Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000263/LER-1983-021-03, /03L-0:on 831019,calibr of Safeguards Bus Degraded Voltage Relays Performed 8 Days Beyond Allowable Schedule Deviation.Caused by Scheduling Error.Personnel Instructed & Schedule Form Revised + (11:58:21, 14 December 2024)
- ML20082J806 + (11:58:22, 14 December 2024)
- ML20082J790 + (11:58:23, 14 December 2024)
- ML20082J794 + (11:58:23, 14 December 2024)
- ML20082J783 + (11:58:24, 14 December 2024)
- ML20082J784 + (11:58:24, 14 December 2024)
- 05000316/LER-1983-104-03, /03L-0:on 831104,Fire Door 388 to Quadrant 2 of Reactor Cable Tunnel Found Intermittently Unable to Latch. Caused by Bent Door Spindle,Apparently Due to Blow to Knob. Spindle Replaced + (11:58:26, 14 December 2024)
- 05000266/LER-1983-011-03, /03L-0:on 831027,w/unit in Cold Shutdown,Insp of 4,160-volt Ac Breaker for Safety Injection Pump 1P15B Revealed Loose Wire in Lockout Relay Circuit 86.W/circuit Open,Electrical Protection Disabled + (11:58:27, 14 December 2024)
- ML20082J764 + (11:58:28, 14 December 2024)
- ML20082J762 + (11:58:29, 14 December 2024)
- 05000316/LER-1983-103-03, /03L-0:on 831024,letdown Isolation Valve QCR-301 Would Not Close within Specified Time.Caused by Boron Solidification in Stuffing Box Due to Minor Packing Leak. Boric Acid Removed & Packing Adjusted + (11:58:30, 14 December 2024)
- ML20082J759 + (11:58:31, 14 December 2024)
- ML20082J756 + (11:58:32, 14 December 2024)
- 05000315/LER-1983-111-03, /03L-0:on 831024,steam Generator 1-4 Channel IV Pressure Transmitter Removed from Svc to Allow for Repair of Steam Leak Between Transmitter & Transmitter Isolation Valve.Leak Repaired by Replacing Tubing + (11:58:33, 14 December 2024)
- 05000373/LER-1983-134-03, /03L-0:on 831028,blowdown Recorder Failed Downscale & Instrumentation Failed in Radwaste Control Room. Caused by Large Concentrations of Shad Entering Blowdown Line & Plugging Sensing Ports.Probe Repaired + (11:58:35, 14 December 2024)
- ML20082J751 + (11:58:36, 14 December 2024)
- ML20082J737 + (11:58:37, 14 December 2024)
- ML20082J747 + (11:58:37, 14 December 2024)
- 05000305/LER-1983-025-03, /03L-0:on 831025,during Full Power Operation,Svc Water Pump 1A2 Removed from Svc to Perform Maint on Lube Water Line Flow Indicator.Caused by Frozen Check Flapper on Indicator Due to Crud Buildup + (11:58:39, 14 December 2024)
- ML20082J726 + (11:58:40, 14 December 2024)
- ML20082J733 + (11:58:40, 14 December 2024)
- ML20082J725 + (11:58:41, 14 December 2024)
- ML20082J717 + (11:58:42, 14 December 2024)
- ML20082J713 + (11:58:43, 14 December 2024)
- ML20082J708 + (11:58:43, 14 December 2024)
- ML20082J700 + (11:58:44, 14 December 2024)
- 05000373/LER-1983-136-03, /03L-0:on 831026,rod Worth Minimizer Failed to Initialize & Function for Startup.Caused by Failure in Computer Digital Scan Program.Computer Digital Scan Program Reinitialized + (11:58:45, 14 December 2024)
- U-602392, Responds to Concerns About Radiation Protection & Radioactive Source Control Practices + (11:58:48, 14 December 2024)
- 05000254/LER-1983-041-03, /03L-0:on 831019,while Analyzing Standby Liquid Control Sodium Pentaborate Concentration,Concentration Found to Exceed Tech Spec Limits.Caused by Inadequate Procedures. Concentration Tank Temp Increased + (11:58:50, 14 December 2024)
- ML20082J668 + (11:58:51, 14 December 2024)
- ML20082J665 + (11:58:52, 14 December 2024)
- 05000237/LER-1983-079-03, /03L-0:on 831018,while Testing MSIVs 1B & 2B,half Scram Received.Relay 590-102H Found Dropped Out.Caused by Misalignment of Plate Operating Actuating Arm for Limit Switch 1B.Actuating Plate Readjusted + (11:58:57, 14 December 2024)
- ML20082J654 + (11:58:58, 14 December 2024)
- ML20082J643 + (11:58:59, 14 December 2024)
- ML20082J652 + (11:58:59, 14 December 2024)
- 05000305/LER-1983-024-03, /03L-0:on 831020,during Full Power Operation, Technical Review of Maint Work Requests Disclosed That Svc Water Pump 1B2 Removed from Svc on 830914 for Corrective Maint.Limiting Condition Reportable + (11:59:01, 14 December 2024)
- ML20082J638 + (11:59:02, 14 December 2024)
- ML20082J636 + (11:59:03, 14 December 2024)
- ML20082J588 + (11:59:04, 14 December 2024)
- ML20082J635 + (11:59:04, 14 December 2024)
- ML20082J581 + (11:59:05, 14 December 2024)
- 05000331/LER-1983-041-99, /99X-0:on 831028,following Scram,Rcic Would Not Manually Trip.Solenoid Repaired & Reinstalled + (11:59:07, 14 December 2024)
- ML20082J573 + (11:59:09, 14 December 2024)
- ML20082J570 + (11:59:12, 14 December 2024)
- ML20082J563 + (11:59:16, 14 December 2024)
- 05000315/LER-1983-110-03, /03L-0:on 831020,during post-refueling Startup, Fire Suppression Water Sys to Drumming Cask Handling Area Isolated for Repair of Priming Valve on Cask Handling Area Deluge Valve,Contrary to Tech Spec 3.7.9.2 + (11:59:18, 14 December 2024)
- 05000254/LER-1983-040-03, /03L-0:on 831019,11 Instances of Weekly Surveillance Not Performed Identified within Surveillance Interval.Caused by Personnel Error.Shift Engineers Assured Full Compliance for Future Surveillances + (11:59:21, 14 December 2024)
- ML20082J546 + (11:59:22, 14 December 2024)
- ML20082J543 + (11:59:22, 14 December 2024)
- 05000254/LER-1983-042-03, /03L-0:on 831024,station Diesel Fire Pump 1/2A Made Inoperable When Diesel Failed to Start on Battery Bank A.Caused by Battery end-of-life.New Battery Installed + (11:59:25, 14 December 2024)
- 05000373/LER-1983-126-03, /03L-0:on 831027,control Rod Drive at Core Location 30-19 Indicated Overtravel When Withdrawn to Full Out Position During Unit Startup.Caused by Inner Filter Retainer Spring Damage Due to Crud Buildup + (11:59:27, 14 December 2024)