Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000302/LER-1983-019-03, /03L-0:on 830406,breaker in Engineered Safeguards (Es) Motor Control Ctr 3B1 Shorted,Rendering Es Bus 3B (480-volt) & Associated Equipment Inoperable.Caused by Personnel Not Properly Aligning Breaker Connectors + (ML20074A582)
- ML20074A583 + (ML20074A583)
- ML20074A584 + (ML20074A584)
- 05000315/LER-1983-033-03, /03L-0:on 830409,during Normal Operation,Following Daily Routine Particulate Filter Change on Lower Containment Airborne Monitor,Train B ERS-1400 Failed to Operate. Cause Unknown.Flush Channel Cleared + (ML20074A586)
- ML20074A587 + (ML20074A587)
- 05000346/LER-1982-020-03, Loss of 120 Volt Alternating Current Distribution Panel Y2 Experienced While in Mode 6.Safety Feature Actuation Signal Channel 2 Actuated.Caused by Blown YV2 Inverter Fuse.Fuse Replaced + (ML20074A591)
- ML20074A594 + (ML20074A594)
- 05000280/LER-1983-068, Forwards Updated LER 83-068/03X-1 + (ML20074A596)
- ML20074A602 + (ML20074A602)
- ML20074A604 + (ML20074A604)
- 05000346/LER-1981-058-01, Very Little Air Flow Through Chlorine Detectors AE5358A & B Observed.On 811009, Detectors Declared Inoperable.Caused by Design Error. Detector Discharge Routed Back to Ventilation Duct + (ML20074A605)
- ML20074A606 + (ML20074A606)
- ML20074A607 + (ML20074A607)
- 05000255/LER-1983-027, Forwards LER 83-027/01T-0 + (ML20074A608)
- ML20074A610 + (ML20074A610)
- 05000254/LER-1983-019, Forwards LER 83-019/03L-0 + (ML20074A612)
- 05000255/LER-1983-027-01, /01T-0:on 830428,w/safety Injection Tank D T-820 Inoperable,Tank T-82B Became Inoperable Due to Low Level. Caused by Leakage Past Fill & Drain Valve on Tank B.Fill & Drain Valves to Be Inspected & Repaired + (ML20074A616)
- ML20074A619 + (ML20074A619)
- 05000254/LER-1983-019-03, /03L-0:on 830412,1A Loop Core Spray Discharge Piping Pressure Indicated Above Tech Specs.Caused by Operator Failure to Properly Bleed Down Core Spray Discharge Piping & Failure of High Pressure Alarm to Annunciate + (ML20074A623)
- ML20074A625 + (ML20074A625)
- 05000255/LER-1983-025, Forwards LER 83-025/03L-0 + (ML20074A629)
- ML20074A631 + (ML20074A631)
- 05000280/LER-1983-020, Forwards LER 83-020/03L-0 + (ML20074A632)
- ML20074A634 + (ML20074A634)
- 05000255/LER-1983-025-03, /03L-0:on 830410,sample from T-82c Showed Boron Concentration Below Tech Spec Limit of 1720 Ppm.Caused by Minor Leakage Past Loop Check Valve & SIT Check Valve. Primary Coolant Leak Rate Being Closely Monitored + (ML20074A635)
- 05000366/LER-1983-019, Forwards LER 83-019/03L-0 + (ML20074A639)
- ML20074A641 + (ML20074A641)
- ML20074A643 + (ML20074A643)
- 05000366/LER-1983-019-03, /03L-0:on 830127,during Fire Protection Isolation Valve Position & Lube Check Procedure HNP-2-3358,lube Oil Room Deluge Sys Isolation Valve 2U43-F101 Found Locked Closed.Cause Unknown.Valve Locked Open + (ML20074A646)
- 05000280/LER-1983-020-03, /03L-0:on 830408,20 of 58 Snubbers Failed to Meet Acceptance Criteria Stipulated in Periodic Test.Caused by Seal Degradation.Snubbers Either Readjusted,Repaired or Replaced + (ML20074A647)
- ML20074A648 + (ML20074A648)
- GO2-83-366, Forwards WNP-2 Project Review of Completed Safety-Related Work, Fourteenth Progress Rept for Jan-Mar 1983,per Util 800717 Commitments in Response to Notice of Violation & Addl Info in Accordance w/10CFR50.54(f) + (ML20074A649)
- ML20074A650 + (ML20074A650)
- ML20074A652 + (ML20074A652)
- ML20074A654 + (ML20074A654)
- ML20074A660 + (ML20074A660)
- ML20074A683 + (ML20074A683)
- ML20074A701 + (ML20074A701)
- ML20074A717 + (ML20074A717)
- ML20074A718 + (ML20074A718)
- ML20074A721 + (ML20074A721)
- ML20074A722 + (ML20074A722)
- 05000361/LER-1983-035, Forwards LER 83-035/03L-0 + (ML20074A724)
- ML20074A726 + (ML20074A726)
- 05000361/LER-1983-035-03, /03L-0:on 830405,pin Hole Leaks Discovered in Mini Flow Line for Auxiliary Feedwater Pump P141,downstream from Flow Orifice FO-4711.P141 Delcared Inoperable.Caused by Cavitation Downstream of Flow Orifice.Pipe Section Replac + (ML20074A727)
- ML20074A731 + (ML20074A731)
- 05000247/LER-1983-010, Forwards LER 83-010/03L-0 + (ML20074A732)
- ML20074A735 + (ML20074A735)
- ML20074A736 + (ML20074A736)
- 05000247/LER-1983-010-03, /03L-0:on 830401,svc Water Pump 25 Declared Inoperable When Pump Could Not Be Restarted After Pump Trip. Caused by Nylon Rope from Old Cathodic Protection Sys in Travelling Screens Wrapping Around Impeller & Shaft + (ML20074A738)
- ML20074A739 + (ML20074A739)