y NUREG-1140 i

?

A Regulatory Analysis on Emergency Preparedness for Fuel Cycle and Other Radioactive Material Licensees j

Final Report l

U.S. Nuclear Regulatory

' Commission Office of Nuclear Regulatory Research S. A. McGuire l

,9* *

  • u e

"N

'?

l

{

i I

8882228888oo2 2

1140 R PDR l

NOTICE Availability of Reference Materials Cited in NRC Publications Most documents cited in NRC publications will be available from one of the following sources:

1. The NRC Public Document Room,1717 H Street, N.W.

Washington, DC 20555

2. The Superintendent of Documents, U.S. Government Printing Office, Post Office Box 37082, Washington, DC 20013 7082
3. The National Technical Information Service, Springfield, VA 22161 Although the listing that follows represents the majority of documents cited in NRC publications, it is not intended to be exhaustive.

Referenced documents available for inspection and copying for a fee from the NRC Public Docu-ment Room include NRC correspondence and internal NRC memoranda; NRC Office of Inspection and Enforcement bulletins, circulars, information notices, inspection and investigation notices; Licensee Event Reports; vendor reports and correspondence; Commission papers; and applicant and licensee documents and correspondence.

The following documents in the NUREG series are available for purchase from the GPO Sales Program: formal NRC staff and contractor reports, NRC sponsored conference proceedings, and NRC booklets and brochures. Also available are Regulatory Guides, NRC regulations in the Code of Federal Regulations, and Nuclest Regulatory Commission issuances.

Documents available from the National Technical Information Service include NUREG series reports and technical reports prepared by other federal agencies and reports prepared by the Atomic Energy Commission, forerunner agency to the Nuclear Regulatory Commission.

Documents available from public and special technical libraries include all open literature items, such as books, journal and periodical articles, and transactions. Feders/ Register notices, federal and state legislation, and congressional reports can usually be obtained from these libraries.

Documents such as theses, dissertations, foreign reports and translations, and non NRC conference proceedings are available for purchase from the organization sponsoring the publication cited.

Single copies of NRC draf t reports are avai!able free, to the extent of supply, upon written request to the Division of Information Support Services, Distribution Section, U.S. Nuclear Regulatory Commission, Washington, DC 20555.

Copies of industry codes and star.dards used in a substantive manner in the NRC regulatory process are maintained at the NRC Library, 7920 Norfolk Avenue, Bethesda, Maryland, and are available there for reference use by the public. Codes and standards are usually copyrighted and may be purchased from the originating organization or, if they are American National Standards, frcm the American National Standards Institute,1430 Broadway, New York, NY 10018.

NUREG-1140 A Regulatory Analysis on Emergency Preparedness for Fuel Cycle and Other Radioactive Material Licensees Final Report i

Dfts u shed au 1

S. A. McGuire Division of Reactor Accident Analysis Office of Nuclear Regulatory Research U.S. Nuclear Regulatory Commission W:shington, DC 20555

,s ~*m, t

I

L EXECUTIVE SUM 4ARY The question this Regulatory Analysis sought to answer is:

Should the NRC impose additional emergency preparedness requirements on certain fuel cycle and other radioactive material licensees for dealing with accidents that might have offsite releases of radioactive material? To answer the question, we analyzed potential accidents for 15 types of fuel cycle and other radioactive material licensees.

{

The most potentially hazardous accident, by a large margin, was determined to be the sudden rupture of a heated multi-ton cylinder of UFs.

Acute fatal-ities would be possible in the immediate vicinity of the release point.

Acute permanent injuries may be possible for many hundreds of meters, and clinically observable transient effects that have no known long term consequences may be possible for distances up to a few miles.

These effects would be caused by the chemical toxicity of the UFs and the products resulting from its reaction with moisture.

Accompanying radiation doses would not be of significance.

The most potentially hazardous accident due to radiation exposure was determined to be a large fire at certain facilities handling large quantities of alpha-emitting radionuclides (i.e.. Po-210, Pu-238, Pu-239, Am-241, Cm-242, Cm-244) or radioiodines (I-125 and I-131).

However, acute fatalities or injuries to people offsite due to accidential releases of these materials do not seem plausible.

A few other radionuclides are of lesser importance (H-3, P-32, Sr-90, and Cs-137).

If plutonium were to be handled at fuel cycle facilities, a fire in such a facility may also be of significance.

The only other significant accident was identified as a long-term f

pulsating criticality at fuel cycle facilities handling high-enriched uranium

(

or plutonium in aqueous solutions.

Aside from fires or accidents that lead to fires, UFs releases, or cri-1 ticality accidents, no other significant accidents were identified.

Explosions were not seen to yield as large a release unless they were followed by a fire.

Tank ruptures were not identified as having a potential for significant releases.

Earthquakes also were not identified as leading to significant 111 l

releases unless they were followed by a fire.

Tornados might cause large release, but would disperse the material so widely that significant doses would not result.

lhe criterion for deciding whether an accident was significant is whether a releise could cause a person outside the plant on the plume centerline to receive an effective dose equivalent of more than 1 rem, a thyroid dose of more than 5 rems, or an intake of soluble uranium exceeding 2 mg.

One rem whole body or 5 rems thyroid are at the lower end of the range of dose for which the EPA says protective actions should be considered.

A rough screening identified 64 licensees authorized to possess cuantities of radioactiv4 materials for which an accident release could cause doses exceeding 1 rem effective dose equivalent, 5 rems thyroid, or intake of 2 mg of soluble uranium.

However, some of these licensees do not actually possess all of the materials authorized by the license.

These licensees are likely to amend their licenses to lower their possession limits rather than submit a plan.

Other licensees could demonstrate that a significant release is not possible.

In actuality, only about 30 plans would be submitted.

For most of these licensees the degree of hazard is small.

For most such licensees maximum doses for even the mest severe postulated accidents are only a few rems.

The areas within which people should take protective actions are small - for most licensees much less than a square mile.

At most sites these areas would contain few people.

And the probability of a major release is small - less than 10 /yr, for radiological releases (but higher for UFs releases.) The probability of a major release simultaneous with highly adverse

.s meteorology is less than 10 /yr.

Thus the probability of even a single person's receiving a dose in excess of 1-rem at most of these facilities has about the same probability as a core melt accident with containment failure at a nuclear power plant.

A further feature of major accidents at such licensed facilities is that airborne releases are likely to occur rapidly with little warning.

Ruptures of UFs cylinders and fires would give little or no warning.

Releases could start before a fire is detected or shortly thereafter.

P'ume travel time to nearby peuple is likely to be no more than a few minutes.

Releases would, in a major-ity of cases, end within half an hour to an hour when the fire department con-trolled the fire.

In most instances, actions taken half an hour after accident detection would be fairly ineffective.

Actions taken 15 minutes after accident 1

iv i

1

detection could on the average be expected to be roughly 50% effective.

Thus protective actions would have to be taken quickly.

This requires prompt actions by people in the vicinity of the site to notify nearby residents.

There is not likely to be enough time for dose projections or complicated decision-making during the accident, nor for participation of personnel not in the immediate vicinity of the site.

An appropriate plan would (1) identify accidents for which protective actions should be taken by people offsite.

(2) list the licensee's respon-sibilities for each type of accident, including notification of local author-ities (fire and police generally), and (3) give sample messages for local authorities including protective action recommendations.

This approach more closely follows the approach used for research reactors than for power reac-tors.

The low potential offsite doses (acute fatalities and injuries not possible except possibly for UFs releases), the small areas where actions would be warranted, the small number of people involved, and the fact that the local polico and fire departments would be doing essentially the same things they normally do, are all factors that tend to make a simple plan adequats.

