ND-21-1026, ITAAC Closure Notification on Completion of ITAAC 2.6.01.02.i (Index Number 579)

From kanterella
(Redirected from ML22045A971)
Jump to navigation Jump to search

ITAAC Closure Notification on Completion of ITAAC 2.6.01.02.i (Index Number 579)
ML22045A971
Person / Time
Site: Vogtle 
Issue date: 02/14/2022
From: Yox M
Southern Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
ND-21-1026
Download: ML22045A971 (8)


Text

^

Southern Nuclear Michael J. Yox Regulatory Affairs Director Vogtie 3 & 4 7825 River Road Waynesboro, GA 30830 706-848-6459 tei FEB 1 4 2022 Docket No:

52-025 ND-21-1026 10CFR 52.99(c)(1)

U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 Southern Nuclear Operating Company Vogtie Electric Generating Plant Unit 3 ITAAC Closure Notification on Completion of ITAAC 2.6.01.02.1 (Index Number 5791 Ladies and Gentlemen:

In accordance with 10 CFR 52.99(c)(1), the purpose of this letter is to notify the Nuclear Regulatory Commission (NRC) of the completion of Vogtie Electric Generating Plant (VEGP) Unit 3 Inspections, Tests, Analyses, and Acceptance Criteria (ITAAC) Item 2.6.01.02.1 [Index Number 579]. This ITAAC confirms that the seismic Category I Main AC Power System equipment identified in the VEGP Unit 3 Combined License (COL) Appendix C, Table 2.6.1-1 can withstand seismic design basis loads without loss of safety function. The closure process for this ITAAC is based on the guidance described in Nuclear Energy Institute (NEI) 08-01, "Industry Guideline for the ITAAC Closure Process Under 10 CFR Part 52," which was endorsed by the NRC in Regulatory Guide 1.215.

This letter contains no new NRC regulatory commitments. Southern Nuclear Operating Company (SNC) requests NRC staff confirmation of this determination and publication of the required notice in the Federal Register per 10 CFR 52.99.

If there are any questions, please contact Kelli Roberts at 706-848-6991.

Respectfully submitted, Michael J. Yox^

Regulatory Affairs irector Vogtie 3 & 4

Enclosure:

Vogtie Electric Generating Plant (VEGP) Unit 3 Completion of ITAAC 2.6.01.02.1 [Index Number 579]

MJY/JMF/sfr

U.S. Nuclear Regulatory Commission ND-21-1026 Page 2 of 3 To:

Southern Nuclear Operating Company/ Georgia Power Company Mr. Peter P. Sena III Mr. D. L. McKinney Mr. H. NIeh Mr. G. Chick Mr. S. Stimac Mr. P. Martino Mr. J.B. Williams Mr. M. J. Vox Mr. A. S. Parton Ms. K. A. Roberts Ms.'J.M. Coleman Mr. C. T. Defnall Mr. C. E. Morrow Mr. K. J. Drudy Mr. J. M. Fisher Mr. R. L. Belike Mr. S. Leighty Ms. A. C. Chamberlain Mr. J. C. Haswell Document Services RTYPE: VND.LI.L06 File AR.01.02.06 Nuclear Regulatory Commission Ms. M. Bailey Mr. M. King Mr. G. Bowman Ms. A. Veil Mr. C. P. Patel Mr. G. J. Khourl Mr. C. J. Even Mr. B. J. Kemker Ms. N. C. Coovert Mr. C. Welch Mr. J. Gaslevic Mr. O. Lopez-Santiago Mr. G. Armstrong Mr. M. Webb Mr. T. Fredette Mr. C. Santos Mr. B. Davis Mr. J. Vasquez Mr. J. Eargle Mr. T. Fanelli Ms. K. McCurry Mr. J. Parent Mr. B. Griman Mr. V. Hall

U.S. Nuclear Regulatory Commission ND-21-1026 Page 3 of 3 Qqlethorpe Power Corporation Mr. R. B. Brinkman Mr. E. Rasmussen Municipal Electric Authority of Georgia Mr. J. E. Fuller Mr. 8. M. Jackson Dalton Utilities Mr. T. Bundros Westinqhouse Electric Company. LLC Dr. L. Orlani Mr. D. 0. Durham Mr. M. M. Corletti Mr. Z. 8. Harper Mr. J. L. Coward Other Mr. 8. W. Kline, Bechtel Power Corporation Ms. L. Matis, Tetra Tech NUS, Inc.

Dr. W. R. Jacobs, Jr., Ph.D., CDS Associates, Inc.

