RC-96-0035, Application for Amend to License NPF-12,revising Testing Methodology Utilized by Facility to Determine Operability of Charcoal Filters in ESF Air Handling Units

From kanterella
Jump to navigation Jump to search
Application for Amend to License NPF-12,revising Testing Methodology Utilized by Facility to Determine Operability of Charcoal Filters in ESF Air Handling Units
ML20097F463
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 02/10/1996
From: Byrne S
SOUTH CAROLINA ELECTRIC & GAS CO.
To: Tilda Liu
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20097F470 List:
References
RC-96-0035, RC-96-35, NUDOCS 9602160072
Download: ML20097F463 (3)


Text

. ~_ . . . . _ _ _ __

, South Carolina Elsctric & Gas Company

. Virgil C. Summ!r Nucisar Station S. A.Byrne

  • 8 P. O. Box 88 GeneralMan gtr, Jenkinsville, SC 29065 Nuclear Plant Operations

. (803)345-5209 Ascamcmvany February 10,1996 RC-96-0035 Document Control Desk U. S. Nuclear Regulatory Commission ,

Washington, DC 20555 l Attention: Ms. Tilda Y. Liu Gentlemen:

Subject:

VIRGIL C. SUMMER NUCLEAR STATION (VCSNS)

DOCKET No.50/395 OPERATING LICENSE No.NPF-12 EMERGENCY TECHNICAL SPECIFICATION CHANGE REQUEST TSP 960002, CHARCOAL FILTERS South Carolina Electric & Gas Company (SCE&G), acting for itself and as agent for l South Carolina Public Service Authority, hereby requests an emergency amendment 1 to the Virgil C. Summer Nuclear Station (VCSNS) Technical Specifications (TS) in accordance with 10CFR50.90. The proposed changes will revise the testing methodology utilized by VCSNS to determine the operability of the charcoal filters in the engineering safeguards features (ESF) air handling units.

Currently, the station tests the charcoal in the ESF air handling units per ANSI N509-1980. Although this method of testing provides better assurance that these air handling units will perform their design function, it does not meet the requirements of the TS. Therefore, an emergency TS amendment is being submitted to recognize current testing methodology to preclude an unnecessary plant shutdown. A significant reduction in pubh,c health and safety does not exist. The justification for an emergency TS change is attached.

TS pages 3/4 7-15 and 3/4 9-13, relating to Surveillance Requirements for charcoal filter laboratory testing, are being revised such that existing flawed test methodology in the TS will reflect the currently utilized acceptable test methodology in accordance with industry standards. SCE&G is currently aware that the NRC believes that ASTM D 3803-1989 is the preferred test methodology. An additional submittal will be forthcoming to incorporate this standard into our TS.

The TS change request (TSCR) is contained in the following attachments:

AttachmentI Explanation of Changes Summary Marked-up Technical Specification Pages Revised Technical Specification Pages l AttachmentII Justification for Emergency Action AttachmentIII Safety Evaluation AttachmentIV No Significant Hazards Determination Attachment V Environmental Impact Determination 9602160072 960210 PDR ADOCK 05000395 ,h p PDR g 1cc02o \\

.l Document Control Desk TSP 960002

. RC-96-0035 Page 2 of 2 This proposed TSCR has been reviewed and approved by the Plant Safety Review Committee and the Nuclear Safety Review Committee.

These statements and matters set forth herein are true and correct to the best of my knowledge,information and belief.

Should you have questions, please call Mr. Michael Zaccone at (803) 345-4328.

Very truly yours, f 0'h A MJZ/GJT/dr Attachments (4) c: J. L. Skolds (w/o Attachments) S. D. Ebneter O. W. Dixon NRC ResidentInspector R. R. Mahan (w/o Attachments) J. B. Knotts Jr.

R. J. White M. K. Batavia Roy P. Zimmerman K. R. Jackson Frederick J. Hebdon DMS John J. Hayes, Jr RTS(TSP 960002)

File (813.20)

STATE OF SOUTHCAROLINA  :

TO WIT :

COUNTY OF FAIRFIELD  :

I hereby certify that on the / o* day of /ra 19 94 ,before me, the subscriber, a Notary Pubile of the State of South Carolina, personally appeared Stephen A.

Byrne being duly sworn, and states that he is General Manager, Nuclear Plant erations of the South Carolina Electric & Gas Company, a corporation of the State o uth Carolina, that he provides the foregoin g response for the pur ?oses therein set forth, that the statements made are true anc correct to the best of ais knowle e, information, and belief, and that he was authorized to provide the response on be If of said Corporation.

WITNESS my Hand and Notarial Seal Adb NotaryPublic f

I My Commission Expires ( 4 / 3,. 2.o o r  !

l 1

NUCLEAR EXCELLENCE - A SUMMER TRADITION! l l

g_ _

Document Control Desk l Attachment I TSP 960002

.RC-96-0035 Page l ofi i SCE&G -- Explanation of Changes Summary i

^If t d PAGE Description ofChange Reason for Change Seetion 3/4 7-15 4.7.6.c.2 1 Replaced words: To reflect a proposed change to the

" Regulatory Position C.6.a of Regulatory testing criteria stated in Technical ,

Guide 1.52, Revision 2, March 1978." Specifications for the testing ofcarbon with: samples from the Control Room

" ANSI N509 1980, at a relative humidity Emergency Ventilation System charcoal of 70% and 25 C with a methyliodide adsorbers.

penetration of <1%."

4.7.6.d 2 Replaced words: To reflect a proposed change to the

" Regulatory Position C.6.a of Regulatory testing criteria stated in Technical Guide 1.52, Revision 2, March 1978." Specifications for the testing of carbon with: samples from the Control Room

" ANSI N509-1980, at a relative humidity Emergency Ventilation System charcoal of 70% and 25 C with a methyliodide adsorbers.

penetration of <1%."

3/4 9-13 4.9.11.b.2 1 Replaced words: To reficct a proposed change to the

" Regulatory Position C.6.a of Regulatory testing criteria for the testing of carbon Guide 1.52, Revision 2, March 1978." samples from the Fuel Handling with: Building Exhaust System charcoal

" ANSI N509-1980, at a test media adsorbers.

temperature of 30 C."

4.9.11.c 2 Replaced words: To reflect a proposed change to the

" Regulatory Position C 6.a of Regulatory testing criteria for the testing of carbon Guide 1.52, Revision 2, March 1978." samples from the Fuel Handling with: Building Exhaust System charcoal

" ANSI N509-1980, at a test media adsorbers. l temperature of 30 C."

l 1