications to the REMP during 2001. However, some modifications were made early in 2002. In February, 2002, REMP sample locations were cited using GPS coordinates and geological mapping software while revising the Offsite Dose Calculation Manual. As a result of this study, several discrepancies were noted with respect to sample locations including the following:

S TLD location R-1 was actually located in sector Q.

0 TLD location H-6 was actually located in sector G.

S TLD location G-9 was actually located in sector F at a distance of 8 miles.

S Air Sample location APG-1 was actually in sector F.

S Drinking/Surface water location DWG/SWG-2 was actually in sector F.

3

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station As a result of these descrepancies, the following changes were implemented in Revision 7 of the ODCM in March 2002:

  • TLD location R-1 was moved a short distance to a location actually in sector R.
  • TLD location H-6 was relocated to sector H eight miles from the plant because there was not a suitable location in sector H within the 6-8 km distance specified in Table 3.12-1 of the Technical Requirements Manual (TRM).
  • TLD location G-9 was moved a short distance to a location actually in sector G, and the designation was changed to G-8.
  • Air Sample location APG-1 was renamed to APF-1 and a verification of appropriate sector citing in accordance with the requirements of Table 3.12-1 of the TRM was performed.
  • Drinking/Surface water location DWG/SWG-2 was renamed to DWF/SWF-2.

The following additional changes to the REMP were also incorporated in Revision 7 of the ODCM:

"* Sample location descriptions were modified to include GPS coordinates, bearing, and distance.

"* A control Shoreline Sediment sample (SHWQ-6) was added as a result of a requirement change to TRM Table 3.12-1 under DRN 02-357 which added an upstream requirement due to Entergy Nuclear - South REMP standardization.

"* Shoreline Sediment frequency was changed from Semi-Annually to Annually as a result of a requirement change to TRM Table 3.12-1 under DRN 02-357 due to Entergy Nuclear - South REMP standardization.

"* Broad Leaf and Milk collection frequency was changed from Monthly to Quarterly as a result of a requirement change to TRM Table 3.12-1 under DRN 02-357 due to Entergy Nuclear South REMP standardization.

"* Deleted Broad Leaf control location BLK-1 5 because this location was replaced with BLE-20 which meets the TRM Table 3.12-1 directional requirements and has been shown to provide sufficient vegetation throughout the year.

"* Reclassified GWK-1 as Surface Water and installed a composite sampler at this location as required for surface water sampling. Ground Water sampling is no longer performed.

  • Deleted Milk location MKQ-1 because this location no longer provides milk.
  • Added a new fish location, FH-3, because fish can conceivably be affected by plant discharges via the 40 Arpent Canal discharge pathway.

A copy of the affected ODCM Tables are included in this report in Attachment 3.

4

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Attachments contains results of air, TLD, water, sediment, milk, fish and broadleaf vegetation collected in 2001. TLDs were analyzed by Waterford-3 Dosimetry. All remaining samples were analyzed by the River Bend (RBS) Environmental Laboratory. Attachment 1 also contains River Bend's participation in the interlaboratory comparison program during 2001. contains statistical comparisons of:

"* TLD measurements from stations grouped by distance

"* TLD radiation dose to historical data by location

"* Gross beta activity measurements on air particulate filters

"* Gross beta activity measurements in surface/drinking water samples contains 2002 revised ODCM tables.

5

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station 1.0 Introduction 1.1 Radiological Environmental Monitoring Program W3 established the REMP to ensure that plant operating controls properly function to minimize any associated radiation endangerment to human health or the environment. The REMP is designed for:

"* Analyzing important pathways for anticipated types and quantities of radionuclides released into the environment.

"* Considering the possibility of a buildup of long-lived radionuclides in the environment and identifying physical and biological accumulations that may contribute to human exposures.

"* Considering the potential radiation exposure to plant and animal life in the environment surrounding W3.

"* Correlating levels of radiation and radioactivity in the environment with radioactive releases from station operation.

1.2 Pathways Monitored The airborne, direct radiation, waterborne and ingestion pathways, as seen in Figure 1-1, are monitored as required by W3 TRM Table 3.12-1. A description of the W3 REMP utilized to monitor the exposure pathways is described in Table 1.1 and shown in Figures 1-1, 1-2 and 1-3.

Section 2.0 of this report provides a discussion of 2001 sampling results with Section 3.0 providing a summary of results for the monitored exposure pathways.

1.3 Land Use Census W3 conducts a land use census biannually, as required by Section 3.12.2 of the TRM. The purpose of this census is to identify changes in uses of land within five miles of W3 that would require modifications to the REMP and the Offsite Dose Calculation Manual (ODCM). The most important criteria during this census is to determine the location in each sector of the nearest:

1) Residence
2) Animal milked for human consumption
3) Garden of greater than 50 m2 (500 ft2 ) producing broadleaf vegetation.

W3 conducts the land use census by:

" Field surveys in each meteorological sector out to five miles in order to confirm:

Nearest permanent residence

> Nearest garden and approximate size

> Nearest beef cow

> Nearest food product

> Nearest milking animal.

"* Identifying locations on maps, measuring distances to W3 and recording results on data sheets.

"* Comparing current census results to previous results.

6

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Airborne Radioiodine and Particulates Three samples from close to the three APQ-1 (NW, 0.8 Miles) - (West bank) Continuous sampler operation Radioiodine Cannister - 1-131 SITE BOUNDARY locations, in different Located at northwest corner of with sample collection bi- analysis bi-weekly.

sectors, in or near sectors having the soybean/sugarcane field on east side of with sample colletio i highest calculated annual average Killona. Access from River Road (LA 18) weekly, or more frequently if groundlevel D/Q. approximately 0.6 miles east of LA 18/3141 required by dust loading. Particulate Sampler - Gross intersection. beta radioactivity analysis following filter change: Gamma APG-1 (SE, 0.5 Miles) - (West bank) isotopic analysis of composite Located at the north side of the Secondary (by location) quarterly.

Meteorological Tower.

APC-1 (NE, 0.8 Miles) - (East bank)

Located inside the Little Gypsy Cooling Water Intake Structure fence enclosure.

Radioiodine and Particulates One sample from the vicinity of a APP-1 (WNW, 0.8 Miles) - (West bank) community having the highest Located in soybean/sugarcane field at calculated annual average groundlevel northwest corner of Short St. in Killona.

D/Q.

Radioiodine and Particulates One sample from a control location, as APE-30 (E, 27.0 Miles) - (West bank) for example 15 -30 km distance and in Located on the roof of the Entergy's the least prevalent wind direction. General Office building on Delaronde St. in Algiers. (Control) 7

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An inner ring of stations, one in each A-2 (N, 1.1 Miles) - (East bank) Located Quarterly Gamma dose quarterly.

meteorological sector in the general on a utility pole on River Road (LA 628) at area of the SITE BOUNDARY. the south corner of the Zephrin L. Perriloux Fire Station (Station 5) in Montz, La.

B-1 (NNE, 0.8 Miles) - (East bank) On fence enclosing the transmission tower 0.3 miles west (up-river) from Little Gypsy.

Access from River Road (LA 628). TLDs are located at SW corner of fence enclosure.

C-1 (NE, 0.8 Miles) - (East bank) On fence enclosing the Little Gypsy Cooling Water Intake. Access is from River Road (LA 628) across from Little Gypsy Steam Electric Station entrance. TLDs are on the south side (inside) of the Cooling Water Intake fence enclosure, directly opposite the entrance gate.

D-2 (ENE, 1.1 Miles) - (East bank)

Located approximately 0.3 miles east of Little Gypsy Power Station. Access from River Road (LA 628). TLDs are attached to a stop sign post located at the peak of the levee on the west entrance road through the Bonne Carre Spillway.

8

Annual Radiological 2001 Environmental Oneratina Report Waterford 3 Steam Electric Station Environmental Oneratina Report Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An inner ring of stations, one in each E-1 (E, 0.2 Miles) - (West bank) Located on Quarterly Gamma dose quarterly.

meteorological sector in the general utility pole along River Road (LA 18) area of the SITE BOUNDARY. approximately 0.3 miles east of Waterford 3 plant entrance. Access from LA 18. TLDs are on the third utility pole east of the construction entrance road.

F-2 (ESE, 1.1 Miles) - (West bank) Located on fence enclosure surrounding the LP&L sub station on LA 3142. Access from LA 3142 approximately 0.2 miles south of LA 18. TLDs are on the southeast corner of the fence enclosure G-2 (SE, 1.2 Miles) - (West bank) Located on utility pole on east side of LA 3142 (Next to Union Carbide Star Plant Gate 3). Access from LA 3142 approximately 0.2 miles north of railroad overpass.

H-2 (SSE, 1.2 Miles) - (West bank) Located on fence enclosure to shell road off of LA3142. Access from LA 3142 south of railroad overpass on east side of LA 3142.

TLDs are on the south side of the gate for shell road (just south of Texaco pipeline station).

9

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An inner ring of stations, one in each J-2 (S, 1.3 Miles) - (West bank) Located on Quarterly Gamma dose quarterly.

meteorological sector in the general northeast corner of fence enclosing Texaco area of the SITE BOUNDARY. valve station south of LA 3127. Access from LA 3127, approximately 0.6 miles west of LA 3127/3142 intersection.

K-1 (SSW, 1.0 Miles) - (West bank) Located on stop sign at entrance to Entergy Training Center. Access from LA 3127, approximately 1.3 miles west of LA 3127/3142 intersection.

L-1 (SW, 1.0 Miles) - (West bank) Located on fence of Gate 97 entrance off of LA 3127, approximately 1.6 miles west of LA 3127/3142 intersection. (Gate 97 is an access road for Waterford 3.)

M-1 (WSW, 0.7 Miles) - (West bank) Located on south gate into the Waterford 1 and 2 fuel oil storage tank enclosure. Access is through the Waterford 1 and 2 access road.

N-1 (W, 0.9 Miles) - (West bank) Located on a pole at the end of Short Street in Killona near the railroad track south of the Killona Elementary School.

10

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An inner ring of stations, one in each P-I (WNW, 0.8 Miles) - (West bank) Located Quarterly Gamma dose quarterly.

meteorological sector in the general on Short Street, in Killona. TLD is located on area of the SITE BOUNDARY. housing of air sample station APP-1.

Q-1 (NW, 0.8 Miles) - ((West bank) Located on fence enclosing air sample station APQ-1 approximately 0.5 miles west of Waterford 1 and 2 on River Road (LA 18).

R-1 (NNW, 0.5 Miles) - (West bank) Located on fence enclosure for Waterford 1 and 2 Cooling Water Intake Structure. Access is from River Road (LA 18) opposite Waterford 1 and 2. TLDs are on the southwest corner of fence.

TLDs An outer ring of stations, 1 in 10 of the A-5 (N, 4.5 Miles) - (East bank) Located on meteorological sectors in the 6- to 8- utility pole just east of the Shady Nook Trailer km range from the site. Park on Hwy 61 in LaPlace. TLDs are on second utility pole east of trailer park on north side of Hwy 61 (eastern end of LaPlace).

11

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An outer ring of stations, 1 in 10 of the B-4 (NNE, 3.8 Miles) - (East bank) Located Quarterly Gamma dose quarterly.

meteorological sectors in the 6- to 8- on utility pole guidewire west of shell access km range from the site. road to South Central Bell transmission tower on south side of Hwy 61. Transmission tower is just east of weigh station at St. John/St.

Charles Parish line. TLDs are on the first utility pole east of access road.

D-5 (ENE, 4.2 Miles) - (East bank) Located on fence gate on shell access road to Big 3 Chemical Plant. Shell access road is approximately 0.1 miles west of Hwy 61/48 intersection (at black and yellow gate). TLDs are on fence gate 0.1 miles north on shell access road from Hwy 61.