V

a L

l CONTENTS Pa21 EXECUTIVE SDMMARY iii ACKNOWLEDGEMENTS...........................

xi 1.

PROPOSED ACTION 1

1.1 Descript' ion of the Propos'ed Action.............

1 1.2 Need for the Proposed Action................

4 2.

TECHNICAL BASIS FOR THE PROPOSED RULE,.............

6 i

2.1 Methodology 6

2.1.1 The Accident History Approach............

6 2.1.2 Accident Source Terms................

8 2.1.3 Calculations of Doses................

9 2.1.4 Protective Action Guides 14 2.1.5 A Discussion of the Conservatism in the Calculations 16 2.2 Fuel Cycle Facilities 19 2.2.1 Uranium Mining 19 2.2.2 Uranium Milling...................

19 2.2.3 UFs Conversion Plants................

27 2.2.4 Enrichment Plants..................

40 2.2.5 Fuel Fabrication - Uranium 42 2.2.6 Fuel Fabrication - Plutonium 53 2.2.7 Spent Fuel Storage 59 4

2.2.8 New Fuel Storage 62 2.2.9 Reprocessing of Spent Fuel 62 2.2.10 Research with Nuclear Fuels.............

67 2.3 Byproduct Material Facilities 69 2.3.1 A Generic Overview 70 2.3.2 Radiopharmaceutical Manufacturing..........

84 2.3.3 Radiopharmacies and Hospitals............

86 2.3.4 Sealed Source Manufacturing.............

88 2.3.5 University Research Laboratories 90 i

2.3.6 Waste Warehousing and Burial 94 2.3.7 Depleted Uranium Products..............

96 2.4 Summary of Facilities to be Covered 99 2.5 A Protective Action Strategy................

101 i

i vii

S 4

f i

CONTENTS (Continued)

N t

101 2.5.1 The Initial Response................

105 2.5.2 Locating Contamination................

2.5.3 The Assessment Phase................

105 106 l

3.

VALUE/ IMPACT..........................

106 3.1 Alternatives........................

107 3.2 Value of the Proposed Action 109 3.3 Cost.............................

109 3.4 Value/ Impact of Alternatives................

110 l

4.

STA1UTORY CONSIDERATIONS....................

110 4.1 NRC Regulatory Authority..................

110 4.2 Agreement States......................

110 4.3 Environmental Impact Appraisal...............

111 5.

CONCLUSIONS...........................

FIGURE S

13

- 1.

Atmospheric dispersion versus distance TABLES 21 1.

Fires in Uranium Mills through 1986...............

2.

Uranium Mill Tailings Releases, 1959-1986............

22 l

3.

Accident Source Terms and Doses From Uranium Mill Accidents...

24 4.

Accidents Involving UFs Releases through 1986..........

29 i

5.

Criticality Accidents In Fuel Cycle Facilities through 1986...

43 l

6.

Fires and Explosions Involving Uranium and Thorium through 45 1986................

7.

Other Accidental Releases from Uranium Fuel Fabrication Plants 46 through 1986..........................

8.

Amounts of Radioactive Materials Released to Room Air Oue to 48 a Criticality Accident.....................

50 9.

Offsite Doses Calculated for Fuel Fabrication Plants 10.

Calculated Releases and Doses from Spent Fuel Storage Accidents.

63 11.

Fires and Explosions Involving Release of Byproduct Materials j

71 through 1986..........................

12.

Accidental Releases of Byproduct Material Except Fires 72 and Explosions through 1986...................

13. Quantities of Radioactive Materials Requiring Evaluation of the l

78 Need for Offsite Emergency Preparedness.............

14.

Radiopharmaceutical Manufacturing:

Maximum Possession Limits, i

85 l

Release Fractions, and Doses Oue to a Major Facility Fire....

15.

Radiopharmacy:

Maximum Possession Limits, Release Fractions, r

88 l

and Doses Due to a Major Facility Fire viii

CONTENTS (Continued) fagg TABLES (Continued) i 16.

Sealed Source' Manufacturing:

Maximum Possession Limits, Release Fractions, and Doses Due to a Major Facility Fire....

91 17.

University Research Laboratories:

Maximum Possession Limits Release Fractions, and Doses Due to a Major Fire 93

18. Waste Warehousing Airborne Releases and Doses Due to a Major Facility Fire..........................

95 19.

Comparison of Costs and Benefits of Special Emergency Preparedness 110 I

I i

h l

I

(

)

ix L

ACKNOWLEDGEMENTS We would like to thank tne following people for helping us prepare this Regulatory Analysis.

David Bennett, Eugene Runkle, Daniel Alpert, Kenneth Adams, and David Aldrich of Sandia National Laboratory for performing dose calculations and meterological modeling.

Peter Owczarski, Sue Sutter, Jofu Mishima, and Mark Halverson of Battelle-Pacific Northwest Laboratory for performing release fraction experiments, analyzing release fraction experiments, reviewing the literature on release fractions, developing accident scenarios, and analyzing accidents.

Moshe Simon-Tov and Reid Williams of Martin-Marietta Energy Systems, Oak Ridge, for performing analyses of UFs releases.

Robert Just for discussions on the health effects of UFe.

Bruce Hicks of the National Oceanic and Atmospheric Administration for reviewing calculations of uranium haxafluoride releases.

Andreas Jensen of the John Hopkins University Applied Physics Laboratory for descriptions of the U.S. Department of Transportation accident modeling

methods, Joseph Logsdon of the U.S. Environmental Protection Agency for discussions on the use of the EPA's protective action guides.

Paul Morrow of the University of Rochester and Mcdonald Ed Wrenn of the University of Utah for discussion on the chemical toxicity of uranium.

Duane Hall of 3M for hosting a tour of the 3M sealed source manufacturing plant in New Brighton, Minn, and for discussion on the release fractions of polonium-210.

Edward Janzow of Monsanto Research Corporation for hosting a tour of the Monsanto Dayton, Ohio, sealed source manufacturing plant and for information on the particle size of americium oxide powder.

Melita Rodeck of the Federal Emergency Management Agency for helpful comments.

Al Arcuni and Sandy Mullen of International Energy Associates Limited for helpful comments.

xi l

On the NRC's Office of Nuclear Material Safety and Safeguards staff:

Fritz Storz, Lee Rouse, and John Roberts for assistance in preparing the section on spent fuel storage; Dennis Sollenberger and George Gnugnoli for assistance in preparing the section on uranium milling; Fred Fisher, Ed Shun, and R. Gerry Page for suggestions throughout the analysis; Joseph Wang for assistance in preparing sections in byproduct material licensees; Ron Cardarelli for help in collecting information in emergency plans submitted tu NRC, On the NRC's Office of Nuclear Regulatory Research staff:

Steven Bernstein and Don Solberg for assistance on accident scenarios and release fractions, as well as contract assistance; Robert Kornasiewicz and Leta Brown for comments and assistance on meterological modeling; James Martin and Leonard Soffer for comments and assistance with regard to existing NRC policy on emergency prepar-edness, especially as it relates to nuclear power plants; Michael Jangochian, James Norberg, Philip Ting, Robert Bernero, Frank Gillespie, James Malaro, and Karl Goller for many helpful comments and valuable support.

On the NRC's Office of Nuclear Reactor Regulation staff:

Irwin Spickler for many valuable comments and discussions on meterological modeling.