Mr. 8. Roetger, Georgia Public Service Commission Mr. R. L. Trokey, Georgia Public Service Commission Mr. K. C. Greene, Troutman Sanders Mr. 8. Blanton, Balch Bingham

U.S. Nuclear Regulatory Commission ND-21-1026 Enclosure Page 1 of 5 Southern Nuclear Operating Company ND-21-1026 Enclosure Vogtle Electric Generating Plant (VEGP) Unit 3 Completion of ITAAC 2.6.01.02.1 [Index Number 579]

U.S. Nuclear Regulatory Commission ND-21-1026 Enclosure Page 2 of 5 ITAAC Statement Desion Commitment

2. The seismic Category I equipment identified in Table 2.6.1-1 can withstand seismic design basis loads without loss of safety function.

Insoections/Tests/Analvses i) Inspection will be performed to verify that the seismic Category I equipment identified in Table 2.6.1-1 is located on the Nuclear Island.

ii) Type tests, analyses, or a combination of type tests and analyses of seismic Category I equipment will be performed.

iii) Inspection will be performed for the existence of a report verifying that the as-built equipment including anchorage is seismically bounded by the tested or analyzed conditions.

Acceptance Criteria i) The seismic Category I equipment identified in Table 2.6.1-1 is located on the Nuclear Island.

ii) A report exists and concludes that the seismic Category I equipment can withstand seismic design basis loads without loss of safety function.

iii) A report exists and concludes that the as-built equipment including anchorage is seismically bounded by the tested or analyzed conditions.

ITAAC Determination Basis This ITAAC requires that inspections, tests, and analyses be performed and documented to ensure the Main AC Power System (ECS) equipment identified as seismic Category I or Class 1E in the Combined License (COL) Appendix C, Table 2.6.1-1 (the Table) are designed and constructed in accordance with applicable requirements.

i) The seismic Cateaorv I eouipment identified in Table 2.6.1-1 is located on the Nuclear Island.

To assure that seismic Category I equipment can withstand seismic design basis loads without loss of safety function, all the equipment in the Table is designed to be located on the seismic Category I Nuclear Island. In accordance with Equipment Qualification (EQ) Walkdown ITAAC Guideline and the EQ ITAAC As-Built Installation Documentation Guideline (References 1 and 2), an inspection was conducted of the ECS to confirm the satisfactory installation of the seismically qualified equipment.

The inspection includes verification of equipment make/model/serial number and verification of equipment location (Building, Elevation, Room). The EQ As-Built Reconciliation Reports (EQRR)

(Reference 3) identified in Attachment A document the results of the inspection and conclude that the seismic Category I equipment is located on the Nuclear Island.

ii) A report exists and concludes that the seismic Cateaorv I eouipment can withstand seismic design basis loads without loss of safetv function.

U.S. Nuclear Regulatory Commission ND-21-1026 Enclosure Page 3 of 5 Seismic Category I equipment in the Table requires type tests and/or analyses to demonstrate structural integrity and operability. Safety-related (Class 1E) electrical equipment in the Table was seismically qualified by type testing combined with analysis in accordance with Institute of Electrical and Electronics Engineers (IEEE) Standard 344-1987 (Reference 4). The specific qualification method (i.e., type testing, analysis, or combination) used for each piece of equipment in the Table is identified in Attachment A. Additional information about the methods used to qualify API 000 safety-related equipment is provided in the Updated Final Safety Analysis Report (UFSAR) Appendix 3D (Reference 5). The EQ Reports (Reference 6) identified in Attachment A contain applicable test reports and associated documentation and conclude that the seismic Category I equipment can withstand seismic design basis loads without loss of safety function.

iii) A report exists and concludes that the as-built equipment including anchorage is seismicallv bounded bv the tested or analyzed conditions.

An inspection (References 1 and 2) was conducted to confirm the satisfactory installation of the seismically qualified equipment in the Table. The inspection verifies the equipment make/model/serial number, as-designed equipment mounting orientation, anchorage and clearances, and electrical and other interfaces. The documentation of installed configuration of seismically qualified equipment includes photographs and/or sketches/drawings of equipment/mounting/interfaces.

As part of the seismic qualification program, consideration is given to the definition of the clearances needed around the equipment mounted in the plant to permit the equipment to move during a postulated seismic event without causing impact between adjacent pieces of safety-related equipment. When required, seismic testing by measuring the maximum dynamic relative displacement of the top and bottom of the equipment was performed. EQ Reports (Reference 6) identified the equipment mounting employed for qualification and establish interface requirements for assuring that subsequent in-plant installation does not degrade the established qualification. Interface requirements are defined based on the test configuration and other design requirements.

Attachment A identifies the EQRR (Reference 3) completed to verify that the as-built seismic Category I equipment listed in the Table, including anchorage, are seismically bounded by the tested or analyzed conditions, IEEE Standard 344-1987 (Reference 4) and NRG Regulatory Guide (RG) 1.100 (Reference 7).

