PHILA3Z1FEIA ELIOTRIC CCkPA3Y Peach Botto= Ate =ie Fever Otation Delta. Pennsylvania 17314 Septe=ber 3, 1975 Mr.'.*ames P.
O'Beilly, Director Office of Inspection and Enforcenent
- 4. hN M
.h tates nuclear Regulassry Co==ission
- e i
631 parh Avenue i
King of Prussia, Pennsylvania 19LO6
Subject:
Abnornsi Ceeurrence 2*4-Ecur Notifiestion Confirsing R.
S. Fleisch= ann's phone conversation with Mr. Valt Bauna t Recion 1. United States Nuclear Begulatory Con =ission.on Septe=her 3, 1975
Reference:
License Su=ber 0?R-56
'"echnical Specification
Reference:
3.7.D.1
.,Reporf. No.:
50-278-75-5h Report Date:
Septe=ber 3, 1975
- i Occurrence Date:
3epte=ber 2, 1975.
Facility:
Peach Botto= Ato=ic Power Station R.D. 1 Delta, Pennsylvania 17314 Identification of Occurrence:
Instru=ent 31troces Co= pressor Suction Yalve. AO-5235, failed to close during surveillance testing.
s, l
Conditions Prior to occurrence:
~
Hot standby.
4 Description of Cccurrence:
During the perfor=ance of a surveillance test, AO-5235 failed to close when given an isolation signal.
l*
Designation of Apparent'Cause of Occurrence:
- ~
The solenoid valve for operation of AQ-5235 was apparently dirty becat subsequent cycling of the valve caused it to operate correctly.
The cause of the failure is presently under investigation.
~Analysis of Occurrence:
l.'
Safety i=plications are =ini=al, because the valve subsequently I
)
operated correctly several ti=es.
Corrective Action:
..! fader investigation.
Tailur e'~ 3 atsi ~ ~ ~
~
sone.
l l
Very truly yours, I
1
(
fY.W$ss.W
'd. O. Ullrich, Superintendent Peach Botton Ato=ic Power Station I
i i
7 y
-c.
i 8401iB0044'750903 PDR ADOCK 05000278 1
S PDR f1 f'j l
.ppp_sswrarmon
-