Dear Mr. Bajwa:
.This is'to forward the final letter. report
" Considerations Regarding Certain Aspects of Severe Accident
' Mitigation Afforded by Operation'of Shoreham at Reduced Power"-
by S. A. Hodge and R. M. Harrington. The report.provides the results of various calculations done at Oak Ridge at the request of Mr. Robert L.
Palla of the Risk. Applications Branch of NRR.
The calculations address Total Loss of' Injection, Anticipated Transient Without Scram ( ATWS), and Large-Break LOCA Accident Sequences with emphasis on the differences in event timing for sequences initiated from 255 power as opposed to.100%
power.
'Please.let me know if you desire additional information concerning these matters.
Sincerely, 4.--
. P. Malinauskas, Director APM:SAH:Jem NRC Programs Encl:
Letter Report cc:
R. M. Harrington J..B. Henderson, NRR #
S. A. Hodge R. L. Palla, NRR 8706240166 970M4 i
PDR ADOCK 05000322 p
PDR h
lx W
w-u, m
,n - ;;,
W'
' yi k..
,.' g /, b re g _L u 2D R2 cc&
'. CONSIDERATIONS REGARDING CERTAIN ASPECTS OF SEVERE-ACCIDENT MITIGATION AFFORDED BY.. OPERATION.-
FO 0F.SHOREHAM AT REDUCED POWER 4
$@i.
S. A.,Hodge-N3 R. M. Harrington b.i Boiling' Water Reactor Severe Accident : Technology Program :
Oak Ridge National; Laboratory
.c Oak Ridge, Tennessee;-
3j m-w 3
}
1 Le t t.f r Re po rt
- June 12, 1987-i.
j I
J Research er tr t rod by the. U.S.
Nuclear Regulatory Co mmi s-R i sion Offb #.4. dear Reactor Regulation under ; Interagency'
~ 4 l Agreement.j..bv 0554-0554-Al with the U.S.
Department-of
- Energy c under. contract 00E-AC05-840R21400 with the Martin Marietta Energy Systems,. Inc.
/rA
.., y-
[ ](
L
.x
-r,.
'l
.s.
L.:Q'
! L $ hy i
(
NOTICE r
This report was prepared as an' account of work sponsored by an agency s of the United St;ates Government.
Neither the United States > Government nor 'any agency ' thereof, or any of their ecploytes, makes 'any Varranty, expressed or implied, or-.dau w t ad/ legc1 liability 'or responsibility for any third party's um e',
oc the results.'of such use, of any in-formation,. apparatus, product or process disclosed in this j
j report, or, represents. that its use by such third party J
.v.twid not infringe privately owned rights.
.i -
dhI 34
-l r
e v
g l
s
. 5].9
.} ' Id
b,l t..
D a
L.
4' CONSIDERATIONS REGARDING CERTAIN ASPECTS OF SEVERE ACCIDENT MITIGATION AFFORDED-BY OPERATION
.0F SHOREHAM AT REDUCED POWER S. A. Hodge
^E R. M. Harrington.
Boiling Water Reactor Severe Accident Technology Program Oak Ridge National Laboratory Oak Ridge, Tennessee Letter Report June 12, 1987
[
g:
Research sponsored by the U. S. Nuclear Regulatory Commis-sion Of fice of Nuclear Reactor Regulation under. Interagency Ag reement DOE. 0554-0554-Al with the U. S. De pa rtment. of Energy under contract DOE-AC05-840R21400. wi th the. Martin Marietta Energy. Systems, Inc.
NOTICE This report was prepared as an account of work sponsored by an agency - of the United States Government.
Neither the United States Government nor any agency thereof, or any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibility for any third party's use, or the results of such use, of any in-
-formation, apparatus, product or process disclosed in this report, or represents that its use by such third party would not infringe privately owned rights.
a
t F
CONTENTS e.
Page 4:
.1..
INTRODUCTION 1.1
- 2.. MAJOR POTENTIAL SEVERE ACCIDENT MITICATION ASPECTS OF OPERATION AT-25% POWER
- 2. l' 2.1 Delay in 'the Timing of Severe Accident Events 2.1 2.2 Reactor Response to Sudden Reactivity Insertion Under-ATWS. Conditions 2.1 2.3, ' Reduced Opportunity for Core Debris-Concrete Interaction
- 2. 2 3.
CALCULATIONS FOR LOSS OF INJECTION (TQUV) SEQUENCES 3.1 3.1 BWRSAT Program Severe Accident Models
- 3. 2 3.2 The Total Loss-of-Injection Sequence 3.2-
- 3. 3 Comparison with Total Loss of Injection From 100% Power'..............................................
3.4 4.
.ATWS CALCULATIONS 4.1 4.1 Operator Actions if the Poison Injection Function Fails
- 4. 2 14 4.2. Consequences ' of Low-Pressure Criticality 4.3'
' 4. 3 1The' C9D ATWS' Sequence
- 4. 5 5.
CALCULATIONS FOR LARGE-BREAK LOCA WITH LOSS OF ALL
'ECCS (AE) SEQUENCES.........................................
5.1
' 6.
SUMMARY
AND FINDINGS.
6.1 7.
REFERENCES 7.1 APPENDIX A.1 4
e
=
n-L i
1.
INTRODUCTION o
i This report describes the results of analyses performed at Oak Ridge National Laboratory (ORNL) to assess certain aspects of the effec-D tiveness of operation of the Shoreham Nuclear Power Station at reduced power as a Severe Accident mitigation technique.
This work was per-formed at the request of the Risk Applications Branch of the Nuclear Regulatory Commission (NRC) Of fice of Nuclear Reactor Regulation in re-sponse to a current request of the Long Island Lighting Company (LILCO) to operate the Shoreham facility at 25% of full rated power.
(The facility would be so operated until certain emergency planning issues related to the granting of a full power license are resolved. )
The specific calculations performed in this work are those speci-fled by the NRC technical sponsor.
These include representation of both Loss of Inj ection and Anticipated Transient Without Scram ( AWS ), the two accident classes that in general dominate the risk of core melt at boiling water reactor f acilities.
This general status applies also to Shoreham, for which LlLC0 has indicated, in its request for 25% power operation, that loss-of-inj ection type accident sequences contribute about 70% and AWS type sequences contribute about 14% of the cotal estimated core melt frequency.
Other calculations have been performed to estimate the timing of events for the large-break LOCA accident sequence compounded by loss of all reactor vessel injection.
Although this combination of initiating events represents a much lower f raction of the overall estimated core melt frequency, it is of interest because it leads to the shortest esti-mated time to the onset of core degradation.
All accident sequence studies include, where appropriate, a calculation of the event timing for the case of initial operation at 100% of rated power, for comparison with the results f or 25% power operation.
The authors of this report have been involved with severe accident calculations for boiling water reactor facilities since late 1980.
These previous efforts were perfo rmed as part of the Severe Accident Sequence Analysis (SASA) Program from October 1980 until September 1986 and for the follow-on Boiling Water Reactor Severe Accident Technology (BWRSAT) Program f rom October 1986 to the present.
Bo th of these pro-grams have been conducted at ORNL under the auspices of the Office of Nuclear Regulatory Research.
A list of the SASA and BWRSAT program re-ports that the authors of this letter report either wrote entirely or co-authored is provided as Ref s.1-15.
All of the calculations whose results are represented in this letter report were carried out on a best-estimate basis.
This includes the models employed for representation of the decay heat power as a function of time.
1.1
e 2.
MAJOR POTENTIAL SEVERE ACCIDENT MITIGATION ASPECTS OF OPERATION AT 25% POWER e
The ' purpose of this chapter _ is to provide' a brief discussion of e
each of three major. areas in which operation of the Shoreham Nuclear 1
Power Station at 25% of rated power would be expected to decrease the severity of postulated severe accident sequences.
)
2.1 Delay in the Timing of Severe Accident Events i
Reactor scram from 25% power operation as opposed to scram from 100% power operation translates directly into a factor-of-four reduction i
in the subsequent decay heat power levels.
This cannot, however, be ex-pected to simply be reflected in a f actor-of-four increase in the time periods between successive major events of a severe accident sequence.
Because of the effects of chemical energy release caused by oxidation of the metals within the core region and the complicated action of the safety / relief valves.in releasing steam f rom the vessel, code calcula-tions are necessary to provide estimates of the extended event timing.
I Nevertheless, there can be no question that the reduced level of decay heat power will have a significant effect upon extending the time
+
available for opera. r action, equipment repair, or personnel evacua-tion.
Results of calculations of the severe accident sequence event timing for total loss-of-injection sequences are provided in Chap.
3, Anticipated Transient Without Scram (A'IWS) event timing is discussed in 5
Chap. 4, and event timing for large-break LOCA with failure of ECCS is t
provided in Chap. 5.
- 2. 2 Reactor Response to Sudden Reactivity Insertion Under ATWS Conditions The extent of control blade insertion into the core is greater for operation at 25% power than it is for operation at 100% power.
Accord-i ingly, under ATWS conditions, less of the total negative reactivi ty,
which serves in the overall reactivity balance to maintain the core critical, is due to voids.
It follows that perturbations to the crit-ical state ' that tend to collapse voids in the core region will insert less positive reactivity with the control blades in their 25% power positions r.han with the control blades in their 100% power positions.
This matter is important because required operator actions in the unlikely event of failure of the sodium pentaborate neutron-absorbing poison function are complicated and difficult to accomplish properly.
