l m amme

- N h M C0irgicssy -

r - E: Ratt D. Wahers Vce Presdent June 24, 1986 Trojan Nuclear Plant Docket 50-344 License NPF-1 Director of Nuclear Reactor Regulation ATTN: Mr. Steven A. Varga Director, PWR-A Project Directorate No. 3 U.S. Nuclear Regulatory Commission Washington DC 20555

Dear Sir:

TROJAN NUCLEAR PLANT Detailed Control Room Design Review (DCRDR)

The enclosed attachments provide the information requested in your April 17, 1986 Supplemental Safety Evaluation (SSE) on the Detailed Control Room Design Review (NUREG-0737, Item I.D.1) for the Trojan Nuclear Plant.

Attachment A provides responses to the general issues raised in the SSE.

Attachment B provides revised pages for Amendment 3 of Topical Report PGE-1041, "DCRDR Summary Report", Volume 2.

Please let me know if additional information is needed, or if a meeting between our technical staffs would be useful to achieve closure of this issue.

Sincerely, Bart D. Withers Vice President Nuclear Attachment c: Mr. Lynn Frank Director State of Oregon Department of Energy Mr. John B. Martin Regional Administrator Region V I

000 8607030143 860624 '

PDR ADOCK 05000344 l l P PDR 121 S W Satmon Stret Prrand. Orecyn 97204 L 1

l Trojan Nuclear Plant Mr. S. A. Varga Docket 50-344 Attachment A License NPF-1 June 24, 1986 Page 1 of 6 1

I PGE RESPONSE TO DETAILED CONTROL DESIGN y

REVIEW SUPPLEMENTARY SAFETY EVALUATION Gdalitications and Structure of the DCaaR Team: 1 Human factors specialists continue to be involved in activities related to the DCRDR. PGE initiated a continuing services contract with General Physics Corporation (GPC) so that human factors expertise would be avail-able upon request.

Human factors specialists were not involved in the comparison of tasks and information and control requirements between the Revision 1 and Revision O Emergency Response Guidelines. A member of the DCRDR team performed these reviews and the verification of the controls and displays required to satisfy their requirements. Based upon his experience in the DCRDR as well as Trojan's validation and verification of the plant-specific Emergency Operating Procedures, assistance from a human factors specialist was not needed.

Human factors specialists have been involved and will continue to be involved in the annunciator system upgrade effort.

The selection of design improvements was a process in which human factors specialists were always involved. Conclusions reached during the meter study were discussed with GPC's specialist. For those instances in which we are unable to modify the control room as originally indicated at the completion of the DCRDR, GPC's specialist is consulted to discuss alter-native resolutions.

The verification of design improvements has had some -involvement by the

~

GPC specialist. In particular, last November while onsite for the SPDS human factors evaluation, a GPC specialist reviewed the surface enhance-ments made to the control boards as well as specific design changes installed.

Finally, PGE has issued a Human Factors Design Criteria and Review Program document. That document was critiqued several times by GPC's specialist for its human factors content.

Control Room Survey:

The objective of the annunciator study was to determine whether condi-tions warranted system replacement or selective modifications to resolve HEDs. The completion of the study resulted in selection of the replace-ment alternative. That decision was made in December 1985 and subse-quently the design group initiated the work required to develop the 1 preliminary and detailed engineering plans. These tasks include alarm l

Trojan Nuclear Plant Mr. S. A. Varga Docket 50-344 Attachment A License NPF-1 June 24, 1986 Page 2 of 6 reduction and prioritization and improvement in interpretability and arrangement as well as in-depth review of the system installation requirements.

Human factors principles have been part of the annunciator system upgrade design criteria from the beginning of the review. The intent is to re-solve, as much as possible, all HEDs in accordance with accepted human factors guidelines provided either by NRC or industry standards. GPC has been tasked to review the annunciator system upgrade study and provide a proposal to perform a review of the new annunciator system design.

While PGE cannot state at this time exactly how each individual HED will be corrected by the annunciator system replacement, we can generally pre-dict that the effects on HED resolutions will be as shown in Table 1.

Prior to approval of the final design, mockups of the annunciator panels will be constructed so that arrangement and interpretability resolutions can be approved by human factors engineering and management personnel.

Selection of Design Improvements:

Responses to comments in the SAIC Technical Evaluation Report (TER) on specific HEDs are included as revision to the individual HED forms, PGE-1041, Volume 2. As a group they make up Attachment B to this letter.

Numerous comments (HEDs 298, 299, 301-305, 307-309, and 311) concerning the P-250 computer design and operating characteristics were received.

Responses'to each are given on the applicable HED forms. In general, the P-250 provides display, alarming, data logging and some engineering cal-culations. There are no process control functions associated with the computer and it is not required for Plant operation. Since the P-250 is not safety-related nor the primary indicator of Plant status, we do not foresee any adverse impact upon Plant operations by the use of the P-250.

The SAIC TER Summary and Conclusions states that "Through the revisions in Amendment 2 to the description of the " ongoing human factors mainte-nance plan" and in HED descriptions and resolutions, PCE has indicated that it is no longer including the remote shutdown panels in the DCRDR". The removal of the remote shutdown panel from the DCRDR was described in Amendment 1 submitted on April 17, 1985. Amendment 1 was subsequently referenced in the original DCRDR Safety Evaluation of July 24, 1985.

HED Forms 470, 471 and 472 are indicated not to have been found in Amendment 2 received by SAIC. PGE verified that in-house data sets made in the same production run as those sent to the NRC did include these J

Trojan Nuclear Plant Mr. S. A. Varga Docket 50-344 Attachment A License NPF-1 June 24, 1986 l Page 3 of 6

- l forms. Therefore, we believe they were lost in transmittal between the NRC and its subcontractor. In any event, they are included in this sub-mittal.

As stated in the Summary Report, PGE's rationale for scheduling modifica-tions not only took into account the HED category, but also complexity of the solution, time for preliminary and detailed design work, procurement of material, and installation. In general, modifications not only re-solve DCRDR issues, but also affect other issues such as environmental qualification, fire protection, etc. Resource loading requires phased implementation of planned changes. While the company has attempted to be as responsive as possible, not all changes could be made in the first one or two outages after the study.

Please note that several HEDs with implementation dates of concern to the staff have been completed ahead of schedule. The original dates, se-lected in 1984, were best estimates, but where feasible, acceleration of the work has occurred. This is the case for HEDs 1, 55, 57, 115, 120, and 131 from Appendix D of the TER. The majority of other HEDs listed in that appendix are part of the annunciator system upgrade effort which is addressed above. .

I Verification That Improvements Will Provide the Necessary Corrections Without Introducing New HEDs:

1 l

Except for the annunciator system replacement, verification will occur i after, rather than before installation. Thus PGE recognizes that the verification process must continae beyond implementation to assure our-selves that resolution has been achieved and no new HEDs created. >

Section 6.0 of PGE's Human Factors Design Criteria and Review Program

document provides the methods utilized to accomplish this
surveys of j features, task analysis, verification of suitability and availability and J

validation of performance capability. One or more of the methods may be required for a given change.

i We would prefer not to leave the DCRDR open until such verfications are

, complete. Such items could be referred to the NRC regional office to verify completion as part of their routine plant inspections. Our desire is to conclude the DCRDR phase of our human factors effort at the earliest possible date.

Coordination of the DCRDR With Other Improvement Programs:

Specific response to the concerns on HED 403 is provided on the HED form. Operator training is clear that plant safety is the operator's primary responsibility and production-related activities are secondary.

Hence, it is understood that administration of tag-outs, when a clearance operator is not-stationed, is a secondary duty.

J

i Trojan Nuclear Plant Mr. S. A. Varga Docket 50-344 Attachment A License NPF-1 June 24, 1986 Page 4 of 6 Almost all changes to the control room occur during the refreling out-age. Prior to return to power, all operating crews and shift technical advisors attend " Ready for Startup" training. Lectures are given on all design changes, including the control room. Important design changes installed during the operating cycle may be addressed during periodic retraining sessions when necessary.

LWE/DJM/djh 0580P.0686

)

Trojan Nuclear Plant Mr. S. A. Varga Docket 50-344 Attachment A License NPF-1 June 24, 1986 Page 5 of 6 Table 1 Impact of Approved Annunciator System Replacement Scope on HED Resolutions by Category Alarm Deficiency Probable CateKory HED No. & Deficiency Resolution and Effect

1. Prioritization 126 - Grouping not New system will have ability and Reduction optimized: lack of to position any alarm in any system prioritization group. Alarms will be reor-ganized systematically.

127 - Global acknowledge New system will have sectional only (upsets priority acknowledge and new sequence decisions) per NUREG 0659.

132 - First-out erased New system will use sequence by acknowledge (upsets of events recorder (SER) that priority decisions) will obviate need for first-out on boards.

133 - First-out not Same as 132.

optimal.

236, 345 - Audibles New system will have no more confuse (upset priority than three tones to: 1)-Distin-decisions) guish SER from board, and 2) to distinguish top priority alarms from secondary priority alarms.

269, 137 - No priori- New system will have two color tization scheme authorization scheme on boards and third, lower level of pri oritization on'SER.

2. Interpretability 125, 276, 357 - New system will have uniform Lettering: Font sizes, lettering. All new tiles, use of tape; both upper legends will be approved by lower case; hard to see Human Factors Engineering.

135, 270 - No ringback New system will have visual

, ringback.

138 - Similar windows New system will have all new need to be grouped, tiles and can be arranged in lettered for improved Jany order with minimum effort. ,

interpretability J

I Trojan Nuclear Plant Mr. S. A. Varga Docket 50-344 Attachment A l License NPF-1 June 24, 1986 l Page 6 of 6 l l

Alarm Deficiency Probable Category HED No. & Deficiency Resolution and Effect

2. Interpretability 139 - Wordy or inac- New system will have all new (concluded) curate legends tiles, with concise, accurate legends.
3. Arrangements 364 - Grouping by New system can be arranged in functional designation any order with minimum effort.
4. New Features 128, 129 - Set of A new set of acknowledge buttons acknowledge buttons will be added.

missing 134 - Multiple input Additional reflash capability reflash missing will be added.

234, 235 - Sound levels -New system will result in removal unacceptable of fans, in noise reduction, and in new audible sounds. A new sound survey will be conducted.

271 - No ringback New system will have visual ring-unique flashing visual back (slow flash).

277 - Test button A new test button will be added missing on inner ring to inner ring.

P LWE/DJM/ cab 0580P.686 J

I

!!r. S. A. Varga Attachmint B l June 24, 1986 l DETAILED CONTROL ROOM DESIGN REVIEW (DCRDR)

SUMMARY

REPORT FOR THE TROJAN NUCLEAR PLANT PGE-1041 File this instruction sheet in the front of this manual as a record of changes.

The following information is furnished as a guide for the insertion of new sheets for Amendment 3 into the DCRDR Summary Report for the Trojan Nuclear Plant, PGE-1041. This material is denoted by "RPT DATE" of 06-II-86 on the individual human engineering discrepancy sheets.

New sheets should be inserted as listed below:

Discard Old Sheet Insert New Sheet Volume 2 HED 8 HED 8 HED 10 HED 10 HED 15 HED 15 HED 23 HED 23 HED 31 HED 31 HED 35 HED 35 HED 42 HED 42 HED 46 HED 46 HED 50 HED 50 HED 55 ,

HED 55 HED 58 HED 58 HED 59 HED 59 HED 65 HED 65 HED 66 HED 66 HED 87 HED 87 HED 91 HED 91 HED 107 HED 107 HED 119 HED 119 Amendment 3 (June 1986) 1

l l

DETAILED CONTROL ROOM DESIGN REVIEW (DCRDR) '

SUHMARY REPORT FOR THE TROJAN NUCLEAR PLANT PGE-1041 File this instruction sheet in the front of this manual as a record of changes.

The following information is furnished as a guide for the insertion of new sheets for Amendment 3 into the DCRDR Sununary Report for the Trojan Nuclear Plant, PGE-1041. This material is denoted by "RPT DATE" of 06-XX-86 on the individual human engineering discrepancy sheets.

1 j New sheets should be inserted as listed below:

Discard Old Sheet Insert New Sheet HED 131 HED 131 I

HED 136 HED 136 HED 138 HED 138 i

1 HED 156 HED 156 HED 172 HED 172 j

HED 226 HED 226 l

HED 228 HED 228 HED 230 HED 230 HED 238 HED 238 HED 260 HED 260 HED 278 HED 278 thru thru HED 282 HED 282 HED 284 HED 284 HED 288 HED 288 thru thru HED 290 HED 290 HED 296 HED 296

! Amendment 3 (June 1986) 4 t

e

. , ,- .r, - - - , , - --

- - - - - , - , - - - n -

F DETAILED CONTROL ROOM DESIGN REVIEW (DCRDR)

SUMMARY

REPORT FOR THE TROJAN NUCLEAR PLANT PGE-1041 File this instruction sheet in the front of this manual as a record of changes.

The following information is furnished as a guide for the insertion of new sheets for Amendment 3 into the DCRDR Summary Report for the Trojan Nuclear Plant, PGE-1041. This material is denoted by "RPT DATE" of 06-II-86 on the individual human engineering discrepancy sheets.

New sheets should be inserted as listed below:

Discard Old Sheet Insert New Sheet HED 298 HED 298 HED 299 HED 299 HED 301 HED 301 thru thru HED 305 HED 305 HED 307 HED 307 thru ,

thru HED 311 HED 311 HED 317 HED 317 HED 319 HED 319 HED 321 HED 321 HED 332 HED 332 ,

HED 346 HED 346 HED 353 HED 353 HED 357 HED 357 HED 368 HED 368 HED 369 HED 369 HED 386 HED 386 HED 387 HED 387 HED 398 HED 398 HED 400 HED 400 Amendment 3 (June 1986)

J

4

DETAILED CONTROL ROOM DESIGN REVIEW (DCRDR)

SUMMARY

REPORT FOR THE TROJAN NUCLEAR PLANT PGE-1041 J

File this instruction sheet in the front of this manual as a record of l changes.

The following information is furnished as a guide for the insertion of new sheets for Amendment 3 into the DCRDR Summary Report for the Trojan Nuclear Plant, PCE-1041. This material is denoted by "RPT DATE" of 06-KK-86 on the individual human engineering discrepancy sheets.

New sheets should be inserted as listed below:

Discard Old Sheet Insert New Sheet HED 402 HED 402 HED 403 HED 403 HED 406 HED 406  !

t HED 410 HED 410 HED 420 HED 420 HED 428 HED 428 HED 437 HED 437 i HED 440 HED 440 HED 444 HED 444 [

I HED 445 HED 445

! HED 447 HED 447 i

! HED 470 HED 470 HED 471 HED 471 j HED 472 HED 472 '

i I

l i

Amendment 3 (June 1986)

. l l  !

]

i 7 - , . -- -

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR I RPT NO: D06320 HED NO: 0008 RPT DATE: 06-17-88 - PLANT: TROJAN RPT TIME: 15:37:07 DATE: 02-09-82 TRACKING STATUS: CORRECTION REVIEWER: PRELIMINARY STUDY - P12 DATA SOURCE: CONTROL ROOM SURVEY - GP DOCUMENT NO: 1.2.2.3 0700 GUIDELINE NO: G.4.2.2 GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS CODING OF CONTROLS PANEL / WORKSTATION ID: COMPCNENT NO: COMPONENT DESCRIPTION:

GENERIC GENERIC PUMP AND VALVE CONTROLS DESCRIPTION OF DISCREPANCY IT CANNOT BE EASILY DETERMINED BY OPERATORS IF SOME VALVES ARE THROTTLEABLE OR NOT. THERE IS LITTLE USE OF SHAPE CODING FOR DISTINCTION OF CONTROLS.

RECOMMENDATION:

CHANGE INCORPORATE SHAPE CODING FOR PUMP AND VALVE CONTROLS. SEE APPENDIX A 0F THE PRELIMINARY STUDY FOR SUGGESTED SHAPE CODING CHARACTERISTICS.

ACTION:

RDC NO: 84-125 COMPLETE. SHAPE CODING FOR VALVES AND PUMPS IS NOT UTILIZED ON THE MAIN CONTROL BOARDS AT TROJAN. RATHER THE LABEL CONVENTION OF PROVIDING AN ALPHANUMERIC DESIGNATION ABOVE THE NOUN NAME IS USED. THEREFORE, THE OPERATOR READS "MG' CR "CV" TO INDICATE THE SWITCH IS A VALVE OR "P" TO INDICATE A PUMP PRIOR TO OPERATING THE SHITCH. THERE ARE VERY FEW THROTTLED VALVE CONTROL SWITCHES ON THE MAIN CONTROL BOARDS AND NO SPECIAL SHAPE CODE FOR IDENTIFICATION IS PROVIDED. INSTEAD, THOSE VALVES THAT ARE THROTTLEABLE (3)

ARE LABELED " THROTTLE" IN THE LOWER, RIGHT CORNER OF THE LABEL PLATE.

SEE EXAMPLE BELOW.

PROBLEN CATEGORY: 3 IMPLEMENTATION SCHEDULE: 12-31-85 '

I M o-7lOO A o)

BYPASS 83447 T HROTTLE ,

1 l

I

._ ~ . ,n s

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR i RPT NO: D06320 HED NO: 0010 RPT DATE: 00-23-86 PLAT 4T: TROJAN RPT TIME: 13:32:34 DATE: 02-09-82 TRACKING STATUS: CORRECTION REVIEWER: PRELIMINARY STUDY - P13 DATA SOURCE: CONTROL ROOM SURVEY - GP DOCUMENT NO: 1.2.3.2 0700 GUIDELINE NO: 6.4.1.2.A GUIDELINE AREA: GUIDELINE. SUBAREA:

C0t4TROLS PREVENTION OF ACCIDENTAL ACTIVATION PANEL / WORKSTATION ID: COMPONENT NO: COMP 0t1ENT DESCRIPTION:

, GEt4ERIC GEt1ERIC PUMP CONTROLS DESCRIPTION OF DISCREPANCY OPERATORS HAVE STATED THAT PUMPS IN THE WR0t1G TRAIN HAVE BEEN TRIPPED WHEN CONTRCLS ARE PLACED IN CLOSE PROXIMITY.

RECCMMENDATI0ti:

CHAtiGE C0t1 SIDER USE OF PLASTISCL HANDLES TO DESIGNATE DIFFERENT TRAINS.

ACTICri:

RDC NO: 84-125 COMPLETE. PLASTISOL HANDLES WERE C0tiSIDERED, BUT NOT USED DUE TO THE ABUNDANCE OF COLOR CODING ALREADY UTILIZED Ill THE C0t4 TROL RCOM. THE SURFACE ENHANCEMENT SCHEME UTILIZED COLOR (FOR CRITICAL SYSTEMS), DEMARCATI0t1 h3)

AtiD LABELS IN A COCRDINATED EFFORT AND HAS SIGNIFICATHLY IMPROV3CED i THE OPERATORS ABILITY AND EASE IN SELECTING COMPONEllTS IN THE CORRECT TRAIN. l THE CONVENTI0t1 0F TRAIN A COMPONENTS ON THE LEFT At1D TRAIN B COMP 0t4ENTS Oil l THE RIGHT IS GENERALLY FOLLOWED. FOR MAJOR SYSTEMS (CCW, SWS, SI, CS, HHSI)

HIERARCHICAL LABELING INDICATES THE TRAIN SEPARATION. FOR RHR, THE MINIC FLOWPATH MOVES FROM LEFT TO RIGHT, HENCE THE TWO TRAINS ARE PARALLEL TO THE (3)

FR0t4T EDGE OF THE pat 1EL, WITH TRAIN A INBOARD FROM TRAIN B. ONE EXCEPTION TO THE A/B LEFT/RIGHT CF fltATION ARE VALVE CONTROL SWITCHES ASSOCIATED WITH THE DIRTY WASTE DRAIN 'F.'ir. WHICH IS A SPLIT tat 4K CotiTAINING A CROSS CONtiECT.

THIS WAS PREVIOUSL? ' T dT7' :ED IN HED 028 AND C0tlSIDERED NOT TO BE A PROBLEM SINCE THE TANK IS U Jd0 i: RATED CROSS CONNECTED AND THUS THE SWITCHES ARE REALLY NOT TWO SEPARATE TRAINS.

PROBLEM CATEGORY: 1 IMPLEMENTATION SCHEDULE: 12-31-85 h

-_ - _ _ _ _ _ __ _ . - - . - -- 2

PORTLAND GENERAL ELECTRIC HUHAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0015 RPT DATE: 06-17-86 PLANT: TROJAN RPT TIME: 15:36:32 DATE: 02-03-82 TRACKING STATUS: CORRECTION REVIEHER: PRELIMINARY STUDY - P15 DATA SOURCE: CONTROL ROOH SURVEY - GP DOCUMENT NO: 1.2.3.4 0700 GUIDELINE NO: 6.4.1.2.C GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS PREVENTION OF ACCIDENTAL ACTIVATION PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-04 N/A FH PUMP TURB OVERSPD TRIP CONT DESCRIPTION OF DISCREPANCY THE FEEDWATER PUMP OVERSPEED TRIP BUTTON IS ONLY A ONE-STEP OPERATION.

RECCHMENDATION:

CHANGE PROVIDE A RED " COLLAR" FOR THAT BUTTON.

- ACTION:

i RDC NO:

COMPLETE. PLANT STAFF HAS TO PROVIDE A RED COLLAR VIA HAINTENANCE REQUEST.

HOWEVER, FURTHER INVESTIGATION OF PRINTS 6478-HS-19-6 AND G478-HS-9-10 REVEALED THAT THE HFP OVERSPEED TRIP TEST DEVICE HAS A DUAL STEP OPERATION. (3)

PUSHING THE OVERSPEED TRIP BUTTON ALONE WILL NOT CAUSE A PUMP TRIP.

RATHER, THE OVERSPEED TRIP TEST BUTTON IN THE CONTROL ROOH IS USED TC TEST THE OVERSPEED DEVICE WITHOUT ACTUALLY CAUSING A HFP TRIP. FOR THAT BUTTON TO HAVE ANY EFFECT, THE "0VERSPEED BLOCK" PUSHBUTTON IMMEDIATELY TO THE LEFT OF THE "0VERSPEED TRIP" PUSHSUTTON HUST FIRST BE DEPRESSED. THEN THE (3)

OVERSPEED TRIP TEST CONTINUES BY DEPRESSING THE OVERSPEED TRIP PUSHBUTTON.

ACTUAL CONTROL VALVE CLOSURE IS PREVENTED. THEREFORE, INSTALLATION OF A RED COLLAR DEVICE IS NOT HARRANTED.

