Final Deficiency Rept DER 83-12 Re Malfunction of GE add-on Electric Interlocks Used W/Class Ie,Size 2,starters in 480-volt Motor Control Ctrs.Initially Reported on 830309. Design Change Packages Issued.Also Reportable Per Part 21
ML20074A583
Person / Time
Site: Palo Verde  
Issue date: 05/03/1983
From: Van Brunt E
ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR
To: Sternberg D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
REF-PT21-83 10CFR-050.55E, 10CFR-50.55E, ANPP-23644-RQT, ANPP-23644-RT, DER-83-12, NUDOCS 8305130189
Download: ML20074A583 (5)


Text

.

Ecavio

?:!n Arizona Public Service Company P.o. BOX 21666

  • PHOENIX. ARIZONA 85036 l7,{ *) p is

,7 May 3, 1983 ANPP-236444QT/BSK

,g t o-Y$D U. S. Nuclear Regulatory Commission Region V:

,Creekside Oaks Office Park 1450 Maria Lane - Suite 210 Walnut Creek, California 94596-5368 Attention:

Mr. D. M. Sternberg, Chief Reactor Projects Branch 1

Subject:

Final Report - DER 83-12 A 50.55(e) Reportable Condition Relating to General Electric (GE) 480V MCC Size 2 Starter Add-On Inter-locks May Malfunction File: 83-019-026 D.4.33.2

Reference:

(A) Telephone Conversation between P. Narbut and G. Duckworth on March 9, 1983 (B) ANPP-23415, dated April 4, 1983 (Interim Report)

Dear Sir:

Attached, is our final written report of the Reportable Deficiency under 10CFR50.55(e), referenced above.

Very truly yo rs, R LL-OL E. E. Van Brunt, Jr.

L APS Vice President

(

Nuclear Projects l

ANPP Project Director

(

EEVBJr/RQT:skc l

-Attachment cc: See Page 2 8305130189 830503 DR ADOCK 0500052s l

g PDR i

Mr. D. M. Sternberg, Chief ANPP-23644-RQT/BSK May 3, 1983

- Page 2 cc:

Richard DeYoung, Director Office of Inspection and' Enforcement

- U. S. Nuclear Regulatory Commission Washington, D. C. 20555 T. G. Woods, Jr.

G. C.LAndognini J. A. Roedel D. B. Fasnacht A. C. Rogers B. S. Kaplan W. E. Ide J. Vorees J. R. Bynum P. P. Klute/D. D. Green j-A. C. Gehr W. J. Stubblefield W. G. Bingham R. L. Patterson R. W. Welcher R. M. Grant D. R. Hawkinson L. E. Vorderbrueggen G. A. Fiorelli Records Center.

Institute of Nuclear Power Operations 1100 Circle 75 Parkway - Suite 1500 Atlanta, Georgia 30339 t

i I

l l

l l-l l

r r

9

-ur-s

FINAL REPORT - DER 83-12 DEFICIENCY EVALUATION 50.55(e)

ARIZONA PUBLIC SERVICE COMPANY (APS)

PVNGS UNITS #1 AND #3 1.

Description of Deficiency General Electric (GE) has advised Bechtel Power Corporation that an inherent operational Deficiency may exist in normally open electric interlocks (GE Part No. CR206D022ZACN) used with Class 1E, Size 2, Starters (see attached GE Letter, dated February 9, 1983). These Starters are located in Class 1E 480 Volt Motor Control Centers (MCC's) supplied by GE.

The identified MCC's (1-E-PHA-M31, 1-E-PHB-M32 and 3-E-PHB-M34) are used in conjunction with the following safety-related equipment:

1.

Diesel Generator Control Room Essential AHU Fans M-HDA-A01 and M-HDB-A01 2.

Essential Chilled Water Circulation Pumps M-ECA-P01 and M-ECB-P01 3.

Fuel and Auxiliary Building Essential Exhaust AFU Heater M-HFB-E01 This condition was conveyed to Bechtel after the GE equipment had been received and all of the qualification documentation completed.