The operators may lose control of the situation resulting in the sudden injection of large amounts of cold wa te r or in pressure excursions, either of which causes sudden void collapse.
The more sluggish response of the core to void collapse with the control blades in their 25% power position is discussed in Chap. 4.
2.1
2.3 Reduced Opportunity f or Core Debris-Concrete Interaction The Shoreham Nuclear Power Station is fitted with four downcomers immediately beneath the reactor vessel within the pedestal region of the g
d rywell.
All potential flow pathways f rom the inpedestal region to the expedestal region of the drywell are blocked to a level about two feet I
above the floor.
Since the upper surface of the inpedestal downcomers is flush with the floor, the majority of any molten material emanating f rom the reactor vessel would be expected to flow through the downcomers and be quenched in the pool.
If there is no significant buildup of core debris on the drywell floor, there will be no significant degree cf core debris-concrete in-teraction.
It is important to recognize that in order for fission prod-ucts other than noble gases to reach the outside-plant environment, they must be propelled from the plant by some motive force.
This motive force might be provided by the pressure stored within the reactor vessel before vessel bottom head failure, by the pressure stored within the primary contain=ent before drywell or wetwell pressure boundary failure, by flashing of an overheated pressure suppression pool upon primary con-tainment depressurization, or by the gases released f rom concrete by the ablation process driven by the hot core debris.
In general, BWR severe accident sequences proceed in such a manner that most of the volatile 3
l fission products are trapped in the pressure suppression pool or are condensed upon reactor vessel surf aces; furthermore, the reactor vessel j
and containment pressure sources have been dissipated by the time the j
core debris begins to leave the reactor vessel.
In these cases, it is j
+
the core debris-concrete interaction that provides the motive gases, which sparge through the core debris and carry a small fraction of the remaining fission products to the outside environment, bypassing the pressure suppression pool via the previously-failed primary containment boundary.
1 i
The lower decay heat power of core debris resulting from 25% power operation would, of course, slow the rate of concrete ablation.
On the other hand, if all of the core debris were to leave the reactor vessel as. molten liquid and flow through the inpedestal downcomers to the pool, there would be no core debris-concrete interaction at all.
These matters are discussed in connection with the total los s-o f-inj ection calculation results in Chap. 3.
2.2
,,e 9:
I g
3.
CALCULATIONS FOR LOSS OF INJECTION (TQUV) SEQUENCES 1
In the TQUV [ Transient-induced scram, f ailure of ' normal feedwater system to provide core make-up water, f ailure ' of high pressure (H PCI, RCIC) and low pressure (RHR, Core Spray) systems to provide reactor ves-sel injection) accident sequence, there is a transient followed by reac-tor scram, followed by f ailure of function of all of the systems that would normally be relied upon to deliver cooling water into the reactor vessel'as necessary to keep the core covered.
If the reactor scram occurs from 100% power, the uncovering of active fuel begins in
<1/2 h.6 The TQUV accident sequence has been among the dominant I
sequences in almost all BWR probabilistic risk assessments (PRAs).6 j
Indeed, in the LILCO submission for operation of the Shoreham Station at 25% of full power, the loss-of-injection class of accident sequences is indicated to' constitute ~70% of the total risk of core melt.
L It is important to recognize that only a small injection source is L
necessary to keep the core covered when the only energy release within j
the reactor vessel is that due to decay heat.
This point is discussed in - Chap.
1-of Ref. 6 for the case of scram f rom 100% power, and, of course, even less injection is required in the case of scram from 25%
power.
For example, with the reactor vessel remaining at pressure, an injection rate of just 77.5 gpm taken f rom the condensate storage tank at a temperature of 90*F would be sufficient to maintain a. constant
-reactor vessel water level above the core for times greater than 10 min af ter. scram.
Since the core would not be uncovered during the 10 min period before injection is assumed to be initiated, an injection rate of l
77.5 gpm, which'is less than the capacity of the control rod drive (CRD)
]
hydraulic system when the reactor is scrammed, would preclude core un-
]
covery.*
Thus, ~ we must include loss of the CRD hydraulic system in l
l addition to the loss of function of the standard injection systems j
l specified by the TQUV definition if we are to define a basis for consid-1 eration of a severe accident situation.
We will term this heightened
)
level-of pumping system degradation " total loss of injection."
i I
- Plant tests at Shoreham have demonstrated a CRD hydraulic system injection capacity of 112 gpm with the reactor scrammed and the reactor vessel at pressure.
However, if the control room operator should reset the scram, this inj ection rate would automatically decrease to about 57 gpm.
This demonstrates why plant procedures and operator training should emphasize the relation between the condition of the shutdown reactor (scrammed or scram-reset) and the available CRD hydraulic system i
injection flow.
3.1
)
l7
(
F 3.1 BWRSAT Program Severe Accident Models
,e The Boiling Water Reactor Severe Accident Technology (BWRSAT) Pro-P gram at Oak Ridge National Laboratory employs.the severe accident model-
,c-ing strategy outlined in Table 3.1.
The models described in this table were. developed at ORNL by L.
J. Ott and have been incorporated into the Boiling Water Reactor Severe Accident Response (BWRSAR) code.
It should-be carefully noted that this methodology results in significantly longer times to reactor vessel bottom head penetration failure than other methods because of the contention that the. large amount of water in the BWR bottom head must first be boiled away and that the debris must then reheat to about 1800*F before the reactor vessel bottom head penetra-tions can fail.
It should also be noted that, in general, the debris in the bottom head is not' molten at the time of penetration failure and therefore the debris begins to pour from the vessel sometime after penetration failure.
if the reactor vessel is pressurized.at the time of penetration failure, then the gas blowdown through the bottom head debris has a cooling effect upon the debris.-
- 3. 2 The Total Loss-of-injection Sequence The sequence and timing of events following a postulated' total loss L..
of reactor vessel injection at the Shorehau station as calculated by the
- BWRSAR code are provided in Table 3.2.
It is assumed that the reactor had been operating at 25% power at the time of scram and, in spite of the long times involved, it is assumed that no injection source is ever 4
recovered.
. For. conservatism -in the analysis, there is no modeling of pressure suppression pool' cooling or operation of the drywell coolers.
The reactor vessel is assumed to remain at pressure.
Plots of certain key parameters representing events within the re-actor vessel are provided in Fig.
3.1.
These plots represent events from just af ter. core uncovery, which occurs at time 138 min, until 1500 min, which is some 24 min af ter reactor vessel bottom head penetra-tion f ailure and the beginning of reactor vessel blowdown to the dry-well.
The effect of bottom head penetration failure at time 1476 min upon reactor vessel pressure can be seen on the extreme right side of Fig. 3.la, which also shows the effect of earlier safety / relief valve actuations that occurred before bottom head dryout puts an end to reactor vessel steam generation at time 1181 min.
The swollen reactor vessel water level, which includes considera-tion of the effect of voids, is shown in Fig.
- 3. l b.
The calculated level in general follows a smoothly descending curve, with perturbations caused by safety / relief valve actuations, as water is boiled off by decay heat.
However, after time 395 min, molten core debris begins to fall into the remaining water above the core plate, accelerating the rate of decrease in level.
Af ter core plate dryout at time 483 min, the i
water level remains relatively constant, just below the core plate (whose upper surface is at 19 9. 6 in. ).
Howeve r, the BWRSAR code does 3.2 l
recognize ' the displacement of water in the bottom head whenever large debris masses are introduced into it; this is manifested most clearly in Fig. 3. lb byl the temporary water level increase shown when radial region two of the core collapses into the bottom head at time 644 min.
This temporary level increase is followed by a rapid major decrease of almost c
100 in. caused by steam generation as the mass of radial column two is quenched.
Subsequently, the decay heat associated with the fuel pellets j
of radial column two causes a boiloff of the remaining water in the bot-tom head and bottom head dryout occurs at 1181 min.
j Figure 3.1c represents the gradual heatup of the fuel rods in radial column three and the subsequent large reduction in temperature that follows collapse of radial column (zone) two at time 644 min.
The quenching of the mass of radial column two in the bottom head releases a large amount of steam, which causes accelerated zirconium-water reaction and a concomitant temperature increase in the outer regions of the core where zirconium metal still exists in the cladding.
However, all of the remaining clad structure in radial column three is zirconium oxide at j
this time, so the steam release associated with the collapse of radial column two produces only rapid cooling there.
This ef fect is important, because without it, radial column three would soon reach temperatures that would cause its remaining zirconian oxide clad structure to lose strength and it would also f all into the bottom head, instead of remain-ing in place.
Plots (d), (e), and (f) of Fig. 3.1 pertain to the extent of hydro-gen generation by the zirconium-steam reaction.
Some 51% of the clad and 39% of the channel box wall is predicted to be oxidized during the accident sequence, producing about 1840 lbs of hydrogen.
(This demon-strates the wisdom of maintaining an inerted primary containment atmos-phere during reactor operation. )
l Selected primary containment response characteristics are displayed in the individual plots provided in Fig.
- 3. 2.
The primary containment pressure (Fig. 3.2a) shows significant increase in response to the col-lapse of radial column two into the reactor vessel bottom head at time 644 min and the associated discharge of noncondensible gases.
The con-comitant drywell atmosphere temperature response (Fig. 3.2b) is slight because this discharge from the reactor vessel is via the safety / relief valves and is cooled during its passage through the pressure suppression pool.