F-4 (ESE, 3.5 Miles) - (West bank) Located on utility pole behind blonde brick house on Aquarius St. in Hahnville. Access from River Road (LA 18) and turn onto Oak St. Follow Oak St. to Hickory St., turn right on Hickory St.

and follow to Aquarius St. and turn left.

Blonde brick house is on the west side of Aquarius Street.

12

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An outer ring of stations, 1 in 10 of the E-5 (E, 4.2 Miles) - (East bank) Located on Quarterly Gamma dose quarterly.

meteorological sectors in the 6- to 8- the Norco Substation fence enclosure. Access km range from the site. from River Road (LA- 48) onto Wesco St.

(adjacent to Norco Shell Chemical Plant), take Wesco St. to the dead end. TLDs are located on sixth fence post south of the north substation gate.

G-4 (SE, 3.2 Miles) - (West bank) Located on railroad sign northwest side of LA 3160/railroad track intersection. Access- from either LA 3127 or River Road (LA 18) onto LA 3160.

H-6 (SSE, 5.7 Miles) - (West bank) Located on a road sign on the northwest side of the second canal bridge east of LA 3160 along LA 3127.

P-6 (WNW, 5.5 Miles) - (West bank) Located on a fence surrounding the Union Pacific communications tower at the LA 640/railroad intersection. Tower is located approximately 500 ft. west from LA 640.

Q-5 (NW, 5.0 Miles) - (West bank) Located on fence along River Road (LA 18) across from the Webre's house.

13

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation An outer ring of stations, 1 in 10 of the R-6 (NNW, 5.3 Miles) - (East bank) Located on Quarterly Gamma dose quarterly.

meteorological sectors in the 6- to 8- lay down yard fence on LA 3223 in LaPlace.

km range from the site. Access from Hwy 61 onto Elm St. (LA 3223); take Elm St. to the northeast corner of LA 3223/railroad intersection. TLDs are located on the southeast corner of fence enclosure.

TLDs The balance of the 31 routine F-9 (ESE, 8.2 Miles) - (East bank) Located on monitoring stations to be in special entrance gate to Destrehan Substation. Access interest areas such as population from River Road (LA 48), approximately 1.5 miles centers, nearby residences, schools, east of Luling-Destrehan bridge, onto Jonathan and in 1 or 2 areas to serve as control Street (west of Bunge Corp. Grain Elevator), and stations. proceed to substation gate. (Special Interest)

G-9 (SE, 8.1 Miles) - (West bank) Located on back fence of Entergy's District Office in Luling.

Access via Ellington St. from either River Road (LA 18); or Second or Third St. from Paul Mallaird Rd. (LA 52) to Ellington St. (Special Interest)

E-15 (E, 11.8 Miles) - (East bank) Located on Kenner Substation fence enclosure. Access from either River Road (LA 48) or Hwy 61, turn onto Alliance Ave. TLDs are located at the entrance of the fence enclosure. (Special Interest) 14

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Direct TLDs Radiation The balance of the 31 routine J-15 (S, 12.0 Miles) - (West bank) Located on utility Quarterly Gamma dose quarterly.

monitoring stations to be in special pole near the LA 631/Hwy 90 intersection in Des interest areas such as population Allemands. TLDs are on the utility pole on east side of centers, nearby residences, schools, LA 631. Access is from LA 631 via shell road.

and in 1 or 2 areas to serve as control (Special Interest) stations.

E-30 (E, 27.0 Miles) - (West bank) Located at Entergy's General Office on Delaronde St. in Algiers.

TLDs are on a tree in the courtyard at the south entrance to the building. (Control)

Waterborne Surface Water One sample upstream. SWP-7 (WNW, 6.5 Miles) - (West bank) Located at Composite sample over Gamma isotopic analysis the St. John Parish Waterworks off of LA 18 in one quarter period, quarterly. Composite for Edgard. (Control) tritium analysis quarterly.

One sample downstream. SWG-2 (SE, 2.0 Miles) - (West bank) Located at the Dow Chemical drinking water canal. Access from LA 3142 through Gate 28.

SWE-5 (E, 4.5 Miles) - (East bank) Located at the St.

Charles Parish Waterworks off of River Road (LA 48) near New Sarpy.

Ground Water Samples from one or two sources only GWK-1 (SSW, 0.5 Miles) - (West bank) Located at 40 Quarterly Gamma isotopic and tritium if likely to be affected. Arpent Canal south of the plant. The canal is analysis quarterly.

northwest of the shell road/railroad track intersection.

15

Annual Radiological 2001 Fnvironmental Oneratina Renort Waterford 3 Steam Electric Station Environmental Operating Report Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Waterborne Drinking Water One sample of each of one of the DWG-2 (SE, 2.0 Miles) - (West bank) Located at Composite sample over one 1-131 analysis on each three nearest water supplies that the Dow Chemical drinking water canal. Access month period when 1-131 composite when the dose could be affected by its discharge. from LA 3142 through Gate 28. analysis is performed, quarterly calculated for the consumption of DWE-5 (E, 4.5 Miles) - (East bank) Located at composite otherwise. the water is greater than one the St. Charles Parish Waterworks off of River mrem per year. Composite for Road (LA 48) near New Sarpy. gross beta and gamma isotopic analyses quarterly. Composite DWP-7 (WNW, 6.5 Miles) - (West bank) Located for tritium analysis quarterly.

at the St. John Parish Waterworks off of LA 18 in Edgard. (Control)

Sediment From Shoreline One sample from downstream SHWE-3 (E, 3.0 Miles) - (West bank) Located Semiannually Gamma isotopic analysis area with existing or potential at the Foot Ferry Landing off of LA 18 in Taft. semiannually.

recreational value.

SHWE-1 (SSW, 0.5 Miles) - (West bank)

Located at the 40 Arpent Canal south of the Plant.

Ingestion Milk Samples from milking animals in MKQ-1 (NW, 1.0 Miles) - (West bank) 1.0 miles Monthly Gamma isotopic and 1-131 the three locations within 5 km west of Waterford 3 SES at the corner of River analysis monthly.

distance having the highest dose Road and Post Street in Killona.

potential. If there are none, then, one sample from milking animals MKQ-5 (NW, 5.0 Miles) - (West bank) Located in each of the three areas at the Webre's house, just across LA 18 from between 5 to 8 km distant where river marker, at the eastern end of Edgard.

doses are calculated to be greater than 1 mrem per year.

16

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Radiological Environmental Sampling Program Exposure Requirement Sample Point Description, Sampling and Type and Frequency Pathway Distance and Direction Collection Frequency Of Analyses Ingestion Milk One sample from milking animals at a MKR-40 (NNW, 40.0 Miles) - (East bank) Located Monthly Gamma isotopic and 1-131 control location 15 - 30 km distance at 24254 LA Highway 442, Holden. La. (Control) analysis monthly.

and in the least prevalent wind direction.

Fish and Invertebrates One sample of each commercially and FH-2 (Distance/Direction Not Applicable) - Sample in season, or Gamma isotopic analysis recreational important species in Downstream of the plant discharge structure. annually if they are not vicinity of plant discharge area. seasonal on edible portion.

One sample of same species in area FH-1 (DistancelDirection Not Applicable) not influenced by plant discharge. Upstream of the plant intake structure. (Control)

Broadleaf Samples of one to three different kinds BLQ-1 (NW, 0.8 Miles) - (West bank) Located Monthly when available Gamma isotopic and 1-131 of broadleaf vegetation grown nearest between LA 18 and soybean field on eastern edge of analysis.

each of two different off-site locations of Killona, near air sample station APQ-1.

highest predicted annual average groundlevel D/Q if milk sampling is not BLB-1 (NNE, 0.8 Miles) - (East bank) Located at performed. wooded area at the southwestern corner of the Little Gypsy plant along River Road.

One sample of each of the similar BLK-15 (SSW, 15.0 Miles) - (West bank) Located broadleaf vegetation grown 15 - 30 km 3.5 miles SSW of Des Allemands on Hwy. 90.

distant in the least prevalent wind (Control) direction if milk sampling is not performed. BLE-20 (E, 20.0 Miles) - (West bank) Located on property of Nine Mile Point in Westwego, LA.

(Control) 17

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station FIGURE 1-1 1E PRw SAMPLES WnIHI 2 MILES OF WATERFORD 3 1 N

I

  • TLD MK MILK AP AIR PARTICLE, IODINE DW DRINKINGISURFACE WATER GW GROUNDWATER PH RSH BL BROAD LEAF VEGETATION 4W SMOREUNE SEDIMENT PP FOOD PRODUCT PARISH 1OUNDRIES

-HIGHWAYS SWATER

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station FIGURE 1-2 11HEMP SAMPLES WTHN 10 MLES OF WATERFORD 3 11 Ii I

I UK TLD MILK SHW SHOREUNE SEDIMENT OW DRINKING/SURFACE WATER PARISH BOUNDRIES HIGHWAYS WATER 19

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station FIGURE 1-3 tHMP SAMPLES W1THIN 50 MILES OF WATERFORD 3 N

I I TLD UK MILK AP AIR PARTICLE, IODINE BL BROAD LEAF VEGETATION

... PARISH BOUNDRIES WATER 20

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station 2.0 Interpretation and Trends of Results 2.1 Air Particulate and Radioiodine Sample Results Samples of airborne particulate and radioiodine were collected at four indicator locations and one control location and analyzed for gross beta radionuclides, Iodine-131 and gamma radionuclides (quarterly air particulate filter composites only). W3 did not detect any gamma radionuclides in the quarterly air particulate composites or Iodine-131 in the radioiodine cartridges during the reporting period, as has been the case in previous years. Indicator gross beta air particulate results for 2001 were similar to those background levels obtained in previous years of the operational REMP and well below preoperational levels as seen below.

Results are reported as annual average pCi/m 3 .

Monitoring Period Result Preoperational 0.080 1983 -2000 0.019 2001 0.020 Table 3.1, which includes gross beta concentrations for 2001 and provides a comparison of the indicator and control means, further emphasizes that the airborne pathway continues to remain at background levels. In addition, as shown in Attachment 2, the standard "t" test was used to compare average gross beta activity from each indicator station to the average gross beta activity at the control station. The results from this test show the average activity detected at all indicator stations is statistically the same as the average activity detected at the control station. Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2001.

2.2 Thermoluminescent Dosimetry Sample Results The average exposure rates during 2001 are consistent with those from the preoperational program and the previous five years of operation as seen in Figure 2-1. In particular, the preoperational survey indicates that exposure rates ranged between 11 and 33 mrem/standard quarter with an average of 20 mrem/standard quarter. The range during the previous five years of operation was 9 to 16 mrem/standard quarter with an average exposure rate of 13 mrem/standard quarter.

A comparison of the indicator results to the control results, as seen in Table 3.1, shows that the average indicator is slightly higher than that of the control. As shown in Attachment 1, Table 2.1, several indicator locations are higher than the control by a few mrem with a maximum difference of six mrem on one occasion (G-2, 4th Qtr).

As shown in Attachment 2, Table 2.1, the standard "t" test was used to compare average exposure rates for TLD stations located in groups 0-2 miles and 2-5 miles from the plant to those >5 miles. The results indicate that the average exposure rates 0-2 miles from the plant are statistically the same as >5 miles while those 2-5 miles are statistically higher.

The differences between indicator locations and the control, and TLD stations grouped by distance from the plant are expected due to a variety of factors not related to W3 plant operations that can affect background radiation in the vicinity of each TLD station. Direct radiation measurements at each TLD station have remained statistically the same in 2001 as previous years of operation as evidenced on Attachment 2, Table 2.2. In addition, Radiological Gaseous Effluents for 2001 were only a small fraction of the limits as is typical in previous years of operation and are not expected to have any impact on environmental TLD measurements.

