List of results
- ML20054H620 + (ML20054H620)
- ML20054H622 + (ML20054H622)
- ML20054H624 + (ML20054H624)
- ML20054H625 + (ML20054H625)
- ML20054H626 + (ML20054H626)
- 05000315/LER-1982-042-03, /03L-0:on 820524,during Operation,Containment Air Particulate Radiation Monitoring Sys (R-11) Found Operating Erratically.Caused by High Ac Ripple on Low Voltage Dc Power Sys.Low Voltage Dc Power Sys Replaced + (ML20054H627)
- ML20054H628 + (ML20054H628)
- ML20054H629 + (ML20054H629)
- B10519, Forwards Startup Test Rept Cycle 5 + (ML20054H632)
- ML20054H634 + (ML20054H634)
- ML20054H635 + (ML20054H635)
- ML20054H637 + (ML20054H637)
- ML20054H638 + (ML20054H638)
- ML20054H639 + (ML20054H639)
- ML20054H641 + (ML20054H641)
- ML20054H642 + (ML20054H642)
- ML20054H644 + (ML20054H644)
- IR 05000341/1982009 + (ML20054H645)
- ML20054H646 + (ML20054H646)
- PNO-I-82-044, on 820619,w/Unit 3 at Full Power,Hpci & Reactor Core Isolation Cooling Sys Injected Water to Core for 30 Before Safety Injection Verified Unnecessary.Caused by Degradation of Power Supply Unit + (ML20054H647)
- ML20054H648 + (ML20054H648)
- 05000338/LER-1982-040, Forwards LER 82-040/03L-0 + (ML20054H649)
- ML20054H651 + (ML20054H651)
- ML20054H652 + (ML20054H652)
- W3P82-1604, Requests Comments on Encl Public Info Brochure by 820625. Aperture Cards Are Available in PDR + (ML20054H653)
- 05000338/LER-1982-035, Forwards LER 82-035/03L-0 + (ML20054H659)
- 05000338/LER-1982-035-03, /03L-0:on 820517,2B Fuel Oil Storage Sys for Emergency Diesel Generators Found Below Tech Spec Limits. Caused by Slow Flow Rate from Transfer Line to Day Tank. Filling Rate to 2B Tank Increased + (ML20054H661)
- ML20054H662 + (ML20054H662)
- ML20054H663 + (ML20054H663)
- ML20054H664 + (ML20054H664)
- 05000327/LER-1982-067, Forwards LER 82-067/03L-0 + (ML20054H665)
- 05000327/LER-1982-067-03, /03L-0:on 820521,diesel Generator 1B-B Declared Inoperable When 120-volt Control Power Fuses Blew During Replacement of Bulb in Control Board.Caused by Shattered Bulb Glass Shorting Filaments.Fuses & Bulbs Replaced + (ML20054H667)
- ML20054H668 + (ML20054H668)
- 05000296/LER-1982-024, Forwards LER 82-024/03L-0 + (ML20054H670)
- IR 05000373/1981030 + (ML20054H672)
- 05000296/LER-1982-024-03, /03L-0:on 820523,during Startup testing,5% Average Insertion Time for All Control Rods Exceeded & 11 2x2 Arrays Failed to Meet 5% Insertion Time for Fastest 3 Rods.Cause Undetermined + (ML20054H673)
- AECM-82-279, Fifth Interim Deficiency Rept Re Valves & Actuators Not Manufactured Under QA Program,Initially Reported 811029.Util to Upgrade Seals,Lubricants & Coatings on Pins & Rollers. Final Rept Expected by 820924 + (ML20054H674)
- ML20054H675 + (ML20054H675)
- 05000338/LER-1982-033, Forwards LER 82-033/03L-0 + (ML20054H676)
- ML20054H678 + (ML20054H678)
- 05000338/LER-1982-033-03, /03L-0:on 820525,w/unit in Mode 5,fire Door M80-1 Between Rod Control Room & Outside Found Blocked Open W/O Fire Watch.Door Blocked by Air & Electrical Lines.Blocks Removed & Door Closed + (ML20054H679)
- 05000213/LER-1982-004, Forwards LER 82-004/01T-0 + (ML20054H680)
- ML20054H682 + (ML20054H682)
- 05000213/LER-1982-004-01, /01T-0:on 820606,during Shutdown,Main Steam Trip Isolation Valve 1 Disassembled to Determine Why Valve Would Not Cycle When Cooled Down.Caused by Misaligned Valve Disc Due to Warped Tail Link + (ML20054H683)
- 05000409/LER-1982-015, Forwards LER 82-015/01T-0.Detailed Event Analysis Submitted + (ML20054H684)
- ML20054H686 + (ML20054H686)
- 05000409/LER-1982-015-01, /01T-0:on 820616,both HPCS Pumps Placed in Pullout & LPCS Valve Control Switch Turned to Close to Prevent Challenging of Eccs.Caused by Shift Supervisor Not Cognizant of Work Scope Involved W/Change + (ML20054H687)
- ML20054H688 + (ML20054H688)
- 05000316/LER-1982-046, Forwards LER 82-046/03L-0 + (ML20054H690)
- 05000316/LER-1982-046-03, /03L-0:on 820520,west Centrifugal Charging Pump Removed from Svc to Repair Leaking 1/2-inch Threaded Seal Water Line Elbow at Inboard Mechanical Seal Hx.Cause of Leak Undetermined.Fitting Removed & Threads Cleaned + (ML20054H694)
- 05000338/LER-1982-040-03, /03L-0:on 820525,pressure in Nitrogen Reservoir for Pressurizer Power Operated Relief Valve (PORV) PCV-1455C Dropped Below Required Min Pressure.Caused by Leakage in PORV Nitrogen Supply Sys.Sys Will Be Modified + (ML20054H696)