PROBLEM CATEGORY: 3 IMPLEMENT ATION SCHEDULE: 09-30-85

( I ,

O Q.D

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0023 RPT DATE: 06-17-86 PLANT: TROJAN RPT TIME: 15:36:15 DATE: 02-09-82 TRACKING STATUS: CORRECTION REVIEHER: PRELIMINARY STUDY - P19 DATA SOURCE: CONTROL ROOM SURVEY - GP DOCUMENT NO: 1.1.1.7 0700 GUIDELINE NO: G.8.2.3 GUIDELINE AREA: GUIDELINE. SUBAREA:

PANEL LAYOUT LAYOUT CONSISTENCY PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-13 MO-205GA CS INDICATOR LIGHT C-19 MO-2053A CS INDICATOR LIGHT C-19 P-204A CS INDICATOR LIGHT C-19 P-204B CS INDICATOR LIGHT C-18 HO-2053B CS INDICATOR LIGHT C-18 HO-205GB CS INDICATOR LIGHT C-19 P-202A RHR PUMP INDICATOR LIGHTS C-19 P-2028 RHR PUMP INDICATOR LIGHTS DESCRIPTION OF DISCREPANCY IN THE SET OF INDICATOR LIGHTS REFERRED TO AS THE " CHRISTMAS TREE", THE LIGHTS IDENTIFIED AS STEPS 3 (CONTAINMENT SPRAY) AND 4 (RHR PUMPS) ARE REVERSED IN POSITION. THIS MAY LEAD TO A MISTAKEN READING BY AN OPERATOR.

RECOMMENDATION: l CHANGE SWAP POSITIONS OF THESE INDICATORS TO PROVIDE A NUMERICAL ORDER CONGRUENT WITH SEQUENCING OF EVENTS.

ACTION:

RDC NO:

NO CHANGE. DURING A SAFETY INJECTION IT IS NOT LIKELY NOR NECESSARY THAT THE OPERATOR OBSERVE THE INDICATING LIGHTS AS THE DBA LOADS SEQUENCE ON. g)

(THE XMAS TREE IS MOSTLY USED DURING SURVEILLANCE TESTING TO ASSURE PROPER LOAD START SPACING.) IN THE EVENT OF AN ACTUAL SAFETY INJECTION, UNLESS CONTAINMENT PRESSURE IS ABOVE 30 PSIG, THE CONTAINMENT SPRAY PUMPS ARE NOT GOING TO SEQUENCE ON ANYWAY. HENCE, THE MOST LIKELY SEQUENCE HILL BE THE STARTING OF THE SI PUMPS AND THEN THE RHR PUMPS. THE PROCEDURE DIRECTS THE OPERATOR TOWARD THE SEQUENCER TREE LIGHTS TO VERIFY SI ACTUATION.

IF NOT LIGHTED, HE IS DIRECTED TO START THE APPLICABLE EQUIPMENT, WHOSE CONTROLS ARE LOCATED ON C-12, C-13, C-18 AND C-19. DISPLAYS SUCH AS MOTOR (g)

AMPS, BREAKER SHUT, VALVE POSITION, COMPONENT FLOW RATE AND DISCHARGE PRESS ARE AVAILABLE. THE LATTER TWO ARE VERIFIED SEVERAL STEPS LATER BY PROCEDURE.

SEE ALSO HED 369.

PROBLEM CATEGCRY: 4 IMPLEMENTATION SCHEDULE: N/A J

{

PORTLAND GENERAL ELECTRIC HUHAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D08320 HED NO: 0031 RPT DATE: 06-17-88 PLANT: TROJAN RPT TIME: 15:35:57 DATE: 02-09-82 TRACKING STATUS: CORRECTION REVIEWER: PRELIMINARY STUDY - P21 DATA SOURCE: CONTROL ROOH SURVEY - GP DOCUMENT NO: 0700 GUIDELINE NO: 6.6.5.1 GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS USE PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-18 HO-3210A RHR HX CCW INLET FLOW RATE C-18 HO-3210B RHR HX CCW INLET FLOW RATE DESCRIPTION OF DISCREPANCY ON THE RHR HX CCW INLETS, THE FLOW RATES ARE CURRENTLY INDICATED ON A PIECE OF PAPER TAPED ONTO THE SWITCH HANDLE. THESE FLOW RATES ARE DISPLAYED IN THE AUXILIARY BUILDING ONLY.

RECOMMENDATION:

CHANGE IT WOULD BE PREFERRED TO HAVE THESE HEASURES INDICATED IN A HORE PERMANENT FASHION IF THEY ARE REQUIRED IN THE CONTROL R00H.

ACTION:

RDC NO:

NO CHANGE. THE INFREQUENT CHANGES HADE IN FLOW ARE NOT DIFFICULT TO HAKE AND REACTOR SAFETY REQUIREHENTS ARE ADEQUATELY DENOTED IN PROCEDURES. HIGH AND LOW CCW FLOW TO THE RHR HX ARE ANNUNCIATED. THE ANNUNCIATORS ARE LOCATED [3)

ON K-03, IMMEDIATELY ABOVE THE CCW CONTROLS ON PANEL C-18.

PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A I

O J0 D

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

' RPT NO: DOG 320 -

HED NO: 0035 ,

RPT DATE: 06-17-86 PLANT: TROJAN RPT TIME: 15:35:28 DATE: 02-09-82 TRACKING STATUS: CORRECTION REVIEHER: PRELIMINARY STUDY P23 DATA SOURCE: CONTROL ROOM SURVEY - GP DOCUMENT NO: 1.1.5.4 0700 GUIDELINE NO: 6.5.1.3 GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS READABILITY I

PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-14 TJR-2950 FH HEATER TEMP CHART RECORDER DESCRIPTION OF DISCREPANCY PRINTED RECORDS ON FEED WATER HEATER TEMPERATURE CHART RECCRDER (TJR 2950) ARE NOT READABLE.

RECOMMENDATION:

CHANGE REPAIR TO ENHANCE READABILITY. IF NOT REPAIRABLE, REPLACE. ]

.......____...........................................................__....... l l I ACTION:

l RDC NO:

l NO CHANGE. THE CHART RECORDER IS USED TO DISPLAY TRENDING INFORMATION I ON FEEDWATER HEATER TEMPERATURES. THERE ARE FOUR CHANNELS RECORDING AT EACH OF FIVE TEMPERATURE RANGES. THE CONCERN OF THIS HED IS THAT WITHIN EACH TEMPERATURE RANGE INDIVIDUAL CHANNELS CANNOT BE DIFFERENTIATED DUE TO SEVERAL VALUES PRINTED OVER ONE ANOTHER. THIS IS TRUE BUT NOT RELEVANT.

THE CRITICAL INFORMATION IS THE TRENDING OF TEMPERATURE AND IDENTIFYING THE FAILUTE OF A FEEDWATER HEATER. THIS RECORDER PROVIDES THAT INFORMATION.

IF AN INDIVIDUAL HEATER FAILS, ITS TEMPERATURE WILL BE DISPLAYED CLEARLY, AWAY FROM THE NORMAL PLOTTING OF THE OTHER HEATERS IN ITS RANGE.

IN

SUMMARY

, THE PRINTHHEEL HAS NEITHER REPLACED NOR REPAIRED. (3)

PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A

{

I

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0042 RPT DATE: 06-17-86 PLANT: TROJAN RPT TIME: 15:35:16 DATE: 02-09-82 TRACKING STATUS: CORRECTION REVIEWER: PRELIMINARY STUDY P-27 DATA SOURCE: CONTROL ROOH SURVEY - GP DOCUMENT NO: 1.1.5.14e 0700 GUIDELINE NO: G.1.5.3.F GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS ILLUHINATION PANEL / WORKSTATION ID: COMPONENT NO: CCHPONENT DESCRIPTION:

GENERIC NA RECORDERS AND HETERS C-02 NI-41B,428,438 AFD HETERS C-02 NI-44B AFD HETERS C-05 FI-3043A2,C2 AFW FLOW HETER C-05 FI-3043F2,H2 AFW FLOW HETER C-05 V-85,V-SYS SWYD AND SYSTEH VOLTS

C-05 FI-142A-145A SEAL INJECTION FLOW l C-12 TI-412,422,432 TAVG HETER l C-12 PI-403 LOOP D PRESSURE (WR)

- C-12 PI-120A CHARGING PRESSURE DESCRIPTION OF DISCREPANCY RECORDERS AND HETERS ARE NOT FREE OF GLARE WHEN VIEWED AT PANEL.

RECONHENDATION:

CHANGE USE NON-REFLECTING COATINGS OR HOODS ON RECORDERS AND HETERS.

ACTION:

ROC NO:

COMPLETE. THE DCRDR TEAM EVALUATED GLARE AS PART OF THE HETER SUITABILITY STUDY (SEE HEDS 032, 050, 059, 063, 283, 286, 287, 416, AND 417).

THE CONCLUSION OF THE STUDY WAS THAT GLARE IN NO CASE PREVENTED OPERATORS FRCH READING THE INDICATION. DUE TO THE ANGLE OF SOME CONTROL PANEL 3, THE APPLICATION OF SHALL HOODS DID NOT AFFECT THE GLARE ON THE HETER FACE. USE OF LARGER HOODS THAT WOULD EFFECTIVELY SHIELD THE HETER HERE CONSIDERED TO BE HORE OF A HINDRANCE THAN HELP. USE OF NONREFLECTIVE COATINGS WERE COH-SIDERED , BUT REJECTED FOR TWO REASONS: (1 INDUSTRY RESEARCH INDICATES THEY b>

00 A POOR JOB 0F REDUCING GLARE AND (2) NO READILY AVAILABLE SUPPLIER OF VX-252 (THE MAJORITY ARE THIS TYPE) HETER FACES WITH NONREFLECTIVE COATINGS COULD BE FOUND. THEREFORE, NO CORRECTIVE ACTION WILL BE TAKEN WITH RESPECT TO GLARE.

OTHER HETERS THAT HAVE SOME GLARE, AS IDENTIFIED DURING THE STUDY ARE:

PZR LEVEL (LI-459A,460A,461 A,462), PZR TEMP (TI-450,451,452,453,454 A),

DIESEL FUEL OIL TANK LEVELS (LI-4908, 4900A1/B1, 4904A/B), CST LEVEL (LI-5201

{ -5201,5265A), AFW ON C-19, AND PROCESS RADIATION HONITORS. l PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: 12-31-85

.o .ow

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

-( RPT NO: D06320 HED NO: 0046 RPT DATE: 06-17-86 PLANT: TROJAN RPT TIHE: 15:34:51 DATE: 02-09-82 TRACKING STATUS: CORRECTION REVIEHER: PRELIMINARY STUDY - P28 DATA SOURCE: CONTROL ROOH SURVEY - GP DOCUMENT NO: 1.1.4.15a 0700 GUIDELINE NO:

GUIDELINE AREA: GUIDELINE. SUBAREA:

PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

GENERIC NA VALVE & PUMP INDICATING LIGHTS DESCRIPTION OF DISCREPANCY THERE IS NO POSITIVE HEANS OF DIAGNOSING FAILED INDICATING LIGHTS FOR VALVES AND PUMPS.

RECOMMENDATION:

CHANGE THE ON-DUTY OPERATOR HILL REVIEW THE HAIN CONTROL BOARDS ONCE PER SHIFT

' TO ENSURE THAT THE INDICATOR LAMPS ARE OPERABLE DURING SURVEILLANCE l TESTING. AS PUMPS, VALVES AND OTHER EQUIPMENT CHANGE STATUS, THE LAMPS

  • l HILL BE VERIFIED TO BE LIT. A DETAILED ENGINEERING INVESTIGATION SHOULD BE IMPLEMENTED TO INVESTIGATE ALTERNATE SOLUTIONS. THE RESULTS OF THE ENGINEERING STUDY HILL DICTATE THE ADVISABILITY AND FEASIBILITY OF HODIFICATIONS TO THE PLANT'S CONTROL PANELS TO PROVIDE LAMP TEST CAPABILITY.

1 i

ACTION:

I RDC NO:

COMPLETE. AD 3-2, SHIFT ROUTINES, REQUIRES HALKDOWN OF THE CONTROL BOARDS l

SHIFTLY, NOTING PUMP AND VALVE STATUS. LACK OF AN ON OR OFF, OPEN OR SHUT, OR UNUSUAL COMBINATIONS OF, INDICATING LIGHTS ARE INVESTIGATED. ALTHOUGH (3)

THE PROCEDURE DOES NOT SPECIFICALLY IDENTIFY THE NEED TO 00 THAT, TO BE ALERT FOR SUCH DEFICIENCIES IS TAUGHT'THROUGH ON-THE-JOB TRAINING.

)

PROVIDING LAMP TEST CAPABILITY IS NOT REASONABLE DUE TO THE DESIGN OF THE INDICATING LIGHTS. THE GENERAL DESIGN IS TO USE CONTROL POWER FROM THE VALVE OR PUNP TO PROVIDE INDICATION. IT THUS PROVIDES POSITIVE INDICATION OF SYSTEM CONTROL POWER AVAILABILITY. LAMP TEST CABABILITY WOULD EITHER REQUIRE INDIVIDUAL PUSH-TO-TEST CIRCUITRY OR A SINGLE TEST BUTTON TO ACTUATE ALL LAMPS. NEITHER SOLUTION IS DESIREABLE.

USE OF DUAL FILAMENT BULBS IS UNFEASIBLE. THE CURRENT INDICATING LIGHTS ARE OPERATED OFF OF 120 VAC OR 125 VDC. THE SCHEHE USED IS A DROPPING RESISTOR IN SERIES WITH A 55 VOLT, .05 AMP, 1.1 NEAN SPHERICAL CANDLE POWER INDICATING LIGHT IN A T-31/4 ENVELOPE (GE 1835). THERE ARE NO MANUFACTURERS OF A DUAL FILAMENT BULB THAT CAN BE DIRECTLY PLACED IN OUR INDICATORS. SPECIAL PRODUC-i TION AT A COST IN EXCESS OF $1 PER BULB WITH A HINIMUM ORDER OF 100,000 MAY I BE POSSIBLE, BUT NOT WARRANTED. ,

NO FURTHER ACTION WILL BE TAKEN.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: N/A

PORTLAND GENERAL ELECTRIC HUHAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR I

( RPT NO: D06320 HED NO: 0050 RPT DATE: 06-18-86 PLANT: TROJAN RPT TIME: 14:28:15 DATE: 02-08-82 TRACKING STATUS: CORRECTION REVIEHER: PRELIMINARY STUDY - P30 DATA SOURCE: CONTROL ROOM SURVEY - GP

. DOCUMENT NO: 1.1.3.1 0700 GUIDELINE NO: 6.5.1.5.C I

GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS SCALE HARKING j PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-05 N/A HAIN GENERATOR FREQUENCY

C-05 PI-507/508 STEAM DUMP & HFP DISCHG PRESSURE 3

C-11 A1,A2,A5,AG,H1,H2 BUS VOLTAGE INDICATION C-11 232KV LINES BUS VOLTAGE INDICATION C-12 FI-110 BORIC ACID TO BLENDER FLCH C-12 TI-412 THRU 442 T AVG INDICATION C-12 PI-44GS INST AIR HEADER PRESSURE C-18 P-203A/B,-204A/B SIP AND CSP HOTOR AMPS INDICATION C-19 PI-2071A/B CSP HEADER PRESSURE C-19 PI-960 TO 967 SI ACCUHULATOR PRESSURE i

DESCRIPTION OF DISCREPANCY THE HETERS INDICATED ABOVE HAVE SCALES WHICH ARE NOT NUMBERED ON EVERY TENTH INTERVAL.

! RECOHHENDATION:

CHANGE I

INVESTIGATE THE DEGREE TO HHICH THIS DISCREPANCY DETRACTS FROH READABILITY. )

ACTION:

RDC NO:

COMPLETE. DUE TO THE NUMBER OF ITEMS REQUIRING REVIEH, AN ADDITIONAL STUDY HAS REQUIRED. IT IS DOCUMENTED IN JHL-642-85H DATED OCT 14, 1985.

OTHER RELATED HEDS ARE 032, 042, 053, 063, 283, 286, 287, 416, AND 417.

t THE STUDY CONCLUDED THAT ALTHOUGH THE HETERS INDICATED ABOVE DID NOT SPECIFICALLY HEET NUREG-0700 CRITERIA, SCALE MARKINGS HERE SUFFICIENTLY

, CLEAR AND DO NOT REQUIRE ADDITIONAL NUMBERS ON EVERY TENTH OR HAJOR SCALE INTERVALS. THE HETER STUDY INCLUDED INPUT FROM THE DCRDR TASK ANALYSIS (3)

IN DETERMINING THE READING ACCURACY HEEDED AND CONCLUSIONS STATED ABOVE.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: N/A 1

I ,

1 1

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0055 RPT DATE: 06-18-86 PLANT: TROJAN RPT TIME: 14:28:00 DATE: 02-09-82 TRACKING STATUS: CORRECTION -

REVIEHER: PRELIMINARY STUDY - P33 DATA SOURCE: CONTROL ROOM SURVEY - GP DCCUMENT NO: 1.7.1.10 0700 GUIDELINE NO:

GUIDELINE AREA: GUIDELINE. SUBAREA:

PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-05 LR- 50' S.G. HIDE RANGE LEVEL REC C-05 LR-503 S. G. HIDE RANGE LEVEL REC DESCRIPTION OF DISCREPANCY THE FUSE BLOWS ON THE STM GEN HIDE RANGE LEVEL RECORDERS (LR-501 &

LR-503) ON THIS PANEL.

RECOMMENDATION:

CHANGE THIS PROBLEM SHOULD BE INVESTIGATED AND CORRECTED.

ACTION:

RDC NO: 84-093 CCMPLETE. RDC 84-093 REPLACED THE TWO HIDE RANGE RECORDERS WITH CHESSELL MODEL 301*S. NEW CHANNELIZED POWER SUPPLIES FROM PREFERRED INSTRUMENT BUSES HERE PROVIDED. THE SEISMIC QUALIFICATION TESTING HAS COMPLETED AHEAD OF SCHEDULE AND THEREFORE INSTALLATION OCCURRED DURING THE 1986 REFUELING OUTAGE. SYSTEM RELIABILITY IS ENHANCED BY APPLICATION OF MORE STRINGENT (3)

DESIGN CRITERIA. IN KEEPING WITH THE NEW CHANNELIZED DESIGN, RECORDER DESIGNATIONS HERE CHANGED TO LR-501 AND LR-502.

............................................................................... _1 PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: 09-30-87 l

__ _.__ _ _ _ _ _ _ _ _ . . J

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR i

( RPT NO: D06320 HED NO: 0058 f RPT DATE: 06-18-86 PLANT: TROJAN ,

RPT TIHE: 14:27:51 DATE: 02-09-82 TRACKING STATUS: CORRECTION REVIEHER: PRELIMINARY STUDY- P34 ,

...............__..__.......................................................... j DATA SOURCE: CONTROL ROOH SURVEY - GP DOCUMENT NO: 1.1.1.1 0700 GUIDELINE NO: G.8.2.1.C GUIDELINE AREA: GUIDELINE. SUBAREA:

PANEL LAYOUT SEQUENCE PANEL /HORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-06 RIS-4184 (PRM-14) CONTAINHENT SUHP RAD HETER DESCRIPTION OF DISCREPANCY THE CONTAINHENT SUHP RAD HETER (RIS4184) IS ON PANEL C-06 AND HOULD BE ,

HORE PROPERLY PLACED ON PANEL C-41 HITH THE REST OF THE PROCESS RAD HETERS.

RECOHHENDATION:

CHANGE THIS HETER SHOULD BE HOVED TO PANEL C-41.

ACTION:

RDC NO: 84-134 NO CHANGE. PANEL C-41 IS ALREADY EXTREHELY CONGESTED. ROUTINE SUR-VEILLANCE TESTING AND CORRECTIVE HAINTENANCE IS EXTREMELY DIFFICULT. -

ALTHOUGH IT IS RECOGNIZED THAT FROM AN OPERATIONS VIEHPOINT IT IS DESIREABLE TO HAVE ALL PRHS IN ONE LOCATION, ONE HUST ALSO CONSIDER

.THE IMPACT ON EQUIPMENT HAINTAINABILITY AND HORKER SAFETY. SINCE C-41 AND PRM-14 ALERT AND HIGH ALARM LIGHTS ARE EASILY VISIBLE FROH THE CENTRAL CONTROL PANELS, HOVEMENT OF PRH-14 IS NOT HARRANTED. THERE ARE NO SEQUENTIAL OPERATIONS INVOLVING PRM-14 AND COMPONENTS ON C-41. HENCE, (3)

NO ENHANCEMENT TECHNIQUES HERE EMPLOYED TO ASSOCIATE PRH-14 HITH C-41.

PROBLEH CATEGORY: 3 IMPLEMENTATION SCHEDULE: N/A i I m an

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0059 RPT DATE: 06-19-86 '

PLANT: TROJAN RPT TINE: 15:55:53 DATE: 02-09-82 TRACKING STATUS: CORRECTION REVIEHER: PRELIMINARY STUDY - P34 DATA SOURCE: CONTROL ROOM SURVEY - GP DOCUMENT NO: 0700 GUIDELINE NO: G.5.1.4.F GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS PRINTING ON THE DISPLAY FACE PANEL /HORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-06 FI-7111A CONDENSATE DEMINERALIZER HETER C-06 FI-7111H CONDENSATE DEHINERALIZER HETER DESCRIPTION OF DISCREPANCY CONDENSATE DEMINERALIZER HETERS (FI 7111A TO FI 7111H) ARE SCALED 0-500

} GPH AND IT IS NOT INDICATED THAT THIS HEASURE SHOULD BE X10 (i.e.

l 0-5000).

RECOMMENDATION:

CHANGE

(

SCALE FACE SHOULD READ X10.

ACTION:

RDC NO:

NEW SCALES ARE TO BE INSTALLED UTILIZING BLACK CHARACTERS ON A HHITE BACK-l

' (3)

GROUND. THE SCALE HULTIPLIER OF TEN HILL BE ADDED TO THESE SCALES.

l SEE ALSO HEDS 0042,050, 283, 288, 287, 416 AND 417.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: 09-30-86 l

\

I 1

l

( i

PORTLAND GENERAL ELECTRIC HUHAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR i RPT NO: 006320 HED NO: 0065 RPT DATE: 06-18-86 PLANT: TROJAN RPT TIME: 14:27:23 DATE: 02-09-82 TRACKING STATUS: CORRECTION REVIEHER: PRELIMINARY STUDY - P38 DATA SOURCE: CONTROL R00H SURVEY - GP DOCUMENT NO: 1.1.3.2 0700 GUIDELINE NO: 6 . 5 .1. 2 GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS USABILITY OF DISPLAYED VALUES PANEL /HORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-41 GENERIC PROCESS RADIATION HETERS DESCRIPTION OF DISCREPANCY PRCCESS RADIATION HETERS USE LOG SCALES AND ARE DIFFICULT TO SET AT SETPOINTS CALLED FOR IN THE PROCEDURES. PRESENTLY SOME SETPOINTS ARE HARKED IN GREASE PENCIL (e.g. RIS-4372A) .