21

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station 2.3 Water Sample Results Analytical results for 2001 drinking/surface water and groundwater samples were similar to those reported in previous years.

Drinking/Surface Water Drinking water samples also serve as surface water samples for W3. Therefore, monthly and quarterly gamma spectroscopy and tritium analyses of drinking water also satisfy the surface water sampling requirement.

Composite drinking/surface water samples were collected from two indicator and one control location and analyzed for Iodine-131, gamma radionuclides and tritium. Results indicate that all measurements were below the calculated LLDs.

Although gross beta was detected in the drinking/surface water samples, results for the indicator locations are similar to previous operational and preoperational years as seen below.

Results are reported as annual average pCi/I.

Monitoring Period Result Preoperational 7.0 1983 -2000 5.3 2001 4.5 Table 3.1, which includes gross beta concentrations for 2001 and provides a comparison of the indicator and control means, shows that the waterborne pathway continues to remain at background levels. In addition, as shown in Attachment 2, the standard "t" test was used to compare average gross beta activity from each indicator station to the average gross beta activity from the control station. The results from this test show average activity detected at all indicator stations are statistically the same as the average activity detected at the control station. Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2001.

Groundwater Groundwater samples were collected from one indicator location and analyzed for gamma radionuclides and tritium. W3 did not detect any gamma radionuclides in groundwater samples during the reporting period.

Tritium concentrations detected in 2001 are higher than those from the preoperational program as seen below. Results are reported as annual average pCi/I.

Monitoring Period Result Preoperational 121 1983 -2000 909 2001 775 Tritium is expected due to liquid effluent releases from the Turbine Building Industrial Waste Sump (TBIWS) and Dry Cooling Tower Sumps (DCTSs) normally being directed to the 40 Arpent canal where samples are collected for groundwater monitoring. Water from these pathways is typically discharged at a rate of approximately 20,000 gallons per day total with tritium concentration ranging from 6.1E-6 uCi/ml to 1.7E-5 uCi/ml. The plant effluent is diluted by adjoining canals and rain, which can vary significantly depending on weather conditions, prior to reaching the sample location. As a result, samples collected after periods of heavy rain can indicate concentrations below detection levels, while those collected during dry periods have the potential to approach concentrations discharged directly from the plant via the TBIWS and DCTSs.

22

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station As of March 14, 2002, the groundwater sample location was reclassified as Surface Water which requires the use of a continuous composite sampler. This sampling methodology should provide a better representation of the actual concentration of tritium at this location with less variability in sample results due to short-term changes in weather conditions.

2.4 Sediment Sample Results Sediment samples were collected from two indicator locations and analyzed for gamma radionuclides. Cesium-137, a man-made nuclide, was detected in one sample (SHWE-3) with a concentration of 53 pCi/kg. No other man-made radionuclides were detected in any of the samples.

The Cesium-137 results obtained during 2001 are consistent with those from the preoperational program and previous years of operation. In particular, the preoperational survey indicates that Cesium-137 was detected in 9 of 14 soil samples at concentrations ranging between 30 and 890 pCi/kg with an average concentration of 164 pCi/kg. Similarly, the range indicated during the previous years of operation was 18 to 142 pCi/kg with an average activity of 56 pCi/kg.

W3 has detected Cs-137 in wastewater tanks discharged to the Mississippi River at concentrations typically below 1E-6 uCi/mI in the past few years. After dilution by Circulating Water, this concentration is reduced to well below 1E-10 uCi/mI prior to mixing with the Mississippi River where it is diluted even further. At the minimal concentrations being discharged from W3 as compared to the typical Cs-137 concentrations commonly found in soils and sediments in Louisiana as a result of atmospheric fallout from nuclear weapons testing as noted in the preoperational study, plant operations is not expected to result in any appreciable quantities of radioactivity in sediment collected from the bank of the Mississippi River where SHWE-3 is located. In addition, the radioactivity detected in sediment this year is consistent with preoperatioal data even after applying a correction for natural decay of Cs-137.

Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2001.

2.5 Milk Sample Results Milk samples were collected from one indicator and one control location and analyzed for Iodine-131 and gamma radionuclides. Results indicate that all measurements were below the calculated LLDs. Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2001.

2.6 Fish Sample Results Fish samples were collected from one indicator and one control location and analyzed for gamma radionuclides. Results indicate that all measurements were below the calculated LLDs. Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2001.

23

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station 2.7 Broadleaf Vegetation Sample Results Broadleaf vegetation samples were collected from two indicator and two control locations and analyzed for Iodine-131 and gamma radionuclides. Results indicate that all measurements were below the calculated LLDs. Therefore, W3 concluded that plant operations had no significant impact on this pathway during 2001.

2.8 Land Use Census Results In compliance with the Waterford 3 ODCM and TRM, the land use census was conducted September 26 through September 28, 2000. The nearest residence, garden, beef cow, food product and milk animal in each sector within a five mile radius of the plant was located by visual inspection and verbal inquiry.

While milk cow and food product locations remained unchanged for 2000, three locations of goats (sectors N, P and Q) and one location of beef cow (sector F) were removed. Two new resident locations (sector B and G), four new garden locations (sectors C, N, P and Q), one new goat location (sector E) and one new beef cow location (sector G) was identified in 2000.

Based upon the locations identified in this survey, the locations identified in previous surveys and the locations currently being used to calculate dose commitments from liquid and gaseous effluents released from W3, no REMP sampling location changes are necessary.

Results of the 2000 biannual census are shown in Table 2.1.

2.9 Interlaboratory Comparison Results The River Bend Station Environmental Laboratory analyzed interlaboratory comparison samples for W3 to fulfill the requirements of Section 5.7.2 of the ODCM. Attachment 1 contains these results. For the sample result outside the acceptable control limit, W3 and RBS's review indicated no impact on previously reported data. Attachment 1 also provides additional discussion regarding the sample result outside the acceptable control limit.

24

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station TABLE 2.1 Biannual Land Use Census Results Sector Direction Distance from Plant in Miles Milk Beef Food Residence Garden Cows Cows Goats Products N 1.3 1.7 *4.6 4.6 A 4.1 NNE 1.1 1.3 A A A 1.3 A A A A NE 0.9 0.9 A

ENE 0.9 0.9 A A A

  • 2.3 E 2.2 2.2 A 2.3 *2.3 0.3 A

A ESE 3.1 2.2 A 2.3 0.3 SE A 4.1 A 2.4 A 0.3 A

SSE A A A A 0.3 A

S A A A A 0.5 A A A A A SSW 0.5 A A A A A SW 0.5 A A WSW A 1.4 1.2 0.5 W 1.0 1.1 A 1.0 A 0.6 WNW 0.9 0.9 A 0.9 A 0.6 NW 0.9 1 **4.9 0.9 A 0.6 A

NNW 3.0 3.0 4.9 A 2.6 A Indicates that nothing was found in the Sector within a five mile radius of Waterford 3

  • Animals were located at this distance from Waterford 3, but the milk is not currently used for human consumption
    • Samples are being obtained from animals at this location (MKQ-5) for the REMP 25

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station FIGURE 2-1 TLD RADIATION DOSE COMPARISON (BY YEAR) 40 40 35 35 30 30 25 25 w 20 20 CO)

EU C.

15 15 E

0) 10 10 5 5 0 0 YEAR 26

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station 3.0 Radiological Environmental Monitoring Program Summary 3.1 2001 Program Results Summary Table 3.1 summarizes the 2001 REMP results. W3 did not use values reported as less than the lower limit of detection (<LLD) when determining ranges and means for indicator and control locations.

27

2001 Annual Radiological Inn~r~ini Pr~nnrt" Waterford 3 Steam Electric Station F:n,,irg-nmnrn2I~

TABLE 3.1 Radiological Environmental Monitoring Program Summary Name of Facility: Waterford 3 SES Docket No: 50-382 Location of Facility: St. Charles, Louisiana Reporting Period: January - December 2001 Sample Type Type & Number LLD b Indicator Locations Location with Highest Annual Mean Control Number of (Units) Of Analyses a Mean (F c Locations Nonroutine Mean (F) c Results e

[Range]

[ Range]

Mean ( F ) c Location d [ Range I Airborne Particulates GB 135 0.01 0.019 ( 108 / 108) APQ-1 0.020 (27 / 27) 0.018 (27 / 27) 0

[ 0.001 - 0.045] (NW, 0.8 mi.) [0.010 - 0.045] [0.001 - 0.0441 (pCilm 3 )

GS 20 Cs-134 0.05 <LLD N/A N/A <LLD 0 Cs-1 37 0.06 <LLD N/A N/A <LLD 0 Airborne Iodine 1-131 135 0.07 <LLD N/A N/A <LLD 0 3

(pCi/m )

Indicator TLDs Gamma 120 (f) 12.3 ( 120 / 120) G-2 15.1 (4 / 4) N/A 0 (mremlStd. Qtr) [9.8 - 15.1 ] (SE, 1.2 mi.) [13.3 - 16.2]

Gamma 4 (f) N/A N/A N/A 10.3(4/4) 0 Control TLDs

[9.0.-11.0]

(mrem/Std. Qtr) 28

2001 Annual Radiological Waterford 3 Steam Electric Station LI viI 011 Ie ILdl OperwIdL Iing Kepoit TABLE 3.1 Radiological Environmental Monitoring Program Summary Name of Facility: Waterford 3 SES Docket No: 50-382 Location of Facility: St. Charles. Louisiana Reporting Period: January - December 2001 Sample Type Type & Number LLD b Indicator Location Location with Highest Annual Mean Control Number of (Units) of Analyses a Mean ( F ) c Locations Nonroutine Mean (F) c Results e

[Range]

[ Range]

Mean ( F ) c Location d [ Range I Surface Water & Gross Beta 12 4 4.5(8/8) DWG-2 5.3(4/4) 4.4(4/4) 0 Drinking Water [3.2 - 6.2] (SE, 2.0 mi.) [3.9 - 6.2] [3.7 - 5.7 (pCi/I) 1-131 42 1 <LLD N/A N/A <LLD 0 H-3 12 2000 <LLD N/A N/A <LLD 0 GS 12 Mn-54 15 <LLD N/A N/A <LLD 0 Fe-59 30 <LLD N/A N/A <LLD 0 Co-58 15 <LLD N/A N/A <LLD 0 Co-60 15 <LLD N/A N/A <LLD 0 Zn-65 30 <LLD N/A N/A <LLD 0 Zr-95 30 <LLD N/A N/A <LLD 0 Nb-95 15 <LLD N/A N/A <LLD 0 Cs-1 34 15 <LLD N/A N/A <LLD 0 Cs-137 18 <LLD N/A N/A <LLD 0 Ba-140 60 <LLD N/A N/A <LLD 0 La-140 15 <LLD N/A N/A <LLD 0 29

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station TABLE 3.1 Radiological Environmental Monitoring Program Summary Name of Facility: Waterford 3 SES Docket No: 50-382 Location of Facility: St. Charles, Louisiana Reporting Period: January - December 2001 Sample Type Type & LLD b Indicator Locations Location with Highest Annual Mean Control Locations Number of (Units) Number Mean (F) c Mean (F) c Nonroutine of Analyses a [Range] [Range] Results e Mean ( F) c Location d [ Range ]

Groundwater H-3 5 2000 774.5 ( 3/5) GWK-1 774.5 ( 3 / 5) N/A 0 (pCi/I ) [515.0-1136.1] [SSW, 0.5 mi.] [515.0-1136.1]

