Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- IR 05000280/1988031 + (ML18152B101)
- ML18152B102 + (ML18152B102)
- ML18152B103 + (ML18152B103)
- ML18152B104 + (ML18152B104)
- ML18152B106 + (ML18152B106)
- ML18152B107 + (ML18152B107)
- IR 05000280/1988027 + (ML18152B109)
- ML18152B110 + (ML18152B110)
- 05000281/LER-1988-017-02, :on 880730,failure of Recirculation Spray Svc Water MOVs Due to Premature Actuation of Torque Switch. Both Valves Declared Inoperable & Tech Spec 3.0.1 Entered on Basis That Both Subsystems Were Inoperable + (ML18152B111)
- ML18152B112 + (ML18152B112)
- 05000280/LER-1988-023, :on 880802,C Steam Generator Channel IV Steam Flow Failed to Low Flow Indication.Caused by Failed Multiplier/Divider Unit Power Supply Transformer.Technicians Called in & Placed Channels in Trip Mode + (ML18152B113)
- 05000280/LER-1988-028, :on 880801,spent Fuel Assembly Placed in Wrong Location Due to Inadequate Procedure.Fuel Assembly Was Transferred to Region Ii.Other Assemblies Reviewed to Verify Compliance W/Tech Specs + (ML18152B114)
- ML18152B115 + (ML18152B115)
- ML18152B117 + (ML18152B117)
- ML18152B118 + (ML18152B118)
- 05000280/LER-1988-011, :on 880415,PORVs PCV-1455C & PCV-1456 Failed to Manually Open When Selector Switches Placed in Open Position from Auto Position.Caused by Procedural Inadequacy. Valve Actuator Bolts & Screws Torqued + (ML18152B120)
- ML18152B128 + (ML18152B128)
- ML18152B130 + (ML18152B130)
- 05000281/LER-1988-007-02, :on 880405,individual Rod Position Indicators Declared Inoperable Due to Instrument Drift.Setpoint Change Evaluated to Lower Rod Deviation Alarm to Warn Operator Before Deviation Reached + (ML18152B131)
- ML18152B133 + (ML18152B133)
- IR 05000280/1988007 + (ML18152B134)
- IR 05000280/1988004 + (ML18152B135)
- ML18152B136 + (ML18152B136)
- 05000280/LER-1988-010-01, :on 880409,individual Rod Position Indicators (Irpis) Inoperable.Caused by Incorrect Rod Position Indication Due to Primary Coolant Temp Changes.Work Request to Calibr Irpis Submitted + (ML18152B137)
- ML18152B138 + (ML18152B138)
- ML18152B140 + (ML18152B140)
- ML18152B142 + (ML18152B142)
- 05000280/LER-1988-011-01, :on 880415,power-operated Relief Valves Failed to Manually Open When Selector Switches Placed in Open Position.Cause Under Investigation.Selector Switches,Air Supply & Valves Examined for Malfunctions + (ML18152B143)
- IR 05000280/1988001 + (ML18152B146)
- ML18152B148 + (ML18152B148)
- 05000281/LER-1988-009-02, :on 880420,component Cooling Water HXs Declared Inoperable.Caused by Vacuum Priming Lines Up to Isolation Valves Not Being Seismically Supported.Engineering Work Request to Install Seismic Supports Made + (ML18152B152)
- ML18152B153 + (ML18152B153)
- ML18152B154 + (ML18152B154)
- 05000280/LER-1988-012-01, :on 880418,Tech Spec 1.0.H.5 Violated.Caused by Discovery of Valve 1-RS-11 Held in Open Position by Counter Weight Due to Personnel Error.Valves Inspected & Verified to Be in Closed Position & 1-RS-11 Disassembled + (ML18152B156)
- 05000281/LER-1988-011-02, :on 880423,control Room/Relay Room Chiller Removed from Svc After Second Chiller Removed from Svc. Caused by Fouled Chiller Refrigerant filter-dryer Elements. Filter-dryer Elements Replaced + (ML18152B157)
- ML18152B158 + (ML18152B158)
- ML18152B159 + (ML18152B159)
- PNO-II-88-035, on 880524,small Hydrogen Fire Occurred in Containment.Caused by Hydrogen Gas Leaking from Pressure Relief Tank (Prt),Past Valve 2-RC-144 & Out Pipe Nipple & Ignited by Spark.Leakage Flowpath Capped & PRT Purged + (ML18152B160)
- PNO-II-88-034, on 880516,outage Exceeded 48 H.Caused by Time Requirements to Resolve Problems Identified Following 880516 Reactor Trip/Safety Injection Event.Unit Brought to Cold Shutdown on 880517 & Unusual Event Declared Then Terminated + (ML18152B161)
- ML18152B163 + (ML18152B163)
- ML18152B164 + (ML18152B164)
- PNO-II-88-037A, on 880606,licensee Notified Region II That Westinghouse Contract Worker Committed Suicide During Weekend of 880604-05 at Worker Home.Worker Received Quarterly Whole Body Radiation Dose of 3.3 Rem on 880527 + (ML18152B166)
- PNO-II-88-034A, on 880516,reactor Trip/Safety Injection Occurred.Caused by Small Piece of Metal Which Partially Blocking Flow Through Limiting Venturi.Defective Parts Replaced & Course Strainer Installed in Each Line + (ML18152B167)
- PNO-II-88-037, on 880527,Westinghouse Worker Received 2.527 Rem Whole Body Exposure While Cleaning Reactor Vessel Head. Licensee Technician Who Monitored Activity Relieved.Worker Not Expected to Suffer Adverse Health Effects + (ML18152B168)
- ML18152B169 + (ML18152B169)
- ML18152B171 + (ML18152B171)
- ML18152B172 + (ML18152B172)
- ML18152B173 + (ML18152B173)
- ML18152B176 + (ML18152B176)
- 05000281/LER-1988-014-02, :on 880528,RCS PORV PCV-2455C Cycled Open & Closed,Simultaneous W/Rcs Venting & Filling.Caused by Failure to Revise RCS Venting Procedure.Operating Procedures Revised + (ML18152B177)
- ML18152B179 + (ML18152B179)