RECOHHENDATION:

CHANGE DETERMINE THE POSITION OF SETPOINTS ON THE HETERS AND USE TAPE TO INDICATE THEH.

ACTION:

RDC NO:

COMPLETE. THE AREA RADIATION HONITOR ALARHS ARE SET BY I&C TECHNICIANS AND-DO NOT VARY. THE PROCESS RADIATION HONITORS HAVE SETPOINTS THAT VARY I g)

ACCORDING TO THE RADIDACTIVITY LEVELS OF THE EFFLUENTS PLANNED TO BE RELEASED. THE CONTROL OF THESE SETPOINTS IS HELL CONTROLLED BY PROCEDURE.

THE EXPECTED PRM COUNT RATE IS CALCULATED BY A CHEHISTRY TECHNICIAN. A MARGIN TO ACCOUNT FOR THE BACKGROUND COUNTS IS ADDED TO THE EXPECTED COUNT RATE TO ESTABLISH THE FIRST ALARM LEVEL. THE SETPOINT IS ADJUSTED BY TAKING THE PRM OPERATING SWITCH TO " CAL" AND ADJUSTING A KNURLED KNOB TO THE ALARM (3)

, LEVEL DESIRED. UTILIZING THE LOG SCALES, THE OPERATOR IS ABLE TO ADJUST THE SETPOINTS TO THE VALUE DESIRED. THE SETPOINT IS AN APPROXIMATE VALUE AND NEED HOT BE SET TO HORE THAN 2 OR 3 SIGNIFICANT DIGITS (IE. 2.3E3 OR 4.5EG) .

PROBLEH CATEGORY: 3 IMPLEHENTATION SCHEDULE: N/A

(

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR i RPT NO: 006320 HED NO: 0066 RPT DATE: 06-18-86 PLANT: TROJAN RPT TIME: 14:27:07 DATE: 02-09-82 TRACKING STATUS: CORRECTION REVIEWER: PRELIMINARY STUDY - P38 DATA SOURCE: CONTROL ROCH SURVEY - GP DOCUMENT NO: 1.1.1.2 0700 GUIDELINE NO: 6.1.1.3.C ,

GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS FURNITURE AND EQUIPMENT LAYOUT PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-41 RIS-5701A PROCESS RADIATION HETER l C-41 RIS-57018 PROCESS RADIATION HETER '

C-41 RIS-43GSA PROCESS RADIATION HETER C-41 RIS-43BSB PROCESS RADIATION HETER DESCRIPTION OF DISCREPANCY RADIATION HETERS ARE AS HIGH AS 82". ONE OPERATOR REQUIRES A STOOL TO TURN THE SWITCH.

RECOMMENDATION:

INVESTIGATE FURTHER INVESTIGATE POSSIBLE SOLUTIONS.

ACTION:

RDC NO: ._

NO CHANGE. ThE SWITCHES ARE NOT OPERATED FREQUENTLY AND A LADDER, IS PROVIDED WHEN REQUIRED BY THOSE OPERATORS SHORT IN STATURE. THE LADDER HAS AN UPPER PLATFORM APPROXIHATELY 3.5 FEET OFF THE DECK AND IS {

THE SAME ONE UTILIZED BY OPERATORS TO REACH ANNUNCIATOR TILES WITHOUT CLIMBING ON THE CONTROL PANELS. IT REMAINS IN THE CONTROL ROOH AT ALL (

TIMES. THESE HETERS ARE ORIENTED HORIZONTALLY AND PARALLAX IS NOT A PROBLEH.

PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A l

i se

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0087 RPT DATE: 06-18-86 PLANT: TROJAN ~

RPT TIME: 14:26:46 DATE: 02-08-82 TRACKING STATUS: CORRECTION REVIEHER: PRELIMINARY STUDY - P45 DATA SOURCE: CONTROL ROOH SURVEY - GP DOCUMENT NO: 1.2.1.5 0700 GUIDELINE NO: G.S.1.1.C GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS SINGLE CONTROL AND DISPLAY PAIRS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

l C-14 PDC-2967 AFH PUHP D/P CONTROLLER C-14 PDC-3083A AFH PUMP D/P CONTROLLER C-14 PDC-3083B AFH PUHo D/P CONTROLLER C-14 HIC-3455 HAIN TURBINE COLD LUBE DIL DESCRIPTION OF DISCREPANCY AUX FH PUHP D/P CONTROLLERS ARE NOT IN ORDER HITH THE AFH PUHP DISCH PRESSURE HETERS ABOVE, AND HAIN TURB COLD LUBE OIL (HIC 3455) IS NOT IN ORDER HITH ITS RELATED RECORDERS.

I RECOMMENDATION:

CHANGE LINE THESE CONTROLLERS UP SO THEY ARE IN ORDER OF (LEFT TO RIGHT):

STARTUP AFW PUMP (PDC 2967), HEST AFH PUHP (PDC 3083A), EAST AFH PUMP (PDC 3083B) AND HIC 3455. THIS INVOLVES DRILLING FOR ONE INDICATOR -

LIGHT. AN ALTERNATIVE IS TO SWAP THE HETERS ALTHOUGH STARTUP IS USED FIRST AND SHOULD BE ON THE LEFT.

ACTION:

RDC NO: 84-136 THE LINEUP OF THE AFHP CONTROLLERS HILL BE CHANGED BY RDC 84-136 HITH THE STARTUP AFHP ON THE LEFT FOLLOWED BY THE HEST AND EAST AFHP TO THE RIGHT.

THE AFHP DISCHARGE PRESSURE HETERS ON THE VERTICAL PART OF THE PANEL HILL BE IN THE SAME ORDER. THESE CONTROLLERS AND HETERS HAVE BEEN COLOR PADDED LIGHT BLUE FOR ASSOCIATION HITH THE REST OF THE AFH CONTROLS ON OTHER PANELS.

THE MAIN TURB OIL TEMP CONTROLLER HILL BE HOVED TO THE RIGHT HAND SIDE OF THE BANK OF CONTROLLERS. IT HILL BE OUTSIDE THE DEMARCATION AND COLOR PADDING OF THE AFW CONTROLS.

DEMARCATION, COLOR PADDING AND HIERARCHICAL LABELING HAS PERFORMED AS IF THE CONTROLLER HAD ALREADY BEEN RELOCATED. ALTHOUGH THIS RESULTS IN THE MAIN TURB OIL TEMP CONTROLLER INSIDE THE DEMARCATION AND THE STARTUP AFHP OUTSIDE, IT HAS FELT THIS HAS PREFERABLE TO REDOING THE COLOR PADDING AND DEMARCATION (g) i A SECOND TIME. A DISTINCT DIFFERENCE IN THE APPEARANCE OF THE DIL TEMP AND AFHP CONTROLLERS HAKES IT UNLIKELY THAT ONE HOULD BE HISTAKEN FOR THE OTHER.

< PROBLEH CATEGORY: 3 IMPLEMENTATION SCHEDULE: 12-31-87 6

PORTLAND EENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SiECIFIED BY HED NBR f RPT NO: D06320 HED NO: 0091 RPT DATE: 06-18-8B PLANT: TROJAN RPT TIME: 14:26:20 DATE: 02-09-82 i

TRACKING STATUS: CORRECTION l REVIE ER PRELIMINARY STUDY P47 l

DATA SOURCE: CONTROL ROOM SURVEY - GP DOCUMENT NO: 1.2.1.13 0700 GUIDELINE NO: 6.8.2.1.C 1 GUIDELINE AREA: GUIDELINE. SUBAREA: ,

PANEL LAYOUT SEQUENCE PANEL /HORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION: i C-15 UI-500 STEAM DUMP VALVE SIGNAL INDIC DESCRIPTION OF DISCREPANCY METER UI 503 STEAM DUMP VALVE SIGNAL ON PANEL C 15 IS USED HITH THE STEAM DUMP VALVE INDICATORS.

RECOMMENDATION:

CHANGE HOVE THIS HETER CLOSER TO STEAM DUMP VALVE INDICATORS ON C-15 OR TAPE IT OFF FOR ASSOCIATION HITH THE STEAM DUMP VALVE INDICATORS.

ACTION:

RDC NO:

NO CHANGE. OPERATOR USE OF THE UI-500 HETER HAS NOT OBSERVED DURING THE TASK ANALYSIS AND HALK THROUGHS OF THE EMERGENCY INSTRUCTIONS. THE OPERATOR HUST BE AT C-02 TO OPERATE STEAN DUMPS AND THE CONTRCLLER ON C-02 INDICATES THE SAME DEHAMD SIGNAL AS IS PRESENT ON THE UI-500 METER.

THE UI-500 METER IS NOT A VALVE POSITION INDICATOR. RATHER IT IS A MEASURE OF THE DEGREE TO HHICH THE STEAM DUMP CONTROL SYSTEM THINKS THE STEAN DUMPS SHOULD BE OPEN. BASED UPON THAT SIGNAL STRENGTH, THE OPERATOR CAN VERIFY THE DUMPS ARE OPERATING PROPERLY BY OBSERVING STEAH (3)

DUMP VALVE POSITION INDICATION ON C-15, TAVG, AND S/G STEAM PRESSURE.

THEREFORE, A DEMAND SIGNAL IS THE CORRECT TYPE OF INDICATION FOR UI-500.

PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A l i l

PORTLdND GENERAL ELECTRIC I HUMAN ENGINEERING DISCREPANCY l NED RECORD SPECIFIED BY HED NBR l

i RPT NO: D06320 HED NO: 0107 i RPT DATE: 06-18-86 PLANT: TROJAN l 4 RPT TIME: 14:26:C DATE: 02-09-82 TRACKING STATUS: CORRECTION

, REVIEWER: PRELIMINARY STUDY - P53 DATA SOURCE: CONTROL R00H SURVEY - GP 4 ............................................................................... i i

DOCUMENT NO
1.2.3.1 0700 GUIDELINE NO: G.5.1.6 I GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS COLOR CODING PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

! C-04 D-5011 EVACUATION SIREN SHITCH l C-04 CONTAINMENT EVACUATION HORN CONT DESCRIPTION OF DISCREPANCY

EVACUATION SIREN AND CONTAINMENT EVACUATION HORN SWITCHES HAVE BEEN j ACCIDENTALLY ACTUATED WHEN OPERATORS ATTEMPTED TO ACTIVATE THE j STEAMLINE AND PRESSURIZER BLOCK AND RESET SWITCHES.

I RECOMMENDATION:

CHANGE I

3 PROVIDE SOME HEANS OF VISUAL DISTINCTION, e.g. RED LABELS.

ACTION:

RDC NO: 84-125 i RDC 84-125 WILL PROVIDE WHITE DEMARCATION AROUND EACH OF THESE CONTROL KNOBS.

i AFTER SEEING CROSSHATCHING ON THE LOCFOUT SWITCH COLOR PADS EARLIER, IT HAS DECIDED THAT ADDITIONAL CROSSHATCHING OF CONTROLS WITH ECONOMIC SIGNIFICANCE

, WCULD BE OVERBEARING. THEREFORE, WHITE DEMARCATION WAS SELECTED TO HAKE THIS (3)

DISTINCTION WITHOUT USING THE CROSS HATCHES. RAPID OR INADVERTENT OPERATION i 0F THESE SHITCHES IS NOT CONSIDERED NEARLY AS SIGNIFICANT AS THE REACTOR TRIP SWITCHES. THUS THE USE OF RED COLOR PADS TO HIGHLIGHT THEIR LOCATION i NAS DISREGARDED.

PROBLEM CATEGORY: 1 IMPLEMENTATION SCHEDULE: 05-30-86 l

J d

t I

i l

1 1

i

.- -. - . . - - _ _ . .= . _ . - - . -- . . _ . - - .

I PORTLAND GENERAL ELECTRIC I

HUHAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: 006320 HED NO: 0118 i RPT DATE: 06-18-8C PLANT: TROJAN l RPT TIHE:' 14:25:45 DATE: 02-08-82 TRACKING STATUS: CORRECTION t

l REVIEHER: PRELIMINARY STUDY - P58 t j DATA SOURCE: CONTROL ROOH SURVEY - GP

DOCUMENT NO
1.2.1.14e 0700 GUIDELINE NO:

i ...............................................................................

I GUIDELINE AREA: GUIDELINE. SUBAREA:

l PANEL /HORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

j C-18 GENERIC VALVE POSITION INDICATORS FOR SI i ...............................................................................

i DESCRISTION OF DISCREPANCY l THERL IS NO EASY HETHOD TO IDENTIFY THE VALVES WHICH REALIGN DURING A i SAFETY INJECTION.

j ...............................................................................

j RECOMMENDATION:

! CHANGE CONSIDER COLOR PADDING THESE VALVES THE SAME COLOR AS THE SI HODULE. AN i ALTERNATIVE SOLUTION HOULD BE TO PROVIDE PLASTISOL HANDLES ON THESE i k VALVE SWITCHES.  ;

j ...............................................................................

) AC1 0N:

j RDC NO: 84-125 COMPLETE. ALL COMPONENTS ARE ADDRESSED IN INDIVIDUAL SYSTEM PORTIONS OF j COLOR PADDING ENHANCEMENT SCHEME. THE SCHEHE ALLONS THE OPERATOR TO FOCUS

! HIS ATTENTION ON A SHALLER PORTION OF THE BOARD, THEREBY SIGNIFICANTLY REDUCING THE NUMBER OF VALVES HE HUST LOOK AT IN ORDER TO FIND THE ONE HE I WANTS. THIS EFFECT WAS NOTED BY OPERATORS PERFORMING PERIODIC OPERATING

! TESTS SHORTLY AFTER INSTALLATION OF THE COLOR PADDING.

i ACTUAL RECOGNITION OF CORRECT ALIGNMENT IS A FUNCTION OF OPERATOR PROCEDURES (3)

I AND TRAINING. SI STATUS PANEL PROVIDES CRITICAL LINEUP INFORMATION THAT l INDICATES IF THE PROPER INJECTION OR RECIRCULATION FLOWPATH IS AVAILABLE.  !

IN ADDITION CRITICAL VALVES IN THE FLOW PATHS HAVE THEIR CONTROL SWITCH

! LABEL PLATES COLOR CODED WITH EITHER A RED OR GREEN DOT TO INDICATE THE

{ INTENDED POSITION DURING AN SIS. THE OPERATOR CAN THEN HAKE A COMPARISON 1

BETHEEN THE DOT AND THE VALVE POSITION INDICATING LIGHT TO VERIFY CORRECT  ;

POSITIONING.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: 12-31-85 i

f 1

e I

i i

l I

} ~l

a PORTLAND GENERAL ELECTRIC '

j HUMAN ENGINEERING DISCREPANCY l HED RECORD SPECIFIED BY HED NBR  !

3 i

( RPT NO: D06320 HED NO: 0131 RPT DATE: 06-18-8G PLANT: TROJAN RPT TIME: 14:25:18 DATE: 02-09-82 TRACKING CIATUS: CORRECTION REVIEWER: PRELIMINARY STUDY - PG3 j ...............................................................................

i DATA SOURCE: CONTROL ROOH SURVEY - GP

]

DOCUMENT NO
1.3.1.47c 0700 GUIDELINE NO: G.3.3.4.C ,

j GUIDELINE AREA: GUIDELINE. SUBAREA:

ANNUNCIATOR WARNING SYSTEMS VISUAL TILE LEGENDS f PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

j N/A N/A RCP UPPER / LOWER OIL RES HI/ LOW

! N/A N/A RCP SEAL WATER STANDPIPE HI/ LOW 1 ............................................................................... ,

l DESCRIPTION OF DISCREPANCY j ON ANNUNCIATOR BOX K10, THE RCP UPPER / LOWER OIL RESERVOIR HI/ LOW LEVEL DOES NOT TELL MUCH. TOO MANY POSSIBLE PROBLENS ARE INDICATED HERE.

j OPERATORS MUST SEND SOMEONE INTO CONTAINMENT TO FIND OUT THIS LEVEL OR j INFER IT FROM THE TEMPERATURE OF BEARINGS. " TROUBLE" ANNUNCIATOR TILES j ARE ALSO USED, REQUIRING DIAGNOSTIC STEPS.

J ,

,- PLANT OPERATIONS SUBSEQUENT TO THE DCRDR INDICATED THAT THE DUAL HI/ LOW LEVEL ANNUNCIATOR ON RCP STANDPIPE IS INADEQUATE, ESPECIALLY WITH THE RCP SEAL PROBLEMS EXPERIENCED DURING CYCLE 7.

RECOMMENDATION:

CHANGE j INFORMATION ON ANNUNCIATOR WINDOWS SHOULD NOT REQUIRE COMPLEX OR LENGTHY DIAGNOSTIC STEPS. ADDITIONAL WINDOWS SHOULD BE USED OR INFORMATION

]

SHOULD BE READILY CBTAINABLE FRCH OTHER SOURCES (OTHER THAN THE i COMPUTER).

1 ACTION:

i RDC N0: 84-138 j COMPLETE. RDC 84-138 IMPROVED INFORMATION AVAILABLE TO THE CCNTROL R00H  ;

j CPERATOR WITH RESPECT TO THE RCP OIL RESERVGIRS AND SEAL STANDPIPES. (S)  !

," THE DESIGN PROVIDED MULTIPLEXING 0F THE 16 INPUTS FROH THE RCP OIL RESERVOIRS AND EIGHT INPUTS FROM THE RCP SEAL STANDPIPES. THESE SIGNALS

! ARE TRANSHITTED TO THE COMPUTER ROCH, DEMULTIPLEXED AND INPUTTED TO TWO ANNUNCIATOR TILES, "RCP OIL RESRVR LEVEL TROUBLE" AND "RCP STANDPIPE LEVEL l

TROUBLE", AND THE PLANT COMPUTER. THE COMPUTER WILL IDENTIFY THE SPECIFIC

[y; ALARM REQUIRING CORRECTIVE ACTION.

j PROBLEM CATEGORY: 1 IMPLEMENTATION SCHEDULE: 09-30-88 i

3 4

i

. - - , . - - , - - ------,.,_,--.,...,-_,-...-r-- -

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR i

l f RPT NO: 006320 HED NO: 0136 RPT DATE: 06-18-86 PLANT: TROJAN

! RPT TIHE: 14:2S:02 DATE: 02-08-82 l

J TRACKING STATUS: CORRECTION i

REVIEWER: PRELIMINARY STUDY - PG4 l ...............................................................................

DATA SOURCE: CONTROL ROOH SURVEY - GP

)

j DOCUMENT NO: 1.3.1.12 0700 GUIDELINE NO: S.3.1.2.A i

GUIDELINE AREA: GUIDELINE. SUBAREA:

ANNUNCIATOR WARNING SYSTEMS ALARM PARAHETER SELECTION PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTICN:

GENERIC N/A FW HEATER ANNUNCIATOR DESCRIPTION OF DISCREPANCY SEVERAL PARAMETERS HOVER RIGHT AT THE ALARH SETPOINT (e.g. FW HEATER i ALARMS) AND TRIP ALARMS OFTEN. OPERATORS REMOVE THE CARDS IN THESE i

ALARMS TO STOP THE AUDIBLES AND REDUCE THE NUMBER OF NUISANCE ALARHS.

RECOMMENDATION:

INVESTIGATE FURTHER 4

INVESTIGATE HETHODS OF PREVENTING THESE NUISANCE ALARMS.

1 f. ...............................................................................

! ACTION:

i RDC NO:

PARTIAL CCHPLETION. PLANT STAFF SIGNIFICANTLY REDUCED THE NUMBER OF ALARMS THAT ARE EITHER IN FOR LONG PERIODS OF TIME OR CYCLE AROUND THE SETPOINT.

COINCIDENT WITri THE FEEDWATER HEATER REPLACEMENT, REVIEW AND REVISION OF FW HTR LEVEL ALARH SETPOINTS OCCURRED. VERY FEW ALARHS OCCUR NOW AND WHEN

THEY 00, IT INDICATES AN ACTUAL PROBLEH, NOT A NUISANCE. {g)

THE ANNUNCIATOR SYSTEM REPLACEMENT OR MODIFICATION SHCULD ALLOW ONE TO SELECTIVELY SUPPRESS NUISANCE ALARHS. OF COURSE ADMINISTRATIVE CONTROLS WILL BE ESTABLISHED TO ASSURE APPROPRIATE USE OF THE SU*PRESSION CAPABILITY.

! PROBLEM CATEGORY: 2 IMPLEMENTATION SCHEDULE: 09-30 88 f

i 1

I l l

1 i

, CT i

l 1

PORTLAND GENERAL ELECTRIC HUHAN ENGINEERING DISCREPANCY i

HED RECORD SPECIFIED BY HED NBR l ( RPT NO: 006320 HED NO: 0138 1

RPT DATE: 06-18-86 PLANT: TROJAN RPT TIME: 14:24:43 DATE: 02-08-82 TRACKING STATUS: CORRECTION REVIEWER: PRELIMINARY STUDY - PG5

DATA SOURCE
CONTROL ROOH SURVEY - GP DOCUMENT NO: 1.3.1.6 0700 GUIDELINE NO: S.3.3.3.0 i GUIDELINE AREA: GUIDELINE. SUBAREA:

j ANNUNCIATOR WARNING SYSTEMS ARRANGEMENT OF VISUAL ALARM TILES PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

! N/A N/A ANNUNCIATOR TILE CONTENT i ...............................................................................

DESCRIPTION OF DISCREPANCY

ALARM HINDOWS 00 NOT ALHAYS AVOID DUPLICATION OF TERMINOLOGY FOR

} SIMILAR INPUTS, e.g. "4160 BUS Al FAULT" IS ONE WINDON AND THERE ARE d

THREE OTHER HINDOWS FOR A2, A5 & AG.

I RECOHHENDATION:

CHANGE g IN SELECTED CASES LIKE THIS THESE HINDOWS CAN BE GROUPED AND THE 1

OPERATOR CAN DIAGNOSE WHICH CHANNEL FAULTED. HORE SPACE CAN BE GENERATED FOR BETTER ALARN PLACEMENT IN THIS MANNER.

ACTION:

RDC NO:

NO CHANGE. WHILE THE INTENT OF THIS GUIDELINE IS UNDERSTOOD, THAT IS, REDUCE THE QUANTITY OF ANNUNCIATORS BY GROUPING SIMILAR ALARMS INTO ONE TILE, THE IMPACT ON THE OPERATORS OF SUCH A DESIGN HUST BE CONSIDERED.

IN THIS CASE, IT IS CONSIDERED CRUCIAL FOR THE OPERATOR TO KNOH HHICH 4160 VOLT BUS IS FAULTED IMMEDIATELY. THE EXTENT OF HIS ACTIONS ARE HIGHLY DEPENDENT UPON WHETHER IT IS AN ESF OR NON-ESF BUS, A OR B TRAIN.