GS 5 Mn-54 15 <LLD N/A N/A N/A 0 Fe-59 30 <LLD N/A N/A N/A 0 Co-58 15 <LLD N/A N/A N/A 0 Co-60 15 <LLD N/A N/A N/A 0 Zn-65 30 <LLD N/A N/A N/A 0 Zr-95 30 <LLD N/A N/A N/A 0 Nb-95 15 <LLD N/A N/A N/A 0 Cs-134 15 <LLD N/A N/A N/A 0 Cs-137 18 <LLD N/A N/A N/A 0 Ba-140 60 <LLD N/A N/A N/A 0 La-140 15 <LLD N/A N/A N/A 0 Shoreline GS 4 Sediment Cs-1 34 150 <LLD N/A N/A N/A 0 (pCi/kg dry) Cs-137 180 53.0(1/4) SHWE-3 53.0(1/2) N/A 0

[N/A] [E, 3.0 mi.] [N/A]

30

2001 Annual Radiological Waterford 3 Steam Electric Station Environmental Operat~ing RepoiL TABLE 3.1 Radiological Environmental Monitoring Program Summary Name of Facility: Waterford 3 SES Docket No: 50-382 Location of Facility: St. Charles, Louisiana Reporting Period: January - December 2001 Type & Number LLD b Indicator Location with Highest Annual Mean Control Number of Sample Type of Analyses a Location Locations Nonroutine (Units)

Mean (F) c Results e Mean (F) c

[Range] [Range]

Mean ( F ) C Location d [Range]

22 1 <LLD N/A N/A <LLD 0 Milk 1-131 (pCill)

GS 22 Cs-1 34 15 <LLD N/A N/A <LLD 0 Cs-1 37 18 <LLD N/A N/A <LLD 0 Ba-140 60 <LLD N/A N/A <LLD 0 La-140 15 <LLD N/A N/A <LLD 0 Fish GS 9 130 <LLD N/A N/A <LLD 0 (pCilkg wet) Mn-54 Fe-59 260 <LLD N/A N/A <LLD 0 Co-58 130 <LLD N/A N/A <LLD 0 Co-60 130 <LLD N/A N/A <LLD 0 Zn-65 260 <LLD N/A N/A <LLD 0 Cs-134 130 <LLD N/A N/A <LLD 0 Cs-137 150 <LLD N/A N/A <LLD 0 1-131 52 60 <LLD N/A N/A <LLD 0 Broadleaf Vegetation (pCi/kg wet )

GS 52 Cs-1 34 60 <LLD N/A N/A <LLD 0 Cs-1 37 80 <LLD N/A N/A <LLD 0 a GB = Gross beta; 1-131 = Iodine-131; H-3 = Tritium; GS = Gamma scan.

b LLD = Required lower limit of detection based on Waterford 3 TRM.

(F).

c Mean and range based upon detectable measurements only. Fraction of detectable measurements at specified locations is indicated in parenthesis d Locations are specified (1) by name and (2) degrees relative to reactor site.

e Non-routine results are those which exceed ten times the control station value. If no control station value is available, the result is considered non-routine if it exceeds ten times the preoperational value for the location.

f LLD is not defined in Waterford 3 TRM.

31

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Attachment 1 2001 Radiological Monitoring Report Summary of Monitoring Results 32

Annual Radiological 2001 Waterford 3 Steam Electric Station Environmental Operating Report TABLE OF CONTENTS TABLE 1.1 AIR PARTICULATE FILTER 34 35 TABLE 1.2 RADIOIODINE CARTRIDGE 36 TABLE 1.3 AIR PARTICULATE FILTER 37 TABLE 2.1 THERMOLUMINESCENT DOSIMETERS 38 TABLE 3.1 DRINKING/SURFACE WATER 39 TABLE 3.2 DRINKING/SURFACE WATER 40 TABLE 3.3 DRINKING/SURFACE WATER 41 TABLE 3.4 DRINKING/SURFACE WATER 42 TABLE 4.1 GROUNDWATER 43 TABLE 5.1 SEDIMENT 44 TABLE 6.1 MILK 45 TABLE 7.1 FISH 46 TABLE 8.1 BROADLEAF VEGETATION 48 TABLE 9.1 INTERLABORATORY COMPARISON 33

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.1 Sample Type: Air Particulate Filter Analysis: Gross Beta 3

Units: pCi/m Start Date End Date APG-1 APQ-1 APP-1 APC-1 APE-30 (Indicator) (Indicator) (Indicator) (Indicator) (Control)

Required LLD -- 10 0.01 0.01 0.01 0.01 0.01_

12-18-00 01-02-01 0.0251 0.0242 0.0290 0.0176 0.0144 01-02-01 01-16-01 0.0204 0.0223 0.0218 0.0199 0.0210 01-16-01 01-29-01 0.0235 0.0247 0.0234 0.0233 0.0248 01-29-01 02-12-01 0.0177 0.0224 0.0206 0.0185 0.0191 02-12-01 02-26-01 0.0164 0.0145 0.0157 0.0176 0.0166 02-26-01 03-12-01 0.0160 0.0148 0.0152 0.0147 0.0075 03-12-01 03-26-01 0.0139 0.0169 0.0156 0.0154 0.0152 03-26-01 04-10-01 0.0170 0.0201 0.0184 0.0172 0.0191 04-10-01 04-23-01 0.0174 0.0168 0.0175 0.0160 0.0168 04-23-01 05-07-01 0.0203 0.0217 0.0196 0.0201 0.0211 05-07-01 05-21-01 0.0194 0.0207 0.0199 0.0142 0.0191 05-21-01 06-04-01 0.0166 0.0160 0.0148 0.0141 0.0160 06-04-01 06-18-01 0.0144 0.0149 0.0132 0.0131 0.0152 06-18-01 07-02-01 0.0175 0.0154 0.0159 0.0147 0.0162 07-02-01 07-16-01 0.0112 0.0110 0.0099 0.0088 0.0011 07-16-01 07-30-01 0.0142 0.0131 0.0124 0.0124 0.0117 07-30-01 08-13-01 0.0127 0.0133 0.0119 0.0113 0.0103 08-13-01 08-27-01 0.0196 0.0192 0.0191 0.0181 0.0189 08-27-01 09-10-01 0.0112 0.0102 0.0107 0.0093 0.0117 09-10-01 09-24-01 0.0292 0.0304 0.0274 0.0275 0.0287 09-24-01 10-08-01 0.0246 0.0250 0.0238 0.0227 0.0244 10-08-01 10-22-01 0.0184 0.0198 0.0181 0.0173 0.0181 10-22-01 11-05-01 0.0158 0.0165 0.0155 0.0149 0.0158 11-05-01 11-19-01 0.0449 0.0446 0.0440 0.0394 0.0443 11-19-01 12-03-01 0.0156 0.0175 0.0175 0.0166 0.0171 12-03-01 12-17-01 0.0214 0.0226 0.0210 0.0194 0.0210 12-17-01 12-31-01 0.0268 0.0261 0.0258 0.0248 0.0268 34

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.2 Sample Type: Radioiodine Cartridge Analysis: Iodine-131 3

Units: pCi/m Start Date End Date APG-1 APQ-1 APP-1 APC-1 APE-30 (Indicator) (Indicator) (Indicator) (Indicator) (Control)

Required LLD 0.07 0.07 0.07 0.07 0.07

<0.0127 <0.0122 <0.0132 <0.0109 <0.0107 12-18-00 01-02-01

<0.0119 <0.0148 <0.0119 <0.0121 <0.0150 01-02-01 01-16-01

<0.0129 <0.0149 <0.0245 <0.01 39 <0.0163 01-16-01 01-29-01

<0.0133 <0.0218 <0.0139 <0.0131 <0.0139 01-29-01 02-12-01

<0.0143 <0.0135 <0.0128 <0.0120 <0.0125 02-12-01 02-26-01

<0.0120 <0.01 33 <0.0099 <0.0099 <0.0128 02-26-01 03-12-01

<0.0143 <0.0117 <0.0141 <0.0118 <0.0120 03-12-01 03-26-01

<0.0184 <0.0218 <0.0187 <0.0123 <0.0174 03-26-01 04-10-01

<0.0131 <0.0217 <0.0170 <0.0177 <0.0168 04-10-01 04-23-01

<0.0143 <0.0102 <0.0145 <0.0085 <0.0104 04-23-01 05-07-01

<0.0162 <0.0147 <0.0126 <0.0150 <0.0155 05-07-01 05-21-01

<0.0127 <0.0126 <0.0170 <0.0146 05-21-01 06-04-01 <0.0143

<0.0129 <0.0118 <0.0108 <0.0144 <0.0102 06-04-01 06-18-01

<0.0140 <0.0124 <0.0098 <0.0120 <0.0093 06-18-01 07-02-01

<0.0125 <0.01 32 <0.0110 <0.0140 <0.0123 07-02-01 07-16-01

<0.0109 <0.0139 <0.0110 <0.0121 <0.0109 07-16-01 07-30-01

<0.0185 <0.0145 <0.0125 <0.0120 <0.0118 07-30-01 08-13-01

<0.0114 <0.0183 <0.0164 <0.0134 <0.01 59 08-13-01 08-27-01

<0.0154 <0.0170 <0.0145 <0.0116 <0.0138 08-27-01 09-10-01

<0.0176 <0.0136 <0.0150 <0.0148 <0.0144 09-10-01 09-24-01

<0.0138 <0.0104 <0.0092 <0.0143 <0.0098 09-24-01 10-08-01

<0.0148 <0.0139 <0.0128 <0.0016 <0.0162 10-08-01 10-22-01

<0.0212 <0.0271 <0.0194 <0.0215 <0.0213 10-22-01 11-05-01

<0.0225 <0.0197 <0.0200 <0.0226 11-05-01 11-19-01 <0.0261

<0.0151 <0.0137 <0.0133 <0.0137 <0.0145 11-19-01 12-03-01

<0.0137 <0.0158 <0.0138 <0.0148 <0.0134 12-03-01 12-17-01

<0.0155 <0.0155 <0.0184 <0.0123 <0.0167 12-17-01 12-31-01 35

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 1.3 Sample Type: Air Particulate Filter Analysis: Gamma Isotopic Units: pCi/m3 Location Quarterly Cs-1 34 Cs-1 37 Composite Required LLD - 0.05 0.06 APG-1 1st <0.00210 <0.00092 APQ-1 1st <0.00261 <0.00156 APP-1 I st <0.00215 <0.00257 APC-1 1st <0.00243 <0.00257 APE-30 1st <0.00203 <0.00206 APG-1 2nd <0.00215 <0.00167 APQ-1 2nd <0.00218 <0.00238 APP-1 2nd <0.00221 <0.00143 APC-1 2nd <0.00224 <0.00188 APE-30 2nd <0.00113 <0.00181 APG-1 3rd <0.00111 <0.00145 APQ-1 3rd <0.00190 <0.00195 APP-1 3rd <0.00145 <0.001 38 APC-1 3rd <0.00159 <0.00137 APE-30 3rd <0.00169 <0.00118 APG-1 4th <0.00181 <0.00133 APQ-1 4th <0.00232 <0.00208 APP-1 4th <0.00151 <0.00153 APC-1 4th <0.00171 <0.00113 APE-30 4th <0.00163 <0.00143 36

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 2.1 Sample Type: Thermoluminescent Dosimeters Analysis: Gamma Dose Units: mrem/Std. Qtr.-

Indicator Locations Station 1st Qtr'01 2nd Qtr'01 3rd Qtr'01 4th Qtr'01 Annual Mean '01 A-2 13 14 11 13 13 A-5 13 14 11 13 13 B-1 13 14 11 13 13 B-4 14 15 12 14 14 C-1 10 10 9 9 10 D-2 13 14 12 *'21 15 D-5 12 13 10 11 12 E-1 11 12 10 11 11 E-5 11 12 10 11 11 E-15 11 10 9 10 10 F-2 12 12 10 12 12 F-4 14 15 13 15 14 F-9 13 13 11 12 12 G-2* 15 16 13 16 15 G-4 11 12 10 11 11 G-9 12 13 10 11 12 H-2 13 13 12 13 13 H-6 13 12 11 13 12 J-2 12 12 11 12 12 J-15 13 13 11 13 13 K-1 12 12 13 12 12 L-1 14 14 13 12 13 M-1 11 12 10 11 11 N-1 14 14 13 14 14 P-1 10 10 9 10 10 P-6 14 14 13 13 14 Q-1 12 12 11 12 12 Q-5 14 15 12 14 14 R-1 11 11 10 10 10 R-6 11 10 9 11 10 Control Location Station 1st Qtr'01 2nd Qtr'01 3rd Qtr'01 4th Qtr'01 Annual Mean '01 E-30 11 11 9 10 10

  • Location with highest annual mean.
    • TLDs located at D-2 were missing during the fourth quarter due to vandalism. Another set of TLDs were placed in service at this location on 11-13-01.