Both the pressure and temperature response are marked, however, following the inception of reactor vessel blowdown at time 1476 min when the release is directly into the drywell atmosphere.
Nevertheless, the peak pressure is not of a magnit ude to threaten primary containment
.I pressure boundary integrity and the temperature excursion is rapidly terminated as the heat sinks absorb the released energy.
This does not threaten the integrity of the drywell liner, however, since its peak calculated surf ace temperature in response to the reactor vessel blow-l down is only about 270*F, as shown in Fig. 3.2c.
l Certain calculated conditions within the wetwell are shown in Fig. 3.2 plots (d) through (f).
As indicated in Fig. 3.2e, a large mass 3.3
i of hydrogen is collected in the wetwell airspace when the reactor vessel i
is flushed by ~ the large release of steam from the bottom head at the time of collapse of radial column two.
However, it should be recognized that this is not all of the hydrogen in the containment; some 450 lbs are predicted to have been passed back into the drywell via the wetwell-to-drywell vacuum breakers.
Figure 3.3 indicates the integrated mass of molten material pre-dicted by the BWRSAR code to have been released from the Shoreham reac-tor vessel as a function of time following reactor vessel pressure boundary failure at time 1476 min.
There is a small initial release of molten stainless steel immediately upon bottom head penetration f ailure, but the passage of blowdown gases cools the debris and significant addi-i tional release does not occur until about time 1910 min.
The calcula-tion is carried out to time 2880 min (48 h af ter scram), although the I
calculated reactor vessel wall temperature at the end of the calculation (about 2210*F at the connection with the vessel skirt) is much too high I
for the wall structure to have survived.
Indeed, it must be expected j
that the reactor vessel wall would fail shortly af ter time 2100 min, l
when the average wall temperature in the vicinity of the vessel skirt is
)
about 1600*F.
l For accident sequence time 2100 min, the BWRSAR code predicts that
)
some 101,000 lbs of molten metal eutectics have lef t the reactor vessel whereas about 556,000 lbs of solid debris remain within the vessel, in-ciuding all of the original inventory of UO2 fuel.
Should the reactor vessel bottom head wall fail by creep-rupture at about this time, a great deal of solid debris would be deposited onto the drywell floor.
The results of these calculations do not support the contention of the LILCO submission that all debris f alling onto the Shoreham drywell floor would be molcen, subject to immediate passage through the downcomers into the pressure suppression pool.
f
- 3. 3 Comparison with Total Loss of Injection From 100% ?ower In order to clearly demonstrate the very significant delay in j
severe accident event timing associated with operation at 25% of full l
power, the total loss of injection sequence was recalculated with all
)
parameters the same except for the initial power, which was set at 100%
of rated (8.312 x 109 Bt u/h).
The differences in timing of the major events of the accident sequence are indicated in Table 3.3.
In addition to the large delays in severe accident event timing associated with operation at 25% of full power, there are two other sig-nificant differences in the calculated plant response.
Fi r s t, morn hydrogen is generated in the case of total loss of injection f rom 25%
power, 1840 lbs as opposed to 1620 lbs for the 100% power case.
The relative fractions of clad, channel box, and control blade stainless steel sheath oxidation are provided in Table 3.4.
The major source of 3.4
the additional hydrogen is seen to be the additional oxidation of the channel box walls, while they are slowly heated at oxidizing temperature in the 25% power case.
(In the 100% power case, the channel box wall
. reaches its melting' temperature more rapidly and more of the zirconium metal is relocated downward without oxidizing.)
However, a great deal 8
of. hydrogen is predicted to be generated in either case so the addi-tional 14% in the '25% power case, while of interest, does not constitute a special concern.
The second significant dif ference in calculated plant response is also derived f rom the much slower heatup rate in the 25% power case.
Af ter bottom head dryout, the debris in the reactor vessel bottom head is heated by its internal decay heat generation.
For the 100% power case,- the. debris heats rapidly and its temperature greatly exceeds that of 'the reactor vessel wall, which is heated only by conduction f rom the debris.
For the 25% power case, howe ver, the debris temperature in-creases much more slowly and the average reactor vessel wall temperature does not lag so far behind.
The upshot of this is that relatively little of the debris has become molten and lef t the vessel at the time that the average wall temperature reaches the creep-rupture failure range in the 25% power case whereas most (but not all) of the debris has left the vessel by this time in the 100% power case.
A comparison of the calculated quantities is provided in Table
- 3. 5.
This matter is impo rtant because the debris leaving the reactor vessel in the molten
. liquid phase is expected to -immediately enter the pressure suppression pool via the downconers whereas most solid material falling on the dry-well inpedestal region floor upon creep-rupture f ailure of the bottom head would not.
It should be noted that the models now employed f or the BWRSAR cal-culation for definition of the formation of eutectic mixtures within the core debris and.the melting temperatures of these mixtures are current best-estimate and subject to revision upon completion of certain per-tinent experiments now planned by Dr. Dana Powers at Sandia National labora torie s.
1 3.5 I
g Table 3.1.>
BWRSAT program methodology employed to represent events between onset of core g*
, degradation and reactor vessel failure for BWRs i
1.>
As canister and control, blade material becomes molten, it is relo-cated onto the core plate.
This causes:
a.
a temporarily increased steaming rate-b.
' core plate. dryout and cessation of steaming
.c.
buildup of' mass on'the core plate-and core plate heatup.'
2.
Fach radial region' of the core plate fails due to loss of strength j
when. its L calculated E temperature has. increased to 11275'F (964' K).
l Each s core. plate region and its accumulated' debris f alls into the
'l l
lower plenum, producing a burst of steam and l'owering ' the water level there as the f allen material is quenched.
f 3.-
Molten Zr metal flows downward over ' the lower core ' fuel rod nodes,
leaving the UO2 fuel pellets encased in thin Zr02 sheaths.
St eam rising f rom the lower ~ plenum cools the core nodes f rom which all un-oxidized Zr has been removed.
On the other hand,. the rising steam.
- causes energy release in the core peripheral nodes where Zr metal at elevated temperature still remains.
q 4.
The standing portions Jof the core f all.into the lower 1 plenum by
)
C radial column.'
Each core ' column collapses when its average clad temperature reaches 4250*F (2616 K), at. which time very little off the UO2. mass in the region has become molten.
(The actual failure mechanism is weakening, by overtemperature, of the Zr02' sheaths sur-5..
rounding the UO2 fuel pellets.') The f alling mass is' quenched-by the
]
water ' in. the lower plenum until' the time of bottom head dryout.
j Af ter bottom head dryout, the debris begins to reheat.
5.
The structure: of the control rod guide tubes in the lower plenum is heated 'by. the surrounding core debris and is weakened to the point of failure when its temperature reaches 1400*F (1033 K). ' Failure of the control rod guide tubes causes all remaining standing portions of the core to immediately collapse.
6.
Bottom head penetrations fail by a simulated creep-rupture mechanism as the debris mass in their vicinity is reheated to about 1800*F (1255 K).
The reactor vessel depressurizes and equalizes with dry-well pressure.
7.-
The individual components of the debris mass leave the vessel only after they have reheated to their melting points and thereby become liquid.
1 1
)
i
F4 l
r a.
Table 3.2.
Maj or events of the total-loss-of-injection accident sequence f or scram f rom 25% power
- e.
Time Af ter scram Event (mins)
MSIV closure and total' loss of 0
injection The swollen water level f alls below the 138 top of active fuel
' Structural relocation of core material 395 begins Core plate dryout-483 Core plate region 1 fails 522 Core plate region 4 fails 566 Core plate region 2 fails 641 Radial region two of core collapses 644 Core plate region'3 fails 644 Core plate region 5 f ails 856 Bottom head dryout 1,181 Radial. region one of core collapses 1,476 Bottom head penetrations fail and blow-1,476 down into drywell begins High temperature weakens control rod 1,476-guide' tube structure and remaining portions of the core collapse.
A small amount (13,500 lbs) of molten steel leaves the vessel.
The re-mainder'of th'e core debris'is frozen I
Beginning of continuous pour of molten 1,910 material from the reactor vessel Average reactor vessel wall temperature 2,100 exceeds 1600*F in vicinity of attach-ment to supporting skirt.
Creep I
rupture failure of vessel wall and partial separation of lower portion of bottom head is probable 40 :
._-._._._._.________-_______-_____-_.-_--__-______.-___s
- .r.;
h 1 Table 3.3. - Comparison of the timing of major events in' the lcotal-loss-of-injection accident sequences for initial powers of 100% and 25%
4' Time af ter scram
(*'""}
Event 100% power 25% power MSIV closure and total loss of injection 0
0-Swollen water level falls below top of 25 138-active fuel Structural relocation of core material 68-395 begins Core plate dryout 74 483 Radial region two of core collapses 110 644 Bottom head dryout 231 1181 Bottom head penetrations fail, blowdown 267 1476
.into drywell begins Beginning of continuous pour of molten 267-1910 material from the reactor vessel Average reactor vessel wall temperature 610 2100 e
. exceeds'1600*F in vicinity of attach-4 ment to supporting skirt.
Creep rup-
{
ture failure of vessel wall and partial-separation of lower portion of bottom head is probable.
4
'4 e
/
I
i:.