SUCH UNAMBIGUCUS CODING IS NOT POSSIBLE IF ALL FOUR BUS FAULTS ARE LUMPED INTO ONE TILE. ALL FOUR ANNUNCIATOR TILES FOR A1, A2, AS, AND AG FAULTS ARE LOCATED IN CLOSE PROXIHITY ABOVE C-11(ELECTRICAL DISTRIBUTION PANEL). (3)

THEREFORE, EXACT ANNUNCIATION IN THIS INSTANCE IS DESIREABLE AS IT IS.

PRCBLEN CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A l

. ,n

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR l RPT NO: 00G32D HED NO: 015G RPT DATE: 06-18-86 PLANT: TROJAN RAT TINE: 14:24:26 DATE: 02-03-82 TRACMING STATUS: CORRECTION REVIEWER: PRELIMINARY STUDY - P72 DATA SOURCE: CONTROL ROOH SURVEY - GP DOCUMENT NO: 1.2.1.14d 0700 GUIDELINE NO: G.G.G.4.B GUIDELINE AREAt GUIDELINE. SUBAREA:

VISUAL DISPLAYS USE OF HIMICS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-13 GENERIC FLOW PATHS ON RHR HIMIC DESCRIPTION OF DISCREPAttY FLOW PATHS ARE AMBIGUQUS IN THE RHR SECTION OF HIMIC.

RECOMMENDATION:

INVESTIGATE FURTHER AN INVESTIGATION OF THIS PROBLEH SHOULD BE CONDUCTED WITH THE AIM OF CLARIF ING THE HIHIC WITH RESPECT TO PRIHARY AND SECONDARY FLOW PATHS.

ACTION:

RDC NO: 84-125 CCMPLETE. INVESTIGATION REVEALED THAT CHANGE TO THE HIMIC LAYOUT WAS NOT ACCEPTABLE DUE TO SPACE CONSTRAINTS. COLOR PADDING CLARIFIED THE FLOWPATHS By CORRELATING C-13 AND C-19 CONTROLS FOR LOW HEAD SAFETY INJECTION (RHR).

THE NEW LABELS HORE CLEARLY IDENTIFIED THE FUNCTION OF EACH CONTROL SWITCH. (3)

SINCE THE HAJCRITY OF EACH RHR TRAIN'S FLOWPATH HOVES FROM LEFT TO RIGHT, IN PARALLEL, ADDITIONAL CLARIFICATION IS NOT REQUIRED. SEE EXAMPLE LABELS BELOW.

PROBLEM CATEGORY: 2 IMPLEMENTATION SCHEDULE: 12-31-85 MO- 8 700 8 FRM RCS OR R W ST st2 s2. mrs.w (3) l M o - 8 703 TO B8D HOT LEGS sas4o l i l l

1

l PORTLAND GENERAL ELECTRIC HUHAN ENGINEERING DISCREPANCY

, HED RECORD SPECIFIED BY HED NBR

( RPT NO: DOG 320 HED NO: 0172 RPT DATE: 06-23-8G PLANT: TROJAN l RPT TIHE: 11:28:24 DATE: 02-08-82 I TRACKING STATUS: CORRECTION ,

l REVIEWER: PRELIMINARY STUDY - P73 l l

DATA SOURCE: CONTROL R00H SURVEY - GP l DOCUMENT NO: 1.2.4.2 0700 GUIDELINE NO: G.G.1.2.A 4 ...............................................................................

GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS HIERARCHICAL SCHEME PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-02 GENERIC MAIN STEAM ISOLATION VALVE LABELS DESCRIPTION OF DISCREPANCY THE MAIN STEAM ISOLATION VALVES ARE NOT WELL LABELED AS A GROUP.

RECOMMENDATION:

CHANGE PROVIDE UMBRELLA LABELING FOR THESE SWITCHES.

ACTION:

I RDC NO: 84-125 COMPLETE. RDC 84-125 COLOR PADDED THESE CONTROLS AND INDICATING LIGHTS ON C-D2 WHITE ALONG WITH THE HAIN STEAM ISOLATION VALVE BYPASS AND STEAH GENERATOR PORV CONTROLS ON C-14. THIS CORRELATES THE TWO GROUPINGS BETWEEN PANELS WHILE SIHULTANEOUSLY HAKING THE CONTROLS ON C-02 STAND OFF FROM SURROUNDING CONTROLS.

RDC 84-125 ALSO IMPLEMENTED A HIERARCHICAL LABELING SCHEME THAT PROVIDES GROUP LABELS TO COLOR PADDED AND DEMARCATED COMPONENTS. EXAMPLES OF HAJOR SYSTEM LABELS ARE: REACTOR COOLANT SYSTEH, CHEMICAL AND VOLUME CONTROL SYSTEH, RESIDUAL HEAT REMOVAL SYSTEH, PRESSURIZER SYSTEH, CONDENSATE AND g)

FEEDWATER SYSTEH, STEAM GENERATOR FEED SYSTEH, TURBINE GENERATOR SYSTEH, CIRCULATING WATER SYSTEH, RADWASTE SYSTEMS, FIRE PROTECTION SYSTEH, ECCS &

VENTILATION SYSTEH. HANY OF THESE GROUPS HAVE LOWER HIERARCHY LABELS ON SUBSYSTEMS SUCH AS: CONTAINNENT AIR COOLER FANS, CONTAINHENT PURGE FANS, SI ACCUMULATORS, CONTAINHENT SPRAY - A, SAFETY INJECTION - B, ETC.

PROBLEM CATEGDRY: 3 IMPLEMENTATION SCHEDULE: 12-31-85 i *

^ %O

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: 006320 HED NO: 0226 RPT DATE: 06-18-86 PLANT: TROJAN RPT TIME: 14:23:50 DATE! 02-09-82 TRACKING STATUS: CORRECTION REVIEHER: PRELIMINARY STUDY - P101 DATA SOURCE: CONTROL ROOH SURVEY - GP DOCUMENT NO: 1.6.1.4 0700 GUIDELINE NO: G.2.1.2.B GUIDELINE AREA: GUIDELINE. SUBAREA:

COMMUNICATIONS CONVENTIONAL-POWERED TELEPHONE SYSTEMS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A N/A N/A DESCRIPTION OF DISCREPANCY THE PHONE EXTENSION CORD FROM THE AO'S DESK TANGLES IN THE ROD H"7?nN CONTROLS.

RECCMMENDATION:

INVESTIGATE FURTHER DETERMINE WHETHER THIS HILL BE ELIMINATED BY MOVEMENT OF THE A0 DESK HHEN THE SPDS SYSTEM IS INSTALLED. IF NOT, TAKE HEASURES TO AVOID THIS.

ACTION:

RDC NO:

COMPLETE. THE PHONE CORD HAS BEEN SHORTENED SUCH THAT IT CAN NOT REACH THE RCD HOTION CONTROLS YET IS STILL A SUITABLE LENGTH FOR COMMUNICATION (3)

BY THE AUXILIARY CONTROL OPERATOR HHILE MONITORING THE RCD MOTION CONTROL STATION.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A I

- no

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY

HED RECORD SPECIFIED BY HED NBR l ( RPT NO
D06320 HED NO: 0228 i RPT DATE: 06-18-86 PLANT: TROJAN
RPT TIME
14:24:07 DATE: 02-09-82 4

TRACKING STATUS: CORRECTION REVIEWER: PRELIMINARY STUDY - P101 1

DATA SOURCE: CONTROL R00H SURVEY - GP 4 ...............................................................................

j DOCUMENT NO: 1.6.4.3 0700 GUIDELINE N0: 6.1.5.2.B j

GUIDELINE AREA: GUIDELINE. SUBAREA:

j CONTROLS VENTILATION PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

l N/A N/A N/A j DESCRIPTION OF DISCREPANCY j AIR CONDITIONINC IS NOT DIFFUSE AND DISCHARGES AIR DIRECTLY ON

OPERATORS.

j ...............................................................................

I RECOMMENDATION:

I i INVESTIGATE FURTHER I INVESTIGATE THE POSSIBILITY OF INSTALLING A DIFFUSE VENTILATION SYSTEM l TO ELIMINATE THE FORCED AIR.

j ...............................................................................

! ACTION:

i RDC NO:

NO CHANGE. NOT CONSIDERED A SIGNIFICANT PROBLEH. THE AIR DISCHARGE POINTS OF CONCERN ARE NOT PLACES WHERE THE OPERATOR SPENDS LONG PERIODS OF TINE.

! SO ALTHOUGH THERE HAY BE SOME DISCOMFORT, HE IS NOT SUBJECT TO THAT CONDI- (3)

TION FOR ANY SIGNIFICANT PERICC.

{. PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A I

4 I

i i i

i J .

J 4

i j

1 i

}

, . I

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED HBR

( RPT NO: D06320 HED NO: 0230  :

RPT DATE: 06-23-86 PLANT: TROJAN RPT TIME: 11:23:37 DATE: 02-09-62 TRACKING STATUS: CORRECTION REVIEWER: PRELIMINARY STUDY - 102 DATA SOURCE: CONTROL R00H SURVEY - GP DOCUMENT NO: 0700 GUIDELINE NO: 6.2.1.1 GUIDELINE AREA: GUIDELINE. SUBAREA:

COHHUNICATIONS REQUIREMENTS FOR VOICE COHHUNICATION S PANEL / WORKSTATION ID: COMPONENT NO: CCHPONENT DESCRIPTION:

N/A N/A N/A DESCRIPTION OF DISCREPANCY THE FOLLOWING IMPROVEMENTS IN THE COHHUNICATION SYSTEM HAY BE CONSIDERED: 1) INSTALLATION OF SOUND-POWERED PHONES FOR COOLING TOWER (CT) BLOWDOWN AND CT LEVEL CONTROLS ON THE BACK PANELS. 2)

COHHUNICATION CAPADILITY IN THE AUX HECHANICAL FACADE AREA. 3) PAGE CAPABILITY IN THE BIT R00H. 4) PROVISION OF HEADSETS TO PERHIT HAND-FREE PHONE USE. 5) ESTABLISHMENT OF A PRIORITIZATION HETH00 FOR I .. . . .'. .. . . . . . . . . .'.....

RECCHMENDATION:

CHANGE INVESTIGATE THE APPROPRIATENESS OF IMPLEMENTING THE SUGGESTIONS ABOVE.

ACTION:

RDC NO: 80-081 COMPLETE. THE DISCREPANCIES LIS1ED ABOVE WERE EITHER RESOLVED BY RDC 80-081 OR DID NOT WARRANT RESOLUTION AS DESCRIBED BELOW:

1) NO CHANGE. THERE IS NO NEED FOR COORDINATED OPERATION OF BACK PANEL CTB AND CT LEVEL CONTROLS. THE BACK PANEL CONTROLS HAVE BEEN ABANDONED IN PLACE AND WILL BE REMOVED AT A LATER DATE.
2) RDC 80-081 STRENGTHENED AMPLIFICATION OF THE PAGING SYSTEM IN THIS AREA SO THAT IT IS EASILY HEARD ABOVE THE MACHINERY NOISE.
3) RDC 80-081 STRENGTHENED AMPLIFICATION OF THE PAGING SYSTEM IN THIS AREA (3)

SO THAT IT IS EASILY HEARD ABOVE THE MACHINERY NOISE.

4) HEADSETS ARE USED DURING REFUELING OPERATIONS AT THE CONTROL R00H REFUELING STATION, SPENT FUEL POOL AND REFUELING CAVITY. IN THE EVENT OF LOSS OF REGULAR CCHHUNICATIONS EQUIPHENT, SOUND POWERED PHONES WITH HEAD-SETS ARE AVAILABLE AT THE KEY WATCHSTATIONS THROUGHOUT THE PLANT.
5) RDC 80-081 PROVIDED THE CONTROL OPERATOR WITH A HICR0 PHONE THAT OVERRIDES ALL OTHER TRANSHISSIONS, TRANSHITS AT ABOVE NORMAL VOLUME, AND REACHES ALL TRANSHISSION ZONES.
6) RDC 80 081 GAVE I&C DEPT TECHNICIANS TWO VOLUME CONTROL SETTINGS. POST INSTALLATION TESTING ESTABLISHED THE SETTINGS SUCH THAT THE AMPLIFICATION IS HEARD ABOVE AMBIENT NOISE FOR NORMAL OPERATING AND COLD SHUTDOWN CONDITIONS. n 5' ...............................................................................

PROBLEH CATEGORY: 3 IMPLEMENTATION SCHEDULE: N/A v l

PORTLAND GENERAL ELECTRIC HUHAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: 006320 HED NO: 0238 RPT DATE: 06-23-86 PLANT: TROJAN RPT TIME: 12:01:41 DATE: 02-09-82 TRACKING STATUS: CORRECTION REVIEHER: PRELIMINARY STUDY - P106 DATA SOURCE: CONTROL ROOH SURVEY - GP DOCUMENT NO: 1.6.2.2 0700 GUIDELINE NO: G.1.5.3.A GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS ILLUMINATION PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A N/A N/A DESCRIPTION OF DISCREPANCY THE LIGHT LEVELS IN THE SHIFT SUPERVISOR'S OFFICE (SEE TABLE D.2) RANGE FROM 180-220 FOOT-CANDLES. THESE LEVELS ARE FATHER HIGH.

RECOMMENDATION:

CHANGE IT IS RECOMMENDED THAT LIGHT LEVELS IN THE SHIFT SUPERVISOR'S OFFICE BE REDUCED TO 60-F00T CANDLES, BUT NO LOWER THAN 50 FOOT-CANDLES.

ACTION:

RDC NO:

NO CHANGE. PERSONNEL THAT HORK IN THE SHIFT SUPERVISOR'S OFFICE ARE ACCUSTOMED TO THE LIGHTING AND 00 NOT FIND IT PARTICULARLY HARSH ON THEIR EYES. IN FACT THEIR DESIRE IS TO HAINTAIN THE LIGHTING AT ITS PRESENT LEVEL. FURTHER DISCUSSION WITH A HUHAN FACTORS SPECIALIST INDICATES THAT THE GUIDELINE HAY HAVE BEEN INAPPROPRIATELY APPLIED TO (3)

THE SHIFT SUPERVISOR *S OFFICE SINCE NO MONITORING OF INDICATORS OR CRTS TAKES PLACE IN THAT R00H. GLARE IS NOT A PROBLEH EITHER. INSTEAD, THE PERSONNEL HORKING IN THAT OFFICE ARE INVOLVED IN ADMINISTRATIVE ACTIVITIES, READING AND HRITING CORRESPONDENCE.

PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A i

l l

A .

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0260 RPT DATE: 06-18-86 PLANT: TROJAN RPT TIME: 14:23:18 DATE: 08-30-83 TRACKING STATUS: ASSESSMENT REVIEHER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6.1.1.3.F GUIDELINE AREA: GUIDELINE.SUB AREA:

CONTROLS FURNITURE AND EQUIPMENT LAYOUT PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-PRINTER CONSOLE N/A N/A DESCRIPTION OF DISCREPANCY THERE IS LESS THAN 50" BETHEEN THE BACK OF THE PRINTERS CONSOLE AND ADJACENT VERTICAL PANELS.

................................................................ 4.............

RECOMMENDATION:

NO CHANGE DEVIATION FROM THE GUIDELINE HAS BEEN JUSTIFIED IN THE SPDS WORKSPACE

, STUDY (GP-L-221227) . LINK ANALYSIS RESULTS HAVE SUGGESTED THAT THIS IS NOT A FREQUENTLY TRAVERSED AREA DURING EMERGENCIES.

ACTION:

ROC NO:

NO CHANGE. toEE RECOMMENDATION). THE DISTANCE BETHEEN PRINTER CONSOLES AND THE OPPOSITE PANELS VARIES FROM 40 TO 44". NO SAFETY-RELATED CONTROLS ARE LOCATED ON THOSE PANELS, ALTHOUGH NOTEHORTHY INDICATORS UTILIZED BY THE OPERATOR IN THE EMERGENCY OPERATING PROCEDURES ARE: MAIN STEAM LINE

{3)

RADIATION HONITORS, CONTAINMENT SUMP PROCESS RADIATION MONITOR, CORE SUB-COOLING MARGIN MONITOR, CONTAINMENT PRESSURE, HIGH RADIATION AND HATER LEVEL INDICATORS, AND REACTOR VESSEL LEVEL INDICATING SYSTEM.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A l

l I

PORTLAND GENERAL ELECTRIC HUHAN ENGINEERING DISCREPANCY ,

HED RECORD SPECIFIED BY HED NBR I

( RPT NO: D06320 HED NO: 0278 RPT DATE: 06-19-86 PLANT: TROJAN RPT TIME: 15:57:18 DATE: 09-26-83 TRACKING STATUS: CORRECTION

............................................................................... j REVIEWER: LIDDLE DATA SOURCE: CONTROL ROOH SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6.4.3.3.B (5)

GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS LEGEND PUSHBUTTONS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

GENERIC N/A N/A DESCRIPTION OF DISCREPANCY' SOME LEGEND HESSAGES CONTAIN HORE THAN THREE LINES OF LETTERING.

RECOMMENDATION:

NO CHANGE HESSAGES WITH TOUR LINES ARE EASILY READ AND UNDERSTOOD.

ACTION:

I RDC NO:

NO ACTION. (SEE RECOMMENDATION) . THE ONLY LEGEND PUSHBUTTONS, BESIDES THE HAGAN CONTROLLER UP AND DOWN ARROWS, IN THE CONTROL ROOH ARE LOCATED ON THE EHC PANEL AT C-05. THE PANEL HAS SUPPLIED AS AN INTEGRAL UNIT BY THE TURBINE (3)

VENCCR, GE. EACH LEGEND HESSAGE IS EASILY READ AND PGE A' (ICIPATES NO NEED TO CHANGE THEH. .HENCE, A LEGEND CONVENTION WAS NOT CONSIDERED.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A I \

m mm

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

{ RPT NO: 006320 HED N0: 0273 RPT DATE: 06-19 86 PLANT: TROJAN RPT TIME: 15:57:02 DATE: 09-26-83 TRACKING STATUS: CORRECTION REVIEHER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6. 4. 3.3. C (1)

GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS LEGEND PUSHBUTTONS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

GENERIC N/A N/A DESCRIPTION OF DISCREPANCY THERE IS NO LAMP TEST CAPABILITY OR DUAL BULBS FOR LEGEND BUTTONS.

RECOMMENDATION:

CHANGE IMPLEMENT LAMP TEST OR PROVIDE DUAL-FILAMENT BULBS FOR LEGEND PUSHSUTTONS.

ACTION:

RDC NO:

COMPLETE. ADMINISTRATIVE ORDER 3-2, SHIFT ROUTINES, REQUIRES WALKDOHN OFD THE CONTROL BOARDS SHIFTLY, NOTING PUMP AND VALVE S7ATUS. LACK OF ON OR OFF, OPEN OR SHUT, OR UNUSUAL COMBINATIONS OF, INDICATING LIGHTS ARE (g)

INVESTIGATED. ALTHOUGH THE PROCEDURE DOES NOT SPECIFICALLY IDENTIFY THE NEED TO DO THAT, TO BE ALERT FOR SUCH DEFICIENCIES IS TAUGHT THROUGH OH-THE-JOB TRAINING. PLANT STAFF EVALUATED THE USE OF DUAL FILAMENT BULBS AND CONCLUDED THAT THEY ARE NOT FEASIBLE. SEE HED 046 FOR DETAILS.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: 12-31-85 l

i

- =. - . . - .

PORTLAND GENERAL ELECTRIC o HUMAN ENGINEERING DISCREPANCY

, HED RECORD SFECIFIED BY HED NBR l' RPT NO: D06320 HED NO: 0280 RPT DATE: 06-19-86 PLANT: TROJAN RR1 TIME: 15:56:48 DATE: 09-26-83 TRACKING STATUS: CORRECTION REv7EHER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6. 4 .3 . 3.C (4)

GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS LEGEND PUSHBUTTONS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

GENERIC N/A N/A DESCRIPTION OF DISCREPANCY LEGEND COVERS ARE NOT KEYED TO PREVENT THE POSSIBILITY OF INTERCHANGING THE COVERS.

j RECOMMENDATION:

CHANGE IMPLEMENT A PROCEDURE THAT HOULD PRECLUDE INTERCHANGEABILITY: e.g.

l REMOVE ONE AND REPLACE ONE COVER AT A TIME.

ACTION:

RDC NO:

NO CHANGE. INSIGNIFICANT DISCREPANCY THAT HAS NOT PROVEN TO BE A PROBLEH IN THE PAST. IN THE EVENT LIGHT BULBS REQUIRE REPLACEMENT, ONLY ONE LEGEND IS REMOVED AT A TIME. HORE COMPLICATED EVOLUTIONS, IE. DESIGN CHANGE, ARE CONTROLLED BY DESIGN CHANGE PACKAGES. CONTROLLED DRAHINGS ARE AVAILABLE IN (3)

THE CONTROL ROOH THAT INDICATE THE PROPER POSITION OF ALL LEGENOS ON THE PANELS. THERE ARE SAFETY-RELATED LEGEND INDICATORS BUT NO SAFETY-RELATED LEGEND PUSHSUTTONS IN THE CONTROL ROON.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: N/A o

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR I RPT N0: 006320 HED NO: 0281 RPT DATE: 06-19-86 PLANT: TROJAN RPT TIME: 15:56:18 DATE: 09-26-83 TRACKING STATUS: CORRECTION REVIEWER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 j DOCUMENT NO: 0700 GUIDELINE NO: G .4.4.2. A (1)

I GUIDELINE AREA: GUIDELINE.SUB AREA:

d CONTROLS J-HANDLES 4

PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

GENERIC N/A N/A 4 DESCRIPTION OF DISCREPANCY l

J-HANDLE LENGTH IS LESS THAN 3.75 INCHES.

RECOMMENDATION:

NO CHANGE J-HANDLE IS EASY TO MAINPULATE WITH THE DIMENSION INDICATED ABOVE. NO PROBLEM NOTED IN INTERVIEWS.

ACTION:

RDC NO:

NO CHANGE. (SEE RECOMMENDATION). THE J-HANDLE LENGTH IS 2 INCHES. THE HANDLE LENGTH PROVIDES ADEQUATE TORQUE FOR SWITCH ACTUATION. h3)

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A 4

W n

e

- - ~, . . _ . _

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

! RPT NO: D06320 HED NO: 0282 )

RPT DATE: 06-19-86 PLANT: TROJAN '

RPT TIME: 15:56:32 DATE: 09-26-83 TRACKING STATUS: CORRECTION 1 REVIEWER: LIDDLE j DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: G.4.5.1.0 GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS THUMBWHEELS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

GENERIC N/A THUMBWHEELS DESCRIPTION OF DISCREPANCY '

TROUGH DISTANCE IS 1" WHICH EXCEEDS RECOMMENDED MAXIMUM OF .75".

RECOMMENDATION:

NO CHANGE DEVIATION FROM GUIDELINE IS CONSIDERED INSIGNIFICANT.