37

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 3.1 Sample Type: DrinkinglSurface Water Analysis: Gross Beta Units: pCi/I Quarterly DWGISWG-2 DWEISWE-5 DWPISWP-7 Composite (Indicator) (Indicator) (Control)

Required LLD -N 4 4 1st 6.21 5.08 5.65 2nd 6.22 3.38 4.68 3rd 4.73 3.52 3.76 4th 3.87 3.22 3.66 38

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 3.2 Sample Type: DrinkinglSurface Water Analysis: Iodine-131 Units: pCi/I Collection DWGISWG-2 DWEISWE-5 DWPISWP-7 Date (Indicator) (Indicator) (Control)

Required LLD -- I 1 01-02-01 <0.90 <0.67 <0.88 01-29-01 <0.89 <0.90 <0.89 02-28-01 <0.87 <0.90 <0.89 03-26-01 <0.89 <0.77 <0.86 04-23-01 <0.77 <0.88 <0.77 05-21-01 <0.83 <0.89 <0.88 06-18-01 <0.87 <0.89 <0.89 07-16-01 <0.89 <0.88 <0.87 08-13-01 <0.72 <0.90 <0.90 09-10-01 <0.89 <0.89 <0.89 10-08-01 <0.75 <0.89 <0.87 11-05-01 <0.90 <0.90 <0.87 12-03-01 <0.82 <0.86 <0.89 12-31-01 <0.88 <0.88 01-02-02 <0.85 39

2001 Annual Radiological Waterford 3 Steam Electric Station rn,,ir~nmmnn+l nr rofinri P.n t-HV I U"I I IVH 0 ji- . ýj F Table 3.3 Sample Type: Drinking/Surface Water Analysis: Gamma Isotopic Units: pCi/I Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-95 Nb-95 Cs-134 Cs-137 Ba-140 La-140 Location Collection Date 15 30 15 15 30 30 15 15 18 60 15 Required LLD -0I

<2.64 <8.36 <5.01 <4.01 <10.3 <7.61 <4.91 <4.94 <5.09 <17.7 <6.21 DWGISWG-2 (Indicator) 03-26-01

<5.39 <7.11 <3.13 <6.59 <12.6 <10.1 <6.25 <5.93 <5.35 <20.6 <7.33 DWE/SWE-5 (Indicator) 03-26-01

<4.06 <8.19 <4.13 <3.90 <11.1 <8.87 <5.04 <4.88 <3.77 <17.4 <7.83 DWP/SWP-7 (Control) 03-26-01

<5.10 <11.3 <6.80 <5.32 <10.0 <7.83 <7.31 <5.87 <4.91 <21.0 <8.99 DWG/SWG-2 (Indicator) 06-18-01

<5.30 <9.75 <4.41 <4.62 <10.6 <7.44 <6.79 <4.31 <6.39 <18.6 <9.56 DWE/SWE-5 (Indicator) 06-18-01

<5.00 <10.1 <4.72 <3.51 <12.8 <9.25 <7.83 <5.74 <4.93 <22.1 <7.04 DWP/SWP-7 (Control) 06-18-01

<2,99 <7.51 <2.65 <4.20 <8.68 <7.33 <3.88 <4,75 <4.66 <14.9 <4.98 DWGISWG-2 (Indicator) 09-10-01

<5.23 <10.5 <4.63 <4.74 <6.39 <7.47 <4.73 <5.34 <4.55 <17.5 <7.45 DWE/SWE-5 (Indicator) 09-10-01

<6.29 <10.6 <6.06 <3.81 <9.79 <7.65 <4.49 <6.78 <4.31 <15.6 <6.96 DWP/SWP-7 (Control) 09-10-01

<3.77 <8.54 <4.41 <4.19 <10.4 <7.10 <5.87 <3.82 <4.03 <21.8 <5.01 DWG/SWG-2 (Indicator) 12-03-01

<5.92 <9.07 <6.08 <5.93 <11.0 <11.3 <9.28 <6.42 <5.57 <28.5 <9.36 DWE/SWE-5 (Indicator) 12-03-01

<4.42 <10.1 <4.80 <4.87 <9.58 <8.34 <2.86 <5.84 <4.99 <24.3 <6.85 DWP/SWP-7 (Control) 12-03-01 40

Annual Radiological 2001 Environmental Operating Report Table 3.4 Sample Type: DrinkinglSurface Water Analysis: Tritium Units: pCi/I Quarter DWGISWG-2 DWEISWE-5 DWPISWP-7 (Indicator) (Indicator) (Control)

Required LLD -- I* 2000 2000 2000 1st <544.00 <534.84 <534.76 2nd <541.78 <531.30 <533.78 3rd <546.78 <545.61 <542.18 4th <545.54 <527.45 <541.85 41

Annual Radiological 2001 C: nfIfrnnmflnorlfina Oonn l- Waterford 3 Steam Electric Station HV 1VH111WH ý I- . 11 F Table 4.1 Sample Type: Ground Water Analysis: Gamma Isotopic Units: pCi/I Location Collection H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-95 Nb-95 Cs-134 Cs-137 Ba-140 La-140 Date Required LLD -* 2000 15 30 15 15 30 30 15 15 18 60 15 GWK-1 (Indicator) 01-16-01 < 551.72 < 6.65 < 8.01 < 5.29 < 2.92 < 6.97 < 8.13 < 7.67 < 5.28 < 5.84 < 21.90 < 5.74 GWK-1 (Indicator) 01-16-01* < 548.43 < 4.60 < 7.62 < 4.17 < 3.64 < 4.74 < 8.06 < 5.08 < 3.87 < 4.27 < 15.50 < 6.43 GWK-1 (Indicator) 04-16-01 1136.11 < 3.60 < 7.03 < 4.36 < 2.25 < 9.83 < 6.74 < 4.44 < 4.76 < 4.95 < 15.90 < 5.75 GWK-1 (Indicator) 07-02-01 672.45 < 3.45 < 6.88 < 3.89 < 3.39 < 8.64 < 7.00 < 5.13 < 3.79 < 3.57 < 14.80 < 6.31 GWK-1 (Indicator) 10-15-01 515.04 < 5.32 < 6.71 < 4.47 < 4.98 < 7.44 < 9.56 < 4.95 < 5.65 < 5.28 < 17.90 < 8.15

  • Duplicate Sample 42

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 5.1 Sample Type: Sediment Analysis: Gamma Isotopic Units: pCi/kg (dry)

Location Collection Mn-54 Co-58 Co-60 Cs-134 Cs-137 Date Required LLD -0 nl.a nla nla 150 180 SHWK-1 (Indicator) 04-16-01 < 35.9 < 29.6 < 30.7 < 29.6 < 47.3 SHWE-3 (Indicator) 10-15-01 < 43.5 < 41.7 < 51.5 < 40.0 53 SHWK-1 (Indicator) 04-16-01 < 67.7 < 53.5 < 73.1 < 59.9 < 66.2 SHWE-3 (Indicator) 10-15-01 < 78.6 < 55.6 < 71.0 < 66.8 < 75.2 43

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 6.1 Sample Type: Milk Analysis: Iodine-131 and Gamma Isotopic Units: pCi/I Location Collection 1-131 Cs-134 Cs-137 Ba-140 La-140 Date Required LLD I 15 18 60 15 MKQ-5 01-17-01 <0.85 <6.94 <7.36 <25.1 <9.76 MKR-40 01-15-01 <0.85 <6.26 <8.19 <29.0 <8.54 MKQ-5 02-20-01 <0.83 <8.88 <10.8 <34.0 <10.3 MKR-40 02-19-01 <0.63 <8.33 <8.69 <27.7 <9.04 MKQ-5 03-20-01 <0.84 <6.69 <8.33 <26.2 <8.65 MKR-40 03-19-01 <0.73 <7.97 <7.79 <21.7 <10.8 MKQ-5 04-17-01 <0.88 <6.49 <6.37 <20.9 <6.01 MKR-40 04-17-01 <0.67 <7.72 <6.75 <15.6 <6.01 MKQ-5 05-15-01 <0.89 <8.05 <5.72 <24.5 <6.31 MKR-40 05-15-01 <0.76 <7.79 <7.90 <26.8 <6.52 MKQ-5 06-19-01 <0.79 <5.87 <9.15 <23.4 <4.82 MKR-40 06-18-01 <0.75 <6.76 <7.16 <20.0 <7.23 MKQ-5 07-17-01 <0.81 <9.33 <6.62 <29.7 <9.18 MKR-40 07-16-01 <0.80 <10.0 <12.2 <27.3 <13.1

  • n/a
  • n/a
  • n/a MKQ-5
  • n/a
  • n/a
  • n/a MKR-40 08-20-01 <0.68 <6.94 <6.70 <18.2 <6.72
  • n/a
  • n/a
  • n/a MKQ-5
  • n/a
  • n/a
  • n/a MKR-40 09-17-01 <0.89 <6.62 <7.51 <19.5 <6.12 MKQ-5 10-16-01 <0.89 <6.73 <8.56 <24.4 <5.99 MKR-40 10-15-01 <0.83 <6.77 <7.55 <18.7 <3.78 MKQ-5 11-20-01 <0.84 <7.66 <8.39 <30.0 <13.9 MKR-40 11-19-01 <0.90 <5.69 <6.27 <24.0 <8.40 MKQ-5 12-18-01 <0.90 <7.33 <8.48 <25.5 <7.59 MKR-40 12-17-01 <0.88 <7.11 <8.49 <26.2 <7.74
  • Samples not available during this time period due to cow expecting calf.

