- 05000280/LER-1975-015, Updated LER 75-15/01T:on 750803,leaking Fitting on Overhead Gas Compressor B Resulted in Unplanned Release of Radioctive Matl from Site.Caused by Loose Fitting.Leaking Fitting Repaired +
- ML20084N748 +
- ML20198F964 +
- ML20236V318 +
- 05000220/LER-1975-023, :on 750826,iodine Detection Sensitivity Milk Sample Found Inadequate.Caused by Failure of Contractor to Fulfill Procedural Requirements.Contractor Reinstructed +
- 05000220/LER-1975-021, :on 750802,during Routine Surveillance Test RV-30A,core Spray Sparger Tripped at 6.4 Psid Instead of Required 5 Psid.Caused by Setpoint Drift.Redundant Component Operable.Sparger Recalibr +
- 05000220/LER-1975-022, :on 750814,during Routine Operations,Reactor Bldg Vent Monitor Spiked Resulting in Operation of Emergency Vent Sys.Caused by Failed Solenoid & Broken Spring Plunger Nylon Tip.Tip Replaced +
- 05000265/LER-1975-032-01, /01T-0:on 750824,Grinnell & Bergen-Paterson Snubbers Found to Have Empty Oil Reservoirs.Caused by Leaking Fittings & Accumulators.Fittings,Reservoirs & Accumulators Tightened +