ACTION:

RDC NO:

NO CHANGE. (SEE RECOMMENDATION) . THERE ARE ONLY TWO THUMBWHEELS IN THE CONTROL ROOM. THEY ARE THE BORON FLOW AND TOTAL FLOW INTEGRATORS. OPERATING EXPERIENCE HAS SHOWN NO DIFFICULTY ONTHE PART OF THE OPERATORS IN USING (g)

THESE THUMBWHEELS. BATCH BORATION AND DILUTION EVENTS ARE RATHER CONTROLLED.

ROUTINE EVOLUTIONS. THE OPERATOR IS UNDER NO STRESS OR TIME CONSTRAINTS TO ESTABLISH THE PROPER VALUE BY USE OF THE THUMBWHEEL.

PR06LEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A 9

i e

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO
D08320 HED NO: 0284 )

RPT DATE: 06-19-86 PLANT: TROJAN

~

RPT TIME: 15:56:05 DATE: 08-26-83 TRACKING STATUS: CORRECTI0t1 REVIEHER: LIDDLE l

............................................................................... l DATA SOURCE: CONTROL ROOH SURVEY - 0700

............................................................................... l DOCUMENT NO: 0700 GUIDELINE NO: 6.5.1.4. A(1) & (2)

GUIDELINE AREA: GUIDELI!4E. SUBAREA:

VISUAL DISPLAYS PRINTING LN THE DISPLAY FACE PANEL /HORKSTATION ID: COMP 0t1ENT NO: COMPONENT DESCRIPTI0ti:

GENERIC N/A RECORDERS DESCRIPTION OF DISCREPAtlCY SOME RECORDERS LACK: 1. PARAMETER IDENTIFICATION AND/OR 2.

INDICATION OF UNITS SHOWN At10/OR 3. TRANSFORMATION INDICATION WHEN APPROPRIATE.

RECOMMENDATION:

CHANGE SURVEY EXISTING RECORDERS At4D ADD NECESSARY INFORMATI0ti TO ALL RECORDERS.

ACTION:

RDC NO:

COMPLETE. OPERATIO!1S DEPARTHENT PERFORMED A REVIEH OF ALL RECORDERS ON THE MAIN CONTROL PANELS FOR THIS It4 FORMATION. AS A RESULT, ALL RECORDERS HAVE BEEN RELABELED TO SHOW THE PARAMETER HONITORED. WHERE DEEMED

, APPROPRIATE THE Ut4ITS HAVE ALSO BEEN INCLUDED IN THE LABELS. THE CONDENSATE DEMINERALIZER FLOWHETERS HERE THE ONLY O!1ES REQUIRING TRAllSFORMATI0tt THAT fgg DID NOT HAVE IT INDICATED ON THE HETER. THE ACTION TO REFLECT A HULTIPLICA- \7 TI0tt Bf A FACTOR OF 10 IS INDICATED Ott HED 059.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: 12-31-85

. n

_ - ,n

PORTLAND GENERAL ELECTRIC i 1

HUMAN ENGINEERING DISCREPANCY l HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0288 -

RPT DATE: 06-20-86 -

PLANT: TROJAN RPT TIME: 07:29:25 .

. DATE: 09-26-83 TRACKING STATUS: CORRECTION REVIEHER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6.5.3.1. A (1)

GUIDELINE AREA: GUIDELINE.SUB ARE A:

VISUAL DISPLAYS CHARACTERISTICS AND PROBLEMS OF LIGHT PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

GENERIC N/A INDICATING LIGHTS DESCRIPTION OF DISCREPANCY DUAL BULB OR DUAL FILAMENT LIGHT ASSEMBLIES ARE NOT UTILIZED FOR INDICATING LIGHTS.

RECOMMENDATION:

CHANGE UTILIZE DUAL FILAMENT BULBS TO ASSURE AVAILABILITY.

t ACTION:

RDC NO:

COMPLETE. ADMINISTRATIVE ORDER 3-2, SHIFT ROUTINES, REQUIRES WALKDOWN OF THE CONTROL BOARDS SHIFTLY, NOTING PUMP AND VALVE STATUS. LACK OF ON OR OFF, OPEN OR SHUT, OR UNUSUAL COMBINATIONS OF, INDICATING LIGHTS ARE INVESTIGATED. ALTHOUGH THE PROCEDURE DOES NOT SPECIFICALLY IDENTIFY THE (3)

NEED TO TO THAT, TO BE ALERT FOR SUCH DEFICIENCIES IS TAUGHT THROUGH CH-THE-JOB TRAINING.

PLANT STAFF EVALUATED THE USE OF DUAL FILAMENT BULBS AND CONCLUDED THAT THEY ARE NOT FEASIBLE. SEE HED 046 FOR DETAILS.

NO FURTHER ACTION IS ANTICIPATED IN THE HEAR TERM.-

RELATED HEDS ARE 279 AND 380.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: 12-31-85 4

- Q, _ go.

PORTLAND GENERAL ELECTRIC I HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR RPT NO: D06320 HED NO: 0288 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 07:28:49 DATE: 09-26-83 TRACKING STATUS: CORRECTION REVIEWER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 3 ................................................................................

DOCUMENT NO: 0700 GUIDELINE NO: 6. 5.3.3.B (5)

GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS LEGEND LIGHT INDICATORS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-04 N/A BYPASS STATUS DISPLAY C-04 N/A PERMISSIVE STATUS DISPLAY DESCRIPTION OF DISCREPANCY LEGEND MESSAGES CONTAIN HORE THAN THREE LINES OF TEXT.

RECOMMENDATION:

) NO CHANGE MESSAGES WITH FOUR LINES ARE EASILY READ AND UNDERSTOOD.

ACTION:

RDC NO:

NO CHANGE. (SEE RECOMMENDATION) . THESE LEGENDS PROVIDE INDICATION ONLY, HENCE THEY ARE NOT PUSHBUTTONS. THE TROJAN CONVENTION ALLOWS UP TO FOUR LINES WITH A LETTER HEIGHT OF 1/8". THE WIDTH STROKE IS APPROXIMATELY bN)

.015". PGE AGREES WITH THE CONCLUSION OF OUR HUMAN FACTORS SPECIALIST THAT THE HESSAGES ARE EASILY READ AND UNDERSTOCD.

PRCBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A

' I

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0290 RPT DATE: 06-20-86 PLANT: TROJAN I RPT TIME: 07:28:06 DATE: 08-26-83 TRACKING STATUS: CORRECTION REVIEHER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6.5.5.1. A (3)

GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS DRUH-TYPE COUNTERS l ...............................................................................

PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-02 FY-110A BORON FLOW C-02 FY-111A TOTAL FLOW DESCRIPTION OF DISCREPANCY THERE ARE NO COMMAS SEPARATING GROUPS OF NUMERALS ON DRUM COUNTERS (NHERE THERE ARE MORE THAN FOUR DIGITS).

RECOMMENPATION:

NO CHANGE DEVIATION FROM THE GUIDELINES IS CONSIDERED INSIGNIFICANT.

ACTION:

RDC NO:

NO CHANGE. (SEE RECOMMENDATION) . OPERATING EXPERIENCE HAS SHOWN NO DIFFI-CULTY IN SETTING THE INTEGRATORS TO THE PROPER VALUES. BOTH BORATION AND DILUTION EVENTS ARE CONTROLLED, ROUTINE EVOLUTIONS. THE OPERATOR IS UNDER (3)

NO STRESS OR TIME CONSTRAINTS TO ESTABLISH THE PROPER VALUE. DURING EMERGENCY BC' RATION, WHEN A CUICK RESPONSE IS CRITICAL, THE INTEGRATORS ARE NOT USED TO METER THE ADDITION OF BORATED WATER.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A ,

i l

1 1

l l

I l

l

. i

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY

+ HED RECORD SPECIFIED BY HED NBR RPT NO: D06320 HED NO: 0286  ;

( PLANT: TROJAN RPT DATE: 06-20-86 RPT TIME: 07:28:31 DATE: 09-26-83 TRACKING STATUS: CORRECTION REVIEWER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: G.G.5.1.G GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS USE PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

GENERIC N/A N/A DESCRIPTION OF DISCREPANCY PAPER TAG OUTS SLIP OVER ESCUTCHEONS AND 00 NOT PHYSICALLY PREVENT ACTUATION OF A CONTROL.

RECOMMENDATION:

CHANGE IMPLEMENT COVERS THAT INCORPORATE TAGOUTS.

t ACTION:

RDC NO:

NO CHANGE. PERSONNEL ARE HELL AWARE THAT VIOLATING A TAGOUT HOULD RESULT IN SEVERE DISCIPLINARY ACTION. IT DOES NOT OCCUR, BECAUSE THE TAGS ARE VERY PLAIN TO SEE AND ALL PERSONNEL ARE AWARE OF THEIR MEANING. IN TEN YEARS OF ggy PLANT OPERATION, THERE IS NOT ONE CASE OF A PERSON INADVERTENTLY OPERATING A SWITCH OR PIECE OF EQUIPMENT THAT HAD A DANGER TAG PLACED ON IT. THEREFORE ,

PGE BELIEVES THE POTENTIAL FOR SUCH INADVERTENT ACTUATION DOES NOT HARRANT THE USE OF HARD, PL/STIC COVERS IN LIEU OF PAPER TAGS.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A i I

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0288 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 07:28:07 DATE: 03-26-83 TRACKING STATUS: CORRECTION REVIEWER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6 .7.2.1.C (4)

GUIDELINE AREA: GUIDELINE.SUB AREA:

PROCESS COMPUTERS CRT DISPLAY CHARACTERISTICS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A P-250 COMPUTER CRT DESCRIPTION OF DISCREPANCY CHARACTER LUMINANCE WAS MEASURED AS 5.2 FT-L, LESS THAN THE RECOMMENDED MINIMUM OF 23 FT-L.

RECOMMENDATION:

CHANGE INCREASE CHARACTER LUMINANCE TO AT LEAST 23 FT-L MINIMUM, BUT NO GREATER THAN 46 FT-L.

ACTION:

RDC NO:

NO CHANGE. THE CHANGE IS NOT HITHIN THE CURRENT CAPABILITIES AND THE COST HOULD NOT BE JUSTIFIED BY THE MAGNITUDE OF THE PROBLEM.

THE P-250 IS A THIRD GENERATION COMPUTER THAT WORKS IN REAL TIME AND FROVIDES DISPLAY, ALARMING, DATA LOGGING AND SOME ENGINEERING CALCULATIONS.

THERE ARE NO PROCESS CONTROL FUNCTIONS ASSOCIATED WITH THE COMPUTER AND IT ,

IS NOT REQUIRED FOR PLANT OPERATION. bb) l THE CRT DISPLAYS CAN PROVIDE PRE-SELECTED BLOCKS OF DATA POINTS AND THE MOST l RECENTLY ALARMING CONDITIONS. MONITORING OF THE CRT IS GENERALLY NOT CON-TINUCUS. THE OPERATOR USUALLY GLANCES AT THE SCREEN FOLLOWING A COMPUTER ALARM TO DETERMINE THE ALARMING PARAMETER AND ITS VALUE. ALTHOUGH LUMINANCE  !

LEVELS ARE LESS THAN THE LIMIT, OPERATORS HAVE NO DIFFICULTY READING THE i DISPLAYS NOW.  ;

.........__.................................................................... j PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A i 1

1 1

k l

i n no j

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

(. RPT NO: D06320 HED NO: 0293 RPT DATE: 06-24-86 PLANT: TROJAN RPT TIME: 13:45:55 ,

DATE: 03-26-83 TRACKING STATUS: CORRECTION REVIEWER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: G .7.2.1.D (1)

GUIDELINE AREA: GUIDELINE. SUBAREA:

PROCESS COMPUTERS CRT DISPLAY CHARACTERISTICS PANEL /HORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A P-250 COMPUTER CRT O

DESCRIPTION OF DISCREPANCY i CONTRAST BETHEEN LIGHT CHARACTERS AND A DARK SCREEN BACKGROUND IS LESS l THAN THE MINIMUM RECOMMENDED 15:1 (MEASURED AT APPROXIMATELY 5:1) .

............................__.___............................................. I RECOMMENDATION:

CHANGE INCREASE CHARACTER BRIGHTNESS TO ACHIEVE THE MINIMUM RECOMMENDED RATIO OF 15:1.

ACTION:

RDC NO:

NO CHANGE. THE CHANGE IS NOT WITHIN THE CURRENT CAPABILITIES AND THE COST HOULD NOT BE JUSTIFIED BY THE MAGNITUDE OF THE PROBLEM. SEE HED 288. (

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A 4

t I n no

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0301 RPT DATE: 06-24-86 PLANT: TROJAN RPT TIME: 13:45:58 '* DATE: 09-26-83 I

TRACKING STATUS: CORRECTION REVIEHER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6.7.2.5.H GUIDELINE AREA: GUIDELINE. SUBAREA:

PROCESS COMPUTERS SCREEN LAYOUT AND STRUCTURING PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION: l l

N/A P-250 PROGRAM CONTROLLED ANNUNC. 1 DESCRIPTION OF DISCREPANCY THERE IS NO INDICATION OF PAGE NUMBER AND TOTAL NUMBER OF PAGES DISPLAYED HHEN DATA ARE CONTAINED ON MULTIPLE PAGES.

RECOMMENDATION:

CHANGE HHERE MULTIPLE PAGES EXIST, EACH PAGE OF DATA SHOULD DISPLAY BOTH PAGE NUMBER AND TOTAL NUMBER OF PAGES.

L .......................................__...................................... 1 ACTION:

RDC NO:

NO CHANGE. THE BUFFER MAY CONTAIN PREVIOUSLY ALARMED CONDITIONS THAT STILL EXCEED THEIR SETPOINT BUT HERE CHRONOLOGICALLY MOVED OFF THE CRT DISPLAY. SHOULD SPACE BECOME AVAILABLE ON THE SCREEN, THESE ALARMS (3)

HOULD REAPPEAR. HOWEVER, THEY ARE NOT AVAILABLE AS ADDITIONAL PAGES OF DATA. ONLY ONE PACE OF DATA IS AVAILABLE TO BE PLACED ON THE CRT. THE ORIGINAL REVIEHER WAS INCORRECT IN IMPLYING THAT MULTIPLE PAGES EXIST.

PROBLEM CATEGORY: 4 IMPLEHENTATION SCHEDULE: N/A

( I

)

i i

n no

i PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: 006320 HED NO: 0302 x RPT DATE: 06-24-86 PLANT: TROJAN RPT TIME: 13:46:16 DATE: 03-26-83 TRACKING STATUS: CORRECTION REVIEHER: LIDDLE -

DATA SOURCE: CONTROL ROOM SURVEY - 0700 1

DOCUMENT NO: 0700 GUIDELINE NO: 6.7.2.5.k (1)

GUIDELINE AREA: GUIDELINE. SUBAREA:

PROCESS COMPUTERS SCREEN LAYOUT AND STRUCTURING PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A P-250 PROGRAM CONTROLLED ANNUNC.

DESCRIPTION OF DISCREPANCY URGENT MESSAGES REQUIRING IMMEDIATE OPERATOR RESPONSE ARE NOT HIGHLIGHTED TO ATTRACT THE OPERATORS 9 ATTENTION. IMPORTANT DATA ITEMS SHOULD ALSO BE HIGHLIGHTED TO FACILITATE DECISION-MAKING.

RECOMMENDATION:

CHANGE y ,

URGENT MESSAGES REQUIRING IMMEDIATE OPERATOR RESPONSE SHOULD BE HIGHLIGHTED TO ATTRACT THE OPERATOR'S ATTENTION.

ACTION:

RDC NO:

NO CHANGE. THE P-250 PROVIDES DISPLAY, ALARMING, DATA LOGGING, AND SOME ENGINEERING CALCULATIONS. THERE ARE NO PROCESS CONTROL FUNCTIONS ASSOCIATED WITH THE COMPUTER AND IT IS NOT REQUIRED FOR PLANT OPERATION.

PRIORITIZING ALARMS BY URGENCY IS NOT HITHIN THE CAPABILITIES OF THE P-250. (3)

OTHER CONTROL ROOM SYSTEMS (IE. SPDS AND FLANNED ANNUNCIATOR SYSTEM REPLACE-hENT) ARE BETTER SUITED FOR THIS ROLE. THE HEED FOR SUCH AN UPGRADE ON THE P-250 IS NOT APPARENT WHILE THE CCST HOULD BE VERY HIGH.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: N/A i

i i

PORTLAND GENERAL ELECTRIC  !

i

  • 1 hUHAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0303 l RPT DATE: 06-24-86 PLANT: TROJAN l RPT TIME: 13:46:29 DATE: 09-26-83  ;

l TRACKING STATUS: CORRECTION l

, REVIEWER: LIDDLE l i

DATA SOURCE: CONTROL ROOM SURVEY - 0700 l

............................................................................... 1 DOCUMENT NO: 0700 GUIDELINE NO: 6.7.2.5.m j GUIDELINE AREA: GUIDELINE. SUBAREA: l PROCESS COMPUTERS SCREEN LAYOUT AND STRUCTURING  ;

............................................................................... l PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A P-250 PROGRAM CONTROLLED ANNUNC. l DESCRIPTION OF DISCREPANCY THE AMOUNT OF INFORMATION-BEARING ACTIVATED SCREEN AREA EXCEEDS 25X OF ,

THE TOTAL SCREEN AREA. i RECOMMENDATION:

CHANGE l UTILIZE SPACING B:THEEN LINES OF INFORMATION TO HINIMIZE SCREEN DENSITY.

ACTION:

RDC NO:

NO CHANGE. THE P-250 IS BEING INAPPROPRIATELY JUDGED AGAINST SCREEN LAYOUT CRITERIA THAT WAS INTENDED FOR SPDS TYPE COMPUTER SYSTEMS.

THE P-250 CRTS' DISPLAY A LIST OF ALARMING POINTS (THE ID NUMBER, (3)

DESCRIPTION AND VALUE). A HIGH DENSITY OF TEXT IS NOT DIFFICULT TO INTERPRET AS COMPARED TO HIGH DENSITY FIGURES OR PROCESS AND INSTRUMENTATION DIAGPAMS THAT MAY APPEAR CN PROCESS COMPUTERS.  ;

............................................................................... 1 PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A i

4 g s

e l

l l

+

\ l

(

l l

l n- rw i

PORTLAND GENERAL ELECTRIC i l

HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR  !

l

( RPT NO: D06320 HED NO: 0304 l RPT DATE: 06-24-86 PLANT: TROJAN l RPT TIHE: 13:46:46 DATE: 09-26-83 i

~

I TRACKING STATUS: CORRECTION

............................................................................... 1 REVIEHER: LIDDLE l

...............___ ............................................................ 1 DATA SOURCE: CONTROL ROOM SURVEY - 0700 l DOCUMENT NO: 0700 GUIDELINE NO: G.7.2.6.C ,

GUIDELINE AREA: GUIDELINE. SUBAREA:

PROCESS COMPUTERS HESSAGES PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A P-250 PROGRAH CONTROLLED ANNUNC.

DESCRIPTION OF DISCREPANCY PROMPTS ARE NOT DISPLAYED WHENEVER THE OPERATOR HAY NEED DIRECTIONS OR GUIDANCE TO INITIATE OR COMPLETE AN ACTION OR SEQUENCE OF ACTIONS.

RECOMMENDATION:

CHANGE 4

PROVIDE PROMPTS WHENEVER THE OPERATOR HAY NEED DIRECTIONS OR GUIDANCE TO INITIATE OR COMPLETE AN ACTION OR SEQUENCE OF ACTIONS.

ACTION:

RDC NO:

NO CHANGE. AN ALARH OCCURS WHENEVER AN OPERATOR PROVIDES AN INCORRECT ENTRY INTO THE P-250 CONTROL CONSOLE. THE HARNING PRINTS OUT ON THE ALARH TYPEHRITER AS HELL AS PROVIDING A VISUAL / AUDIO ALARM AT THE CONSOLE.

THE QUICK FEEDBACK ALLOWS HIH TO DETERMINE HIS ERROR AND PERFORM THE SEQUENCE DIFFERENTLY. THE ERROR ALARM DOES NOT DISRUPT ANY OTHER OPERATIONS bI)

BEING PERFORMED BY THE P-250. SHOULD THE OPERATOR REQUIRE DIRECTION IN PERFORMING A SPECIFIC TASK, AN OPERATOR'S MANUAL PROVIDED BY THE VENDOR IS AVAILABLE AT THE CCHTROL OFERATOR'S DESK. THE HANUAL IS INDEXED HELL AND PROVIDES STEP BY STEP PRCCEDURES FOR USING ALL OF THE P-250'S CAPABILITIES.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A I

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0305 RPT DATE: 06-24-8B PLANT: TROJAN RPT TIME: 13:46:57 DATE: 09-26-83 TRACKING STATUS: CORRECTION REVIEWER: LIDDLE DATA SOURCE: CONTROL ROOH SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6.7.2.6.G GUIDELINE AREA: GUIDELINE. SUBAREA:

PROCESS COMPUTERS HESSAGES PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A P-250 PROGRAM CONTROLLED ANNUNC.

DESCRIPTION OF DISCREPANCY ERROR HESSAGES DO NOT CONTAIN INSTRUCTIONS TO THE OPERATOR REGARDING

, REQUIRED CORRECTIVE ACTION.

RECOMMENDATION:

CHANGE ERROR HESSAGES SHOULD CONTAIN INSTRUCTIONS REGARDING REQUIRED CORRECTIVE ACTION.

ACTION:

RDC NO:

NO CHANGE. THE P-250 PROVIDES DISPLAY, ALARMING, DATA LOGGING, AND SOME ENGIMEERING CALCULATIONS. THERE ARE NO PROCESS CONTROL FUNCTIONS ASSOCIATED WITH THE COMPUTER AND IT IS NOT REQUIRED FOR PLANT OPERATION.

l AS NOTED IN HED 304, THE CONTROL OPERATOR'S DESK CCNTAINS A DETAILED e

OPERATING MANUAL PROVIDED BY THE VENDOR. IT CONTAINS STEP BY STEP DIRECT- (3)

IONS FOR PERFORMING ALL FUNCTIONS POSSIBLE WITH THE P-250. THUS, IF AN ERROR OCCURS, THE OPERATOR CAN REFER TO OTHER PERSONNEL OR THE MANUAL.

PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A 5

a

+

,- .- - - - - - . - - - _ _ e ,-.

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR RPT NO: D06320 HED NO: 0307

{

RPT DATE: 06-24-86 PLANT: TROJAN RPT TIME: 13:47:21 DATE: 09-26-83 TRACKING STATUS: CORRECTION REVIEWER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6.7.2.8.C GUIDELINE AREA: GUIDELINE. SUBAREA:

PROCESS COMPUTERS MULTIPLE-PAGE CONSIDERATIONS

  • PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A P-250 PROGRAM CONTROLLED ANNUNC.