44

Annual Radiological 2001 Environmental Operatin~q Report Waterford 3 Steam Electric Station Table 7.1 Sample Type: Fish Analysis: Gamma Isotopic Units: pCi/kg (dry)

Location Collection Species Mn-54 Fe-59 Co-58 Co-60 Zn-65 Cs-134 Cs-137 Date Required LLD -1 130 260 130 130 260 130 150 FH-1 (Control) 10-18-01 Carp <16.4 <44.6 <21.6 <17.1 <48.3 <18.9 <16.3 FH-1 (Control) 10-18-01 Catfish <15.5 <60.5 <19.1 <24.2 <56.1 <16.6 <14.2 FH-1 (Control) 10-18-01 Shad <18.5 <59.6 <24.9 <30.1 <60.7 <15.4 <12.7 FH-1 (Control) 10-18-01 Mullet <16.3 <48.4 <23.8 <24.4 <49.3 <16.5 <19.9 FH-2 (Indicator) 10-23-01 Carp <13.7 <20.7 <6.07 <16.3 <33.9 <10.6 <8.09 FH-2 (Indicator) 10-23-01 Catfish <17.3 <28.1 <8.0 <23.1 <39.7 <15.6 <13.1 FH-2 (Indicator) 10-23-01 Shad <9.58 <44.0 <12.1 <20.0 <43.5 <13.8 <9.11 FH-2 (Indicator) 10-23-01 Mullet <15.3 <43.7 <13.0 <18.7 <33.3 <13.0 <13.3 FH-2 (Indicator) 10-23-01 Drum <10.8 <24.3 <15.7 <17.8 <40.0 <15.3 <13.3 45

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 8.1 Sample Type: Broad Leaf Vegetation Analysis: Iodine-131 and Gamma Isotopic Units: pCi/kg (wet)

Location Collection 1-131 Cs-134 Cs-137 Date Required LLD 60 60 80 BLQ-1 (Indicator) 01-08-01 <52.3 <45.9 <36.8 BLQ-1 (Indicator) 02-05-01 <45.5 <39.6 <36.8 BLQ-1 (Indicator) 03-05-01 <58.6 <46.6 <43.2 BLQ-1 (Indicator) 04-02-01 <49.8 <57.0 <53.8 BLQ-1 (Indicator) 04-30-01 <58.3 <34.6 <34.9 BLQ-1 (Indicator) 05-29-01 <59.3 <58.0 <47.2 BLQ-1 (Indicator) 06-25-01 <35.2 <34.1 <48.0 BLQ-1 (Indicator) 07-25-01 <57.3 <36.5 <51.2 BLQ-1 (Indicator) 08-20-01 <43.0 <38.1 <57.1 BLQ-1 (Indicator) 09-17-01 <57.9 <40.2 <42.0 BLQ-1 (Indicator) 10-15-01 <60.0 <32.8 <27.5 BLQ-1 (Indicator) 11-12-01 <47.7 <59.6 <44.5 BLQ-1 (Indicator) 12-11-01 <48.6 <33.2 <26.2 BLB-1 (Indicator) 01-08-01 <51.8 <52.2 <69.7 BLB-1 (Indicator) 02-05-01 <32.9 <29.9 <38.4 BLB-1 (Indicator) 03-05-01 <54.7 <34.4 <21.6 BLB-1 (Indicator) 04-02-01 <59.5 <48.5 <41.1 BLB-1 (Indicator) 04-30-01 <59.3 <46.3 <28.3 BLB-1 (Indicator) 05-29-01 <58.6 <45.7 <46.4 BLB-1 (Indicator) 06-25-01 <57.8 <51.9 <37.5 BLB-1 (Indicator) 07-25-01 <51.9 <39.5 <59.0 BLB-1 (Indicator) 08-20-01 <47.7 <48.2 <63.4 BLB-1 (Indicator) 09-17-01 <59.4 <58.1 <67.8 BLB-1 (Indicator) 10-15-01 <55.5 <37.9 <36.4 BLB-1 (Indicator) 11-12-01 <32.3 <24.3 <26.2 BLB-1 (Indicator) 12-11-01 <58.5 <50.0 <37.9 46

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 8.1 (continued)

Sample Type: Broad Leaf Vegetation Analysis: Iodine-131 and Gamma Isotopic Units: pCi/kg (wet)

Location Collection 1-131 Cs-134 Cs-137 Date Required LLD 0 60 60 80 BLK-15 (Control) 01-08-01 <42.5 <44.1 <47.8 BLK-1 5 (Control) 02-05-01 <52.7 <25.0 <27.2 BLK-15 (Control) 03-05-01 <58.5 <29.4 <29.2 BLK-15 (Control) 04-02-01 <52.5 <36.1 <29.1 BLK-15 (Control) 04-30-01 <59.7 <34.4 <28.4 BLK-15 (Control) 05-29-01 <59.9 <45.8 <42.3 BLK-15 (Control) 06-25-01 <24.9 <25.0 <24.2 BLK-15 (Control) 07-25-01 <59.8 <37.0 <40.0 BLK-15 (Control) 08-20-01 <32.0 <52.8 <38.9 BLK-15 (Control) 09-17-01 <58.3 <42.2 <55.5 BLK-15 (Control) 10-15-01 <52.2 <27.9 <25.3 BLK-15 (Control) 11-12-01 <59.6 <52.9 <48.5 BLK-15 (Control) 12-11-01 <53.8 <26.4 <24.8 BLE-20 (Control) 01-08-01 <42.4 <35.8 <33.1 BLE-20 (Control) 02-05-01 <34.0 <26.5 <39.3 BLE-20 (Control) 03-05-01 <58.8 <31.4 <37.0 BLE-20 (Control) 04-02-01 <43.6 <29.4 <35.4 BLE-20 (Control) 04-30-01 <55.4 <26.7 <27.3 BLE-20 (Control) 05-29-01 <56.5 <50.2 <36.0 BLE-20 (Control) 06-25-01 <35.4 <27.9 <41.7 BLE-20 (Control) 07-25-01 <49.8 <41.2 <34.1 BLE-20 (Control) 08-20-01 <48.3 <42.6 <52.4 BLE-20 (Control) 09-17-01 <47.0 <37.8 <37.3 BLE-20 (Control) 10-15-01 <57.6 <28.9 <37.0 BLE-20 (Control) 11-12-01 <56.0 <45.7 <53.1 BLE-20 (Control) 12-11-01 <58.0 <27.6 <28.1 47

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 9.1 Sample Type: Interlaboratory Comparison Analysis: Gross Beta, Iodine-131, Tritium and Gamma Isotopic Sample Type (units) Study Date Analysis "Valuea R RBS RIBS "Known" Vauo Value N-DEfVb N-RANGEc Air Filter (pCi/filter) E2818-125 9/20/01 BETA 90.0 +/- 17.3 93.0 0.60 0.065 Charcoal Cartridge E2673A-125 6/14/01 1-131 80.0 +/- 13.9 79.8 -0.04 0.148 (pCi/cartridge) E2908_125 1/ 01 _ 39 .+/- 59 8-004 E2908-125 1216/01 1-131 91.0+/-+15.8 90.8 -0.03 0.467 Water (pCi/liter) E2576-125 3/22/01 BETA 168 +/- 43.7 162 -0.44 0.211 E2574-125 3/22/01 CR-51 242 +/- 21.0 240 -0.29 0.391 MN-54 101 +/- 8.75 104 1.03 0.234 CO-58 48.0 +/- 8.66 47.2 -0.28 0.189 FE-59 84.0 +/- 8.66 89.5 1.91 0.992 CO-60 147 +/- 12.7 144 -0.63 0.643 ZN-65 186 +/- 32.2 180 -0.59 0.064 1-131 90.0 +/-15.6 89.6 -0.08 0.965 CS-134 129 +/- 11.2 132 0.90 0.733 CS-137 102 +/- 8.83 101 -0.37 0.845 CE-141 94.0 +/- 8.66 93.4 -0.21 0.697 E2575-125 3/22/01 CR-51 242 +/- 21.0 251 1.24 2.734 (Duplicate) MN-54 101 +/- 8.75 103 0.57 0.234 CO-58 48.0 +/- 8.66 52.3 1.48 0.295 FE-59 84.0 +/- 8.66 91.6 2.63 0.697 CO-60 147 +/- 12.7 140 -1.57 0.321 ZN-65 186 +/- 32.2 187 0.09 0.349 1-131 90.0 +/-15.6 93.7 0.72 1.523 CS-134 129 +/- 11.2 128.7 -0.09 0.733 CS-137 102 +/- 8.83 99.8 -0.76 0.220 CE-141 94.0 +/- 8.66 94.9 0.32 0.591 E2674-125 6/14/01 H-3 7494 +/- 1298 7635 0.33 0.130 E2816-125 9/20/01 CR-51 265 +/- 23.0 269 0.48 1.382 MN-54 149 +/-12.9 155 1.39 0.000 CO-58 128 +/-11.1 127 -0.27 0.369 FE-59 62.0 + 8.66 70.0 2.84 0.473 CO-60 193 + 16.7 197 0.78 0.551 ZN-65 18431.9 185 0.06 0.032 1-131 60.0 +/- 10.4 59.0 -0.19 0.276 CS-134 116 10.1 109 -2.09 0.204 CS-137 232 20.1 233 0.15 0.815 CE-141 88.0 +/- 8.66 91.0 1.17 1.004 48

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Table 9.1 Sample Type: Interlaboratory Comparison Analysis: Gamma Isotopic Sample Type (units) Study Date Analysis "Known" Valuea RBS Value RBS N-DEVb RBS N-RANGEc E2817-125 9/20/01 CR-51 265 +/- 23.0 269 0.57 0.401 (Duplicate) MN-54 149 +/- 12.9 155 1.47 0.159 CO-58 128 +/- 11.1 128 0.09 0.646 FE-59 62.0 +/- 8.66 71 3.24d 0.366 CO-60 193 +/- 16.7 195 0.30 0.796 ZN-65 184 +/- 31.9 189 0.44 0.225 1-131 60.0 +/- 10.4 59.7 -0.09 0.226 CS-134 116 +/- 10.1 111 -1.39 0.306 CS-137 232 +/- 20.1 230 -0.35 0.153 CE-141 88.0 +/- 8.66 94 2.24 0.236 Sediment E2909-125 12/6/01 CR-51 0.631 +/- 0.055 0.613 -0.97 0.600 (pCi/gram) MN-54 0.189 +/- 0.033 0.207 1.69 0.241 Co-58 0.115 +/- 0.010 0.117 0.68 0.267 FE-59 0.129 +/- 0.022 0.145 2.10 0.545 CO-60 0.449 +/- 0.039 0.465 1.21 0.465 ZN-65 0.262 +/- 0.045 0.288 1.70 0.187 CS-1 34 0.252 +/- 0.022 0.250 -0.29 0.319 CS-137 0.531+/- 0.046 0.537 0.39 0.707 CE-141 0.481 +/- 0.042 0.498 1.20 0.069 NOTES

a. The "known" values are listed with a range reflecting control (3 sigma) limits.
b. The normalized deviation from the "known" value is computed from the deviation and the standard error of the mean; +/-2.000 is the warning limit and +/-3.000 is the control limit. This is a measure of accuracy of the analytical methods.
c. The normalized range is computed from the mean range, the control limit, and the standard error of the range; +2.000 is the warning limit and +3.000 is the control limit. This is a measure of precision of the analytical methods.
d. The results reported were outside the control limits.

49

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Interlaboratory Comparison Program Exceptions There was one result outside the control limit for accuracy in the 2001 cross check program participation study. This result was in a gamma isotopic analysis of a duplicate water sample.

The study result outside the control limit for accuracy was the Fe-59 analysis of a duplicate water sample E2817-125 (09/20/01). The Fe-59 result for the other water sample taken during this quarter was within the control limit. RBS normalized-deviation for the analysis was +3.24 with control limits of +/-3.00. This high bias result is considered conservative and has no impact on past results of the program. The bias high result for Fe-59 is contributed to coincidence summing effects. A coincidence summing correction was employed in the past, but was discontinued due to the production of non-conservative low-bias results. Fe-59 results were within control limits in other cross check samples for 2001. The normalized-deviations for Fe-59 in other samples during 2001 were 1.91, 2.63, 2.84, and 2.10.

50

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station ATTACHMENT 2 Statistical Comparisons 51

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station TABLE OF CONTENTS TABLE 2.1 STATISTICAL COMPARISON OF 2001 TLD MEASUREMENTS FROM STATIONS GROUPED BY DISTANCE 55 TABLE 2.2 STATISTICAL COMPARISON OF 2001 TLD RADIATION DOSE TO HISTORICAL DATA BY LOCATION 56 TABLE 2.3 STATISTICAL COMPARISON OF 2001 GROSS BETA ACTIVITY MEASUREMENTS ON AIR PARTICULATE FILTERS 57 TABLE 2.4 STATISTICAL COMPARISON OF 2001 GROSS BETA ACTIVITY MEASUREMENTS IN DRINKING/SURFACE WATER SAMPLES 58 52

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station Statistical Analyses

  • Calculation of the Mean and Standard Deviation The mean and standard deviation for different groups of analyses are calculated using the following equations:

i n and

0.5 where

X = mean of sample population, S = standard deviation of sample population, n = number of samples in sample population, and Xi = value of the i'th sample.

