Issue date | Title | Topic | |
---|---|---|---|
ML20154H615 | 8 October 1998 | Notice of Violation from Insp on 960715-0826 & 1208-970315. Violations Noted:During Periods of Power Operation from Dec 1991 Until 960817 No Channels of High Containment Pressure or Low Pressurizer Pressure Operable in SIAS a | Condition Adverse to Quality Liquid penetrant |
ML20154H642 | 8 October 1998 | Notice of Violation from Insp During Dec 1995 & Oct 1997. Violations Noted:Util Did Not Determine Operating Limits for Cycle 13 Operations Using RELAP5YA SBLOCA Anaylsis Required by TS 5.14.2 | |
ML20247P133 | 20 May 1998 | Notice of Violation from Insp on 980308-0502.Violation Noted:On 980413,items Associated W/Scaffolding Project (Pins,Tie Wraps,Wood Toe Boards & Orange Safety Net) Inside Fuel Foreign Matl Exclusion Zone & Not Logged as Required | Foreign Material Exclusion Scaffolding |
ML20217H249 | 26 March 1998 | Notice of Violation from Insp on 971208-980307.Violation Noted:Air Regulator Outlet Valve & Test Device Relief Valve Isolation Valve Were Not Closed as Specified by Procedure | |
ML20197K176 | 29 December 1997 | Notice of Violation from Insp on 970908-1129.Violation Noted:On 971010,security Force Member Circumvented Reset Button Associated W/Audible Alarm in 1 of Assessment Towers | Fire Watch |
ML20210N963 | 14 August 1997 | Notice of Violation from Insp on 970609-0727.Violation Noted:Operator Failed to Properly Open Suction valve,CPU-2 Prior to Starting Pump P-8 | |
ML20210L081 | 11 July 1997 | Notice of Violation from Insp on 970414-0608.Violation Noted:Ist Requirements of 10CFR50.55a(f) Were Implemented Without Authorization of Director of NRR as Listed | Stroke time Incorporated by reference Condition Adverse to Quality |
ML20140C691 | 5 June 1997 | Notice of Violation from Insp on 970316-0426.Violation Noted:During Testing of Containment Spray Pump on 960409, Operators Failed to Stop Test When Control Room Operator Unexpectedly Started Low Pressure Safety Injection Pump | |
ML20137B619 | 13 March 1997 | Notice of Violation from Insp on 961208-970125.Violation Noted:On Four Occasions from 970107-13,problems Identified That Invalidated Checkout.In Each Problem,Cause of Crane Failure Not Determined & Operability of Crane Not Evaluated | |
ML20135F553 | 9 December 1996 | Notice of Violation from Insp on 960915-1026.Violation Noted:Safeguards Info Was Left Unattended for Approx 2 H on Desk in Security Ofc Inside Protected Areas | |
ML20059A328 | 17 December 1993 | Notice of Violation from Insp on 931012-1119.Violation Noted:Cea Deviation Alarms from Both Computer Pulse Counting Sys & Reed Switch Indicating Sys Were Inoperable & Had Apparently Been in That Condition Since Plant Startup | |
ML20059J717 | 4 November 1993 | Notice of Violation from Insp on 930917-21.Violation Noted: Maint Contract Electricians Did Not Reset Torque Switch to 1 & 1 Prior to Installation | |
ML20058P275 | 15 October 1993 | Notice of Violation from Insp on 920611-0716.Violation Noted:Identified Logs Incomplete & Inaccurate | |
ML20128A594 | 26 January 1993 | Notice of Violation from Insp on 921120-1231.Violation Noted:Failure to Properly Verify Adequacy of Design Review of Primary & Secondary Component Cooling Sys | |
ML20058K297 | 6 December 1990 | Notice of Violation from Insp on 900919-1030.Violation Noted:Inadequate Sealing of Conduit Connection to Multiple Limit Switches & ESF Valve Position Status & Lightboxes Not Supplied by Independent Channels | |
ML20058B935 | 5 October 1990 | Notice of Violation from Insp on 900312-15.Violation Noted:Licensed Training Instructor Did Not Take Required Annual Operating Test | |
ML20055G600 | 19 July 1990 | Notice of Violation from Insp on 900516-0619.Violation Noted:Important Activity Affecting Quality,Rcs Fill & Vent Not Satisfactorily Accomplished When Operators Inadvertently Drained Pressurizer & Reduced Inventory in RCS | |