DESCRIPTION OF DISCREPANCY HHEN SCROLLING A LIST, ONLY PART OF HHICH IS VISIBLE AT ANY ONE TIME, THE PRESENT AND MAXIMUM LOCATION IS NOT SHOWN.

RECOMMENDATION:

CHANGE ,

SHOW PRESENT AND MAXIMUM LOCATION OF SCROLLING LIST.

! ACTION:

RDC NO:

NO CHANGE. THIS DISCREPANCY IS REALLY NOT APPLICABLE TO THE P-250 SINCE MULTIPLE PAGES OF DATA DO NOT EXIST, AS DISCUSSED IN HED 301. ALL ALARMS GENERATED BY THE P-250, ARE PRINTED OUT ON THE ALARM TYPEHRITER, IT IS ONE OF FOUR TYPEWRITERS THAT ARE DEDICATED FOR P-250 OUTPUT. THE BANK OF TYPE-HRITEPS ARE PLACED IN A COLUhN DIRECTLY BEHIND THE ASSISTANT CONTROL OPER- (3)

ATCR,S DESK, FACING TOWARD THE RAISED FLATFORM OPERATING AREA. IN THE EVENT AN ALARMING CONDITION IS CHRONOLOGICALLY HOVED OFF THE P-250 CRT, IT IS STILL AVAILABLE ON THE ALARM TYPEWRITER PRINTOUT. OPERATORS MUST COMPLETE A QUALIFICATION CARD ON THE P-250 PRIOR TO ATTENDING LICENSE TRAINING.

DURING LICENSE TRAINING THEY RECEIVE IN DEPTH LECTURES ON ITS OPERATION AND DESIGN. AS THE NEED ARISES IT MAY BE ADDRESSED IN PERIODIC RETRAINING CLASSES.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A

I '

l n pn

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0308 RPT DATE: 06-24-86 PLANT: TROJAN RPT TIME: 13:47:30 DATE: 03-26-83 TRACKING STATUS: CORRECTION ,

REVIEHER: LIDDLE DATA SOURCE: CONTROL R00H SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: G .7. 3.1. e (2) g ..........__...................................................................

GUIDELINE AREA: GUIDELINE. SUBAREA:

PROCESS CCHPUTERS PRINTER CHARACTERISTICS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A P-250 PRINTER DESCRIPTION OF DISCREPANCY THERE IS NOT A POSITIVE INDICATION OF THE REMAINING SUPPLY OF RECORDING HATERIAL.

RECOMMENDATION: '

CHANGE CONSIDER PROVIDING A POSITIVE INDICATION OF THE REMAINING SUPPLY OF RECORDING MATERIALS.

ACTION:

RDC NO:

NO CHANGE. THE P-250 HAS FOUR DEDICATED TYPEHRITERS: ALARM, TREND, UTILITY AND LOG. EACH HAS THEIR OWN RECORDING FUNCTIONS. EXCEPT FOR THE LOG TYPEWRITER (HHICH HAS SPECIALLY FORMATTED PAPER INSTALLED).

EACH TYPEWRITER HAS ANOTHER AS A DEDICATED BACKUP. FOR EXAMPLE, THE ALARM TYPEWRITER ALTERNATE IS THE TREND TYPEHRITER, THE TREND ALTERNATE IS THE g) ,

ALARM TYPEWRITER, AND THE UTILITY ALTERNATE IS THE TREND TYPEkRITER.

THE P-250 GENERATES A "T/W FAILURE" ALARH IF ThE PRIMARY TYPEWRITER RUNS ,

OUT OF PAPER OR FAILS AND SINULTANEOUSLY SHIFTS TO THE ALTERNATE.

THE LOG TYPEWRITER RECEIVES OUTPUT HOURLY FROM A VARIETY OF DATA POINTS ON SPECIAL LOG SHEETS. TWO SHEETS ARE ADEQUATE FOR ONE DAY WORTH OF DATA.

THERE IS ADEQUATE TIME AVAILABLE FOR THE OPERATOR TO REPLENISH THIS PAPER SUPPLY. ,

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A f I n an

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

{ RPT NO: D06320 HED NO: 0303 ,

~

RPT DATE: 06-24-86 PLANT: TROJAN RPT TIME: 13:47:41

  • DATE: 03-26-83 TRACKING STATUS: CORRECTION REVIEHER: LIDDLE DATA SOURCE: CONTROL R00H SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6.7.3.2.a (2)

GUIDELINE AREA: GUIDELINE.SUB AREA:

PROCESS COMPUTERS ALARM HESSAGES PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A P-250 PRINTER DESCRIPTION OF DISCREPANCY ALL ANNUNCIATOR ALARMS ARE NOT RECORDED.

RECOMMENDATION:

CHANGE PROVIDE.A.HEANS OF RECORDING ALL ANNUNCIATCR ALARMS.

  • ACTION:

RDC NO:

NO CHANGE. IN GENERAL, HOST SIGNIFICANT PLANT PARAMETERS AND EQUIPMENT STATUS ARE HONITORED BY THE ANNUNCIATOR SYSTEM AS HELL AS THE P-2E0 COMPUTER. THE P-250 ALARH TYPEWRITER RECORDS ALL ALARHING CONDITIONS IT RECEIVES. HOWEVER, SINCE THE ANNUNCIATOR TILES DO NOT DUPLICATE ALL THE INPUTS HONITCRED BY THE P-250, THERE WILL BE ANNUNCIATORS THAT ACTUATE THAT HIL L NOT BE RECORDED. THERE IS NO PEQUIREMENT FOR THE (3)

  • ANNUNCIATOR SYS1 ?1 TO HAVE SUCH A CAPABILITY. TO ASSIET IN TRCUBLE-  :

SHOOTING OF PLANT TRANSIENTS AND ACCIDENTS, THE SEQUENCE OF EVENT AND POST TRIP REVIEW PROGRAMS PROVIDE HARD COPY DATA 07 KEY +

PARAMETERS AND THEIR CHANGE CVER THE TIME' PERIODS OF INTEREST.

PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A I

h i

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D08320 HED NO: 0310 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 13:34:30 DATE: 09-26-83 TRACKING STATUS: CORRECTION REVIEWER: LIDDLE DATA SOURCE: CONTROL ROOH SURVEY - D700 DOCUMENT NO: 0700 GUIDELINE NO: 6.7.3.2.c

, GUIDELINE AREA: GUIDELINE. SUBAREA:

PROCESS COMPUTERS ALARM HESSAGES PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A P-2SO PRINTER

< DESCR.IPTION OF DISCREPANCY THERE ARE NO PROVISIONS TO PROVIDE, UPON OPERATOR REQUEST, PRINTOUTS BY .

ALARM GROUP (E.G., SYSTEH, SUBSYSTEH, COMPONENT).

RECOMMENDATION:

CHANGE PROVIDE A MEANS TO OBTAIN PRINTOUTS BY ALARM GROUP AS DESCRIBED ABOVE.

- ACTION:

RDC NO:

NO CHANGE. IT IS NOT WITHIN THE CURRENT CAPABILITY OF THE CURRENT SYSTEH.

SPDS WILL IMPROVE THIS SY ALLCWING ANY SPDS DISPLAY TO BE PRINTED OUT EITHER IN THE CONTROL ROOM CR TECHNICAL SUPPORT CENTER. DISPLAYS INCLUDE DVERALL PLANT (!OP LEVEL ICONOGRAPHIC), INDIVIDUAL SYSTEM OR SUBSYSTEM

[3)

^

DATA. THOSE PARAMETERS IN AN ALARM CONDITION HAVE A RED BACKGROUND HIGHLIGHTIN3 THEM. ALTHOUGH THE PRINTOUT IS IN BLACK AND WHITE, THE RED BACKGROUND RESULTS IN A SHADED PRINTOUT SO THAT IT STANDS OUT.

PROBLEM CATEGOR(: 4 IMPLEMENIATION SCHEDULE: N/A i

t l

l

)

i i

l i

a I i

J

_I*

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR RPT NO: D06320 HED NO: 0311

(

RPT DATE: 06-24-86 PLANT: TROJAN RPT TIME: 13:48:03 DATE: 09-26-83 TRACKING STATUS: CORRECTION REVIEWER: LIDDLE DATA SOURCE: CONTROL ROOM SURVEY - 0700 D000HENT NO: 0700 GUIDELINE NO: 6.7.3. 3.D (2)

GUIDELINE AREA: GUIDELINE. SUBAREA:

PROCESS COMPUTERS GRAPH AND TABLE REQUIREHENTS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION N/A P-250 PRINTER DESCRIPTION OF DISCREPANCY TABLE COLUMNS ARE NOT SEPARATED INTO GROUPS BY PROVIDING A SPACE

, EETWEEN GRCUPS OF FIVE WHEN COLUMNS ARE LONG.

RECOMMENDATION:

CHANGE PROVIDE SPACING ON PRINTOUTS.

ACTICH:

RDC NO:

NO CHANGE. THE CHANGE IS NOT WITHIN THE CAPABILITY CF THE CURRENT SYSTEM AND THE COST WOULO NOT SE JUSTIFIED BY THE HAGNITUDE OF THE PROBLEH. FOR ALARdING CCNDITIONS THAT ARE RCCEIVED OVER A PERIOD OF TIME, NOT HAVING SEPARATED TABLES IS NOT SIGNIFICANT SINCE THE OPERATOR IS CNLY LOOKING AT THE l

LAST ONE OR THO ALARMS RECEIVED. IF A PLANT TRANSIENT INITIATES THE PRINTOUT h8) 0F HANY ALARMS, FOR EXAMPLE, THE SEQUENCE OF EVENT OR POST TRIP REVIEW PROGRAMS, THE OPERATOR IS GOING TO BE RESPONDING INITIALLY TO THE ANNUNCIATOR SYSTEM ALARMS AND CCNTRCL BOARD INDICATIONS. THE TYPEWRITER PRINTOUTS ARE HORE OF AN AID IN RECONSTRUCTION OF THE EVENT THAN IT AS A DECISION AID TO - -

THE OPERATOR.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A 1

l g J

l 4

9 I W

4 e

e Se

PORTLAND GENERAL ELECTRIC

.s HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR RPT NO: D06320 HED N0: 0317 j

( PLANT: TROJAN RPT DATE: 06-20-86 RPT TIME: 13:34:0S DATE: 08-31-83 TRACKING STATUS: CORRECTION REVIEWER: SCHROEDER DATA SOURCE: HISTORICAL DOCUMENT REVIEW DOCUMENT NO: 78-22 0700 GUIDELINE NO:

GUIDELINE AREA: GUIDELINE. SUBAREA:

PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-16 LI-3480 COOLING TOWER LEVEL IND.

C-16 LI-3488 COOLING TOWER LEVEL IND.

DESCRIPTICN OF DISCREPANCY DURING A HANUAL BLOWDOWN OF THE COOLING TOWER BASIN, THE LEVEL IN THE COOLING TOWER BASIN WAS ALLCWED TO DECREASE BELOW THE HINI:tuH TECHNICAL SPECIFICATION LIMIT. SEE LER/ PRO

SUMMARY

IN APPENDIX A 0F VOLUME 1 0F i THE

SUMMARY

REPORT FOR DETAILS.

RECOH!!ENDATION:

5. CHANGE REFERENCE LER

SUMMARY

REPORT.

l ACTION:

RDC NO:

COMPLETE. THE CCOLING TOWER LEVEL PROBLEN HAS NOT REPEATEC ITSELF.

ADDITIONAL ENDHASIS HAS BEEN PLACED ON PROPER WATCH TURHOVER OF CRITICAL ITEMS. THIS EVENT OCCURRED ALHOST EIGHT YEARS AGO, PPIOR TO THE THI-2 ,

ACCIDENT. SINCE THEN, THE CONDUCT OF OPERATIONS HAS UNDERGONE MANY AUDITS AND CHANGES. WATCH TURNOVER OF KEY ITEMS WAS IMPROVED BY PROVIDING A COLUMN CHECKLIST CN THE CQ'S LOG SHEET THAT SERVES AS A TICKLER TO THE OFF GOING OPERATOR TO NOTE ALL EVCLUTIONS IN PROGRESS AND ABNORMAL CONDI- (

TIONS. OTHER CORRECTIVE ACTIDH TAKEN WAS BANDING THE LEVEL HETER AND RAISING THE BASIN LOW LEVEL ALARM TO A VALUE ABOVE THE TECH SPEC HINIMUM.

PREVIOUSLV IF THE ALARM CCCURRED, THE LEVEL WOULD ALREADY BE LOW ENOUGH TO BE A TECH SPEC VIOLATION, PROBLEM CATEGORY: 1 IMPLEMENTATION SCHEDULE: N/A 1

4 l

)

PORTLAND GENERAL ELECTRIC 1 HUMAN ENGINEERING DISCREPANCY ,

HED RECORD SPECIFIED BY HED NBR  !

( RPT NO: D06320 HED NO: 0319 RPT DATE: 06-20-88 PLANT: TROJAN RPT TIME: 13:33:52 DATE: 08-31-83 4 TRACKING STATUS: CORRECTION REVIEHER: SCHROEDER DATA SOURCE: HISTORICAL DOCUMENT REVIEW DOCUMENT NO: 81-12 0700 GUIDELINE NO:

GUIDELINE AREA: GUIDELINE. SUBAREA:

PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-13 N/A RHR SYST. PUMPS & VALVES DESCRIPTION OF DISCREPANCY NO PERMANENT, RELIABLE RCS LEVEL INDICATION IS AVAILABLE IN THE CONTROL RCOM. (DURING A DRAINING OF THE RCS, THE PRESSURIZER VENT VALVE WAS LEFT OPEN. THIS CAUSED THE RCS STANDPIPE LEVEL TO STABILIZE WHILE REACTOR LEVEL DROPPED BELOW RHR SUCTION. THE HEST RHR PUMP CAVITATED AND HAS STOPPED. LOSS OF HEAT REMOVAL RESULTED FOR ONE HOUR AND 15 MINUTES WHICH EXCEEDS TECH SPECS.) SEE LER/ PRO

SUMMARY

IN APPENDIX A 0F VOLUME 1 0F THE

SUMMARY

REPORT. .

RECOMMENDATION:

NO CHANGE NO FURTHER ACTIONS RECOMMENDED.

ACTION:

RDC NO: 84-123 COMPLET

E. PROCEDURE

OI-3-2, " DRAINING THE REACTOR COOLANT SYSTEM" WAS REVISED TO IhCLUDE A PRECAUTION FCR VERIFYING THAT THE VENT VALVE IS OPEN.

A SECOND RCS LEVEL INDICATING COLUMN HAS BEEN ADDED INSIDE CONTAINMENT AND AN EXTENSIVE PROCEDURE REVISION HAS BEEN COMPLETED.

DURING THE 1936 REFUELING OUTAGE A NEW, REMOVAL LEVEL INDICATOR CABINET (C-02A) HAS INSTALLED TO PROVIDE A CAMERA PICTURE OF THE STANDPIPES ALONG HITH AN ELECTRONIC LEVEL INDICATOR ON TOP OF PANEL C-02 DURING (3) ,

RCS DRAIN DOWN CONDITIONS. THUS THE OPERATOR MAY MONITOR LEVEL HHILE NEAR THE MAKEUP, RHR AND RCS CONTROLS ON C-02 AND C-12.

PROBLEM CATEGORY: 1 IMPLEMENTATION SCHEDULE: N/A i

J

- w i

-. ~ - . - . . - . -

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0321 .

PLANT:

' - RPT DATE: 06-20-86 TROJAN

, RPT TIME: 13:33:22 DATE: 08-31-83 TRACKING STATUSi CORRECTION 2 REVIEWER: SCHROEDER DATA SOURCE: HISTORICAL DOCUMENT REVIEW DOCUMENT NO: 82-10 0700 GUIDELINE NO:

GUIDELINE AREA: GUIDELINE. SUBAREA:

PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A N/A SPENT FUEL POOL ALARM DESCRIPTION OF DISCREPANCY SFP LOW LEVEL ANNUNCIATOR IS NOT RELIABLE AND SFP LEVEL INDICATION IS NOT PROVIDED IN THE CONTROL ROOM. (THE DOOR BETWEEN THE SFP AND THE FUEL TRANSFER CANAL WAS CLOSED CAUSING THE SFP LEVEL TO BE PUMPED DOWN -

TO 21 FEET AND S INCHES ABOVE THE SEATED FUEL ASSEMBLIES. THE LOW LEVEL ALARM ALSO MALFUNCTIONED. SEE LER/ PRO

SUMMARY

REPORT FOR DETAILS AND ,

CORRECTIVE ACTION TAKEN TO DATE).

! RECOMMENDATION:

CHANGE SEE LER/ PRO

SUMMARY

REPORT.

i ACTION:

RDC NO:

i COMPLET

E. PROCEDURE

S OI-4-1, " RESIDUAL HEAT REMOVAL", AND CI-4-4, " SPENT FUEL POOL (SFP) COOLING AND DEMINERALIZER OPERATION", HERE REVISED TO TIE ONE PROCEDURE IN WITH THE OTHER. A NEW SFP LEVEL INDICATING SWITCH WAS INSTALLED UNDER RDC-81-003. IT REPLACED THE ONE THAT WAS SUBJECT TO STICKING DUE TO FORMATION OF BORIC ACID CRYSTALS. SINCE ITS INSTALLATION THERE HAVE

(.

BEEN NO REPEATS OF THIS. EVENT. THE NEW SWITCH PROVIDES HIGH AND LOW LEVEL ANNUNCIATION. ADDITION OF LEVEL INDICATORS IN THE CONTROL ROOM WAS CONSIDER-

] ED UNNECESSAP,Ys -

l

..................t............................................................

I PROBLEM CATEGORY: 1 IMPLEMENTATION SCHEDULE: N/A i

I I

I I

l 6

j i

i . ..

I PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0332 -

RPT DATE: 06-20-86 PLANT: TROJAN 1 RPT TIME: 13:33:09 DATE: 09-26-83 l TRACKING STATUS: CORRECTION REVIEWER: SCHROEDER l DATA SOURCE: CONTROL ROOH SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: G.1.5.3.F GUIDELINE AREA: GUIDELINE. SUBAREA: '

! CONTROLS ILLUMINATION

] PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-06 RI-2239 H.S. LINE RAD. HONITOR C-06 RI-2240 H.S. LINE RAD. HONITOR C-06 RI-2241 H.S. LINE RAD. HONITOR C-06 RI-2242 H.S. LINE RAD. HONITOR DESCRIPTION CF DISCREPANCY ALTHOUGH GLARE OFF HETER SURFACES HAS BEEN IDENTIFIED AS A GENERIC PROBLEM, THIS PARTICULAR INDICATOR IS ESPECIALLY AFFECTED. (SEE HED 0042)

I RECOMMENDATICH:

CHANGE CONSIDER IMPLEMENTING DESIGN CHANGES TO REDUCE GLARE OFF OF THESE HETER SURFACES. FOR EXAMPLE, USE OF LOW GLARE GLASS OR A SHIELD / HOOD OVER TOP 0F HETER.

E ACTION:

! RDC NO:

NO CHANGE. PLANT STAFF EVALUATED THE USE OF HOODS OVER THE TOP OF METERS AND NON-REFLECTIVE COATINGS ON HETER COVERS AND CONCLUDED NEITHER WOULD (3)

BE FEASIBLE. SEE HED 0042 FOR DETAILS.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: 12-31-85 4

i +

)

-__ _ x _

PORTLAND GENERAL ELECTRIC

. HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR 4 RPT NO: D06320 HED NO: 0346 RPT DATE: 08-20-86 PLANT: TROJAN RPT TIME: 13:32:49 DATE: 09-30-83 TRACKING STATUS: CORRECTION REVIEWER: SCHROEDER DATA SOURCE: CONTROL ROOH SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO:

GUIDEL'INE AREA: GUIDELINE. SUBAREA:

PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-06 TR-3498 GEN TEMP HONIT. DATA LOGGER DESCRIPTION OF DISCREPANCY THE CHANNEL NUMBER IS DIFFERENT FROH THE TEMPERATURE DETECTOR NUMBER (RTD) AND THE THERMAL COUPLE NUMBER (TC) . OPERATORS INDICATE THAT ERRORS ARE NOW HADE IN CALLING OUT A PARTICULAR CHANNEL.

RECOMMENDATION:

CHANGE CHANNEL NUMBER AND TEMPERATURE DETECTOR HUMBER SHOULD BE THE SAME.

ACTION:

RDC NO:

NO CHANGE. A CROSS REFERENCE INDEX CHART IS SUPPLIED BY THE DATA LOGGER.

THE INFORMATION OBTAINED FROM THE LOGGER IS NOT THE TYPE THAT WOULD BE NEEDED IMMEDIATELY BY THE OPERATOR TO DETERMINE HIS ACTIONS TO A FLANT TRANSIENT. THEREFORE, REQUIRING A CONVERSION FRCH ONE INDICE TO ANOTHER IS NOT SIGNIFICANT.

NOTE THAT THE COMMENT CONCERNING ERRORS WAS MADE SHORTLY AFTER INSTALLATION OF THE DATA LOGGER. THE DATA LOGGER IS INCLUDED IN OPERATOR TRAINING. (g)

THAT PLUS THE EXPERIENCED GAINED IN OPERATING THE EQUIPMENT HAS NOT INDICATED A NEED TO REVISE THE DETECTOR NUMBERING SYSTEM.

PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A n

. nn

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR RPT NO: D06320 HED NO: 0353

( PLANT: TROJAN RPT DATE: 06-20-86 RPT TIME: 13:31:52 DATE: 09-30-83 TRACKING STATUS: CORRECTION REVIEHER: SCHROEDER DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6.5.1.3 GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS READABILITY ,

PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-03 N/A RX VESSEL LEVEL IND. SYS C-06 ACCOUSTIC LEAK MONITOR ,

DESCRIPTION OF DISCREPANCY FOR EASE OF READABILITY DISPLAYS SHOULD PROVIDE GOOD CONTRAST. THE ,

CONTRAST OF RED LEDs ON THE BLACK BACKGROUND IS LOH FOR BOTH INSTRUMENTS.

RECOMMENDATION:

CHANGE CONSIDER PROVIDING AN ALTERNATE LED DISPLAY PROVIDING BETTER CONTRAST.

ACTION:

RDC NO:

NO CHANGE. ADEQUATE CONTRAST EXISTS. THE OPERATOR OR STA READING THE DISPLAY WOULD MOST LIKELY BE NO MORE THAN 2 TO G FEET FROM IT. THE DISPLAY IS CLEARLY LEGIBLE FROM THOSE DISTANCES, HITH THE CHARACTER HEIGHT OF APPROX 3/8". WHEN DISCUSSING THIS HED, THE CRDR HAS SITUATED IN THE VIEHER'S GALLERY ABOVE THE CONTROL ROOM. FROM THAT LOCATION, LOCKING THROUGH GLASS AT A HARSH ANGLE TO THE LEFT, OVER TEN FEET AWAY, (3)

THE TEAM AGREED THEY COULD EASILY READ THE RVLIS DISPLAYS. DURING FURTHER DISCUSSIONS HITH HUMAN FACTORS SPECIALISTS THEY AGREED THE CONTRAST ISSUE HAS NOT SIGNIFICANT. DUE TO LIMITED PRODUCTION OF RVLIS BY THE VENDOR, ALTERING LED DISPLAYS HOULD BE EXPENSIVE, YET NOT HARRANTED.