1 Table 3.4. : Comparison of the calculatsd.hyd rogen generation parameters in the total-loss-of-injection sequences for initial powers
'of.100% and 25%-
Parameter 100% power 25% power Fraction of clad ~ oxidized 0.48' O.51 Fraction of channel box wall oxidized 0.23 0.39 Fraction of control blade stainless steel 0.06 0.09 sheath oxidized Total hydrogen generated, lbs 1620 1843 l
l
\\
l 1
I
.s a
l l
S
';G.
h
. Table s 3. 5. '. Comparison of the. calculated ' quantities of core' debris invessel and exvessel at the c
time that'the reactor vessel wall L
temperature exceeds 1600*F Ya
'100% power caseE 25% power case time 610 min time 2100 min L
Debris _ constituent.
.Invessel~ Exvesseli Invessel Exvessel (1b)'
.(1b)
(1b):
(1b)
Zr 22,600 48,700 44,400 18,000 Fe :
27,200 156,200
,127,200 55,900 Zr02.
~35,600.
17,100 65,200 0
UO2 42,6001 235,600~
278,800 0
'Other"
.14,100 53,600 39,300 27,600 t
Total-142,100~
'511,200 554,900 101,500
- Cr, Ni, B4C, Fe0, Fe304, Cr203, N10, and B203
- M l,
j 4
i g>
)
j i1!lq:
,lil li!!,
1
~
s-E
=.
=
=
m
=
1~.
^.
- =
- a R
A S.
.i
)
, c M
)
R y v
c(
E(
f Wt
(
Bi M
6TI ei l
h c t a 6
f y
b r
~
a
~
d e el t c i n cu
~
=
=
=
"a -
~
d em s
s3 -
phra
- I==4fa;=yI
!.l Uie ig e
sr aoh lS e
s e sE sh et v
=
=
=
t ra a
o t r c e aw eo rp a
e%
- a
. g h5 t 2 g
)
..gw e
nm
)
g
(
i o
, b
.g
,(
t h r g
t f i
wm a
- =
sr
]
t c ns e
- =
vg en i
rw
=
=
.=
m
- ~
oo
=
~
fl l
g E=
s o B9 =E3.oG, ef g cB Eds d9 =ng i "
run t o ai nt gc g 3-i e sj n
n a
u o
t i n
ef d o n
i i.
cs cs g
a.
A o l.
l
. w.
. l i
1 a vi
)
. t d
3 o
)
r
.u
.t
(
a
.,u
(
gr
)
~
i o Ff t
6 e
@g d
oc a
o m.
=
~
=
=g
.ga:"2;etgm
,=gE eE, 1lllllI' m
g a
=
a m
3 e.
]
36 RA 0
. =.
30 SR 4
W f
e e
B
. =
e t
=
h eW t
s
=m (c e
)
eL
)
S W g
y.
r t
(
by u
0u t
. =n
" 1n di 0
el ti cc
. =
SG ia df e
. =
3 8
rr pa e sl
=
8 4
ac
=
=
=
=
=
m m
5 l n e
u e
-E s
lem E5 d $ g
,z i Eh E =! I g%@=
wa thee wro dh a
g_
nS a e
=
=
e
=
=
.t
+
=
lh s
e lt
=
I e
t wt ya 0
. =
3R dr 0
r
=
e ew
. =
3 ho 0
=-
3 t p
.s:
=s
- .e m
)
f%
a
)
w b u
c o5
-(
(
2
(
(
r s
u eu em
+-. =n Tn e
s o nr of
. =
4 ps m e a r r
=
3 c
0 e s h
=
e g
t t
n
=
~
=
=
=
=
m i
r w
o E
Sa f
o l
l E]a sUca % ggaEj
==E
<g el;;
o3 s o e
f ru n t
o a
EE s
i nt gc
~
=..
=
- =
=m 3
=
ie
=
4
=
s m
MR s jn t
i 0
n 30 ef 8
d o i
7 0
0,.
c s 8
c s 5
A o i
l
.s m) 0a)
~
9 n a
(
(
v d
.l
- 2. t a
r
(
t
.u
.u r
n
' 9n 3o 9
.t e
gr S
io e
Ff e
^
3 d
4 o
S c
O E
e
=
u
=
a m
=
=
n a
4" s
n 1
3E s
65E]u sU=
o g,BE yE
! ca }a E. b =Cg3N
~
~
aR ed rs cAhaei yI: - h~
seSt ewh
)
a ajR hot nW' 2
f.
l 0
2 2
2 2
lib m
e e
o oer 1
e 4
2 0
sf e tho s o h 'l t tf 0
e
.Tl o e~
02 vs' Ab b
s ta ro.
l h l ol y e
e t
t t
.s s
0 cl i s
s 0
a a l )s e h e 4
eti rvgv 2
roc u i
t a oehr e
f hh o
ha t ot t
r sc 00 f a8 n a
N 2
toe 4 ise 2
f l( hir O S e) c t
IT N l su A
en sie e I
a TNM gt ew rh t
ut SO6 0
nu m unt 0
in a I
RT4 0
vih neam 7
EC1 2) iz r o WE
/
S ame moe r h
r OJT7 N
0o rpf PNA8 I
f m 9
M s8h0 RFl 0(
i4S8 ed I S1 nt e r2 8
0E b
i t
AOl5 8
E A2 M
e2 al a e o h 'e e 1
LSF dt t ml r I
Y T
CSDA
(
a a UD e
mr w p
AM t
NIE re i
e os at od.s LI 0
MA 0
ca t
I ATL 0
hr e e' npet t
v lOE 1~
wad a o
el a lETS e
h 1
R S t r t u E'
l epd c c 0
ot %ei V
t l
l i
0 mt td a s S
0 a5ae 4
fl 2 c u nr m
1 o
i p em m e d sho r h
st r e st a i
e a
f t y r,h 0
mg 0
ne m
2 li csr e I
o arn ao v t uewt e t
t od u n w o 0
T q
e n v ob 0
ee h
o n 0
ms i
1 i
e
.i t
- h 5
s.
s.
s.
s.
s.
s.
s.
3tt a et 1
s s
s 2
s a
s n
p l
m 2
E i
i 1
3f e uO i
.od c U f
t i
o
?
O,..
d gnc al l
ioc c a s n 4$y> Mo edwkwMQ-
@$ gQ@Ig A%8 Fia ni o S
h a
t i
i.
cnegt t e nodi rm uiort oi ft coapt
~
l, I
1 j
4.
ATWS CALCULATIONS
)
This chapter describes the predicted response of the Shoreham j
Nuclear Power Station to a postulated complete failure to scram follow-ing a transient event that has caused closure of all rain steam isola-tion valves (MSIVs).
This accident sequence is the most severe of a class of sequences commonly denoted "A7WS", the acronym for " Anticipated Transient Without Scram."
With the MSIVs closed, almost all of the steam exiting the reactor vessel would be passed into the pressure sup-l pression pool through the safety / relief valves (SRVs); the remainder l
would be used to drive the High Pressure Coolant Injection (HPCI) or Reactor Core Is olation Cooling (RCIC) system turbines during their i
periods of operation and then, as turbine exhaust, would also enter the l
pressure suppression pool.
Since the rate of energy deposition into the pool can greatly exceed the capacity of the pool cooling equipment, the possibility of excessive pressure suppression pool temperatures leading to primary containment f ailure by overpressurization is of primary con-corn during the analysis of ATWS accident sequences.
i As in all deoigns, the criticality of the Shorehr.m nuclear reactor depends upon a corplicated set of f actors that simultaneously introduce positive or negative reactivity.
Whether there is a power increase, constant powe r, or a power decreaae at a given point in time depends upon the particular reactivity balance at that instant.
In BWR studies, it is necessary to recognize the importance of the void coefficient of j
reactivity.
In the BWR, boiling takes place within the core and " voids" are created by the steam bubbles formed within the core volume.
The moderation or clowing-down of neutrons is much less in steam than in liquid water so increased voiding has the effect of reducing the supply I
of thermal neutrons.
Therefore, an increase in voids introduces nega-tive reactivity and a decrease in voids introduces positive reactiv-ity.
Since the BWR operates with the water moderator at saturation con-ditions within the core, negative or positive reactivity insertions caused by the creation or elimination of voids are a natural and important result of reactor vessel pressure changes.
Provision is made for rapid reactor shutdown under emergency condi-l tions by neutron-absorbing control blades that can quickly and auto-matica11y be inserted (scrammed) into the core upon the demand of the reactor protection system logic.
When inserted, the control blades introduce enough negative reactivity to ensure that the reactor is main-(
tained suberitical even with the moderator at room temperature and with 1
zero voids in the core.
Although all transient-initiated accident sequences can most easily be brought under control and terminated by successful scram of the con-trol blades, they can also be brought under control and terminated by appropriate operator action.
In other words, given properly trained operators and properly functioning equipment, the f ailure of the scram
~
function can be considered to be merely a nuisance requiring a more com-plicated and time-consuming method of achieving shutdown.
)
4.1 o
One important action that the operators are directed to take in the event of ATWS is to initiate the standby liquid control system (SLCS) if the pressure. suppression pool temperature reaches 110*F.
This system injects a neutron-absorbing poison of sodium pentaborate solution into the reactor vessel by means of positive displacement p ump s.
Previous studies ll at ORNL have demonstrated that with operator action limited to successful initiation of the SLCS, the ATWS accident sequence can be brought under control.