On the NRC's Office of Analysis and Evaluation of Operational Data staff:

I Kathleen Black and Eugene Trager for help in collecting information on accident histories.

l t

v b

L l

h i

xii

2 A REGULATORY ANALYSIS.

ON EMERGENCY PREPAREDl1ESS FOR FUEL CYCLE AND OTHER RADI0 ACTIVE MATERIAL LICENSEES 1.

PROPOSED ACTION 1.1 Description of the Proposed Action This regulatory analysis evaluates the need for a proposed rule to require additional emergency preparedness for certain fuel cycle and other radioactive material licensees.

The purpose of the rule would be to require, for certain licensees who are authorized to possess radioactive materials in large quantity, emergency plans for responding to releases of radioactive materials.

These plans would include:

(1) Facility description:

A brief description of the licensee's facility and area near the site.

(2) Types of accidents:

An identification of each type of accident for which protective actions may be needed.

(3) Classification of accidents:

A classification system for classifying accidents as alerts or site area emergencies.

(4) Detection of accidents:

Identification of the means of detecting each type of accident in a timely manner.

1

(5) Mitigation of consequences:

A brief description of the means and equip-ment for mitigating the consequences of each type of accident, including those provided to protect workers onsite, and a description of the program for maintaining the equipment.

(6) Assessment of release:

A brief description of the methods and equipment to assess releases of radioactive materials.

(7) Responsibilities:

A brief description of the responsibilities of licensee personnel should an accident occur, including identification of personnel responsible for promptly notifying offsite response organizations and the NRC; also responsibilities for developing, maiataining, and updating the plan.

(8) Notification and coordination:

A commitment to and a brief description of the means to promptly notify offsite response organizations and request offsite assistance, including medical assistance for the treatment of con-taminated injured onsite workers when appropriate.

A control point must be established.

The notification and coordination must be planned so that unavailability of some personnel, part of the facility, and some equipment will not prevent the notification and coordination.

The licensee shall also commit to notify the NRC immediately after notification of the appro-priate offsite response organizations and not later than one hour after the licensee declares an emergency.

In addition, the licensee shall notify the U.S. Coast Guard National Response Center immediately after the size of the release has been assessed if the estimated quantity of material released exceeds the reportable quantities established by the U.S. Environmental Protection Agency.

j (9) Information to be communicated:

A brief description of the types of information on facility status, radioactive releases, and recommended actions, if necessary, to be given to offsite response organizations and to the NRC.

2

(10) Training:

A brief description of the training the licensee will provide workers on how to respond to an emergency and any special instructions and orientation tours the licensee would offer to fire, police, medical, and other emergency personnel.

(11) Safe shutdown:

A brief description of the means of restoring the facility to a safe condition after an accident.

(12) Exercises:

Provisions for conducting quarterly communications checks with offsite response organizations and annual onsite exercises to test response to simulated emergencies.

Quarterly communications checks with offsite response organizations shall include the check and update of all necessary telephone numbers.

The licensee shall invite offsite response organiza-tions to participate in the annual exercises.

Participation of offsite response organizations in annual exercises although recommended is not required.

Exercises must use scenarios not known to exercise participants.

The licensee shall critique each exercise using individuals not having direct implementation responsibility for the plan.

Critiques must eval-uate the appropriateness of the plan, emergency procedures, facilities, equipment, training of personnel, and overall effectiveness of the response.

Deficiencies found by the critiques must be corrected.

(13) Hazardous chemicals:

A verification of the applicant's compliance with the Emergercy Planning and Community Right-to-Know Act of 1986, Title III, Pub. L.99-499, if applicable to the applicant's activities at the proposed place of use of the special nuclear material.

The question is not whether licensees should have any emergency preparedness.

That question was addressed long ago.

The NRC has long required licensees to be prepared to cope with emergencies.

The question is whether there should be additional requirements.

For example, should NRC require formal written state and local government plans for coping offsite with serious radiation accidents?

Such plans might include provisions for early evacuation by the public or notifying them to take shelter indoors.

The question is also not whether State and local governments should have emergency preparedness capabilities for dealing with radiation accidents.

3

Police departments, fire departments, state radiological health departments, and other agencies that are routinely prepared to cope with emergencies already exist.

This rulemaking is intended to assure that, where needed, there exist emergency procedures for mitigating and coping with offsite releases.

We must also distinguish between emergency response and formal emergency plans.

If an accident happens, the licensee and State and local govern-ments can be expected to respond to the best of their abilities whether or not there are any formal written emergency plans for offsite release'.

s 1.2 Need for the Proposed Action The NRC has always required that its licensees take steps to reduce the likelihood of serious accidents to a minimal level, but yet be prepared to cope with accidents should they occur.

However, during the Commission's delibera-tions on rulemaking concerning nuclear power plant emergency preparedness following the accident at Three Mile Island, the Commission directed the staff to evaluate the need to strengthen the emergency preparedness requirements for fuel cycle and other radioactive material licensees.

In late 1980, the staff reevaluated previously submitted emergency plans for fuel fabrication plants and found some weaknesses in the plans as written.

For example, some plans did not describe (1) timely alerting of potentially affected public to a hazard, (2) recommendations for spacific actions the public should take to protect itself, such as sheltering or evacuation, and l

(3) arrangements for prompt notification of NRC and state and local government agencies.

In February, 1981, the NRC issued orders to 62 licensees to either submit l

comprehensive radiological emergency plans or lower their possession limits for radioactive material.

About half of the licensees submitted plans, and half lowered their possession limits or surrendered their license.

Then, an Advance Notice of Proposed Rulemaking on the subject of offsite emergency pre-paredness was published in the Federal Register on June 3, 1981 (46 FR 29712).

In the Advance Notice the Commission proposed to codify, with some modifi-cations, the radiological emergency requirements set forth in the orders.

A public comment was that there is no need for emergency plans for those facili-ties because the offsite consequences of a credible accident would be so small.

4

On April 20, 1987, the NRC published a Notice of Proposed Rulemaking to establish in its regulations a formal basis for the plans required by order.

Seventeen public comments were received.

Nine were from licensees who would be affected by the regulation, and three were from States who would have a role in responding to an accident.

The comments raised two types of significant policy questions.

The first type said that the rule should not be adopted because it was not needed or not useful.

These comments generally stated that the analyses and accident scenar-ios were too conservative, that actual doses would be far lower than those calculated, that credit should be given for engineered safeguards, that plans should only be required if doses could exceed 5 rems instead of 1 rem, that the costs far outweight the benefits, or that accident would happen so quickly that no offsite response could be effective at reducing offsite exposures, regard-less of cost.

In the end, the staff rejected these arguments.

The staff agreed that the calculations are conservative, that doses in an actual accident would probably be lower than calculated, that the probability of a large release is very small, and that some accidents could happen so quickly that the response would not be effective at lowering doses.

Nevertheless, the Commissioners considered that an emergency plan to be an integral part in protecting public health and safety.

There is no assurance that emergency response would always be effective at reducing exposures offsite or that specified dose levels must not be exceeded.

The requirement should be that the licensee must be prepared to take practical steps that could, in favorable circumstances, reduce radiation exposures of the public.

The other type of comment said that the rule should require the licensee to have a system to promptly warn the public offsite of an accident and be required to give information brochures annually to people near the facility.

These arguments were also rejected.

The licensee has the responsibility to prevent serious accidents.

Should that fail, the responsibility for pro-tecting the public near the facility is considered to belong to offsite public safety authorities.

The rule would require the licensee to immediately notify those authorities of serious accidents.

It is expected that, in general, the authorities would then notify the public in a manner similar to what is done for truck and rail accidents involving hazardous chemicals.