II.

Analysis of Safety Implications This condition is evaluated as Reportable. The subject Deficiency could potentially result in the malfunction of the safety-related equipment itemized above, coastituting a safety significant condi-tion as defined by 10CFR50.55(e).

III.

Corrective Action Design Change Package No. ISE-PH-034 and No. 3CE-PH-034 will be issued to implement GE's corrective action plan.

In addition to reportability under 10CFR50.55(e), Bechtel PVNGS Project considers the Deficiency to be Reportable under the require-ments of 10CFR Part 21.

Deficiency Evaluation Report No. 83-12 addresses the reporting requirements specified under 10CFR21.21(b)(3) with the exception of Sub-Part (vi) which requires the number and location (customers and/or facilities) of other possible defective equipment. A copy of this report will be sent to GE requesting their review for reporting under 10CFR Part 21, including number and location of all components supplied.

.a.

-a e*

')

ATTACletENT TO DER 83-12 I NSTALLATION AND GENERAL ELECTRIC SERVICE ENGINEERING DIVISION CENER AL ELECTRIC COMPANY, P. O. BOX 10419, 5320 NORTH 16TH STREET

- PHOENIX, ARIZONA 85064, Phone (602) 241-7237 INDUSTRfAL SERVICES February 9,1983

-/8 43 %

meios,

}%.&#Al!__

FEB 11'83 A

Bechtel Power Corporation m e =aw.es W 12400 East Imperial Highway y

Norwalk, California 90650

/- --

. m una e awass M alt Attention:

W.G. Bingham

.___ man Project Engineering Manager Z

j

Subject:

Palo Verde Nuclear Generating Station

-y wm

_* i

  • Bechtel Job 10407 480V Motor Control Centers; DiO18

_.I Auxiliary interlocks y y'.m i

Dear Mr. Bingham:

.-lj

  • _ sm a v Verde site having Size 2 Starters containing normally open add-on

.Q Please find attached a list of 480V MCC equipment located at the P interlocks that potentially may malfunction.

Replacement interlocks are presently being certified at our Mebane Manufacturing Facility. However, before we send these replacements to the site, we will need the necessary Bechtel identification (i.e.,

DCP #, NCR #, etc.), so that they can be received at the Bechtel Warehouse.

t Please provide me with this information so that we may proceed with shipment.

In addition, General Electric Engineering Services will provide technical direction to direct Bechtel craft labor in the interlock changeout and therefore, I would appreciate knowing who to contact to schedule the work.

l Your assistance in providing me with the necessary information is greatly l

appreciated.

Thank you.

b Paul S. Rinne Field Engineering Supervisor l

Apparatus & Engineering Services cc: Mike Torikan, Bechtel-Downy Rich Roessler, GE-Mebane John Corbitt, GE-Bloomington Les Fickel, GE-Los Angeles Norm David, GE-Phoenix Attachnents W

~,,, _, _ _ _.

..,y

.._.....s_,_.,___.:

O O

  • w IE SIZE 2 STARTERS WITH N.O. ADD-ON BLOCK

/

Customer:

Bechtel/Palo Verde Address:

P.O. Box 49 Customer P.O.:

13-10407-E018-234 Palo Verde, AZ 85343

~

\\

RequisitIbn No.: ~480-55032 Attention: FieId Procurement, G.E. ML'No'.:

443X015---

Jim Crotwell -

G.E.

Cust.

Cust.

MCC No.

ML Item No.

Unit Loc.

G.E. Part No.

Qty. Unit Ref. Device No.

E-PHA-M31 M02 " -~~

DR2 CR2060022ZACN 1

M3116 42 ERI CR2060022ZACN 1

M3118 42 ER2 CR20600222ACN 1

M3113 42

-E-PHB-M32 M03 AR3 CR206D022ZACN 1

M3216 42 CR2 CR20600222ACH I

M3215 42 BFI CR206D0222ACN 1

M3204 42 3-E-P/f B-M34 MO5 BRI CR206D0222ACN 1

M3423 42 1

l 1

. -