If a postulated ATWS accident sequence is to degenerate into a severe accident, then, we must also assume f ailure of the SLCS.
i 4.1 Operator Actions if the Poison Injection Function Fails The BWR Owners Group Emergency. Procedures Guidelines (EPGs) provide a strategy for operator actions to deal with the MSIV-closure initiated a
ATWS that.can be summarized as follows:
At temp t manual scram and, if
(
not successful, begin manual insertion of control blades.
Initiate the SLCS and pressure suppression pool cooling.
Reduce core power by taking manual control of the reactor vessel injection systems and lowering the reactor vessel. water level to the top of the core; this reduces core inlet flow by interrupting the natural circulation path from the core through the steam separators and back through the jet pumps in the down-comer region.
The result is increased voiding in the core and increased i
temperature of the flow at the core inlet; the latter because the lowered water level uncovers the feedwater spargers through which the HPCI and RCIC systems inject, thereby providing heating of the injected droplets as they all through a steam environment.
The EPGs are intended to be symptom-oriented instructions to the control room operator that are comprehensive and cover every eventual-
)
ity.
To maintain assurance that' the thermal energy released from the primary system can be condensed in the pressure suppression pool, there is a requirement that reactor vessel pressure be reduced as the pressure i
suppression pool temperature increases.
For the Shoreham reactor, pres-sure reduction must begin when the suppression pool temperature exceeds 150*F and continue in accordance with a graph of permissible maximum reactor vessel pressure vs suppression pool temperature.
(Previous studies at ORNL7 demonstrate for Browns Ferry that once reactor vessel depressurization is begun, it must be continuous because each increment of energy deposited in the pool during depressurization increases the suppression pool t emperatu re to the extent that, following the graph, further depressurization would be required.)
There is no suggestion in the EPGs that the graphical schedule for reactor vessel depressurization as pressure suppression pool temperature increases should not be fol-lowed in the event of ATWS.
Recent preliminary work at Rensselaer Polytechnic Institute (RPI) indicates that the Shoreham nuclear reactor would be suberitical with the reactor vessel water level lowered to the top of the core and the reactor vessel depressurized to 200 psi or less, given the control 4.2
l blades stuck in their normal 25% power operating positions.16 In other words, the small rate of water injection to the reactor vessel required to maintain the vessel water level at the top of the core would be converted to steam by decay heat alone, and the associated voids within the core region would keep the core suberitical.
If subsequent analyses confirm this finding, then, should the SLCS system fail, the Shoreham reactor could be brought suberitical simply by lowe ring the reactor vessel water level and pressure, while keeping the core covered.
It is emphasized that this would not be the case if the control blades were stuck in their (more withdrawn) normal 100% power operating positions.
I 4.2 Consequences of Low-Pressure Criticality I
The question as to whether or not the Shoreham reactor would main-l tain criticality with the water level lowered to the top of the core and the reactor vessel depressurized is of some importance because of the potential for rapid insertion of positive reactivity under such condi-tions.
This might occur either by uncontrolled injection of cold water by the large-capacity low pressure injection systems or by any small action that initiates a reactor vessel pressure increase.
As indicated by the data provided in the steam tables, the change in steam vapor specific volume for a given increment in pressure is much greater at low pressures.
If it is considered that the Shoreham reactor would remain critical in a depressurized state with the water level lowered to the top of the core, then it can be demonstrated, in general, that the power and pres-sure transients resulting f rom sudden insertions of positive reactivity I
would be less severe with the control blades stuck in their normal posi-tion for 25% power operation.
To this end, two sets of demonstration calculations with the BWR-LTAS code 9 have been performed for ATWS situs-tions identical except for the control blade positions.
Ihe determina-tion of the additional control blade reactivity associated with 25%
power operation is described in the Appendix.
In both cases, no opera-tor action is assumed and the calculations are based upon Browns Ferry ptrameters.
The calculated results for the two cases are shown in Figs. 4.1 and 4.2.
Without operator action, HPCI, RCIC, and CRD injection maintain reactor vessel water level high above the top of the core until the HPCI turbine is lost upon high lube oil temperature (the system lube oil is cooled by the water being pumped, and without operator action, the sys-tem suction would automatically be shif ted from the condensate storage tank to the pressure suppression pool; HPCI system f ailure is assumed at a pool temperature of 210*F).
With HPCI system f ailure, reactor vessel water level decreases even though the RCIC and CRD hydraulic sys t ems continue to inject.
The automatic depressurization system (ADS) is enacted when the combination of low reactor vessel water level and high drywell pressure is sensed.
4.3
f i
g i
This is much later f or the case of ' AWS f rom 25% power (Fig. 4.2b vs.
4.lb, where six open SRVs represent ADS actuation).
As the reactor vessel is depressurized into the regime in which the
}
1arge-capacity low pressure injection systems are able to pump cold water into the vessel,. large cycles of injection - no injection begin j
(Figs. 4.lc.and 4.2c).
Each period of cold water injection produces j
void - collapse within the core and subsequent reactor powe r spikes
]
(Figs; 4.1d and 4.2d). = However, the power spikes produced for the case with the control blades in their normal 25% power position are much less severe and less numerous than for the case with the' normal 100% power control blade positions.
Each power spike produces a pressure increase within the reactor vessel that quickly terminates further water injection by the low-pressure systems.
Without injection, the core rapidly becomes uncovered and power drops to decay heat levels.
However, as long as the ADS 1
valves remain open, the pressure then rapidly decreases and another cycle of cold-water injection begins.
l If the increasing drywell pressure approaches the available control j
air pressure, the safety / relief valves will close, the reactor vessel j
will repressurize in a permanent f ashion, and no additional low pressure i
inj ection cycles will occur.
As shown in Figs. 4.lc and 4.2c, this happens at about time 39 min in the case of an AWS from 100% power, but not within 45 min for AWS from 25% power.
The associated drywell pres-sure traces are shown in Figs. 4.le and 4.2e.
l The conclusions obtained by this discussion and the associated cal-culations are that adequate mitigation of an AWS accident sequence, j
given failure of complete shutdown, is much simpler for the control room j
operators if the' control blades are in their configuration for 25% power operation as opposed to their configuration at 100% power.
Since the relative negative reactivity contribution of the core voids is less with the blades in their 25% power configuration, any subsequent change in voids also has less effect.
Perhaps the best evidence of the overall effect of this is the difference in predicted pressure suppression pool temperatures at time 40 min in Figs. 4.lf and 4.2f.
It should be noted that the results presented in this section for AWS f rom 25% power operation were calculated on the basis of a negative 0.015 delta-K/K control rod reactivity differential associated with operation at 25% power as opposed to 100% power.
This is considered to j
be a conservative basis since, as discussed in the Appendix, the best-estimate negative reactivity diff erential is -0.019.
A test BWR-LTAS calculation was performed using -0.019 delta-K/K control rod reactivity, but the calculated reactor power was so low following loss of the HPCI system that the low reactor vessel water level required for ADS actua-tion was not reached within the 45 min period represented by the calculation.
4.4
4.3 'Ihe C9D ATWS Sequence Together with their application for Shoreham to operate at 25% of rated power, LILCO submitted the results of several accident sequence calculations in which events were assumed to occur in such a manner that
+
1 the accident proceeded beyond core melting and reactor vessel pressure l'
boundary failure.
Among these is the C9D ATWS accident sequence, in which the control blades are assumed stuck in their 25% power operating configuration.
The sequence of events for the C9D accident sequence up to the time of loss of injection as described by the LILCO submission is described in Table 4.1.
Several conservative as s ump tions were employed by the LILCO subcontractors in determining this event sequence including f ail-ure of the SLCS function and loss of all reactor vessel injection sys-tems upon the inception of wetwell venting, as well as the basic assump-tion that the reactor would be critical when depressurized with the water level at the top of the core.
There would, of course, be no severe accident if any one of these assumptions is not valid.
To determine the sequence of events involving core degradation and reactor vessel f ailure that would occur af ter loss of all injection to the reactor vessel, a BWRSAR code calculation has been performed at ORNL for the period of the accident sequence af ter time 90 min.
Core power was controlled by user input and the control blade positions were established so as to approximate the actual 25% power configuration.
The predicted timing of events is provided in Table 4.2.
Calculated hydrogen generation is 1866 lbs, resulting f rom oxidation of 57% of the clad and 41% of the channel box walls.
The ORNL best-estimate methods of calculating degraded core and reactor vessel f ailure events (Table 3.1) predict a much longer time to reactor vessel pressure boundary f ailure (3 0. 8 h vs. 10.4 h) than does the MAAP code method used in calculating the results of the LILCD sub-mission.
(This ' is primarily because of the BWRSAT Program contention that core debris relocated into the reactor vessel bottom head is quenched as long as there is sufficient water remaining to do it.)
Also, the LILCO submission predicts that molten core debris begins to leave the reactor vessel at the time of pressure boundary f ailure where-as the ORNL method delays the initial pour until the debris in the bot-tom head has reheated to its melting point.
'Ihus, in the ORNL results calculated with the BWRSAR code, the initial pour of molten metal f rom the reactor vessel does not occur until time 37.5 h.
If it is desired to compare the event timing given in Table 4.2 for the ATWS case to the timing provided in Ta ble 3.4 for the loss-of-injection cases, one must remember that only about 24% of the total con-trol blade mass is represented as being in the core f or the ATWS case; this has a significant effect upon the calculated results.