Similarly, the rule would leave the decision on public information brochures to local authorities.

5

t 2.

TECHNICAL BASIS FOR THE PROPOSED RULE 2.1 Methodology This regulatory analysis-identifies the classes of fuel cycle and other-radioactive material licensees that could have accidents that might result in radiation doses to the public exceeding protective action guides established by the EPA.

(Chemical toxicity is also considered for the special case of uranium hexafluoride and soluble uranium releases.) The plausibility of exceeding the EPA's protective action guides was considered from two points of view:

(1) the accident history of fuel cycle and byproduct material licensees, and (2) theoretical calculations of the releases and offsite doses of accidents considered to be possible.

2.1.1 The Accident History Approach The history of accidents involving radioactive byproduct material (Part 30 licensees), source material (Part 40 licensees), special nuclear material (Part 70 licensees), and spent fuel storage (Part 72 licensees) was surveyed.

In summary, we found no evidence that any accidental release of radioactive material from facilities of these types has ever caused an effective dose equivalent to any individual offsite exceeding even 1% of the EPA's 1-rem protective action guide.

The value of the historical review is that it identifies types of accidents that have occurred and draws our attention toward accidents similar to those that have occurred.

In addition, accidents that have happened cannot have violated the physical laws of nature.

This statement cannot be made about theoretical calculations.

Theoretical calculations can use simplifying assump-tions that are internally inconsistent or inconsistent with the laws of nature.

More information on the nature, causes, and frequency of accidents is i

available for fuel cycle and other radioactive material licensees than is available for nuclear power plants because there are so many more fuel cycle and other radioactive material licensees than nuclear power plants.

Currently the NRC regulates about 9,000 non-reactor licensees.

In addition, Agreement l

States regulate roughly another 12,000 non-reactor licensees.

A large number l

of these licensees have operated for many years, and the combined experience l

l 6

i i

of these licensees approaches half a million licensee years.

By contrast, there are only about 110 U.S. nuclear power plants operating with about 1,000 plant-years of combined operating experience.

Thus more experience exists for fuel cycle and other radioactive material licensees than exists-for nuclear power plants.

l Operating experience may be more relevant for these licensees than for nuclear power plants because of the nature of the accident driving force.

In nuclear power plants the driving force is the enormous amount of heat in the reactor.

The available energy is so large that some unique occurrences are conceivable, such as molten cores, large-scale metal-water reactions, and rupturing the containment by overpressurization.

Because these events have never happened they can only be studied theoretically. The dominant driving forces for accidents at non-reactor licensees are common industrial accidents--

fires, chemical explosions, leaks, and the like.

A great deal of industrial accident experience can be drawn upon in analyzing these potential accidents.

Much information on the accident history of fuel cycle and other radio-active material licensees is available.

NRC regulations require the reporting of all significant events.

All licensees must notify NRC of (1) the overexposure of any individual to radiation [10 CFR S20.403 and $20.405], (2) the airborne release of large quantities of radioactive material [10 CFR S20.403 and S20.405], (3) the loss of one day or more of the operation of any facility

[10 CFR 620.403], (4) damage to property in excess of $2000 [10 CFR S20.403],

(5) the loss or theft of licensed material [10 CFR S20.402), (6) excessive radiation levels or contamination on packages received [10 CFR S20.205), and (7) major defects in equipment or noncompliance with regulations that have major safety significance [10 CFR 621.21].

In addition, there are other reporting requirements in NRC regulations that apply to specific classes of licensees.

The reports that licensees have filed provide extensive information for evaluating the history of accidents in this part of the nuclear industry.

Since January 1975, the NRC has carefully and systematically published reports describing accidents of significance, "Report to Congress on Abnormal Occurrences," NUREG-0090.

Accidents in the fuel cycle and at byproduct mate-rial facilities are included for NRC licensees and Agreement State licensees.

All these reports for the period from January, 1975, to December, 1986, were reviewed for this Regulatory Analysis.

7

Also, a comprehensive file of over 5,000 events from the period of 1950 through 1978 was compiled at Argonne National Laboratory.

The file includes primarily events from NRC licensees (formerly AEC licensees) and government-owned laboratories run by DOE (formerly ERDA and AEC), and some reports on accidents from Agreement State licensees and facilities in foreign countries.

The file includes events from nuclear power plants, the nuclear fuel cycle, and other radioactive material usage.

A brief summary of 1634 events in the commercial nuclear fuel cycle was published in 1981.* The Argonne file also includes some events from 1979, but is not complete for that year.

In addition, other sources were searched for this analysis, such as NRC's annual reports on radiation exposures, NRC's preliminary notification of unusual event reports, the memory of NRC staff members, and accounts published in the open literature.

Using all these sources of information this analysis should include most significant accidents for the years from 1950 through 1986. Although some events may have been omitted, it is believed that all relevant events in the United States that caused a significant release of radioactive material outside a restricted area have been included.

2.1.2 Accident Source Terms Many plausible accident scenarios were considered for various types of facilities.

The NRC considers in Safety Evaluation Reports a number of possible accidents and their effects on public health and safety before issuing licenses for fuel cycle facilities.

The NRC requires applicants to evaluate possible accidents.

Additionally, the NRC performs its own analyses of several severe accidents to determine whether there is adequate protection of public health and safety.

The NRC's analyses are then issued when the license is issued.

This regulatory analysis makes use of those NRC staff analyses in developing accident source terms.

  • Deborah J. Bodeau et al., Data Base for Radiation Events in the Commercial Nuclear Fuel Cycle, 1950-1978 Argonne National Laboratory, MREG/CR-2429, ANL/ES-123, March 1982.

8

The significant accidents were determined to be UFs releases, fires, and criticality accidents.

Aside from the special cases of UFs releases and cri-ticalities, the release fractions for fires were considered to be larger than the release fractions for other types of accidents.

Thus, release fractions for fires, as described in Section 2.3.1.2, are used to determine the need for emergency preparedness.

2.1.3 Calculations of Doses Doses from airborne releases were calculated by assuming release fractions for radioactive materials, assuming a atmospheric dispersion model, and calcu-lating doses from three pathways-inhalation, cloud-shine, and ground-shine from particulates deposited on the ground.

In general, the highest doses come from inhalation.

Two kinds of doses were calculated:

effective dose equivalent and child's thyroid dose.* The effective dose equivalent is the sum of the 50 year dose equivalent commitment to each body organ multiplied by a weighting factor for each organ as given in ICRP Publication 26 and, for the skin, ICRP Publica-tion 28.**

For the inhalation pathway, dose conversion factors from ICRP Publication 30*** were used.

Thyroid dose is the dose equivalent delivered to the thyroid by inhaled radioiodines.

The child's thyroid dose is calculated by multiplying the value calculated for an adult by two.

For the two external dose pathways dose conversion factors from Kocher****

were used.

An 8-hour ground exposure time and a 0.7 shielding factori (30%

  • 0 avid E. Bennett et al., Preliminary Screening c Fuel Cycle and Byproduct S f $kN b b bb9*k Yi b

0'

    • htatementfromthe1978StockkolmMeetingoftheICRP, Publication 28, E

International Commission on Radiological Protection, Pergamon Press, Oxford, 1978.

      • Limits for Intakes of Radionuclides by Workers, Publication 30, International Commission on Radiological Protection, Pergamon Press, Oxford, 1979 and 1980.
        • D. C. Kocher, "Dose-Rate Conversion Factors for External Exposure to Photon and Electron Radiation from Radionuclides Occurring in Routine Releases from Nuclear Fuel Cycle Facilities," ORNL, NUREG/CR-1918,1981. Also D. C.