THE ACOUSTIC LEAK MONITOR ON C-06 IS ABANDONED IN PLACE AND HILL BE REMOVED FROM THE CONTROL PANELS.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR .

( RPT NO: D08320 HED NO: 0357 r RPT DATE: 06-20-8B PLANT: TROJAN RPT TIME: 13:32:36 DATE: 09-28-83 TRACKING STATUS: CORRECTION REVIEWER: SCHROEDER DATA SOURCE: CONTROL R00H SURVEY - 0700

..~............................................................. __.............

DCCUMENT NO: 0700 GUIDELINE NO: 6.3.3.5. A (2)

GUIDELINE AREA: GUIDELINE. SUBAREA:

ANNUNCIATOR WARNING SYSTEMS VISUAL TILE READABILITY PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A N/A OIL HASTE SEP. HI ALARH DESCRIPTION OF DISCREPANCY THE ANNUNCIATOR WINDOW ENGRAVING IS 1/2 THE SIZE OF THE OTHER WINDOWS ON K07. BECAUSE OF ITS VISUAL ANGLE THIS ANNUNCIATOR IS DIFFICULT TO SEE FROM THE ACKNOWLEDGE CONTROL AT C-11.

RECOMMENDATION:

CHANGE CONSIDER INCREASING THE SIZE OF THE LETTERING ON THIS TILE TO CONFORM i HITH OTHER TILES AND/OR HOVING IT TO AN AREA CLOSER TO THE ACKNOWLEDGE CONTROL.

ACTION:

RDC NO:

IT IS AGREED THAT THE LETTER HEIGHT SHOULD BE INCREASED. HOWEVER, OTHER LOCATIONS WERE CONSIDERED PREVIOUSLY WITHOUT SUCCESS. INTEGRATION OF THIS TILE WITH OTHERS WILL BE CONSIDERED AS PART OF THE ANNUNCIATCR SYSTEM (3)

REPLACEMENT.

PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: 09-30-89

^ P

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0368 RPT DATE: 06-30-86 PLANT: TROJAN RPT TIME: 03:00:59 DATE: 12-15-83 TRACKING STATUS: CORRECTION REVIEHER: SCHROEDER DATA SOURCE: CONTROL ROOH SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: G.1.5.4 GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS EMERGENCY LIGHTING PANEL /HORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

GENERIC N/A N/A DESCRIPTION OF DISCREPANCY A SURVEY OF THE CONTROL R00H EMERGENCY LIGHTING LEVELS INDICATED THAT '

ILLUMINATION LEVELS RANGED FROH .90 FT C'ANDLES TO 3.20 FT CANDLES AT PANELS AND HORKSTATIONS IN THE CONTROL R00H. THE EMERGENCY ILLUMINATION SYSTEM SHOULD BE DESIGNED TO PROVIDE A HINIMUH ILLUMINATION LEVEL OF 10 l FT CANDLES AT ALL HORKSTATIONS IN THE PRIHARY OPERATING AREA.

RECOMMENDATION:

I CHANGE PROVIDE ADDITIONAL EMERGENCY LIGHTING OR IMPROVE EXISTING SYSTEH TO HEET ILLUHINATION LEVELS SPECIFIED IN GUIDELINES. ENSURE THAT LIGHTING IS UNIFORM AND DOES NOT RESULTS IN CLARE ON PANEL SURFACES.

ACTION:

RDC NO: 84-035 PARTIAL COMPLETION. RDC 84-035 INSTALLED 2 8-HR BATTERY PACKS WITH SIX LAN-TERNS AS PART OF APP R UPGRADES. THE RESULTANT LEVELS HERE CALCULATED BY HAND AND ARE NOT EXPECTED TO HEET THE 10 FOOT CANDLE RECOMMENDED. A PLANT {33/

ENGINEERING TEST IS PLANNED TO TAKE NEH, ACTUAL LIGHTING HEASUREMENTS AS HELL AS VERIFY / CORRECT THE AINING OF THE LIGHTS IN JULY / AUGUST 1986 TO ENSURE UNIFORHITY AND AVOID GLARE. WHETHERE ADDITIONAL PACKS HILL BE INSTALLED IS DEPENDENT UPON THE RESULTS OF THE TEST.

PROBLEH CATEGORY: 3 IMPLEHENTATION SCHEDULE: 02-28-86 4

(

=.

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY

, HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0369 J RPT DATE: 06-20-8B PLANT: TROJAN RPT TIME: 13:31:20 DATE: 10-01-82 TRACKING STATUS: CORRECTION REVIEHER: SCHROEDER DATA SOURCE: CONTROL ROOM SURVEY - 0700 l DOCUMENT NO: 0700 GUIDELINE NO: 6.8.2.3.B 1 GUIDELINE AREA: GUIDELINE. SUBAREA:

PANEL LAYOUT LAYOUT CONSISTENCY PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-13 N/A " CHRISTMAS TREE" IND. LIGHTS DESCRIPTION OF DISCREPANCY SOME ROWS OF INDICATOR LIGHTS ARE MIRROR IMAGED (E.G. ROW 3, CONT SPRAY AND ROW 6, SWS) HHILE SOME ROWS ARE NOT (EG. ROW 8, CONT AIR COOLERS).

ALTHOUGH HIRROR-IMAGING IS NOT ENCOURAGED IN PANEL LAYOUTS, IT IS EQUALLY IMPORTANT TO HAVE A CONSISTENT LAYOUT PHILOSOPHY WITHIN A PANEL GROUPING.

RECOMMENDATION:

CHANGE RECONSIDER REDESIGNING DISPLAY SO THAT THE ORDERING OF INDICATOR LIGHTS FOR THE SYSTEMS REPRESENTED CONFORMS TO POPULATION STEREOTYPES (SEE ALSO HED 0023) .

ACTION:

RDC NO:

NO CHANGE. DURING A SAFETY INJECTION IT IS NOT LIKELY NOR NECESSARY THAT THE OPERATOR OBSERVE THE INDICATING LIGHTS AS THE DBA LOADS SEQUENCE ON. THE OPERATOR CARES WHAT LOADS STARTED, NOT HHAT ORDER. HE WILL LOOK FOR AT LEAST THREE CONTAINMENT AIR COOLER LIGHTS PER TRAIN, BUT NOT TO SEE (N)

HHICH THREE OF THE FOUR ACTUALLY STARTED. OTHER INDICATIONS ON C-13 AND C-19 ARE AVAILABLE TO VERIFY THE LOADS HAVE STARTED. (THE CHRISTMAS TREE IS HOSTLY USED DURING SURVEILLANCE TESTING TO ASSURE PROPER LOAD START TIMING.)

SEE ALSO HED 023.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: N/A

1

'l PORTLAND GENERAL ELECTRIC j l

HUMAN ENGINEERING DISCREPANCY .

HED RECORD SPECIFIED BY HED NBR  !

( RPT NO: D06320 HED NO: 0386 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:38:41 DATE: 09-26-83 TRACKING STATUS: CORRECTION REVIEWER: LIDDLE DATA SOURCE: CONTROL ROOH SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6.1.2.5. A (1)

GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS VERTICAL PANELS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-42 N/A ANNUNCIATOR CONTROLS i DESCRIPTION OF DISCREPANCY THESE CONTROLS ARE LOCATED AT 29 1/2 INCHES ABOVE THE FLOOR. THIS IS BELOW THE RECOMMENDED HINIMUM OF 34 INCHES FOR CONTROL HEIGHT.

I RECOMMENDATION:

NO CHANGE THE LOCATION OF THESE CONTROLS WAS NOT DEEMED TO BE A PROBLEH IN THE WALKTHROUGHS. NO REFERENCE TO ACTIVATION OF THESE CONTROLS WAS HADE IN THE EMERGENCY EVENTS STUDIED.

ACTION:

RDC NO:

NO CHANGE PER RECOMMENDATION. SIGNIFICANT ANNUNCIATOR TILES LOCATED ON C-42 ARE: CONT PERSONNEL HATCH 85 FT - OPEN CONT PERSONNEL HATCH 45 FT - OPEN STATOR HI TEMP ALARM AFW CH A HNL VALVES NOT OPEN AFW CH B HNL VALVES NOT OPEN FW PUMPS TRIPPED AFWP P-102A AUTO-START BLOCKED FW PUMPS TRIPPED AFWP P-102B AUTO-START BLCCKED (

AFW PP WEST LOW CST LEVEL TRIP BLOCKED AFW PP EAST LOW CST LEVEL TRIP BLOCKED UPON COMPLETION OF THE ANNUNCIATOR SYSTEM REPLACEMENT, ALL OF THESE ANNUNCIA-TORS SHOULD BE RELOCATED SO AS TO BE IN NEAR PROXIHITY TO RELATED CONTROLS.

THE AFW SYSTEM ANNUNCIATORS IN PARTICULAR WILL BE GROUPED WITH OTHER AFW ANNUNCIATORS ABOVE C-17. UTILIZATION OF THE ANNUNCIATOR PUSHBUTTONS IS NOT A PROBLEM SINCE THEY ARE NOT USED EXTENSIVELY.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A k

PORTLAND GENERAL ELECTRIC I HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D08320 HED NO: 0387 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:39:01 DATE: 09-26-83 -

TRACKING STATUS: CORRECTION REVIEWER: LIDDLE DATA SOURCE: CONTROL ROOH SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: G .1.2.5. B (1) i GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS VERTICAL PANELS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

l C-OS N/A VESSEL LEVEL HONITORS A&B 76" C-06 RIS4184 CONTAINHENT SUHP (SEE HED 398)

C-06 FR5600 CONTAINHENT PURGE VENT FLOW 78" C-06 N/A FEEDWATER N0ZZLES(NOT APPLIC)

C-11 N/A CIRCULAR HETERS 72-85" i

DESCRIPTION OF OISCREPANCY THESE DISPLAYS ARE LOCATED OVER 70 INCHES ABOVE THE FLOOR. GUIDELINES SUGGEST THAT DISPLAYS SHOULD BE PLACED IN AN AREA BETWEEN 41 AND 70 INCHES ABOVE THE FLOOR LEVEL.

i. ....................................__...............__........................

RECOMMENDATION:

NO CHANGE NOT DEEMED TO BE A PROBLEH IN THE WALK-THROUGHS.

ACTION:

RDC NO:

NO CHANGE PER RECOMMENDATION. THE HETERS DISCUSSED GENERALLY HAVE LARGE ENOUGH SCALES AND LABELS THAT THEIR USE PRESENTS NO DIFFICULTY TO THE OPERATOR. THE FEEDWATER N0ZZLES COMPONENT ON C-06~IS ABANDONED IN PLACE, AS INDICATED IN THE COMPONENT DESCRIPTION SECTION, THEY ARE LOCATED UD 72-85" ABOVE THE FLOOR. OPERATORS OFTEN STAND IN THE CENTRAL OPERATING AREA ON A FLOOR THAT IS RAISED 4.5" RELATIVE TO THE FLOOR THE INSTRUMENT-ATION CABINETS STAND ON.

PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A n

_. _ ., g. _

9

  • PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NPR i RPT NO: D08320 HED NO: 0398 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:39:12 DATE: 03-28-83 TRACKING STATUS: CORRECTION REVIEWER: SCHROEDER

.................................................v.............................

DATA SOURCE: CONTROL R00H SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: 6.1.2.5.B GUIDELINE AREA: GUIDELINE .SUB AREA:

CONTROLS VERTICAL PANELS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-06 PRM-14 PROC. RAD HONITOR-CONT. SUMP C-06 RI-2239 TO 42 H.S. RAD. INDIC.

DESCRIPTION OF DISCREPANCY THE PRM-14 DISPLAY AT HID-SCALE IS LOCATED 81 INCHES ABOVE THE FLOOR.

THE H.S. RAD. INDICATORS ARE 83 INCHES ABOVE THE FLOOR. GUIDELINES RECOMMEND A MAXIMUM HEIGHT OF 70 INCHES OFF THE FLOOR.

RECOMMENDATION:

, NO CHANGE NO CHANGE RECOHdENDED BY GPC. THIS WAS NOT DEEMED TO BE A PROBLEH IN THE WALKTHROUGHS.

ACTION:

RDC NO:

NO CHANGE. SEE RECOMMENDATION. PRM-14 HETER DISPLAY IS ORIENTED HORIZONT-ALLY, WITH VALUES INCREASING FROM L'dFT TO RIGHT. THE MAIN STEAM LINE RADIATION HONITORS ARE ORIENTED VERTICALLY WITH VALUES INCREASING FROM BOTTON TO TOP. EACH INDICATOR HAS A LOG SCALE. THE OPERATOR IS NOT INTERESTED IN EXACT VALUES, BUT RATHER THE LEVEL OF HAGNITUDE. OFTEN THE b3)

OPERATOR IS STANDING ON THE RAISED FLOOR IN THE CENTRAL OPERATING AREA WHEN HE LOCKS AT THESE INDICATORS. THAT FLOOR IS 4.5" HIGHER THAN THE ONE THE CABINET HEIGHT IS HEASURED FROM. HENCE, THE DISPLAYS ARE SUFFICIENTLY 4 VISIBLE FROM THEIR PRESENT LOCATION.

PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A 4

4

PORTLAND GENERAL ELECTRIC 2

HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0400 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:38:29 DATE: 08-30-83 TRACKING STATUS: CORRECTION REVIEWER: SCHROEDER i

DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: G .7.2.2.B (1)

GUIDELINE AREA: GUIDELINE. SUBAREA:

PROCESS COMPUTERS SYMBOLS AND CHARACTERS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DE3CRIPTION:

C-06 TR-3498 GEN TEMP- HON'.ti. DATA LOGGER DESCRIPTION OF DISCREPANCY THE HEIGHT OF ALPHA-NUMERIC CHARACTEPS ON THE CRT SCRECN OF THE GEN TEMP HONITOR DATA LOGGER IS 5/32 INCH. THIS IS AN ACCESTABLE SIZE ONLY FOR VIEWING DISTANCES LESS THAN 3.72 FT.

RECOMMENDATION:

NO CHANGE NO CHANGE RECOMMENDED SINCE ITS USE DOES NOT APPEAR TO LE CRITICAL 5 DURING EMERGENCY OPERATIONS.

ACTION:

RDC NO:

NO CHANGE. SEE RECOMMENDATION.THE DATA LOGGER IS HOUNTED ON A FULLY -

VERTICAL PANEL. THUS THE OPERATOR STANDS DIRECTLY IN FRONT OF THE INSTRUMENT WHILE OPERATING IT. THE ACTUAL VIEWING DISTANCE HAY BE ANY- (3)

WHERE FROM 18 TO 3G INCHES. THUS THE LETTER HEIGHT IS ACCEPTABLE.

j PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A i

n ,

PORTLAND GENERAL ELECTRIC' HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0402 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:39:42 DATE: 09-30-83 i TRACKING STATUS: CORRECTION REVIEWER: SCHROEDER DATA SOURCE: OPERATOR REVIEW DOCUMENT NO: INT.06 0700 GUIDELINE NO:

GUIDELINE AREA: GUIDELINE. SUBAREA:

COMMUNICATIONS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A N/A N/A DESCRIPTION OF DISCREPANCY THE CHAIN OF COMMAND WITHIN THE CREW IS NOT CONSISTANT FOR ALL OPERATING CONDITIONS. COORDINATION BETWEEN THE SHIFT SUPERVISOR AND CONTROL OPERATOR IN DIRECTING ACTIONS OF THE AUXILIARY OPERATORS IS NOT PERFORMED.

RECOMMENDATION:

CHANGE c DETERMINE WHETHER PROCEDURES ARE IN PLACE TO ADDRESS THIS CONCERN AND WHETHER STAFF IS AWARE OF THESE PROCEDURES (IF AVAILABLE) .

ACTION:

RDC NO:

NO CHANGE. AD 1-4, OPERATIONS AND HAINTENANCE RESPONSIBILITIES CLEARLY . (3)

DENOTE THE CHAIN OF COMMAND. INCONSISTENT APPLICATION OF THE CHAIN IS A MANAGEMENT PROBLEH AND NOT AN HED. EFFECTIVE COMMUNICATIONS AND TEAM BUILDING CONCEPTS HAVE SINCE BEEN INCORPORATED INTO THE PERIODIC RETRAINING

, PROGRAM. SUPERVISORY PERSONNEL ARE RECEIVING PERIODIC INSTRUCTION ON HANAGEMENT AND LEADERSHIP SKILLS DEVELOPHENT. IMPORTANT ISSUES THAT OCCUR i DURING THE OPERATING CYCLE HAY BE ADDRESSED DURING THE YEAR IN RETRAINING (3)

> AS WELL.

1 2

PROBLEH CATEGORY: 3 IMPLEMENTATION SCHEDULE: N/A 1

I e 88

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR t RPT NO: D06320 HED NO: 0403 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:40:06 DATE: 09-30-83 TRACKING STATUS: CORRECTION REVIEWER: SCHROEDER DATA SOURCE: OPERATOR REVIEW DOCUMENT NO: INT.07 0700 GUIDELINE NO:

GUIDELINE AREA: GUIDELINE. SUBAREA:

COMMUNICATIONS PANEL /HORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A N/A ~ N/A DESCRIPTION OF DISCREPANCY SEVERAL OPERATORS INDICATED THAT DURING DAYSHIFT THE ACO HAS THE RESPONSIBILITY OF TAKING CARE OF TAGOUTS. AT CERTAIN TIMES THIS CAN CREATE A HEAVY WORKLOAD AND DETRACT FROM OTHER OPERATIONAL DUTIES.

RECOMMENDATION:

CHANGE ESTABLISH HHETHER NORMAL OPERATIONAL DUTIES SUFFER HHEN TAGOUTS ARE i

BEING PERFORMED. DISCU5S THIS PERCEIVED PROBLEH HITH EACH SHIFT SUPERVISOR.

ACTION:

RDC NO:

COMPLETED. RESPONSIBILITY FOR TAGOUTS HAS BEEN SHIFTED TO A CLEARANCE OPERATA0R DURING WEEKDAYS, DAYSHIFT AND OTHER HEAVY HAINTENANCE PERIODS.

(g)

THE CLEARANCE OPERATOR'S DESK IS LOCATED OUTSIDE THE CONTROL R00H AND HE HAS NO POWER PRODUCTION RESPONSIBILITIES DURING THAT PERIOD.

PROBLEH CATEGORY: 2 IMPLEMENTATION SCHEDULE: N/A p ..

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0406 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:40:25 DATE: 09-30-83 TRACKING STATUS: CORRECTION REVIEHER: SCHROEDER DATA SOURCE: OPERATOR REVIEH DOCUMENT NO: INT.10 0700 GUIDELINE NO:

GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A N/A N/A DESCRIPTION OF DISCREPANCY es,- of THE CVCS HOLD-UP TANKS HAVE IMPLODED SEVERAL TIMES DUE TO TOO GREAT A NEGATIVE PRESSURE. ONE OPERATOR SUGGESTS THIS HIGHT HAVE BEEN AVOIDED IF THE CONTROL ROOM HAD A HUTS PRESSURE INDICATOR /ALARH. IT IS HORE LIKELY THAT THIS INDICATION HILL BE DETECTED IN THE CONTROL R00H RATHER THAN IN THE AUX BUILDING HHERE OPERATORS ARE NOT CONSTANTLY ON HATCH.

, RECOMMENDATION:

I CHANGE CONSIDER PROVIDING AN INDICATION OF HOLD-UP TANK PRESSURE IN THE CONTROL ROCM.

ACTION:

RDC NO: 82-050 COMPLETE. RDC 82-050 CORRECTED THE PRESSURE CONTROL PROBLEH AND PROVIDED IMPROVED PRESSURE INDICATION ON C-150 TO THE AUX BUILDING OPERATOR.

ALL SPECIFIC ANNUNCIATORS THAT INPUT TO PANEL C-150 ARE REFLASHED TO THE

CONTROL ROOM AS ", BORON RECYCLE TROUBLE AT PNL C-150" ON K-10 ABOVE THE
CVCS CONTROLS ON PANEL C-12. ANNUNCIATORS FROM C-150 THAT INPUT TO THAT COMMON ANNUNCIATOR ARE

dUT HI/LO LEVEL - 1/ TANK (3)

HUT LOW PRESS - 1/ TANK (3) 3)

HONITOR TANK HILO LEVEL - 1/ TANK (2) ,

4 CONC TANK HI/LO LEVEL

CONC TANK HI/LO TEMP ,

AC SUPPLY OUT DC SUPPLY OUT THE LOW PRESSURE ANNUNCIATOR SETPOINT IS SET TO PROVIDE HARNING HITH TIME TO ACT BEFORE A NEGATIVE PRESSURE DEVELOPS IN THE HUT. )

PROBLEH CATEGORY: 3 IMPLEMENTATION SCHEDULE: N/A

, / )

l l

. 1 5

i-

. 1 PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR HED NO: 0410

(

RPT NO: D08320 1 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:40:38 DATE: 09-28-83 TRACKING STATUS: CORRECTION REVIEHER: SCHROEDER I DATA SOURCE: OPERATOR REVIEW DOCUMENT NO: INT.21 0700 GUIDELINE NO:

GUIDELINE AREA: GUIDELINE. SUBAREA:

CONTROLS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-05 HIC-2993A TO D STH GEN HAIN FH SYPASS CONT DESCRIPTION OF DISCREPANCY THE STM GEN HAIN FH BYPASS CONTROLS ARE NOH HANUAL. THE OPERATION OF VALVES ARE DIFFICULT AND HAS RESULTED IN NUMEROUS PLANT TRIPS.

RECOMMENDATION:

INVESTIGATE FURTHER

, j ACTION:

RDC NO:

THE ISSUE HAD BEEN REVIENED BY ENGINEERING, WHICH CONCLUDED THERE WAS NOTHING IN THE HAY OF AN AUTCHATIC SYSTEM THAT WOULD RESOLVE THE PROBLEH. SUBSEQUENT TO CCHPLETION OF THE DCRDR, NUMARC ANNOUNCED THE SIGNIFICANT REDUCTION IN AUTCHATIC REACTOR TRIPS AS A PRINCIPLE INDUSTRY GOAL. PGE JOINED HITH THE HESTINGHOUSE CHNERS GROUP TO DEVELOP A TRIP REDUCTION AND ASSESSHENT PROGRAM (NOG-TRAP) TO DEFINE GENERIC APPROACHES TO REDUCING THE FREQUENCY OF SUCH TRIPS. THE SCOPE OF THIS EFFORT ENCOMPASSES THIS HED AND THEREFORE ANY COR-RECTIVE ACTION HILL BE DICTATED BY THE RESULTS OF THE HOG-TRAP.

i OBJECTIVES OF THE OF HOG-TRAP INCLUDE: (3)

, 1. ESTABLISH AND HAINTAIN A ROOT CAUSE DATABASE TO IDENTIFY RECURRING j AND GENERIC TRIP CAUSES.