53

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station

+ Comparing Two Sample Population Means The means of two sample populations are compared for statistical difference using the standard 't" test. The use of the test requires the assumption that the data within the populations are normally distributed and that the true standard deviations of the mean are equal for both populations. The standard 't' test tests the hypothesis that the true means of both populations are equal. The "t' value can be calculated from the equation below (obtained from the CRC Standard Mathematical Tables, 26th Edition (1981)):

X-Y t

where:

t = calculated "t" value, X = mean of first data set, Y = mean of second data set, 77x = number of variables in first data set, S x = standard deviation of first data set, 77 = number of variables in second data set, and S y = standard deviation of second data set.

The calculated 't" value is used to test the hypothesis that the true mean of the first population (m x) is equal to the true mean of the second population (m y) assuming that the true standard deviation of both populations are equal (m , = m y). The calculated "t" value is compared to a tabular 't' value such that:

a if t > t p,, then reject the hypothesis when m , > m y,

b. if t < -t P,n then reject the hypothesis when m x < m y,
c. if t > t p/2,, then reject the hypothesis when m x = m y, where t J/2,n and t J,n are the tabular "t" values, with a preselected error (5%), confidence level (1 - p) or (1 p/2), and degrees of freedom n = nx, + ny - 2. Tabular values of the "t" were obtained from the CRC Standard Mathematical Tables, 26th Edition (1981).

54

Annual Radiological 2001

%AlnfnrFrr1'A Qfam IPlmnfriý .Qfnfirnn C:

~IV u;

lvii lii 1i n~If l

(norn4nr aLS 1/4JVI CII O 1ý D nnf

'VIJLJ Mean 12.26 12.66 11.83 (mRem/std.qtr.)

Standard Deviation 1.95 1.55 1.35 (mRemlstd. qtr.)

Number in Sample 64 28 28 Calculated "t" Value 1.07 2.13 NA*

(comparison of stations 0-2 and 2-5 miles from the plant to stations >5 miles from the plant)

Tabular "t" Value at 1.990(a) 2.0060 NA*

95% Confidence(t0 .02 5 ,n)

a. Results indicate the mean for stations located 0-2 miles and 2-5 miles from the plant are statistically identical to the mean for stations located more than 5 miles from the plant.
b. Although the TLD stations located 2-5 miles from the plant are statistically higher than those located more than 5 miles from the plant, the quarterly doses measured in 2001 are consistent with historical data at each location as shown in Table 2.2.

Not Applicable 55

Annual Radiological 2001 PnU~rn:mmntol f"nrtinn I+1onnr"

- - . -- . V- "!:f ýVy Waterford 3 Steam Electric Station A-2 13.9 1.3 A-5 13.3 1.4 11 17 12.8 1.3 11 14 B-1 13.4 1.6 11 19 12.8 1.3 11 14 B-4 13.5 1.2 12 17 13.8 1.3 12 15 C-I 9.1 1.5 7 13 9.5 0.6 9 10 D-2 12.0 2.4 8 19 13.0 1.0 12 14 D-5 12.4 1.7 9 18 11.5 1.3 10 13 E-1 11.4 1.4 10 16 11.0 0.8 10 12 E-5 12.3 1.7 9 17 11.0 0.8 10 12 E-15 11.8 1.9 8 16 10.0 0.8 9 11 E-30* 11.3 1.8 8 17 10.3 1.0 9 11 F-2 12.1 1.3 10 17 11.5 1.0 10 12 F-4 14.4 1.7 11 19 14.3 1.0 13 15 F-9 12.7 1.8 7 17 12.3 1.0 11 13 G-2 15.2 1.3 12 19 15.0 1.4 13 16 G-4 11.5 1.5 9 16 11.0 0.8 10 12 G-9 12.7 2.0 9 19 11.5 1.3 10 13 H-2 13.4 1.3 11 18 12.8 0.5 12 13 H-6 12.3 1.3 10 17 12.3 1.0 11 13 J-2 12.9 1.6 11 17 11.8 0.5 11 12 J-15 12.9 1.5 11 17 12.5 1.0 11 13 K-1 11.4 1.6 9 16 12.3 0.5 12 13 L-1 12.9 1.4 10 16 13.3 1.0 12 14 M-1 12.3 1.6 10 18 11.0 0.8 10 12 N-1 13.5 1.8 8 18 13.8 0.5 13 14 P-1 10.4 1.4 8 15 9.8 0.5 9 10 P-6 13.7 1.7 11 19 13.5 0.6 13 14 Q-1 12.3 1.4 10 16 11.8 0.5 11 12 Q-5 14.5 1.8 9 18 13.8 1.3 12 15 R-1 11.2 1.5 9 15 10.5 0.6 10 11 R-6 13.5 2.5 10 18 10.3 1.0 9 11 a &

  • Control Location

"**Significant outliers were removed from data sets.

PERS data indicates an average of 20 mrem for all indicator locations with a range of 11 to 33 and an average control of 18 mrem.

56

Annual Radiological 2001

\AlnfnrFnrtA 'A Qfam P::lar~fri- qfnfirnn C  ; Ilnnr1;n Innan. 0Dnn4

--. IiV I IIU "iJUI III LOS '.J.,*I I1.1 I LU ., .

Mean 19.3 19.8 19.2 17.7 18.2 (1O'3pCi/m 3)

Standard Deviation 6.72 6.84 6.83 6.05 7.65 (1 0 3pCi/m 3)

Number in Sample 27 27 27 27 27 Calculated "t" Value 0.55 0.80 0.48 0.26 NA*

(comparison of the indicator stations to the control station)

Tabular "t" Value at 2.008(a) 2.008(a) 2.008(a) 2.008(a) NA*

95% Confidence(t0 .02 5 ,n)

& i i I

a. Results indicate the mean for the indicator stations is statistically identical to the mean for the control station.
  • Not Applicable 57

Annual Radiological 2001

\Alnf-*F-Ar 'I Qf==m P::lot-frie', .*'l'flmnn "AVnInUaI IRIoLCog pJICILI20 L 01UI TABLE 2.4 Mean 5.3 3.8 4.4 (pCilliter)

Standard Deviation 1.0 0.7 0.8 (pCi/liter)

Number in Sample 4 4 4 Calculated "t" Value 1.27 1.16 NA*

(comparison of the indicator stations to the control station)

Tabular "t" Value at 2.447(a) 2.447(a) NA*

95% Confidence(t0 .025 ,n)

a. Results indicate the mean for the indicator stations is statistically identical to the mean for the control station.
  • Not Applicable 58

Annual RadiologiGal 2001 c ; In 4; 0 ý# IA/nfmr-F^rr4 'I 4Zfonm Plmýfriý 4Zfnfinn ny ronmenta i1em "m epo 59

Annual Radiological 2001 C- ;r L.I IVHII1l

+ Int ~

III 1 LCII 'JkH

+r;n*D l OLII 1.4 I '.I'I HUL r

l 1A VV 4FAlffrl Q* (Zf-.r IfV l V ,,JLV.L4*

I Il IMlfri, Q:f~finn SIJLI IU SAMPLE LOCATION ANALYSIS FREQUENCY* VOLUME A-2, B-I, C-1, D-2, E-1, F-2, G-2, H-2, J-2, K-1, L-1, M-1, N-i, P-I, Q-1, TLD R-1, A-5, B-4, D-5, E-5 TLD(1 Quarterly N/A F-4, G-4, H-8, P-6, Q-5 R-6, F-9, G-8, E-15, J-15 E-30 Radioiodine and APP-1, APQ-1, APF-1, Gross beta(2), 1-131 Bi-Weekly 285m3 /wk Particulates APC-I, APE-30 y isotopic (2) Quarterly composite 3700m 3/qtr Ground Water NONE NONE NONE NONE H-3 Quarterly composite(5)

DWF-2(4)/SWF-2(4)

Drinking Water/ (3)Surface DWP-7/SWP-7 Gross beta, y, isotopicQurelcopst (5)

Water DWE-5(4)/SWE-5(4) Quarterly composite Homogeneous 8 liters SWK-1 I-131(7) (O SWK-I 1-131 (7) Monthly composite (10)

SHWE-3, SHWK-1, Shoreline Sediment 7 isotopic Annually 2 Kilograms SHWQ-6 Milk MKQ-5, MKR-40 7 isotopic, 1-131 Quarterly 8 liters In season or Fish FH-1, FH-2, FH-3 7 isotopic Annually(9) 500 grams Broad Leaf BLQ-1, BLB-1, BLE-20 y isotopic, 1-131 Quarterly 500 grams (11) (10)

Sanitary System SWR-1 y isotopic Monthly Composite Homogeneous 1 Liter

  • Sample collection at specific locations may be increased at any time in order to increase the effectivenes of the REMP program.

60

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station 1 One or more instrument, such as a pressurized ion chamber, for measuring and recording dose rate continuously may be used in place of, or in addition to, integrating dosimeters. A TLD is considered one phosphor, two or more phosphors in a packet are considered two or more dosimeters. Geographical limitations affect siting of dosimeters.

2. Airborne particulate sample filters shall be analyzed for gross beta radioactivity 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or more after sampling to allow for radon and thoron daughter decay. If gross beta activity in air particulate samples is greater than ten times the yearly mean of control samples, gamma isotopic analysis shall be performed on the individual samples. Gamma isotopic analysis means the identification and quantification of gamma-emitting radionuclides that may be attributable to the effluents from the facility.
3. Drinking Water and Surface Water samples are identical where designated.
4. The downstream sample is beyond the mixing zone.
5. A composite sample will contain aliquots of sample taken proportional to the quantity of flowing liquid that results in a specimen representative of the liquid flow.
6. DELETED
7. This analysis will be performed when the dose calculated for the consumption of water is greater than I mrem per year as calculated for maximum organ and age group.
8. DELETED
9. Striped mullet, gizzard shad, freshwater drum, and catfish will be collected. If they are not available, then substitute species will be collected and identified in reporting.
10. An analysis frequency of every 4 weeks satisfies this requirement. The maximum frequency is monthly.
11. Sanitary System Sampling and analysis performed additionally for this location. This sampling requirement is not derived directly from REMP requirements, but it represents another possible environmental interface with the plant. Information from this sample location will not normally be included in the Annual Radiological Environmental Operating Report.

61

Annual Radiological 2001 Environmental Oneratina Renort S

.................. IW........ * ---- £ Waterford 3 Steam Electric Station SAMPLE LOCATION TABLE LOCATION LOCATION BEARING/

NUMBER DESCRIPTION MILES TO Latitude PLANT Longitude DIRECT RADIATION (TLD)

(Eastbank) Located on a utility pole on 1880 N 30.01381 A-2 LA 628 near the Zephirin L. Periloux 1.27 W 90.46780 Fire House.

(Eastbank) On fence enclosing the 2000 N 30.00576 B-i transmission tower 0.3 miles west (up river) 0.75 W 90.46672 from Little Gyspy on LA 628.

2190 N 30.00307 C-1 (Eastbank) On fence enclosing the Little Gyspy Cooling Water Intake on LA 628 near APC-1. 0.67 W 90.46401 (Eastbank) Located approximately 0.3 miles east of Little Gypsy Power Station 2380 N 30.00471 D-2 on stop sign post located at the peak of the levee on 1.24 W90.45343 the west entrance road through the Bonnet Carre Spillway.