Kocher, "Dose-Rate Conversion Factors for External Exposure to Photons and Electrons, "Health Physics, g, 665, 1983, t"Reactor Safety Study," NRC Report WASH-1400, Appendix VI, page 11-23, 1975.

9

reduction) for a not perfectly flat surface were used to calculate the external exposure from radionuclides deposited on the ground.

The basis for the 8-hour exposure to ground shine is that even if there is no pre-existing offsite emergency preparedness it should be possible to locate areas with high dose rates due to ground shine (greater than 100 mR/hr) and move people out within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />. The contaminated areas from which people would need to relocate would be small and generally near the site.

The atmospheric dispersion model is a standard Gaussian plume model.

Doses were calculated for two sets of meteorological conditions:

stability class F with 1 m/s wind speed and stability class D with 4.5 m/s wind speed.

The F, 1 m/s assumptions are those traditionally used by NRC in hazard evaluations and represent very adverse weather conditions.

The D, 4.5 m/s assumptions are those traditionally used by 00T in calculating evacuation distances for accidents involving toxic chemicalst and represent more typical weather.

00T considers evacuation distances based on D, 4.5 m/s adequate to protect public health and safety as demonstrated by experience with toxic chemical releases.

The NRC's proposed rule associated with this analysis bases the need for emergency preparedness on the traditional NRC assumpti'

' r, 1 m/s.

The doses calcu-lated using the DOT assumptions of D, 4.5 ce cluded for perspective to show doses that would be expected under roi

.,sical or realistic conditions.

The intercept fraction for inhalation of 10 6 is consicered to be about the maximum value likely to be inhaled in an accident.* Using F, 1 m/s meteor-ology and the assumptions described below, 10 E corresponds to a distance of 100 meters for the entire duration of the accident.

Limiting the intake to 10 6 in effect means that a person on the plume centerline in dense smoke closer than i

100 meters from the release point will move out of the smoke before the release j

ends.

Thus, the distance at which doses were calculated was taken to be 100 m from the release point in our mathematical model.

This distance results in an intercept fraction of 0.89 x 10 6 for radioactive materials that deposit on the t"Hazardous Materials-Emergency Response Guidebooks," Materials Transportation Bureau, U.S. Department of Transportation, 00T Publication DOT-P5800.2, 1980.

46 Federal Regi!.ter 29712, 1981; "Criteria for Selection of Fuel Cycle and Kajor Materials Licensees Needing Radiological Contingency Plans," NUREG-0767, 1981; and Allen Brodsky, "Resuspension Factors and Probabilities of Intake of Material in Process (or Is 10 6 a Magic Number in Health Physics?)"

Health Physics, 39, 992, 1980.

10

ground.

In other words a person on the plume centerline is assumed to inhale at most about one one-millionth of the material released.

Doses were calculated for a person standing in an open field in the down-wind direction on the plume centerline breathing at a rate of 2.66 x 10 4 3

m /s.

Atmospheric stability class F and wind speed of 1 m/s were assumed.

Doses to people in buildings would be smaller than the doses given in this analysis because buildings provide shielding and some respiratory protection.

Doses to people standing outside in urban and suburban areas or wooded areas would be less than those given here because obstacles to wind flow would cause the plume to broaden.

Doses were calculated using a slightly modified version of the CRAC2 computer code.* The CRAC2 code has been used extensively by the NRC for calcu-lations of doses that could result from nuclear power plant accidents.

The key input parameters for the CRAC2 calculations are building size, release duration, release height, dose conversion factors for each radio-nuclide, radioactive halflife of each radionuclide, and deposition velocity for particulates.

Building size determines the building wake factor or the initial plume dimension.

In most cases the building size was assumed to be 25 m wide by 10 m high.

For buoyant releases no building wake factor was used.

At close in distances the builoing wake effect from a 250 m2 building significantly reduces the concentrations of airborne materials from a release.

At distances of 1000 m, the building wake factor is relatively unimportant.

The release duration determines the amount of plume meander.

Plume meander was not included at 100 m because the plume is considered to be still in the building wake.

Release height determines plume height and thus affects ground level concentrations.

Greater release heights cause lower ground level air concentrations.

In this regulatory analysis, the release height was assumed to be ground level except that buyancy was considered for UFs release.

  • L.T. Ritchie et al., "CRAC2 Model Description," Sandia National Laboratories,

l NUREG/CR-2552, SAND 82-0342, April 1984.

l l

11 l

The CRAC2 code accounts for the radioactive decay of materials in transit.

In most cases this correction is-negligible.

However, ' Kr-89 with a 3-minute

-half-life dominates the external dose from a criticality accident, so that in this case the decay correction is significant.

The CRAC2 code does not calculate radioactive decay while a material is held up in a building before release.

A separate correction factor was devel-oped to account for radioactive decay before release to the atmosphere. This factor was used to reduce the quantities of short-lived radionuclides for cri-ticality accidents.

In calculating exterr:al dose due to clouds, the CRAC2 code performs the calculation for a finite-size cload rather than an infinite-size cloud.

The difference between the two can be substantial at distances as close as 100 m for stable atmospheric conditions.

For example, failure to correct for this factor at 100 m from a point release (i.e., no building wake) during class F stability would cause external doses to be everestimated by a factor of almost 40.

How-ever, the finite cloud correction factor is much smaller when building wake factors are used.

The results of the atmospheric dispersion calculations for inhalation are shown in Figure 1 for both F, 1 m/s and 0, 4.5 m/s assumptions.

Figure 1, giving x/Q in s/m, can be used to calculate inhalation dose D in rems due to 3

a released quantity Q in uCi by usirg the equation:

0 = DCF x B x X/Q x Q where:

DCF = dose conversion factor, rems /uCi inhaled, as given in Table 13 and 3

B = breathing rate, which is 2.66 x 10 4 m /s.

The doses due to ground-shine and cloud-shine should be added to the inhalation dose to obtain a person's total dose.

As a practical matter, however ground-shine and cloud-shine doses will be considerably smaller than the inhala-tion dose except for a few radionuclides (xenon, krypton, Na-24, Mn-56, Tc-99m, and Ru-105).

12

4,

=;

-g 3 :

E=

=

~

2 ASSUMPTIONS:

l Building size: 10m x 25m.

Refersse at ground level or 20m for buoyant releases.

30-minute release duration 10'3 1 cm/sec depoaltion velocity

\\

g 8

7 6

5 s

s L

Y 3

  • Y E

b

\\ N,0 2

8

=

~

t l

E 10 4

8 1

'I s

3

\\

f

~FD/s N

g

  • l8nt,

^ (

Q 5

\\

/

k/d/n I E o

6 -

y 5

4 I

\\

/

/

\\

\\

E I

I E

T 2

O t

0y,Mr 4g%

  • n

~~

4

/

l

'ob o0 Ui/q;4 Voy,n 1

cy I

II 100 200 400 600 800 1000 1200 1400 Olstance, Meters 1

Figure 1.

Atmospheric dispersion versus distance.

1 13 i

1 2.1.4-Protective Action Guides Protective action guides are expressed in terms of projected doses to individuals in the population which warrant taking protective action.

The EPA has published draft guides for taking protective action in order to avoid expo-sure to radiation as the result of an accident at a nuclear power plant.* The EPA recommends that protective actions should be considered by responsible officials if projected whole body doses are in the range of 1 to 5 rems.

The lower dose of 1 rem is a level which "should be used if there are no major local constraints in providing protection at that level, especially to sensi-tive populations" (children and pregnant women).