4.5
yb
-1
-1 i
.]
q c
. As a final comment in '. regard. to the lessons learned-by review of the C9D ATWS severe ; accident sequence, it should be noted that the pri-i-
mary ' containment atmosphere would be depleted. of noncondensible gases
' af ter, several hours ' of - wetwell. venting. -
If the situation within.the' l
reactor vessel were subsequently brought under. control and the wetwell vent -was. then closed, a vacuum greater than - the design basis might be j
- drawn within the. primary containment as ; the steam therein condensed.
This is why plant emergency procedures should ensure that the composi-tion ~ of the primary containment - atmosphere is ascertained and that-
^
nitrogen is introduced as necessary before the vent is closed.
I I
e i
i i
l c
-I 4
'j
'l 1
4.6 i
m r
I 1
Table 4.1 Major events of the C9D Anticipated Transient j
Without Scram (ATWS) accident sequence up to j
the time of loss of injection-1 Time af ter Event MSIV closure (mins) j 1
3 MSIV. closure and f ailure of. scram function 0.0 1
HPCI/RCIC/CRD maintain reactor vessel level between 0.0-18.0 Level 8 and Level 2 j
'l p
.Two RHR cooling loops aligned for pressure suppression 10.0 j
pool cooling
{
Pressure suppression pool temperature reaches 200'F, 18.0 j
ADS is manually. actuated, vessel depressurization I
causes loss of HPCI operational capability. Operators l
lower reactor vescel water level to the top of the core j
and maintain it there by use of RCIC and CRD.
Re actor l
power is 10% of full power.
The ADS valves automati-I cally open and close to maintain the reactor vessel pressure between~50 and 75 psi higher than that of the wetwell.
I 1
Containment pressure reaches 75 psia.
Operators vent '
90.0
~~
-the wetwell airspace' causing harsh environmental condi-
.tions in the secondary containment.
All reactor vessel' injection capability is assumed lost.
Also, since the j
drywell pressure exceeds the available control air pressure, the ADS function is no longer operable and the reactor vessel repressurizes.
Hereaf ter, the SRVs will i
open only automatically, on high reactor vessel pressure.
l l
i i
l i
k
..e 4
I f
r l
. Table 4.2.
Major events of 'the C9D Anticipated Transient Without Scram -(ATWS) accident sequence af ter loss of injection Time af ter i
Event scram (mins) -
Tne. reactor vessel repressurizes quickly and the core 90 0
.is uncovered rapidly as core' power is restored to 10%
y of ful1~ power by void collapse The swollen water level f alls below the top of active 100-fuel 1
Low waten level and increasing voids restore core-power 103 i
to decay heat levels-
' Structural relocation of core material begins 292 i
Core plate dryout.
518 H
Radial region two' of core collapses 565 Radial region'three of core collapses 920 Core plate region 5 fails
'923' Core plate region 1 fails 1062 Bottom head dryout 1337 1
Overtemperature weakens control rod guide tube structure 1723 i
and remaining portions of core collapse Bottom head penetrations fail and blowdown into drywell 1850 l
begins Molten core dobris begins to pour f rom the. reactor vessel 2250
' Average reactor vessel wall temperature exceeds 1600*F 2700 i
in recently of attachment to supporting skirt.
Creep rupture failure of vessel wall and separation of lower portion of bottom head is probable i
i 9
si,.l tww-
\\
.g y
~
ia,iit>>14
- :=
, j.g
~. -.--
,E
.E b.b&\\1 Mal; e,
?!us mug maWM (a)
(b) e 6.
i e
Iu=
i.
I I
I._
lo t
S.
1 j
is..
g,=
I i
as 088 6
kk'W
'sa t
d w i fl ms mim
== suo (c)
(d)
~
8 g
,,, g g,
g
,,,C l=
.-=
t a
i,/.-
L.
8 I
,,/,,/
l
.s
/
=
=
=
=
ma kun Mr mim (e)
(f) i F15. 4.1.
Accident signatures for the MSIV-clesure ATWS from 100".
)
power operation, first 45 minutes with no operator action.
-- m:
1t
..N ISO ~~
42 h
i 3
s M
g
.g o
,l ~j-
.g g
. li s
WillllllA1Al_lll!
- l 1
I nNwwww M8 0HM miens (a)
(b) 2 1
u u
u
$ ~.
u l
lu fu I
I
~
~
u I
g((
d
~
== wno m:0mo (c)
(d)
=
E
'h'".~..
s_ m
\\
g g..
e g
7
.. g
~.
p 3
,,/*,,
~
/<<,
=
l
-a.
ma num ma man I
(e).
(f)
~
il Fig. 4.2.
Accident signatures for MSIV-closure ATWS fron 25% power I
operation, first 45 minutes without operator action.
l l
a P
I i
c.
E 5.
CALCULATIONS FOR LARGE-BREAK LOCA WITH LOSS OF ALL ECCS (AE) SEQUENCES 1
1 The large-break LOCA initiated by double-ended rupture of a 28-in.
(outside-diameter) recirculation pump suction line serves as the design basis accident to establish the adequacy of the Shoreham containment with regard to drywell internal pressure, suppression chamber internal
- pressure, drywell floor differential pressure, suppression chamber temperature, and secondary containment pressure.
The configuration of the break and the location of the reactor vessel within the containment are shown in Fig. 5.1.
The response of drywell pressure, suppression i
chamber pressure, and drywell floor differential pressure and the associated drywell and suppression chamber atmosphere temperatures with-in the first 30 s af ter the break are shown in Fig.
- 5. 2.
All of the components of these figures were taken from the Shoreham Updated Safety f
Analysis Report (USAR).
At the 30-s point, ECCS injection to the reactor vessel would begin (via core spray) and the accident sequence would be brought under con-trol and terminated without degradation of the original core geometry.
Nevertheless, in the very unlikely case of f ailure of the ECCS function, the resulting accident sequence (termed AE) provides the shortest period of time to the onset of core degradation of any.
Calculations with the BWRSAR models to estimate these times for operation of the Shoreham reactor have been performed for both 100% power operation and 25% power operation.
Although the BWRSAR models were never intended to calculate i
the complex processes of large-break reactor vessel blowdown, their results for the first 30 s of blowdown are in good agreement with those shown in Fig.
5.2.
The calculated event timing for the AE sequence taken f rom the BWRSAR results for both 100%. and 25% power operation is provided in Table 5.1.
Less hydrogen is generated in the N sequences than in the total-locs-of-injection sequences because less steem is retained in the reac-tor vessel to fuel the metal-water reactions.
BWRSAR program results pertaining to hydrogen generation are provided in Table 5.2.
With recognition of the importance of the calculated reactor vessel i
wall. temperature in estimating the time at which the remaining solid core debris could no longer be supported by the reactor vessel bottom head, a finer bottom head debris nodalization was developed and employed f or the large-break LOCA calculations.
This involved implementation of a small node structure near the reactor vessel wall to represent the effeer of debris in close contact with the wall; the effect is to pro-I duce higher calculated wall temperatures.
I
~
The predicted distribution of core debris invessel and exvessel at the time of probable bottom head f ailure is provided in Table 5.3.
More of the debris remains within the reactor vessel bottom head in the 25%
power case, but the difference is not as marked as in the calculation for total loss of injection, which used the original debris noding 1
5.1
i s tructure to produce the results shown in Table 3. 5.
It is intended that all future calculations will use the new debris noding structure.
n D
e 5.2
c:
{,'
[
r, Table 5.1. f Comparison of the timing of major events in the large-break LOCA accident sequences f or initial powers-of 100% and 25%
V Time af ter scram (mins)
Event 100% power 25% power
. MSIV closure and total loss of' injection 0.0
- 0. 0 Recirculation gump suction line break 0.002 0.002 (area 4.22 ft )
Swollen water level f alls below top of 0.05 0.06 active fuel Core plate dryout 0.09 0.10 Structural. relocation of core material 10.9 59.5 begins First collapse of a core radial region 44.8 200 Second collapse of a core radial region 45.3 201-Bottom head dryout 59.2 220 High temperature weakens control rod 59.3 349 guide tube structure and remaining portjons of the core collapse First failure of reactor vessel bottom 70.4 469 head penetrations Beginning of continuous pour of molten 80.0 570 material f rom the reactor vessel 6
..g
,,'d n
Y t'
s:
. Table 5.2.
Comparison of the ' calculated hydrogen generation parameters in the large-break LOCA sequences for initial powers-of 100% and 25%
Parameter 100% power.
25%' power-Fraction of clad oxidized 0.38 0.35 Fraction of ~ channel box wall oxidized.
0.28 0.17-Fraction of control blade stainless' steel 0.08 0.04 sheath oxidized Total 1 hydrogen generated,1bs 1326-1157 l
b.
6v I
Table 5.3.
Comparison of the calculated quantities i
of core debris invessel and exvessel-at the time that the reactor vessel wall temperature exceeds 1600*F 100% power case 25% power case time 200 min time 810 min Debris constituent Invessel Exvessel Invessel Exvessel (1b)
(1b)
(1b)
(1b)
]
Zr 58,600 15,700 75,200 6,400 Fe' 77,900 105,300 163,900 19,800 I
Zr02 47,900 500 38,500 0
UO2 270,400 8,400 278,800 0
i Other" 43,300 24,700 58,500 8,800 l
Total 498,100 154,600 614,900 35,000 "Cr, Ni, B4C, Fe0, Fe304, Cr203, NiO, and B203 O
i G
9 w
r e
c F {b J-n r
a
"' ?S r
f sa o
r n
/4 ).