ML20055G741 | 13 July 1990 | Notice of Violation from Insp on 900605-07.Violations Noted:Licensee Surveys & Evaluations Performed to Support Work on Valve PCC-A-216 During Period 900507-17 Inadequate to Ensure Compliance w/10CFR20.101 & 20.202 | |
ML20244B566 | 7 June 1989 | Notice of Violation from Insp on 880523-0722.Violations Noted:Numerous commercial-grade Items Installed in safety-related Sys W/O Documenting Suitability & Procurement Documents Did Not Specify 10CFR21 Applicability | Condition Adverse to Quality |
ML20245J744 | 25 April 1989 | Partialy Withheld Notice of Violation from Insp on 890320- 24 | |
ML20206G184 | 15 November 1988 | Partially Deleted Notice of Violation from Insp on 880901-1005 (Ref 10CFR73.21).Violations Noted:Security Practices | |
ML20205A820 | 17 October 1988 | Notice of Violation from Insp on 870720-24.Violation Noted: Continental Cable Used in Four of RCS Sys Hot & Cold Leg RTD & States Terminal Used in RCS Cold Leg RTD Loop Circuit Not Included on List of Equipment Important to Safety | |
ML20151A864 | 7 July 1988 | Notice of Violation from Insp on 880527.Violation Noted: Licensed Matl Transfered to Unauthorized Recipient | |
IR 07100117/2012031 | 14 January 1988 | Notice of Violation from Insp on 871117-1231.Violation Noted:Electrical Maint Technicians Did Not Adequately Assure Accuracy of Diagram Included in Repair Order 7277 Prior to Use at Job Location | |
ML20236S557 | 19 November 1987 | Notice of Violation from Insp on 870720-24.Violation Noted: Data of Type Test Results Could Not Be Provided at Time of Insp to Verify Qualification of Connectors Used for Thermocouple Circuits | |
ML20235W447 | 9 October 1987 | Partially Deleted Notice of Violation from Insp on 870608-12 (Ref 10CFR73.21).Violation Noted:Details of Violation Withheld & Assigned Severity Level IV | |
ML20235J280 | 23 September 1987 | Notice of Violation from Insp on 870804-06.Violation Noted: Drill Records Examined for 1985 & 1986 Indicate That Annual Drill for post-accident Sampling & Sample Analysis Has Not Been Performed | |
ML20237J806 | 21 August 1987 | Notice of Violation from Insp on 870601-05.Violation Noted: Lack of Proper Acceptance Criteria for Overcurrent Trip Devices for safety-related Breakers | |
ML20236M124 | 30 July 1987 | Notice of Violation from Insp on 870611-0717.Violation Noted:Door Located in Upper Level of Spray Bldg,Which Controls Access to Lower Levels of Bldg Where Whole Body Radiation Levels Exceed 1,000 M/H,Not in Locked Condition | High Radiation Area Locked High Radiation Area |
ML20235S362 | 14 July 1987 | Notice of Violation from Insp on 870427-30 & 0508-13. Violations Noted:Radiation Work Permits 87-4-231,87-4-232 & 87-4-281 Did Not Indicate Method of High Radiation Area Control or Surveillance Frequency of Checking Work | High Radiation Area Scaffolding |
ML20214D320 | 12 May 1987 | Notice of Violation from Insp on 870406-10 | High Radiation Area |
ML20206A708 | 31 March 1987 | Notice of Violation from Insp on 870126-30 | |
ML20213G050 | 13 November 1986 | Partially Withheld Notice of Violation from Insp on 860911-1022 (Ref 10CFR73.21 & 2.790) | |
ML20206R609 | 26 June 1986 | Notice of Violation from Insp on 860512-16 | |
ML20206M385 | 23 June 1986 | Notice of Violation from Insp on 860212-15 | |
ML20203F331 | 18 April 1986 | Notice of Violation from Insp on 860310-14 | |
ML20210E041 | 21 March 1986 | Notice of Violation from Insp on 860112-0222 | |
ML20151T762 | 4 February 1986 | Notice of Violation from Performance Assessment Team Insp on 850513-24 & 0603-07 & Followup Insp on 851105-1231 | |
ML20138Q510 | 3 December 1985 | Notice of Violation from Insp on 851105-08 | |
ML20134A420 | 29 October 1985 | Unsigned & Undated Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $80,000.Violations Noted:All Channels of Reactor Protective Sys for Each of Three Steam Generators Inoperable for Low Steam Generator Pressure | |
ML20148R952 | 29 September 1978 | Notice of Violation from Inspec on 780905-08 | Condition Adverse to Quality |
ML20148J044 | 12 September 1978 | Notice of Violation from Inspec on 780821-23 |