The EPA believes that "in no case should the higher value (5 rems) be exceeded in determining the need for protective action." Put another way, protective actions may be considered optional at 1 rem, to be taken if readily feasible, but are highly recommended at 5 rems if at all feasible.

Note that the 1-rem and 5-rem doses are projected doses that might occur after the protective action decision.

Doses received prior to the decisionmaking and during the protective action implementation time are not considered in the decisionmaking.

Only dose savings as a result of taking a protective action are to be used in determining whether such protec-tive action is warranted.

For radioactive materials that deliver dose to the body nonuniformly after they are inhaled, the resulting effective dose equivalent is compared to the EPA's protective action guides.

The effective dose equivalent, as defined in the previous section, is the sum of the external gamma dose equivalent, the dose equivalent delivered to each body organ multiplied by a weighting factor for the organ from ICRP Publication 26, and the external beta dose equivalent delivered to the skin multiplied by the weighting factor from ICRP Publication 28.

The factors used to convert intake of radionuclides to an effective dose equiva-lent are taken from ICRP Publication 30.

The Commission's policy on the use of the EPA's protective action guides to establish planning zones for nuclear power plants is stated in NUREG-0654.**

  • EPA-520/1-75-001, "Manual of Protective Action Guides and Protective Actions for Nuclear Incidents," Draft Revision of June, 1980.
    • NUREG-0654/ FEMA-REP-1, Revision 1, "Criteria for Preparation and Evaluation of Radiological Emergency Response Plans and Preparedness in Support of Nuclear Power Plants," joint NRC/ FEMA Report, 1980, page 12.

14 i

"The size (about 10 miles radius) of the plume exposure emergency planning zone was based primarily on the following considerstions:

a.

projected doses from the traditional design basis accidents would not exceed protective action guide levels outside the zone; b.

projected doses from most core melt sequences would not exceed protective action guide levels outside the zone; for the worst core melt sequences, immediate life threatening doses c.

would generally not occur outside the zone; d.

detailed planning within 10 miles would provide a substantial base for expansion of response efforts in the event that this proved necessary."

For nuclear power plants the traditional design basis accident assumes the containment does not fail.

In other words, one major barrier to a radioactive release remains.

Failure of all engineered safeguards is evaluated with respect to life threatening doses rather than protective action guides in the 1 to 5 rem range.

In addition, emergency preparedness does not guarantee there will be no loss of life for the worst case imaginable.

A later report elaborates on the Commission policy.

NUREG-0771* states:

"For the small releases, the lower ranges of the protective action guides (PAG) would be used as the appropriate measure to base plan-ning.

For somewhat larger releases, the criteria shift to the upper ranges of the PAG and levels of exposures which would still be less than medically detectable.

For intermediate level releases early injuries would be used as the measure to base the EPZ distance judg-ment on.

Finally, for the most severe accidants, early fatalities become the immediate concern and therefore the measure to base the criteria upon..."

s

  • NUREG-0771, "Regulatory Impact of Nuclear Reactor Accident Source Term Assumptions," for comment, June, 1981, page 35.

15

lor application to fuel cycle and byproduct material licensees, the lower end of the range (1 rem) of the EPA's protective action guides is used in con-junction with calculations of releases and offsite radiation doses due to severe accidents, such as a major facility fire, to establish the need for a plan.

Thus the lower range of the protective action guides is used to determine the need for offsite emergency preparedness.

The actual assumptions that were used for each facility type are discussed in separate sections in the remainder of this report.

The reasons for selecting the assumptions are also discussed.

2.1.5 A Discussion of the Conservatism in the Calculatio_ns The Commission's policy is that, "Emergency planning should be based on realistic assumptions regarding severe accident'."*

s The doses calculated in this Regulatory Analysis have been conservatively calculated.

Doses to people near a plant experiencing a severe accident are likely to be far below the doses in this analysis, probably by an order of mag-nitude or more, except in very unusual circumstances.

The accident history of such facilities in the U.S. is that there is no known case of a member of the public receiving even as much as 1% of the doses calculated in this analysis as the result of an accidental airborne release from any nonreactor facility.**

A number of factors which cause this analysis to be conservative are discussed below.

  • "U.S. Nuclear Regulatory Commission Policy and Planning Guidance - 1985,"

U.S. Nuclear Regulatory Commission, NUREG-0885, Issue 4, 1985, page 6.

    • For a 1962 release of high-enriched UFs from the NFS plant, Erwin, Tennessee, a plume centerline dose equal to 4% of the 1-rem effective dose equivalent guide was calculated using conservative assumptions (no deposition, open field diffusion parameters, no wind direction shift, etc.) However, the report stated, "No specific information regarding the presence of individuals during the releases was available." Because no one is known to have stood on or near the plume centerline, we can say there are no known exposures exceeding 1% of 1-rem.

The dose calculations are contained in an unpublished report, "Dose Assessment of Airborne Releases from NFS-Erwin Fuel Facility -

1972-1981,"

U.S. Nuclear Regulatory Commission, Region II, Atlanta, Georgia, May, 1983.

16 l

l 2.1.5.1 Conservative Factors 1.

-Entire possession limit assumed to be. involved.

In calculating the quantities of radioactive material for which an emergency plan would be needed, this analysis generally assumed that the licensee's entire or nearly entire possession limit would be involved.

In actuality, most licensees at any particular time possess much less material than they are legally authorized to possess.

In many cases the possessed material will be located at different locations and will not all be subject to release during a particular accident.

For example, the National Institutes of Health is authorized to use and store licensed material in more than 1,000 different laboratories.

2.

Worst-case release fractions.

The release fractions due to fires (the accidents with highest potential release) were determined from experiments designed to maximize releases.

In such experiments a finely powdered material is typically placed on too of a large amount of combustible material.

Having the entire licensed inventory unenclosed on top of a large quantity of combusti-ble material would be most unusual.

Radioactive materials are usually within shielded "pigs" and kept in metal safes or well shielded hot cells or glove boxes.

Amounts of combustible materials present are generally kept low.

3.

No credit for engineered safeguards or response efforts.

No credit is generally given for design or operating features that could reduce releases.

No credit is given for sprinkler systems designed to stop fires.

Generally, no credit is given for filter systems during a fire.

No credit is given for fire fighting efforts to stop the fire before it reaches radioactive materials.

Little or no credit is given for holding up the release of the material by means of deposition or plateout.

For UF releases outdoors, no credit is given for 8

knocking the uranium out of the air using fire hoses.

4.

The exposed individual makes no response.

In the case of fires and UF8 releases, the dose is calculated for a person who stands directly on the plume centerline for 30 minutes.

Such a person would be standing in dense smoke or irritating acid fumes.

Realistically, people can be expected to move from such positions to avoid smoke inhalation.

People close in would only have to move about 20 meters to get completely out of the plume.

5.

No plume-rise for smoke.

Even where the assumed accident is a large fire no credit is given for plume rise due to buoyancy in calculating the quantities of radioactive material for which an emergency plan would be needed.

i The smoke is assumed to be released at and remain at ground level.

17

6.

Conservative dosimetry.

The material is assumed to have the solubil-ity which would result in the highest dose per curie inhaled.

Particulates are generally assumed to have a size of 1 micron making them highly respirable and transportable.

7.

p erse meteorology.

Quantities of radioactive material for which an emergency plan would be needed were calculated for atmospheric stability class F with a 1 m/s windspeed.

These conditions result' in minimal dilution and high plume centerline doses, but also very narrow plumes.