(-
o N ym ke c
\\
n ah n
- - e et l
l ts A
lm\\hs m
r t
bf a
aa A
.[.
.s*,
o K
).\\
.a' ey",
- a. a "
e ss eP t
@I I
nn l
n n
i o
- r. na li ui ma N
m[
na N
k
=h
{
rI.w w' _ t r,-Iii y,.
A oc i o t0 I
tl c
N ue sh A
.b bE t.
7l/
p n
n.
7 N
m;w
^
uRo m
I pAh F y I
S s nU N
o o
1~,, i',,"
1 i ms t al ah a l e urs coi rh iS m c
e eet rh s t y d
s
=
=
en
=
a mit u
n sd e N
sem 0ns t t oa asn L
fi c Ctat si t p A
U t
Os eua a
s
^
~
s t
P Laa h ct J
t t 3 MKeL t sn 1
v v
u U Ao a i o N
~
P EP ss fd c O
Rna
~
NBa T
.O t y o
m, C
T t e s
Ei I Nct nnh L
t
.T e
AI uf n
s a L La oet
.UNas S i d a
s e COe ti n
~
it E RI t f
. t TnA aci u [
p CceO s
Eus P cch RssW P
,A nat T
E e
t I
i
.h-t a
sw a
s u
e.
- n..
.i s
sl e.s s
e e
1 ae a
w t..
.b s
s 5
s e
S
- e..
e ne va es
. m.
.gv c
gi oc i sr e
e_
i
=
e ic.
F eo e
dt m
c es ea h e t r
- y
. 6 49 f?fLL e
sh l
SUPPA134 son g,
CnAusan 6,
88
- V
a.
t
- 0atutLL PLOCA g
Otrf gatu?4aL ee l
9 4
a.
fleet AFTE A ACCIO(Nf, SECONOS Flount 68J-4 PRIMARY CONTAINMENT SHORT. TERM PRES $URE RESPONSE TO A RECsRCUL ATION LINE S AE AR Sh0Atuau selfCL E AA P0w(# SfafiON WPearte suf fy assaLysis agpost a
see
=
neo DAVWi&6 390 9e E.
Am E
i ete SuprattStoss CMautta i
..I a
mit i.it g,
se**
He*
io*
si es TIMC Af f 8A ACClotNT* 8t C0h09 R
TAINWENT SHORT-TERM TEWPEA ATupt RESPON$E TO A RECIRCULAllON LINC SAE AM
! @ 2i"iF #!' 1*!a'4tV*"
1 l
l 1
Fig. 5. 2.
Calculated primary containment pressures and tempera-tures for the first 30 s af ter double-ended rupture of a recirculation l
pump suction line.
The results shown here are taken' f rom the Shoreham USAR.
j i
4 l
t 1
4
f' I
6.
SUMMARY
AND FINDINGS This letter report presents the results of calculations performed by personnel of the Boiling Water Reactor Severe Accident Te chnology (BWRSAT) Program at Oak Ridge National Laboratory.
The purpose of these calculations is to examine certain aspects of the potential for mitiga-tion of severe accident consequences afforded by. operation of the Shoreham Nuclear Power Station at 25% of rated power.
The areas exam-ined are those requested by the NRC-NRR technical sponsor of this work.
Degraded core response calculations have been performed for total l
loss of injection accident sequences using the Boiling Water Reactor Severe Accident Response (BWRSAR) models developed by the BWRSAT program at. 0ak Ridge.
To establish the delay in sequence event timing afforded by.the lowe r decay heat powe r levels derived from operation at 25%
q power, two accident sequence calculations were performed using identical i
input parameters except for the initial power levels, which were equiva-lent to 100% of rated power in one case and to 25% of rated power in the other.
Both calculations were carried out well beyond the time of pre-dicted failure of the reactor vessel bottom head penetrations so that the pouring of molten constituents of core debris f rom the vessel could be analyzed.
Anticipated Transient Without Scram (ATWS) calculations have been performed with the BWR-Long Term Accident Simulation (BWR-LTAS) code to examine the more sluggish reaction of a nuclear reactor to positive reactivity insertions with the control blades in the 25% power config-uration as opposed to the 100% power configuration.
Other ATWS accident sequence calculations were performed with the BWRSAR program models.
These calculations were based upon the C9D acci-dent sequence described in the LILCO submission regarding the operation j
of the Shoreham Nuclear Power Station at 25% power.
Their purpose is to j
examine the difference in predicted timing of severe accident events introduced by the BWRSAT program methodology (described in Table 3.1) as opposed to that used for the calculations cited by LILCO.
j A final set of calculations with the BWRSAR degraded core response
]
models was made to determine the shortest possible period of time be-l tween reactor scram and the onset of core degradation.
This occurs for the very low probability large-break LOCA with total loss of ECCS (AE) j accident sequence.
These calculations were performed both for scram from 100% power and for scram from 25% power, and were carried out i
through the period of release of molten material from the reactor vessel.
)
1
~
The major findings derived f rom the ef forts discussed above are as follows:
i 6.1
n l
L i
1.
Given the unlikely occurrence of an accident sequence that pro-
[
ceeds through core degradation and reactor vessel bottom head penetra-r tion failure, there would be a significantly longer period of time be-i tween the events of the severe accident sequence following operation at j
25% power than following operation at 100% power.
This conclusion is based upon calculations for the total loss of injection sequence and the comparison. of event timing provided in Table 3. 3, as well as calcula-tions for the large-break LOCA with loss of all ECCS sequence with its comparison of event timing provided in Table 5.1.
There is no reason to believe that a similar conclusion can not be drawn for any other acci-
. dent sequence for which comparison of event timing might be made.
- 2.. About 14% additional in-core hydrogen generation is predicted for the total loss of injection accident sequence initiated f rom 25%
power as opposed.to the hydrogen generation predicted for the identical i
sequence initiated from 100% power.
The additional hydrogen generation f
is primarily. caused by increased oxidation. of the channel box walls,
i which occurs during the time that they are slowly heated within the tem-I perature range at which oxidation occurs.
This matter is discussed in
-detail in-Sect. 3.3.
The generation of this additional hydrogen, while
. of interest, is not. a critical consideration because a great deal of I
hydrogen (>1600 lbs) is predicted to be generated regardless of the
)
assumed initial power.
3.
Given the continuance of a severe accident sequence beyond the point at which molten core debris would begin to pour from the reactor vessel, then consideration mist be given to the temperature of the reactor vessel wall in the vicinity of the bottom head.
With the core
-)
debris at the decay heat power level derived f rom previous operation at
]
100% power, the temperature of the debris is predicted to increase 1
rapidly, with the reactor vessel wall temperature lagging f ar behind.
f Under these conditions, much of the debris is predicted to have become
{
molten and left the vessel by the time the wall temperature. reaches I
levels at which creep rupture is expected to occur.
On the other hand, with the core debris heated by the lower decay
)
heat power level derived from previous operation at 25% power, the I
debris temperature increases more slowly, and the vessel wall tempera-
]
ture more closely follows the debris temperature.
Under these condi-tions, the wall temperature is predicted to reach temperatures at which I
creep rupture failure would be expected while a major portion of the core debris is still solid within the bottom head.
Thus, the results of the calculations described in this report do not support the contention of the. L1LCO submission that all core debris would exit the reactor vessel in a molten state.
4.
ATWS accident sequences initiated by transient-induced closure
)
of the main steam isolation valves f rom operation at 25% power should not be of concern.
Successful operation of the Standby Liquid Control l
System (SLCS) to inject neutron-absorbing poison solution would provide safe reactor shutdown.
In the unlikely event of f ailure of the SLCS function, the operators are directed by procedure to lower the water 6.2
{.
level to the top of the core and to depressurize the reactor vessel.
Recent prelimi na ry work at Rensselaer Polytechnic Institute ( Re f.
16) suggests that the Shoreham reactor would be suberitical in this config-uration even without liquid poison injection -- that is, with the con-trol blades in their 25% power positions, the reactor vessel water level at the top of the core, and the reactor vessel pressure at 200 psia (or below). However, if the reactor does remain critical in this configura-tion, then the results of the BWR-LTAS code calculations discussed in Sect. 4.2 demonstrate the sluggish reaction of the core to possible positive reactivity insertions caused by uncontrolled cold-water injec-tion by the low pressure ECCS systems.
5.
A shadow calculation performed for the severe accident phase of the C9D ATWS accident sequence described in the LILCO submission indi-cates that the ORNL BWRSAT program best-estimate method f or calculating degraded core and reactor vessel failure events (Table 3.1) predicts a much longer time to reactor vessel pressure boundary f ailure (30.8 h vs.
10.4 h) than does the MAAP code method used in calculating the results provided by LILCO.
This is because of the approach taken at ORNL that the water in the reactor vessel bottom head muet be boiled away before the bottom head penetration welds can become heated to f ailure tempera-tures.
I 6.
Fo r operation at 25% of rated power, the ve ry earliest that 1
core degradation might begin following the initiating event of an acci-dent sequence is calculated to be 59. 5 min.
This occurs in the large-I break LOCA with total loss of injection accident sequence (AE), which has a much lower probability than the loss-of-injection or ATWS sequences.