! 2. ANALYZE THE INTERLOCKING OF CONT PRESSURE SIGNAL TO S/G LEVEL SETPT TO I ELIMINATE ENVIRONMENTAL COMPENSATION WHEN ADVERSE CONDITIONS 00 NOT EXIST.

j 3. IDENTIFY OPERATIONAL IMPROVEMENTS IN FEEDWATER CONTROL - AUTO AND MANUAL.

4. IMPROVE FEEDHATER SYSTEM STARTUP PRACTICES BY HOLDING PANEL DISCUSSIONS.

HITH EXPERT REACTOR OPERATORS.

5. REDUCE S/G LEVEL SETPT MARGIN, ADD TIME DELAYS FOR LO-LO LVL TRIP AND ADD COINCIDENT LOGIC TO THE TRIP. .

HOG-TRAP CORRECTIVE ACTION IS THE RESPONSIBILITY OF THE NUCLEAR SAFETY AND l REGULATION DEPT. ACTION ON THIS SPECIFIC HED IS COMPLETE.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A

(

i l

i

l l

PORTLAND GENERAL ELECTRIC l l

1 HUMAN ENGINEERING DISCREPANCY  ;

HED RECORD SPECIFIED BY HED NBR

( RPT NO: 006320 HED NO: 0420 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:40:55 DATE: 12-05-83 TRACKING STATUS: CORRECTION REVIEWER: SCHROEDER DATA SOURCE: VERIFICATION DOCUMENT NO: LOC.12 0700 GUIDELINE hW GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A N/A N/A DESCRIPTION OF DISCREPANCY TASK REQUIRES OPERATOR TO CHECK RHST LEVEL SLOWLY DECREASING < 5-10X PER HINUTE. LEVEL INDICATORS, NOT RATE, ON C-18 ARE BEING USED.

RECOMMENDATION:

CHANGE CONSIDER PROVIDING AN INDICATION OF RATE OF RHST LEVEL CHANGE TO

, OPERATOR.

ACTION:

RDC NO:

NO CHANGE. THE TASK REQUIREMENTS ARE SUBJECTIVE AND OPERATOR JUDGEMENT IS SUFFICIENT TO DETERMINE RATE OF CHANGE. IN ANY EVENT, AT 51X RHST LEVEL RHR PUMPS WILL AUTOMATICALLY TRIP (IF AUTO STARTED) AND AN ANNUNCIATOR WILL SOUND. THIS PROVIDES THE OPERATOR ADEQUATE TIME TO PERFORM THE MANUAL LINEUP FOR COLD LEG RECIRCULATION IN THE EVENT OF A DESIGN BASIS LOSS OF COOLANT ACCIDENT.

RATE OF RWST LEVEL CHANGE IS NO LONGER A VALUE UPON WHICH OPERATOR ACTION IS BASED. THE UPGRADE TO REV 1 ENERGENCY RESPONSE GUIDELINES DELETED THE "RWST LEVEL SLOWLY DECREASING" TASK. INSTEAD, ACTION IS BASED UPON 3)

REACHING THE LOW (51X) RHST LEVEL, AT WHICH TIME AN ANNUNCIATOR SOUNDS AND THE RHR PUMPS TRIP AUTOMATICALLY.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: N/A 9

w

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0428 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:41:20 DATE: 12-05-83 TRACKING STATUS: CORRECTION REVIEWER: SCHROEDER DATA SOURCE: VALIDATION DOCUMENT NO: 0700 GUIDELINE NO:

GUIDELINE AREA: GUIDELINE. SUBAREA:

PANEL LAYOUT PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-19 MO-8806 VLV POSIT. SWITCH C-19 MD-8923A,B VLV POSIT. SWITCH C-19 MD-8821A,B VLV POSIT. SWITCH C-18 HO-3296 VLV POSIT. SWITCH C-18 MO-3320 VLV POSIT. SWITCH C-18 MO-3294 VLV POSIT. SWITCH

  • C-18 MO-3300 VLV POSIT. SWITCH C-13 MO-8716A/B VLV POSIT. SWITCH (3)

DESCRIPTION OF DISCREPANCY THESE VALVE POSITION SWITCHES WERE DIFFICULT FOR OPERATORS TO LOCATE ON THE BENCHBOARD. THIS HAS NOTED DURING WALKTHROUGHS.

RECOMMENDATION:

CHANGE PROVIDE DEMARCATIONS / ENHANCEMENTS IN CONCERT WITH OTHER PAINT-TAPE-LABEL CHANGES IN THE CONTROL ROOM.

ACTION:

RDC NO: 84-125 COMPLETE. RDC 84-125 INCORPORATED THESE COMPONENTS INTO THE COLOR PADDING ENHANCEMENT SCHEME. DISCUSSIONS WITH OPERATORS INDICATE IT HAS MADE THESE COMPONENTS MUCH EASIER TO LOCATE.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: 12-31-85 b

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0437 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:41:40 DATE: 05-22-84 TRACKING STATUS: CORRECTION REVIEHER: OPS DATA SOURCE: VERIFICATION DOCUMENT NO: RRR.05 0700 GUIDELINE NO:

j GUIDELINE AREA: GUIDELINE. SUBAREA:

i VISUAL DISPLAYS 4 PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-02 1/N-45 SEL.SH FOR NR-45 C-D2 2/N-45 SEL SH FOR NR-45 DESCRIPTION OF DISCREPANCY THERE IS NO PERMANENT ARROH ON KNOB OR INDICATION OF COLOR PEN SELECTED. ALSO, THE LARGE SIZE OF THE KNOB OBSCURES READING OF SELECTOR POINTS.

1 RECOMMENDATION:

, CHANGE PROVIDE A ROTARY SELECTOR SWITCH WHICH CONFORMS TO GOOD HUMAN FACTORS ENGINEERING DESIGN (NUREG-0700, SECTION G.4 &.5).

ACTION:

RDC NO:

COMPLETE. EACH SHITCH IS LABELED AS TO HHETHER IT ALIGNS THE RED OR BLUE l PEN ON THE RECORDER. RED OR BLUE PAINT HAS ADDED TO THE ENGRAVED SELECTOR (Y)

ARRCH ON THE RESPECTIVE KNOBS TO MORE EASILY IDENTIFY THE NUCLEAR INSTRUMENT SELECTED AND RELATED INK COLOR.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A i

a l

I

! )

i l

l 4

_ _ _ _. .- , , . . , - - . , , , , . . . . , . . , __.m. _ . , .--,. . _ . , - . - , _ , , . ,

PORTLAND GENERAL ELECTRIC HUHAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR j ( RPT NO: D06320 HED NO: 0440 f RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:42:25 DATE: 05-22-84 j TRACKING STATUS: CORRECTION REVIEWER: SCHROEDER DATA SOURCE: VERIFICATION DOCUMENT NO: RRR.20 0700 GUIDELINE NO:

1 GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A N/A N/A DESCRIPTION OF DISCREPANCY

, TASK REQUIREMENTS FOR ES-0.2 REQUIRE AN INDICATION OF VESSEL HEAD TEMPERATURE (LESS THAN 200 DEGREE FARENHEIT). THERE DOES NOT APPEAR TO BE A DIRECT WAY TO GET THAT INFORMATION.

RECOMMENDATION:

CHANGE MODIFY PROCEDURE OR PROVIDE AN INDICATION OF VESSEL HEAD TEMPERATURE '

TO THE OPERATOR.

ACTION:

RDC NO:

! NO CHANGE. THE EMERGENCY INSTRUCTION ES-0.2, STEP 22.B TAKES INTO ACCOUNT I3) j THE LACK OF A VESSEL HEAD TEMPERATURE INDICATOR BY REQUIRING THE OPERATOR TO WAIT FOR A SPECIFIC TIME PERIODS BEFORE PROCEEDING IN THE C00LDOWN.

IN PARTICULAR, IF ALL CRDM FANS ARE NOT RUNNING, RCS PRESSURE IS HELD AT l

i 400 PSIG FOR 29 HOURS. SINCE THE RCS IS ON RHR COOLING, PRESSURE AND j TEMPERATURE CONTROL SHOULD NOT BE DIFFICULT. DELAY IN COOLDOWN/DEPRESSURI- 03)

ZATION IS TO AVOID BUBBLE FORMATION IN THE VESSEL HEAD. THERE ARE NO SECONDARY INDICATIONS OF VESSEL HEAD TEMPERATURE.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: N/A j

1

( I

.- . _ . - _ _ _ , _ ~. _- ._ _ ._ __ . _ - _ _ . . . _ _

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: D06320 HED NO: 0444 j RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:42:48 DATE: 03-30-83 TRACKING STATUS: ASSESSMENT REVIEWER: SCHROEDER DATA SOURCE: CONTROL ROOM SURVEY - 0700 DOCUMENT NO: 0700 GUIDELINE NO: G.5.1.1.b GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS INFORMATION TO BE DISPLAYED PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-03 AI-5755A CONTAINMENT H2 INDIC.

C-03 AI-57558 CONTAINMENT H2 INDIC.

DESCRIPTION OF DISCREPANCY THESE INDICATORS HAVE A RANGE OF 0-10 X. LOW AND HIGH RANGES HAVE NOT BEEN SPECIFIED. UNITS SHOULD RANGE BETWEEN O AND 30/ IF HIGH RANGE IS REQUIRED. (BASED ON DISCUSSIONS WITH OPERATORS DURING THE SURVEY)

RECOMMENDATION: '

g CHANGE ACTION:

RDC NO: 84-133 RDC 84-133 WILL DISABLE THE D TO 30X RANGE IN THE CONTROL ROOM.

REGULATORY GUIDE 1.87 ONLY RECOMMENDS A 0 TO 10X RANGE INDICATION FOR PRESSURIZED WATER REACTORS. THIS CHANGE IS SCHEDULED TO OCCUR DURING THE (3) 1987 OUTAGE INSTEAD OF 1988.

PROBLEM CATEGORY: 3 IMPLEMENTATION SCHEDULE: OS-3C-88 l

l I

- y  ;

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR

( RPT NO: 006320 HED NO: 0445 RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:42:52 DATE: 08-30-83 4

TRACKING STATUS: ASSESSMENT REVIEWER: SCHROEDER DATA SOURCE: CONTROL ROOM SURVEY - 0700 j DOCUMENT NO: 0700 GUIDELINE NO: 6.5.1.1.f GUIDELINE AREA: GUIDELINE. SUBAREA:

VISUAL DISPLAYS INFORMATION TO BE DISPLAYED i ...............................................................................

PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

! C-09 AI-5755A CONTAINMENT H2 INDIC.

t C-OS AI-5755B CONTAINMENT H2 INDIC.

l DESCRIPTION OF DISCREPANCY THESE DISPLAYS DO NOT PROVIDE AN INDICATION OF WHETHER THEY ARE OPERATIVE / INOPERATIVE.

RECOMMENDATION:

CHANGE 1 ...............................................................................

! i ACTION:

I RDC NO: 84-133 I NO CHANGE. RDC 84-133 WAS TO PROVIDE INDICATION THE ANALYZER WAS ON i IN THE CONTROL ROOM. SCOPE REVIEW DETERMINED THE COST TO BE PROHIBITIVE RELATIVE TO THE BENEFIT. THEREFORE, THE EQUIPMENT STATUS WILL CONTINUE '

TO BE PROVIDED BY THE AUXILIARY BUILDING OPERATOR. HE MUST SHIFT THE (3)

ANALYZER FROM 'STBY' TO 'ON' WHEN DIRECTED BY THE EMERGENCY INSTRUCTIONS i ANYWAY. SINCE FSAR ANALYSES INDICATE THE BUILDUP OF HYDROGEN TO A COMBUSTIBLE LEVEL FOLLOWING THE DESIGN BASIS ACCIDENT TO TAKE DAYS, THE i LACK OF ON/0FF INDICATION IN THE CONTROL ROOM IS NOT CONSIDERED CRITICAL.

A r

b i

I l

1 i

s i

i i

, - - wr,. e -+sw> ..,-n m n -w. - . . - , , _ _ _ , . , , , . _ . . , , , , . , _ _ . , _ . , , _ _ , . , _ , , , , , _ _ , _ _ , _ _ _ _ , ,

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED N3R

( RPT NO: D06320 HED NO: 0447 .

RPT DATE: 06-20-86 PLANT: TROJAN RPT TIME: 14:42:58 DATE: 03-04-84 TRACKING STATUS: ASSESSMENT REVIEWER: SCHROEDER DATA SOURCE: CONTROL ROOH SURVEY - GP j ...............................................................................

! DOCUMENT NO: 1.2.1.6 0700 GUIDELINE NO: 6.8.2.2

! GUIDELINE AREA: GUIDELINE. SUBAREA:

PANEL LAYOUT LOGICAL ARRANGEMENT AND LAYOUT

............................................................................... )

PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

C-15 SV-3503 TURBINE STOP VALVE INDIC.

C-15 SV-3511 TURBINE STOP VALVE INDIC.

I C-15 SV-3517 TURBINE STOP VALVE INDIC.

! C-15 SV-3523 TURBINE STOP VALVE INDIC.

j ............................................................................... ,

DESCRIPTICH OF DISCREPANCY

]

THE TURBINE STOP VALVE INDICATORS ARE ARRANGED AS B,C,D,A. THIS i ORDERING IS CONTRARY TO POPULATION EXPECTATION.

] ...............................................................................

RECOMMENDATION:

CHANGE ACTION:

RDC HO:

NO CHANGE. THE CURRENT LABELING IS CONSISTENT WITH PLANT LAYOUT IN THAT THE VALVES ARE PHYSICALLY IN A LINE AS B, C, D, AND A. THEY ARE DESIGNATED (3)

AS SV-1,-2,-3, AND -4 RESPECTIVELY. ON THE EHC PANEL AT C-05 THE VALVES POSITION INDICATORS ARE LINED UP AS SV-1,-2,-3 AND -4. ALL FOUR VALVES OPERATE TOGETHER, WHETHER OPENING OR CLOSING.

PROBLEM CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A I

_ . - . -e , ., _ -

l PORTLAND GENERAL ELECTRIC l HUMAN ENGINEERING DISCREPANCY

. HED RECORD SPECIFIED BY HED NBR p.

"' RPT NO: 006320 HED NO: 0470 ,

RPT DATE: 12-16-85 PLANT: TROJAN RPT TIME: 11:15:15 DATE: 12-02-85 l TRACKING STATUS: CORRECTION REVIEWER: SCHROEDER DATA SOURCE: CONTROL RCOM SURVEY - GP DCCUMENT NO: 5.5.1.1 0700 GUIDELINE NO:

GUIDELINE AREA: GUIDELIdE. SUBAREA:

PROCESS COMPUTERS OPERATOR / COMPUTER INTERFACE PANEL / WORKSTATION ID: COMPONENT NO: COMPONENT DESCRIPTION:

N/A P-2S00 SPDS DESCRIPTION OF DISCREPANCY THE HEAT EXCHANGER SYHBOL ON THE PSSD IS NOT CONSISTENT WITH THE SYMBOL USED ON THE CONTRCL ROOM CONSOLE HIMIC. ALSO, THE PRESSURIZER SYMBOL DOES NOT ALWAYS HAVE THE SPRAY COMPONENT INDICATED (SEE 2PS1, 3RC1 AND 3RC2).

RECOMMENDATION:

, ,.~~

0'

-l CONSIDERATICN SHOULD BE GIVEN TO USING THE HEAT EXCHANGER SYMBOL THAT 1

APPEARS ON THE CONTROL BOARDS AND PROVIDING THE SPRAY REPRESENTATION ON THE PRESSURIZER SYHBOL.

! ACTION:

RDC HO

NO ACTION. THE HEAT EXCHANGER SYMBOL USED ON THE MAIN CONTROL BOARDS WOULD COMPLICATE THE DISPLAY GRAPHICS HORE THAN IS WARRANTED. THE PSSO -

1 HEAT EXCHANGER SYHSOLS ARE CLEARLY LABELED "HX" AND UNDERST000 TO BE HEAT EXCHANGERS BY THE OPERATCRS.

THE SPRAY N0ZZLE IN THE PRESSURIZER GRAPHIC IS SHOWN ONLY IF THE INDIVID-UAL SPRAY LINE CCMPONENTS ARE NOT VISIBLE ON THE DISPLAY. THE N0ZZLE THEN SERVES AS A COMPOSITE REPRESENTATION OF SPRAY LINE STATUS BY BEING FILLED IN IF THERE IS SPRAY FLOW, AND NOT FILLED IN IF THERE IS NO SPRAY FLOW.

THIS CCNVENTION WILL BE COVERED IN OPERATOR TRAINING.

PROBLEH CATEGORY: 4 IMPLEMENTATION SCHEDULE: N/A

. t' .

j l- ~

4 i

i _ . . - . . .- - * **

PCRTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECORD SPECIFIED BY HED NBR RPT NO: 008320 HED NO: 0471 RPT DATE: 12-19-85 PLANT: TROJAN RPT TIME: 07:33:48 DATE: 12-02-85 TRACKING STATUS: CCRRECTION REVIEHER: SCHRCEDER DATA SCURCE: CCNTROL ROCH SURVEY - GP DOCUMENT NO: 5.S 0700 GUIDELINE NO:

GUIDELINE APEA: GUIDELINE.SUDAREA:

PROCESS COMPUTERS OPERATOR /CCHPUTER INTERFACE

............................................................................... 1 PANEL / WORKSTATION ID: COMPCNENT NO: COMPONENT DESCRIPTICN:

N/A P-2500 SPDS DESCRIPTION OF DISCREPANCY THE FOLLCHING DISPLAYS HAVE SECTIONS THAT REQUIRC. CLARIFICATION AND/OR IMPROVED LABELING:

E ON 3RC1, IT IS NOT CLEAR HHETHER THE TAVE INDICATED REPRESENTS THE HIGHEST LOOP VALUE.

I CN 3RC2 THE PORVS AND SAFETY VALVES HAVE NOT BEEN LABELED.

~~

E ON 3MS1, HHEN "COND NOT AVAIL" APPEARS, IT IS NOT CLEAR TO OPERATORS k

HHETHER THE REFERENCE IS TO STH DUMPS (GRP 1 TO 4) CR THE CCNCENSER.

I CN 3CV1 THERE IS NO VALVE LINE-UP TO INDICATE NORNAL OR ALTERNATE CHARGING.

E ONE CONT TEMP POINT DETAIL (INDICATING HAXIMUM DEVIATICN) DOES NOT HAVE UNITS INDICATED (CEGREES FAHRENHEIT) .

RECOMMEhDATION:

CONSIDERATICN SHOULD BE GIVEN TO:

E PROVIDING " HIGHEST TAVE" AS THE DESIGNATOR ON 3RC1.

I PROVIDING A SUBHEADING LABEL FOR THESE VALVE SEIS.

I CLARIFYING THE TERM "CCNQ NOT AVAILABLE" CN 3HS1 OR EMPHASIZING THE SIGNIFICANCE CF THIS POINT IN TRAINING.

I PROVIDING VALVE LINE-UPS FOR NORMAL AND ALTERNATE CHARGING.

I PROVIDING UNITS OF DEGRESS FAHRENHEIT ON ALL APPLICABLE POINT DETAIL DISPLAYS.

ACTION:

, RDC N0:

IINVESTIGATE AND CLARIFY HHICH TAVE IS DISPLAYED ON 3RC1.

ENO ACTICN. THE 3RC2 HIMIC IS A STANDARD SCHEMATIC OF THE PRESSURIZER RELIEF SYSTEM SUCH THAT THE PORS AND PSVS ARE VERY CLEAR TO THE OPERATOR.

IN ADDITICH, VALVE NUMBERS ARE DISPLAVED BY EACH VALVE.

i ITHE REFERENCE IS TO STEAM CUMPS, BUT THE INDICATION IS NOT YET OPERATIONAL, HENCE THE CONFUSION. 0; ICE CONNECTED BY RDC 44-107L BE ADDRESSED IN TRAINING. l ENO ACTION. THERE IS NO NEED TO IH7ICATE TO HHICH LOOP THE CHARGING FLOW

., IS GOING, SINCE ONE LOOP CANNOT BE ISCLATED FRCH THE OTHER ANYHAY. THAT  :

INFORMATION IS AVAILABLE ON PANEL C-1.1 IF NEEDED. l ITHE DEGREES FAHRENHEIT PROBLEH HILL EE RESOLVED BY THE PLANT ENGINEERING STAFF AS PART OF THE SPOS VALIDATICH AND VERIFICATION EFFORT.

PROBLEH CATEGCRY: 4 IMPLEMENTATION SCHEDULE: N/A l

l

PORTLAND GENERAL ELECTRIC HUMAN ENGINEERING DISCREPANCY HED RECCR0 SPECIFIED BY HED NBR i

( ,' RPT NO: 006320 HID NO: 0472

, RPT DATE: 12-17-85 PLANT: TROJAN ,

i RPT TIME: 14:14:01 DATE: 12-02-85 4

TRACXING STATUS: CORRECTION REVIEWER: SCHROEDER l DATA SOURCE: CONTROL ROOM SURVEY - GP

\

{

DCCUMENT NO: 1.4.3 0700 GUIDELINE NO: '

GUIDELINE AREA: GUIDELINE. SUBAREA: .

PRCCESS COMPUTERS SCREEN LOCATICH, SEATED OPERATORC

PANEL /HORKSTATION ID
CCMPONENT NO: COMPONENT DESCRIPTION:
N/A P-25CO SPDS DESCRIPTION OF DISCREPANCY THE SPDS IS A SIT DOWN WCRK STATION, BUT THERE ARE NO CHAIRS ALLOCATED TO THIS AREA. OPERATORS EITHER STAND OVER THE KEYBOARD OR PULL A

! CHAIR FRCH OTHER AREAS OF THE CONTROL ROOM.

l RECOMMENDATION:

CHANGE PROVIDE AT LEAST ONE AND POSSIBLY TWO CHAIRS FOR THE SPDS WCRK STATION.

A.

a ACTION:

RDC NO:

PLANT STAFF PROVIDE ADDITIONAL CHAIRS DESIRED.

PROBLEM CATEGORY: 4 IMPLEMEPTATION SCHEDULE: 03-33-86 1

)

l I

1 I

I i

L i

s I

1 i

.] .g

,e 9

i ,

. i i

.,. . . . . , . . . . . . . ~ . _ . _ . . ~ - . -- -

.-_._.r. - _ . . _ _ .

. - .v.. , ,, . 7-, _ . - .,e.,m w, ,y. ._ . , . . _

,- . .-