It is probable that the actual weather would cause lower doses.

For example, doses during a moderately sunny day with average winds would be a factor of 50 times smaller j

than the doses calculated for the analysis.

j 8.

Open-field site assumed.

A rural open-field site is assumed.

Greater f

i atmospheric dispersion and thus lower doses would occur at an urban or suburban site.

Buildings, trees, or other obstacles in the plume path would broaden the plume.

Heat sources would increase the plume height.

9.

No wind shifts.

Doses are calculated only on the plume centerline.

It is assumed that no wind direction shifts occur during the accident.

In addi-tion, correction factors for plume meander are conservative; the factors were selected to envelope the experimental data.

Normally greater plume meander would be expected.

10.

8-hour criticality.

The source term assumes a pulsating criticality with a total of 48 bursts occurring over 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> (see Section 2.2.5.2).

This is a highly conservative source term.

11.

There may be no one standing on the plume centerline.

The doses are calculated for single point, and they fall off rapidly as one moves away from the point.

Even with no protective actions, the highest dose anyone would receive is likely to be well below the assumed dose.

2.1.5.2 Nonconservative Factors On the other hand there are certain assumptions in the dose calculations that may be nonconservetive in certain instances.

These factors are discussed below:

1.

Adult doses.

Doses are calculated for adults rather than children (except for radioiodine doses which are calculated for children).

This is because dose conversion factors for children using modern dosimeter models are generally not available.

For some inhaled radionuclides a child standing in 18

the plume may perhaps receive a dose 2 or 3 times higher than an adult >tanding at the same location.

2.

Breathing rates.

The. breathing rate used in the dose calculations l

(2.66 x 10 4 3

m /s) represents an average breathing rate.

Breathing rates for above average activity would be higher.

3.

Site-specific factors not considered.

The table of quantities of material for which emergency planning should be considered was based on assump-tions (for example building wake) that would usually be conservative, but may not be conservative for all instances.

For example, the building wake factor for a particular building could be-less than assumed although it would generally be larger.

This should be a minor factor.

Any increases in dose due to such factors would not be significant in size by comparison with the sizes of the conservatisms discussed above.

2.2 Fuel Cycle Facilities 2.2.1 Uranium Mining Uranium mining is not considered in this report because the NRC has no regulatory jurisdiction over uranium mining.

Uranium mining is regulated instead by the Mine Safety and Health Administration, the Environmental Protec-tion Agency, and the individual states.

2.2.2 Uranium Milling Uranium mills extract uranium from ore that typically averages about 1 part per 1000 uranium.

The mills produce concentrated uranium compounds, which are shipped out in 55 gallon drums, and waste "tailings," which contain radium-226 and thorium-230 not removed from the ore by the mill processes.

In late 1984 there were about 10 full-scale uranium mills operating in the U.S.

In addition, there are smaller facilities that perform some of the processes found in milling.

Roughly half the mills are licensed by the NRC.

The others are licensed by Agreement States.

In addition, this section considers "in situ" solution uranium mining, in which a solution that has leached uranium from the ground is pumped up and uranium extracted from the solution.

19

~

2.2.2.1 Accident History Uranium mills have experienced major fires and accidental releases from tailings ponds due to dam failures or tailings line breaks.

Uranium mills have a potential for large fires because large quantities of kerosene are used as a solvent to extract uranium in one mill process.

The 1

kerosene contains dissolved uranium and is contained in large open tanks.

Two large fires in solvent extraction circuits have occurred.

Table 1. lists fires known to have occurred.

It is notable that the fires that have occurred have caused little release of radioactive material even though two of the fires were very intense.

Aside from fires, the other notable type of accident at uranium mills has been tailings pond releases.

There have been at least 16 instances where uranium mill tailings solids and liquids were released from tailings impound-ments.

Table 2 describes these releases.

In no instances were there radiation dose rates that would cause doses to the public in the range of the EPA's protective action guides.

In no case was drinking water contaminated above NRC limits (Appendix B of 10 CFR Part 20).

2.2.2.2 Accident Source Terms Potential releases of radioactive materials and potential doses that could result from accidents at uranium mills are shown in Table 3.

The largest potential releases were determined to occur as a result of:

(1) fires, (2) undetected failures of air cleaning systems, (3) tailing pond releases, and (4) tornadoes. Some reported calculations of the quantities released and projected offsite doses are shown in Table 3.

These calculations show that the largest offsite radiation doses would be due to a fire in the solvent extraction circuit or an undetected failure of the air cleaning system servicing the yellowcake drying area.

However, the l

undetected failure of the air cleaning system servicing the yellowcake drying area does not provide a basis for actions to protect the public.

As long as s

the failure remains undetected no emergency plan can be activated and no protec-tive actions can be taken.

As soon as the failure is detected, the release can be stopped by turning off the ventilation blowers.

Airborne concentrations I

20

L Table 1.. Fires in Uranium Mills through 1986.

Fire Date Mill Description Offsite release 3-19-59 Vanadium Corp.,

Fire in yellowcake None detected

.of America, dryer Durango, C0 6-25-65 American Metal, Fire in ore None detected

-Grand Junction, dryer for 3-5 min.

CO

$2600 damage 2-68 Western Nuclear, Workers started a None detected Jeffery City, WY fire to thaw a frozen ore dryer.

Fire ignited propane from a leaking tank.

11-10-68 Petrotomics Co.,

Solvent extraction None detected Shirley Basin, WY circuit.

$300,000 damage 12-25-68 Atlas Corp.,

Solvent extraction None detected Moab, UT circuit.

Cause unknown.

$1,000,000 damage 10-23-80 Minerals Exploration, Major fire burned None.

Radioactive Sweetwater, WY in mill before it material was started operation not yet being processed.

1-2-81 Atlas Corp.,

Fire in yellowcake None detected Moab, UT scrubber stack for 15 min v

21

. ~,,.

L Table 2.. Uranium Mill' Tailings Releases,~ 1959-1986 Date Mill Type.of Incident Release-8-19-59 Union Carbide Tailings dam washed ~ 15,000 T sands lost to Green River, UT~

out-river in flash floods; no increase in dissolving Ra was noted in river.

8-22-60 Kerr-McGee Raffinate pond 240,000 gal of raffinate Shiprock, NM dike failure releases into river

~ 50 x 10.s pCi/mi Ra-226; river samples collected several days after talease r

showed no increase ~in Ra-226 background.

12-6-61 Union Carbide Tailings dike

~ 500 T solids released Maybe11, C0 failure from tailings area; 200 T reached unrestricted area; no liquid reached any stream.

[

6-11-62 Mines Develop-Tailings dike 200 T solids washed into ment, Inc.

failure creek and some carried Edgemont, SD 25 mi into reservoir.

8-17-62. Atlas-Zinc Slurry pipeline Est. 280 T solids + 240 T Minerals rupture liquids' released from Mexican Hat, UT broken tailings discharge line into draw 1.5 mi from I

river.

6-16-63 Utah Construction Precautionary Material released by 2 ft Riverton, WY release drainage cut made to prevent cresting due to heavy rains; i

material released below 10 CFR Part 20 values.

11-17-66 VCA Raffinate line Est. 16,000 gals of liquid Shiprock, NM failure lost because of break in 1

raffinate line; material spread over 1/4 acre; break 4

occurred 1 mi from river with some small amount reaching river.

i

)

2-6-67 Atlas Corp.

Line failure 440,000 gal lost; average l

Moab, UT Ra-226 concentration was was 5.5 x 10 s mci /ml.

3 i

i i

22

.a

i' h

Table 2.