Failure of the reactor vessel bottom head penetrations is j
not predicted to occur until 469 min (7.8 h).
Additional information regarding event timing for this accident sequence is provided in Table 5.1.
E 6.3
7.
REFERENCES 1.
D.
H. Cooket a 1., Station Blackout at Broons Ferry Unit One -
Accident Sequence Analysis, Vol. 1, NUREC/CR-2182, November 1981.
2.
R. P. Wichner et al., Station Blackout at Broons Ferry Unit One -
j Iodine and Noble Gas Distribution and Release, Vol.
2, NUREG/CR-1 2182, August 1982.
i 3.
W.
A. Condon et a1., SBLOCA Outside Containment at Broons Ferm Unit One - Accident Sequence Analysis, Vol.
1, NUREG/CR-2672, October 1982.
4.
D. H. Cook et a1., Loss of DHR Sequences at Browns Ferry Unit One -
- Accident Sequence Analysis, NUREG/CR-2973, May 1983.
1 5.
R.
P.
Wichner et al.,
SBLOCA Outside Containment at Broons Ferry i
Unit one - Iodine, Cesium, and Noble Gas Distribution and Release, Vol. 2, NUREG/CR-2672, September 1983.
6.
R. M. Harrington and L. J. Ott, The Effect of Sm2tt-Capacity, High-Pressure Injection Systems on T4UV Sequences at Browns Ferry Unit One, NUREG/CR-3179, September 1983.
7.
R. M. Harrington and S. A. Hodge, ANS at Broons Ferry Unit One -
Accident Sequence Analysis, NUREG/CR-3470, July 1984.
8.
R. P. Wichner et al., Noble Cas, Iodine, and Cesium Transport in a Postulated Loss of Decay Heat Removal Accident at Browns Ferry,
NUREG/CR-3617, August 1984.
9.
R.
M.
Ha rrington and L.
C.
Fuller, BWR-LTAS:
A Boiling Water l
Reactor Long-Term Accident Simulation Code, NUREG/CR-3764, February l
1985.
10.
R.
M.
Ha rringt on, Modifications to BWR-LTAS Since December 1984, letter report to Dr. Thomas J. Walker, Division of Accident Evalua-tion, RES, USNRC, dated June 21, 1985.
11.
R.
M.
Harrington, Evaluation of Operator Action Strategies for Mitigation of MSIV Closure Initiated ANS, letter report to 1
Dr. Thomas J. Walker, Division of Accident Evaluation, RES, USNRC, dated November 11, 1985.
i t
12.
R. M. Harrington, The Effect of Reactor Vessel Pressure and Water Level on Equilibrium BWR Core Thern1b Pouer During MSIV-Closure-Initiated AWS, letter report to Dr. Thomas J. Walker, Division of Accident Evaluation, RES, USNRC, dated January 10, 1986.
I 7.1 l
a
.. y.
L-13.
R.
M.
Harrington and S.
A. Hodge, Loss of Control Air _ at Broons Ferry Unit One - Accident' Sequence Analysis, NUREGlCR-4413, April t
1986.~
J 14.- R. M. Harrington and S. A. Hodge, Containment Venting as a Severe
- Accident Mitigation Technique for BWR Plants tuith Mark I Contain-ment, letter' report to Dr. Thomas J. Walker, Division of Accident Evaluation, RES, USNRC, dated June 26, 1986.
15.
D.
H.; Cook, Codes Comparison. Analysks of A1WS for the James A.
Fitzpatrick Nuclear. PotJer Plant, letter report to Dr. Thomas J.
.i Walker, Accident Evaluation Branch, Division' of ' Reactor Accident Analysis,- RES, USNRC, dated May 11, 1987.
- 16. - Dr. R. T. Lahey, Jr.,: Chairman, Department of Nuclear Engineering and Engineering Physics, Rensselaer Polytechnic Institute, letter' of May 6,1987,. to Dr. Charles N. Kelber, Of fice of Nuclear Regula-i tory Research.
j s
l a-t 7.2
.]
a
I: m
< Mi m WN
%/
APPENDIX Memo'to
.S. A. Hodge May 28, 1987 N
' From: - R. M. Harrington
Subject:
' Control Rod Reactivity Input f or BWR-LTAS 25% Initial' Power ATWS Runs
- Three' runs were.made recently to scope theief fect of a 25% initial-power vs.100% initial power on the reactor response during a hypotheti-
. cal ATWS accident without operator action:
a full power run, with zero for parameter DKRODS and two runs with different negative control. rod' reactivities.
DKRODS - is the amount of. reactivity in the core due' to -
control' rods, and is the ~ only parameter affecting dynamic behavior that is different for differing initial power levels. The recirculation pump' speed varies with power. level, ' but during an ATWS, the recirculation pumps. are typically tripped very early on high vessel pressure (o r~.
slightly late.r on low vessel water level).. Since _ BWR-LTAS is initial-ized 50 s 'af ter the - beginning of the ~ accident, the recirculation pumps would' be tripped for all; cases,. so there would be no need ~for different L.
input numbers expressing different recirculation flow between 100% and' 25% initial' power levels.'
~
3 To determine _ what' amount of reactivity to use to : simulate the
. reactor at 25% power, the steady state version of.the BWR-LTAS reactor
. power ' calculating routine 'was run.
This program finds the ateady state power level based on. user -input ' for reactor pressure, downcomer water-level, jet. pump pressure rise (a function of recirculation pump speed),
core: inlet enthalpy, and ' control ' rod reactivity.
The input parameters
. for. void and doppler coefficients are based on Browns Fe rry informa-tion. Multiple runs'were made to search for the combination of jet pump pressure rise (i.e. recirculation pump speed) and negative : control rod reactivity that would be required to match the desired 25% core thermal power, and the 7% core outlet quality specified by - Shoreham in Lap Cheng's May 18, 1987 telecopy message.( Attachment 1).. Other parameters such as reactor vessel pressure were also. specified by Mr. Iap Cheng, and were the same for each run.
The result shows.that the control rods j
must add a negative 0.019 delta-K/K to reach the desired 25% power
' operating condition; the ~ code is set up to reproduce 100% power oper-
- ating-conditions without any control rod reactivity.
Therefore, it is concluded that a negative 0.019 delta-K/K control rod reactivity is required to reduce the reactor power f rom 100% to 25%.
The BWR-LTAS transient case with -0.019 control rod reactivity rep-resents a best estimate of response with 25% initial power.
In order to test'the sensitivity of the results to this input, the negative control rod reactivity was decreased by 20%, to -0.015 control rod reactivity.
A.1 o
r -
o
.i G.
)
As mentioned above, an' input of 0.0 control rod reactivity is used for 7,'
the 100% initial power case.
.In orderLto' test the conservatism of the BWR-LTAS based inputs for 7
negative control rod reactivity at 25% power, an independent estimate was based on the 'results of detailed steady state neutronic codes, also supplied in Attachment 1.
'At full power the total control rod insertion has been calculated by 'Shoreham'to be 514 notches; at 25% power the cor-responding insertion is' 1536 notches.
Since one notch. is 1/48 of the
' total travel of one control rod, and there are 137 control rods, the net total control rod insertion is 7.8% at full power and 23.3% at 25%
. powe r.
The total control rod worth is 24.968 dollars, or 0.18 delta-K/K; therefore, the extra negative reactivity required to decrease power f rom full power to 25% power. is:
y 1
DKRODS = -(0.233-0.078)
- 0.18 = -0.0279 delta-K/K This'shows that the -0.019 and -0.015 numbers used in the BWR-LTAS runs are well on the conservative side.
'1
.g.
.g.
1 e
'4 A.2 q
J
f 4
277C767;et 2 x ox TEL.ECOP!ER 4?5 13-5-67; 42 23Ft1
(
f%Y 18 '87 15127 SNPS NED P.2 N cl)a pa h C
ga n
('
TEl.EPHONE NEMORANDUM 1
Call Date f"/8-87 Time 20#o Bm
(
\\
Incomine Outgoing N
9etween$k of l k N. Y b'
f, f ds Q of. k k h.j h hl S d (/Yr.
e and of NED.
Subject E
bm At Aoout l
/)RNL,
V U
5Utt%RY: _ $D ImA $
sdA A5,o E /)A'//L M$pbw,
~
\\
N 29 'k 0 E e U
(do9 MA )
0 J
O HL Y w N A k 'k k k
=
32.b4 XtD b Ah /)s, Yiw
?]n3.
Ass 944 ocIs.
su VHb abs fla/M 2^7b 172dN. [w a HAAP
=
A n).fod}
I
& a)f sushN
= s.v7
?-
&Ldi K
\\
2 2.4 x d A tL-W L
' % a d s t = - 1(t 2. 4. M 9 ( " $ 1 Y $ 2 9 ? h N %
-~
\\
/
I MJmJ Lshk s+ iki<in - ta ib) 'wu++ %t hai ('lk2L3% %9) s b,
")
\\
(3"NJj\\{c-nbop)
'/
2 C $
h,o
/f3$ db a
lla~}& A sjAn d m N l$5. ~hurn >>L wo(TSo 7d'. 407
%:dL3 '1)~ Ja VN
=
1 % - Asl i M r.J. M L a il n a94. a hAkd L,, i L u.t+,,d nu g
V T/lV
^
7AA.
-- HHB s
gpg
- Ofl~me [NDsh)
Telephone Memoranda File A.3 u
-