62

Annual Radiological 2001 F.nvir~nnrnnt~l Otv'~r~tinr Rennrt Waterford 3 Steam Electric Station Environme al 0 Veratina Report Waterford 3 Steam Electric Station SAMPLE LOCATION TABLE (Continued)

LOCATION LOCATION BEARING/ Position NUMBER DESCRIPTION MILES TO Latitude PLANT Longitude (continued)

DIRECT RADIATION (TLD) 2770 N 29.99468 E-1 (Westbank) Located on utility pole along LA 18 approximately 0.3 miles 0.41 W 90.46437 east of Waterford 3 plant entrance.

(Westbank) Located on southeast corner of fence enclosure surrounding the Entergy substation, 0.2 miles 2940 N 29.98842 F-2 W 90.45387 south of LA 18 on 1.15 LA 3142.

3090 N 29.98371 G-2 (Westbank) Located on fence east of LA 3142 approximately 0.3 miles north of railroad overpass. 1.26 W 90.45498 (Westbank) Located off LA 3142 on southwest edge of 3270 N 29.97659 H-2 fence along shell road 0.4 miles north of LA 3127/3142 1.54 W 90.45753 intersection.

63

Annual Radiological 2001 Environmental Oneratinu Renort Waterford 3 Steam Electric Station Environmental Operating Report SAMPLE LOCATION TABLE (Continued)

LOCATION LOCATION BEARING/ Position NUMBER DESCRIPTION MILES TO Latitude PLANT Longitude DIRECT RADIATION (TLD) (continued)

(Westbank) Located on fence enclosure for valve station south 3560 N 29.97546 J-2 of LA 3127 approxmiately 0.6 miles west of LA 3127/3142 1.38 W 90.47003 intersection.

230 N 29.98153 K-1 (Westbank) Located on stop sign at entrance to Entergy Education Center on LA 3127. 1.06 W 90.47843 (Westbank) Located on gated entrance off of LA 3127, 420 N 29.98427 L-1 approximately 1.6 miles west of LA 3127/3142 intersection. 1.06 W 90.48314 (Westbank) Located on south gate of 670 N 29.99148 M-1 the Waterford 1 and 2 fuel oil storage tank 0.76 W 90.48286 enclosure.

930 N 29.99649 N-1 (Westbank) Located on pole at comer of Railroad Ave. and School House Road. 0.98 W 90.48739 64

Annual Radiological 2001 lFnvironnrnentat O'ne~rztin* Re~nort Waterford 3 Steam Electric Station En ......m al.. Op .......

rain ......... W aeror .. 3 Steam SAMPLE LOCATION TABLE (Continued)

LOCATION LOCATION BEARING/ Position NUMBER DESCRIPTION MILES TO Latitude PLANT Longitude DIRECT RADIATION (TLD) (continued) 1190 N 30.00158 0.84 W 90.48323 P-1 (Westbank) Located on fence enclosing air sample station APP-I.

(Westbank) Located on fence enclosing air 1320 N 30.00355 Q-1 sample station APQ-1. 0.81 W 90.48091 (Westbank) Located at Waterford 1 and 2 Cooling Water 1470 N 30.00181 R-1 Intake Structure on east hand- rail approximately a 0.51 W 90.47564 quarter of the way down the catwalk.

(Eastbank) Located on utility pole at intersection of Oswald 1770 N 30.06212 A-5 Avenue and US 61. 4.59 W 90.47334 (Eastbank) Located on utility pole guidewire next to 1970 N 30.04717 B-4 transmission tower south of weigh station on US 61 at 3.75 W 90.45130 St. John/ St. Charles Parish line.

65

Annual Radiological 2001 Waterford 3 Steam Electric Station Environmental Operating Report Water rd 3 Steam Electric Station SAMPLE LOCATION TABLE (Continued)

LOCATION LOCATION BEARING/ Position NUMBER MILES TO Latitude DESCRIPTION PLANT Longitude DIRECT RADIATION (TLD) (continued)

(Eastbank) Located on gate on shell road 2490 N 30.01628 D-5 approximately 0.1 miles north of US 61/LA 48 4.09 W 90.40730 intersection.

(Eastbank) Located on the Norco Substation 2660 N 29.99840 E-5 fence enclosure at the end of Wesco St. off of LA4.4.08 W 90.40314 LA 48.

(Westbank) Located on utility pole behind 2890 N 29.97818 F-4 house at 646 Aquarius St. in 3.53 W 90.41582 Hahnville.

(Westbank) Located on railroad sign 309 0 N 29.96507 G-4 on LA 3160 approximately 0.1 miles north of railroad 3.30 W 90.42867 track.

66

Annual Radiological 2001 Pnvirnnmental1 Onerating Renort Waterford 3 Steam Electric Station SAMPLE LOCATION TABLE (Continued)

LOCATION LOCATION BEARING/ Position NUMBER DESCRIPTION MILES TO Latitude PLANT Longitude DIRECT RADIATION (TLD) (continued) 3310 N 29.89178 H-8 (Westbank) Located on a road sign on south side of W 90.40725 HWY 90 directly in front of Hahnville High School 8.13 approximately 0.1 miles east of Tiger Dr..

(Westbank) Located on a fence surrounding 1070 N 30.02121 P-6 the communications tower at the W 90.55941 LA 640/railroad track intersection. 5.58 (Westbank) Located on utility pole along LA 18 across 1290 N 30.04274 Q-5 from Mississippi River marker 137. 5.01 W 90.53464 (Eastbank) Located on fence enclosure approximately 1600 N 30.07108 R-6 0.2 miles west of US 61 on 5.52 W 90.50183 LA 3223 near railroad crossing.

(Eastbank) Located on entrance gate to Destrehan Substation just north of railroad tracks on 2940 N 29.94563 F-9 Jonathan St.. Johnathan St. is approximately 1.5 miles 8.18 W 90.34739 east of Luling-Destrehan Bridge, off of LA 48.

67

Annual Radiological 2001 Envirnnmental One.rating Renort Waterford 3 Steam Electric Station Environmental Oneratinor Renort SAMPLE LOCATION TABLE (Continued)

LOCATION LOCATION BEARING/ Position NUMBER DESCRIPTION MILES TO Latitude PLANT Longitude DIRECT RADIATION (TLD) (continued) 35 05 N 29.93055 W 9.3659 (Westbank) Located on southern most comer of the back fence 774 G-8 7.74 W 90.36592 of Entergy Office in Luling.

(Eastbank) Located on Kenner Substation 2750 N 29.97695 E-15 fence enclosure on Alliance Ave. 11.7 W 90.27658 approximately 0.1 miles from LA 48.

the 3570 N 29.82575 J 5 (Westbank) Located on utility pole near 11.7 W 90.46457 LA 631/Hwy 90 intersection in Des Allemands.

2760 N 29.95233 E30* (Westbank) Located at entrance to the Entergy Office on Delaronde St. in Algiers. 25.2 W 90.05441

  • DENOTES CONTROL LOCATIONS 68

Annual Radiological 2001 lPnvirnnrmpntal O~ne~ratina Renort Waterford 3 Steam Electric Station Enviromnental Operating Report SAMPLE LOCATION TABLE (Continued)

BEARING/ Position LOCATION LOCATION NUMBER DESCRIPTION MILES TO Latitude PLANT Longitude AIRBORNE (Westbank) Located in soybean/sugarcane 1190 N 30.00158 APP-1 field at northwest corner of Short St. 0.84 W 90.48323 in Killona.

(Westbank) Located in soybean/sugarcane field off LA 1320 N 30.00356 APQ-1 18 approximately 0.6 miles east of 0.81 W 90.48093 LA 18/3141 intersection.

2990 N 29.99302 APF-1 (Westbank) Located on north side of Secondary Meteorological Tower. 0.35 W 90.46601 (Eastbank) Located inside the Little Gypsy 2190 N 30.00307 APC-1 Cooling Water Intake Structure fence 0.67 W 90.46401 enclosure.

(Westbank) Located on the roof of the 2760 N 29.95289 APE-30* Energy Office building on 25.2 W 90.05430 Delaronde St. in Algiers.

  • DENOTES CONTROL LOCATIONS 69

Annual Radiological 2001 Environmental Operating Report Waterford 3 Steam Electric Station SAMPLE LOCATION TABLE (Continued)

BEARING/ Position LOCATION LOCATION NUMBER DESCRIPTION MILES TO Latitude PLANT Longitude BROAD LEAF 1320 N 30.00367 BLQ-1 (Westbank) Located near air sample station APQ-1. 0.83 W 90.48132 1970 N 30.00665 BLB-1 (Eastbank) Located near transmission tower west of Little Gypsy on LA 628. 0.81 W 90.46691 2800 N 29.94142 BLE-20* (Westbank) Located on property of Nine Mile Point in W 90.14909 BLE-20* Westwego, LA. 19.7

  • DENOTES CONTROL LOCATION(S) 70

Annual Radiological 2001 F*nvirnnmnt~n1* Onprtirnal R~ncbrt Waterford 3 Steam Electric Station Enviromne al 0 V- eratin WR-ort SAMPLE LOCATION TABLE (Continued)

BEARING/ Position LOCATION LOCATION NUMBER DESCRIPTION MILES TO Latitude PLANT Longitude INGESTION MILK MKQ-5 (Westbank) Located at the Webre's house on 1290 N 30.04224 LA 18 across from Mississppi River marker 137. 4.99 W 90.53467 MKQ-40* (Eastbank) Located at 24254 LA Hwy 442, 1660 N 30.57102 Holden, LA. 40.7 W 90.62381 FISH FH-1* Upstream of the plant intake structure. N/A N/A FH-2 Downstream of the plant discharge structure. N/A N/A FH-3 (Westbank) Waterways downstream of plant discharge N/A N/A I directed to 40 Arpent Canal.

  • DENOTES CONTROL LOCATIONS N/A - Not Applicable for this sampling location.

71

Annual Radiological 2001 Environmental Oneratinn Renort Waterford 3 Steam Electric Station n a . r a.....tin - __ r-En io n SAMPLE LOCATION TABLE (Continued)

BEARING/ Position LOCATION LOCATION DESCRIPTION MILES TO Latitude NUMBER PLANT Longitude WATERBORNE (Westbank) Located at 40 Arpent Canal south of the 140 N 29.98866 SWK-1 plant. The canal is northwest of the shell access 0.49 W 90.47324 road/railroad track intersection.

2760 N 29.99063 SHWE-3 (Westbank) Located at Foot Ferry Landing off LA 18 in Taft. 2.99 W 90.42151 (Westbank) Located at 40 Arpent Canal 140 N 29.98866 SHWK-1 south of plant. The canal is northwest of the shell 0.49 W 90.47324 access road/railroad track intersection.

1290 N 30.05154 SHWQ-6* (Eastbank) Located off LA 628 approximately 0.1 miles east of Reserve ferry landing. 5.99 W 90.54748 DWE-5 (Eastbank) Located at St. Charles 2770 N 29.98622 SWE-5 Parish Waterworks off LA 48 in New Sarpy. 4.59 W 90.39525 DWP-7* (Westbank) Located at St. John Parish 1170 N 30.04629 SWP-7* Waterworks off LA 18 in Edgard. 7.37 W 90.57931 DWF-2 (Westbank) Located Dow Chemical Plant drinking water 3020 N 29.98371 SWF-2 canal. 1.51 W 90.44989

  • DENOTES CONTROL LOCATIONS 72

Annual Radiological 2001 Environmental Oneratin* Renort Waterford 3 Steam Electric Station Envirorunental Oneratinp, Renort SAMPLE LOCATION TABLE (Continued)

LOCATION BEARING/ Position LOCATION NUMBER DESCRIPTION MILES TO Latitude PLANT Longitude SANITARY SYSTEM SWR-I** Sewage lift station NW of MSB between 1530 N 29.99684 Protected Area Fence and LA 18 0.10 W 90.47184 0.1 miles from the plant.

    • Sampling requirements are not derived directly from REMP requirements therefore results will not appear in the annual report. However, it represents another possible environmental interface with the plant.

73