Proposed Tech Specs Pages 3.3-4 & 3.3-6,replacing Page 3.3-6 Re Recirculation Loop Flow Transmitters & Applicable SRs Associated with Function 2.b
ML20209A735
Person / Time
Site: Cooper Entergy icon.png
Issue date: 06/23/1999
From:
NEBRASKA PUBLIC POWER DISTRICT
To:
Shared Package
ML20209A727 List:
References
NUDOCS 9907060126
Download: ML20209A735 (4)


Text

- . RPS Instrumentation

, 3.3.1.1 O SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.1.1.5 Verify the source range monitor (SRM) and Prior to intermediate range monitor (IRM) channels withdrawing overl ap. SRMs from the fully inserted position

,c o. 3.3.1.1.6 ------------------NOTE-------------------

Only required to be met during entry into MODE 2 from MODE 1.

Verify the IRM and APRM channels overlap. 7 days SR 3.3.1.1.7 Adjust the channel to conform to a 31 days calibrated flow signal.

o .

SR 3.3.1.1 8 Calibrate the local power range monitors. 1000 MWD /T

, ,, J average core exposure SR 3.3.1.1.9 Perform CHANNEL FUNCTIONAL TEST. 92 days N

a,,J egggt 4Q l L ,. % s J h s SR 3.3.1.1.10 ------------------NOTES- ---------------

1. Neutrondetectorsdreexcluded.
2. For Function 2.a not required to be performed when entering MODE 2 from MODE 1 until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after entering MODE 2.

Perform CHANNEL CALIBRATION. i 184 days

/~'i 9907060126 9 (continued)

(/ PDR ADOCK O 98 P PDR 1 Cooper 3.3-4 -Amendment N .170

  • 1 A .m u ~ +d ^

crsnyt +' %

  • t!~"

. . RPS Instrumentation

, 3.'3.1.1 O Table 3.3.1.1 1 (page 1 of 3)

Reactor Protection System Instrunentation APPLICA8LE CON 0lfl0NS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER TRIP REQUIRED SURVE1LLANCE ALLOWABLE FUNCTION CONDITIONS SYSTEM ACTION 0.1 REQUIREMENTS VALUE

1. Intermediate Range Mont' ors
a. Neutron Flux --High 2 3 G SR 3.3.1.1.1 5 121/125 SR 3.3.1.1.3 divisions of SR 3.3.1.1.4 futt scale SR 3.3.1.1.5 SR 3.3.1.1.6 SR 3.3.1.1.12 SR 3.3.1.1.13

' 'SR 3.3.1.1.15 5(*) 3 H SR 3.3.1.1.1 5 121/125 SR 3.3.1.1.3 divisions of SR 3.3.1.1.4 futt scale SR 3.3.1.1.12 SR 3.3.1.1.13 SR 3.3.1.1.15

b. Inop 2 3 G SR 3.3.1.1.3 NA SR 3.3.1.1.4 SR 3.3.1.1.13 5(*) 3 H SR 3.3.1.1.3 KA SR 3.3.1.1.4 SR 3.3.2.2.13 O, - 2. . Average Power Range
  • ' Monitors
a. Neutron Flux -High 2 2 G SR 3.3.1.1.1 s 14.5% RTP

~(Startup) SR 3.3.1.1.3

'"~ SR 3.3.1.1.4 SR 3.3.1.1.6 SR 3.3.1.1.8 SR 3.3.1.1.10 SR 3.3.1.1.13 .

SR 3.3.1.1.15 {

b. Neutron Flux Nigh 1 2 F SR 3.3.1.1.1 5 0.58 W l (Flow Blased) . SR 3.3.1.1.2 + 61.0% RTP j SR 3.3.1.1.4 and l SR 3.3.1.1.7 511g.0% 1 SR 3.3.1.1.8 RTP( ) i SR 3.3.1.1.9 3,"], l , l . l Q -

SR 3.3.1.1.10 SR 3.3.1.1.13 i SR 3.3.1.1.15 )

i (continued) '

i (a) With any controt rod withdrawn from a core cell containing one er more fuel esseabiles. l (b) 0.58 W + 61.0% 0.58 AW RTP when reset for sInste loop operation per LCO 3.4.1, " Recirculation Loops Operating."