Together, these reports (References 3 and 6) provide evidence that the ITAAC Acceptance Criteria requirements are met:

The seismic Category I equipment identified in Table 2.6.1-1 is located on the Nuclear Island; A report exists and concludes that the seismic Category I equipment can withstand seismic design basis loads without loss of safety function; and A report exists and concludes that the as-built equipment including anchorage is seismically bounded by the tested or analyzed conditions.

References 3 and 6 are available for NRC inspection as part of the Unit 3 ITAAC 2.6.01.02.1 Completion Package (Reference 8).

U.S. Nuclear Regulatory Commission ND-21-1026 Enclosure Page 4 of 5 ITAAC Finding Review In accordance with plant procedures for ITAAC completion, Southern Nuclear Operating Company (SNC) performed a review of all ITAAC findings pertaining to the subject ITAAC and associated corrective actions. This finding review, which Included now-consolidated ITAAC Index Numbers 580 and 581, found no relevant ITAAC findings associated with this ITAAC. The ITAAC completion review Is documented In the ITAAC Completion Package for ITAAC 2.6.01.02.1 (Reference 8) and Is available for NRC review.

ITAAC Completion Statement Based on the above Information, SNC hereby notifies the NRC that ITAAC 2.6.01.02.1 was performed for VEGP Ujilt 3 and that the prescribed acceptance criteria were met.

Systems, structures, and components verified as part of this ITAAC are being maintained In their as-designed, ITAAC compliant condition In accordance with approved plant programs and procedures.

References (available for NRC inspection^

1. ND-RA-001-014, EQ ITAAC As-bullt Walkdown Guideline, Version 3.1
2. ND-RA-001-016, "EQ ITAAC As-bullt Installation Documentation Guideline", Version 1.0
3. EQ As-Bullt Equipment Qualification Reconciliation Reports (EQRRs) as Identified In Attachment A
4. IEEE Standard 344-1987, IEEE Recommended Practice for Seismic Qualification of Class 1E Equipment for Nuclear Power Generating Stations
5. Vogtle 3&4 Updated Final Safety Analysis Report Appendix 3D, Methodology for Qualifying APIOOO Safety-Related Electrical and Mechanical Equipment, Revision 10.1
6. Equipment Qualification (EQ) Reports as Identified In Attachment A
7. NRC Regulatory Guide 1.100, Seismic Qualification of Electric and Mechanical Equipment for Nuclear Power Plants, Revision 2
8. 2.6.01.02.l-U3-CP-Rev 0, Completion Package for Unit 3 ITAAC 2.6.01.02.1 [Index Number 579]

U.S. Nuclear Regulatory Commission ND-21-1026 Enclosure Page 5 of 5 Attachment A System: Main ac Power System (ECS)

Equipment Name ^

Tag No. +

Seismic Cat. 1 +

Type of Qual.

EQ Reports As-Buiit EQRR Reactor Coolant Pump (RCP)

Circuit Breaker ECS-ES-31 Yes Type Test

& Analysis SV3-ES02-VBR-003 /

SV3-ES02-VBR-001 2.6.01.02.i-U3-EQRR-PCDOOI-RevO RCP Circuit Breaker ECS-ES-32 Yes Type Test

& Analysis SV3-ES02-VBR-003 /

SV3-ES02-VBR-001 2.6.01.02.i-U3-EQRR-PCDOOI-RevO RCP Circuit Breaker ECS-ES-41 Yes Type Test

& Analysis SV3-ES02-VBR-003 /

SV3-ES02-VBR-001 2.6.01.02.i-U3-EQRR-PCDOOI-RevO RCP Circuit Breaker ECS-ES-42 Yes Type Test

& Analysis SV3-ES02-VBR-003 /

SV3-ES02-VBR-001 2.6.01.02.i-U3-EQRR-PCDOOI-RevO RCP Circuit Breaker ECS-ES-51 Yes Type Test

& Analysis SV3-ES02-VBR-003 /

SV3-ES02-VBR-001 2.6.01.02.i-U3-EQRR-PCDOOI-RevO RCP Circuit Breaker ECS-ES-52 Yes Type Test

& Analysis SV3-ES02-VBR-003 /

SV3-ES02-VBR-001 2.6.01.02.i-U3-EQRR-PCDOOI-RevO RCP Circuit Breaker ECS-ES-61 Yes Type Test

& Analysis SV3-ES02-VBR-003 /

SV3-ES02-VBR'-001 2.6.01.02.i-U3-EQRR-PCDOOI-RevO RCP Circuit Breaker ECS-ES-62 Yes Type Test

& Analysis SV3-ES02-VBR-003 /

SV3-ES02-VBR-001 2.6.01.02.i-U3-EQRR-PCDOOI-RevO Notes:

Excerpt from COL Appendix C Table 2.6.1-1