Text

. --~--,.

..r.;,* ' *,.,

e VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 May 23, 1988 D.S.CRUDEN VICE PRESIDENT-NUCLEAR United States Nuclear Regulatory Commission Serial No.88-101 Attention: Document Control Desk SPS/GDM:pms Washington, D.C. 20555 Docket Nos. 50-280 50-281 Licensee Nos. DPR-32 DPR-37 Gentlemen:

VIRGINIA ELECTRIC & POWER COMPANY SURRY POWER STATION UNITS 1 & 2 RESPONSE TO GENERIC LETTER 88-03 NRC Generic Letter 88-03, Steam Binding of Auxiliary Feedwater Pumps, dated February 17, 1988, requested confirmation that procedures are in pl ace an*ct will be maintained:

I. To monitor fl uid..,.conditions within the Auxiliary Feedwater (AFW) system each shift when the system is required to be operable. The monitoring should ensure fluid temperature at the AFW pump discharge is maintained at approximately ambient levels.

2. For recognizing steam binding and for restoring the AFW system to operable status if steam binding occurs.

Surry Power Station presently has procedures in place to accomplish the above two items. The fluid temperature in the AFW piping is monitored and logged by an operator once per shift. If excessive pipe temperatures are observed, increased surveillance is initiated, and the affected AFW pump is checked to determine if it is vapor bound. If so, corrective measures are undertaken to return the AFW pump to operable status.

The information provided in this response is true and accurate to the best of my knowledge. If you have any further questions, please .contact us.

Very truly yours,

~~----

cc: U.S. Nuclear Regulatory Commission Region II f\o 7 101 Marietta Street, N.W.

Suite 2900 Atlanta, GA 30323 I \

Mr. W. E. Holland NRC Senior Resident Inspector Su r-_~v_f>ower_St.g..tj_on

380527024*9 SE:0523 '. 1 r PDR - ADOC:I< 05000280

e e COMMONWEALTH OF VIRGINIA)

)

CITY OF RICHMOND )

The foregoing document was acknowledged before me, in and for the City and Commonwealth aforesaid, today by D. S. Cruden who is Vice President - Nuclear, of Virginia Electric and Power Company. He is duly authorized to execute and file the foregoing document in behalf of that Company, and the statements in the document are true to the best of his knowledge and belief.

Acknowledged before me t h i s ~ day of ~ , 19 ~ -

My Commission expires: ~NJ ZS 19 9/J .