.O . , - -

l Cooper 3.3-6 %d;r.t 16._370 A,.v.J 64 9. 4. u s ss q.a t y ar ,.. n l  !

, , RPS Instrum:ntation 3.3.1.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY

~

l SR 3.3.1.1.5 Verify the source range monitor (SRM) and Prior to intermediate range monitor (IRM) channels withdrawing SRMs overlap. from the fully inserted position i

SR 3.3.1.1.6 - -

NOTE-Only reauired to be met during entry into MODE 2 from MODE 1.

Verify the IRM and APRM channels overlap. 7 days SR 3.3.1.1.7 Adjust the channel to conform to a calibrated flow 31 days signal.

l j SR 3.3.1.1.8 Calibrate the local power range monitcts. 1000 MWD /T l average core  !

exposure l SR 3.3.1.1.9 Perform CHANNEL FUNCTIONAL TEST. 92 days SR 3.3.1.1.10 - -

-NOTES

1. Neutron detectors and recirculation loop flow transmitters are excluded.
2. For Function 2.a, not required to be performed when entering MODE 2 from MODE 1 until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after entering MODE 2.

184 days Perform CHANNEL CAllBRATION.

l l

Cooper 3.3-4

. - 1

. i J

i

, , RPS Instrumentation  ;

3.3.1.1 l j

Table 3.3.1.1-1 (poge 1 of 3)

Reactor Protection System Instrumentation APPLICABLE CONDITIONS ,

MODES OR REQUIRED REFERENCED 'j OTHER CHANNELS FROM J SPECIFIED PER TRIP REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS SYSTEM ACTION D.i REQUIREMENTS VALUE

1. Intermediate Range Monitors
a. Neutron 2 3 G SR 3.3.1.1.1 5 121/125 l Flux - High SR 3.3.1.1.3 divisions of full SR 3.3.1.1.4 scale SR 3.3.1.1.5 SR 3.3.1.1.6 SR 3.3.1.1.12 SR 3.3.1.1.13 I SR 3.3.1.1.15 5(a) 3 H SR 3.3.1.1.1 $ 121/125 SR 3.3.1.1.3 divisions of full SR 3.3.1.1.4 scale SR 3.3.1.1.12 SR 3.3.1.1.13 SR 3.3.1.1.15
b. 'Inop 2 3 G SR 3.3.1.1.3 NA SR 3.3.1.1.4 SR 3 3.1.1.13 5(a) 3 H SR 3.3.1.1.3 NA SR 3.3.1.1.4 SR 3.3.2.2.13
2. Average Power j

Range Monitors t I

a. Neutron 2 2 G SR 3.3.1.1.1 s 14.5% RTP Flux - High SR 3.3.1.1.3 (Startup) SR 3.3.1.1.4 SR 3.3.1.1.6 i SR 3.3.1.1.8 SR 3.3.1.1.10 SR 3.3.1.1.13 SR 3.3.1.1.15
b. Neutron 1 2 F SR 3.3.1.1.1 < 0.58 W Flux-High SR 3.3.1.1.2 + 61.0% RTP (Flow Biased) SR 3.3.1.1.4 and SR 3.3.1.1.7 < 119.0%

SR 3.3.1.1.8 ItTP(b)

SR 3.3.1.1.9 SR 3.3.1.1.10 SR 3.3.1.1.12 l SR 3.3.1.1.13 SR 3.3.1.1.15 (cont'nued)

(a) With any control rod withdrawn from a core cell containing one or more fuel assemblies.

(b) 0.58 W + 61.0% 0.58 AW RTP when reset for single loop operation per LCO 3.4.1, " Recirculation Loops Operating."

Cooper 3.3-6 L- _j