- NPL-97-0177, Forwards Rept 97318-2, Suppl to Evaluation of EQ Impact of Wepc TS Change Request 192, Which Is Needed to Address Four Items + (22:00:08, 11 December 2024)
- LR-N970247, Special Rept 97-01:on 970317,test Failure of 1D-G-400, D Edg.Caused by Failed Emergency Start Preset Relay. Relay Was Immediately Replaced & Retest of D EDG Was Satisfactory + (22:00:09, 11 December 2024)
- ML20140D037 + (22:00:09, 11 December 2024)
- 05000369/LER-1985-038-01, :on 851222,reactor Tripped Due to Turbine Trip from 93% Power.Caused by Ground Fault within Motor Operated Disconnect (MOD) on Main Power Busline 1B.Unit Stabilized & MOD Repaired + (22:00:14, 11 December 2024)
- 05000265/LER-1997-004, Forwards LER 97-004-00,IAW 10CFR50.73(a)(2)(ii)(B).Unit 1 DWEDS & DWFDS Will Be Examined to Verify Video Tape Determination During Next Refueling Shutdown to Ensure Covers on Unit Installed Per Applicable Design Drawings + (22:00:15, 11 December 2024)
- ML20140D032 + (22:00:16, 11 December 2024)
- 05000277/LER-1996-009, :on 961001,declared High Pressure Coolant Injection (HPCI) Sys Inoperable Due to Bearing Misalignment. Realigned Bearing Housing,Performed ST-O-023-200-2 Satisfactorily & Declared HPCI Sys Operable + (22:00:18, 11 December 2024)
- 05000374/LER-1985-048-02, :on 851224,RCIC Water Leg Pump Tripped on Breaker Thermal Overload & Could Not Be Restarted.Work Requests Initiated to Replace Water Leg Pump & Identify Cause of Failure.Supplemental Rept Expected + (22:00:20, 11 December 2024)
- 05000455/LER-1997-001-08, :on 970315,Unit 2 Containment Drain Sys Was Clogged Due to Debris.Water Hose Used to clean-out Connection to Blast Blockage Clear & Floor Drain Oil Separator & Weir Box Was Checked & Cleaned + (22:00:23, 11 December 2024)
- ML20140D024 + (22:00:24, 11 December 2024)
- 05000323/LER-1985-024-01, :on 851225,automatic Reactor & Turbine Trips Occurred During Full Load Rejection Test.Caused by Slow Response of Steam Dump Control Sys.Sys Modified to Improve Steam Dump Valve Response Time + (22:00:34, 11 December 2024)
- ML20140D015 + (22:00:39, 11 December 2024)
- ML20140D016 + (22:00:39, 11 December 2024)
- 05000316/LER-1985-043-01, :on 851227,auxiliary Bldg Ventilation Grab Sample Not Obtained within Time Restraints in Tech Spec 3.3.3.10,Table 3.3-13 Action Item 28.Caused by Personnel Error.Administrative Action Taken + (22:00:47, 11 December 2024)
- 05000254/LER-1997-005-03, :on 970319,HPCI Subsystem Was Made Inoperable to Protect Equipment Due to Uncertainties Re Abandoned Power Feed Cable,Which Had Been Inappropriately Abandoned. Plant Design Documents Have Been Updated + (22:00:49, 11 December 2024)
- ML20140D004 + (22:00:54, 11 December 2024)
- ML20140D008 + (22:00:54, 11 December 2024)
- 05000254/LER-1997-005, Forwards LER 97-005-00 IAW Requirements of 10CFR50.73(a)(2)(v)(D) W/Listed Commitments + (22:00:55, 11 December 2024)
- ML20140D001 + (22:00:56, 11 December 2024)
- IR 05000334/1985027 + (22:01:03, 11 December 2024)
- ML20140C999 + (22:01:04, 11 December 2024)
- ML20140C998 + (22:01:05, 11 December 2024)
- ML20140C997 + (22:01:06, 11 December 2024)
- 05000219/LER-1985-025, :on 851216,inadvertent Automatic Main Steam Line Isolation Occurred During Startup Activities.Caused by Operator Cognitive Error.Operator Training Re Event Will Be Initiated + (22:01:10, 11 December 2024)
- NPL-97-0297, Provides Summary of ECCS Evaluation Model Changes & Errors Identified Since Last Rept + (22:01:11, 11 December 2024)
- ML20140C994 + (22:01:12, 11 December 2024)
- ML20140C993 + (22:01:13, 11 December 2024)
- ML20140C991 + (22:01:13, 11 December 2024)
- ML20140C990 + (22:01:14, 11 December 2024)
- 05000265/LER-1997-003-04, :on 970321,2B Core Spray Room Cooler Fouled Due to Hydrolyzing Debris.Cs Room Cooler Was Cleaned Under Nwr 960039336-01 & Qctp 1110-12, ECCS Room Cooler Trending Program, Has Recently Been Rewritten + (22:01:16, 11 December 2024)
- ML20140C988 + (22:01:16, 11 December 2024)
- 05000458/LER-1985-058, :on 851218,RWCU Sys Isolation Occurred.Caused by RWCU Temp Switch Module Malfunction.Malfunction Due to Internal Capacitor Failure.Temp Switch Replaced & Sys Returned to Svc + (22:01:19, 11 December 2024)
- ML20140C981 + (22:01:20, 11 December 2024)
- 05000298/LER-1986-003, :on 860220,functional Section of Surveillance Procedure 6.1.29 Re APRM Sys Not Performed as Required by Tech Specs.Caused by Rev to Surveillance Testing Schedule. Surveillance Procedure Performed + (22:01:25, 11 December 2024)
- ML20140C977 + (22:01:26, 11 December 2024)
- NSD-NRC-97-5165, Submits Changes to W Response to Open Item That Requested Info on Critical Sections That Committed to Providing Design Summary Rept for Nuclear Island Basemat.Rev Includes Changes to Subsection 3.8.5 + (22:01:27, 11 December 2024)
- ML20140C975 + (22:01:27, 11 December 2024)
- ML20140C970 + (22:01:30, 11 December 2024)
- ML20140C971 + (22:01:30, 11 December 2024)
- ML20140C968 + (22:01:31, 11 December 2024)
- IR 05000289/1985028 + (22:03:35, 11 December 2024)
- ML20140C964 + (22:03:36, 11 December 2024)
- ML20140C962 + (22:03:38, 11 December 2024)
- ML20140C960 + (22:03:39, 11 December 2024)
- 05000251/LER-1985-026-01, :on 851224,480-volt Power Supply Breaker to Backup Group 4A Pressurizer Heaters Discovered to Have No Light Indication.Caused by Backing Off Action by Arcing Contacts.Breaker Manually Tripped + (22:03:41, 11 December 2024)
- NSD-NRC-97-5166, Resubmits AP600 Design Certification Fire Protection Open Items,Marked Up to Reflect Resolution of Comments Received from NRC During Joint Fire Protection Meetings + (22:03:43, 11 December 2024)
- ML20140C954 + (22:03:47, 11 December 2024)
- ML20140C953 + (22:03:48, 11 December 2024)
- ML20140C951 + (22:03:48, 11 December 2024)
- ML20140C949 + (22:03:49, 11 December 2024)
- 05000528/LER-1985-047, :on 850702,fire Watch Performed Late on Main Steam Support Structure.Caused by Personnel Not Gaining Timely Access to Area.Priority Given to Fire Watch Access.W/ + (22:03:51, 11 December 2024)
- ML20140C947 + (22:03:52, 11 December 2024)