(continued)

Date Mill Type of Incident Release 7-2-67 Climax Uranium Tailings dit Dike failure released Grand Junction, failure 1-10 acre-ft of waste C0 liquid into Colorado River; no indication that Ra conc.

in river exceeded 10 CFR Part 20 limits.

11-23-68 Atlas Corp.

Slurry pipeline 35,000 gal of tailings Moab, UT rupture slurry lost; flowed 1/2 mile to Colorado River; most solids settled out in drywash.

2-16-71 Petrotomics Secondary tailings 2,000 gal of liquid lost Shirley Basin, dike failure to unrestricted area; spill WY froze in place.

3-23-71 Western Nuclear Tailings line and Break in slurry line caused Jeffrey City, dike failure a dike failure allowing sand WY tails to flow into natural basin adjacent to tailings site on licensee's property.

2-5-77 United Nuclear-Slurry pipeline 50,000 tons of solids and Homestake rupture slimes and somewhere between Partners 2 million and 8 million gal Grants, NM of liquid.

All material was confined to company property.

4-77 Western Nuclear, Failure of tailings ~ 2 million gal of liquid Inc.

pond en,bankment tailings and 55 yd3 of Jeffrey City, WY solids were released.

No inaterial was released to unrestricted areas.

9-26-77 United Nuclear Release from Approximately 1 ton of 9-27-77 Church Rock, NM tailings slurry solids and 900 gal of liquid line entered the waterco"rse.

7-16-79 United Nuclear Tailings dike 100,000,000 gallons of tail-Church Rock, NM failure ings solution and 1,100 tons of tailings solids.

Most of the solids were deposited near the impoundment, but much solution reached a river.

Reference:

Regulatory Guide 3.11.1, "Operational Inspection and Surveillance of Embankment Retention Systems, for Uranium Mill Tailings."

23

W n

Table 3.

Accident Source Terms and Cases From Uranium Mill Accidents Failure of the Air Fire in Solvent.

Cleaning System Serving the.

'{

Tornado Tailing Pond Release Extraction Circuit

.Yellowcate Drying Area R2ference Release Oose Release Dose Release

-Dose Release Dose-

< 1.36 ren*

11 kg insoluble' 86 aren' GEIS 11,400 kg U total

< 2.2 x 10 7 ren 1400 tons solid Small. Cleanup

< 13 kg U

~to bone at u oxides to lung-

< 11,400 kg U to lungs at 500m 14,000,000 gal.

assumed

< 0.65 kg thorium

  • 500 m over 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> at.2000 m.

respirable liquids Sand Rock 4550 kg U total

< 1.1 x 10 7 rem Same as GEIS

< 1.1 kg U 10 7 ren 12 kg insoluble 10 2 ren.

to bone U oxides over to lung at' DES

< 4550 kg U at 4000m at 8000 a 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> 8000 m respirable (max. dose)

(nearest (nearest residence) residence)

This 1.3 kg U 0.01 to O.1 rem EDE Report Rvferences "Final Generic Environmental Impact Statement on Uranium Milling," NUREG-0706, Volume 1, pp 7-1 to 7-20, September, 1980.

GEIS:

"Draft Environmental Statement Related to the Operation of Sand Rocks Mill Project," NUREG-0889, pages 5-1 to -

Sand Rock DES:

5-12 March, 1982.

The solvent extraction was assumed to contain 5% as much Th-230 as uranium by weight..The value should

  • The dose value from GEIS is in error.

have been 5% by activity. This error causes the dose to be overestimated by a factor of about 50,000 times.

of radioactive material promptly drop to very low levels.

External exposure is negligible because uranium is a very weak gamma emitter.

Tornadoes could release a larger amount of radioactive material.

However, they spread the material so' greatly that resulting doses are very small,* as shown in Table 3.

Because the doses that would be caused by tornadoes are so much smaller than doses from other accidents, releases and doses due to torna-does are not discussed further in this analyses.

Tallings pond failures also release a large quantity of material.

However, the dose rates are less than 0.1 mR/hr and radioactive material concentrations are so 1cw that prompt emergency action is not needed to precent anyone's dose from exceeding the EPA's protective action guides.

Thus we conclude that a fire in the solvent extraction circuit is the accident of greatest significance for emergency preparedness.

We assume the release from the building is 1.3 kg of uranium.

The 1.3 kg release is based on 0.1% of the material in process becoming airborne and escaping from the building.

Experiments on releases of uranium in a kerosene fire showed average releases of 0.025% when the residue is not heated with a propane torch after dryness occurs.** Due to licensing policy requiring automatic fire detection and supression systems *** (such as automatic sprinklers, foam, or halon systems) significant heating beyond dryness would not be expected.

Other experiments showed similarly low releases.t The uranium would be in insoluble form (solubility class Y) because a large kerosene fire would produce temperatures exceeding 400 C, the temperature at which the uranium should form insoluble oxides.****

The uranium may be class Y if the fire completely oxidizes the

  • NUREG-0706, Volume 1, "Final Generic Environmental Impact Statement on Uranium Milling," September, 1980, p. 7-4.
    • Jofu Mishima and Lyle Schendiman, "Interim Report:

The Fractional Airborne Release of Dissolved Radioactive Materials During the Combustion of 30 Percent Normal Tributyl Phosphate in a Kerosene-Type Diluent," BNWL-B-274, Pacific Northwest Laboratory, 1973.

      • Regulatory Guide 8.31, "Information Relevant to Ensuring that Occupational Radiation Exposures at Uranium Mills Will Be as Low as Is Reasonably Achievable," Section C.3.4.

tD. Whitney Tharin, Jr., "Burning of Radioactive Process Solvent," Savannah River Laboratory Report OP-942, Aiken, South Carolina, 1965.

        • R. C. Merritt, The Extractive Metallurgy of Uranium, Colorado School of Mines Research Institute, pp. 252-4, 1971.

25

soluble class D uranium in the solvent extraction tanks and converts it to insoluble uranium.

This source term of 1.3 kg of uranium is also considered to be suitable for "in-situ" solution mining.

Some "in situ" mining processes use solvent extraction processes similar to those in uranium mills. More severe = accidents than described above were not identified for "in-situ" mining.

2.2.2.3 Calculations of Doses A 1.3 kg release of natural uranium due to a fire at an uranium mill could result in a potential dose of 0.1 rem effective dose equivalent during adverse weather (F, 1 m/s) or 0.01 rem during typical weather (0, 4.5 m/s).

Assumptions were that the building size was 10 m high by 25 m wide, the release height was ground level, and the release duration was 30 minutes.

The factors for deter-mining effective dose equivalent from ICRP Publication 30 for a particle size of 1 micron AMAD and class Y solubility are:

1.31 x 108 rem /Ci for U-234, 1.21 x 10s res/Ci for U-235, and 1.17 x 108 rem /Ci for U-238.

If I curie of uranium is composed of U-234, U-235, and U-238 in their naturally occurring proportions, the dose conversion factor is 1.24 x 108 rem /Ci.

The calculated dose from this accident is small (0.1 rem or less) because of the very low specific activity of the uranium and the low volatility of the I

uranium compounds, which causes a low release fraction.

Low release fractions are the reason why no offsite ground contamination was ever detected due to the fires listed in Table 1.

2.2.2.4 Implications for Emergency Preparedness On the basis of the very low doses calculated, the staff concludes that there is no need for offsite emergency protective actions on the part of the public at uranium mills or for "in-situ" mining.

The staff concludes that no credible accident would justify emergency protective actions because radiation doses to the public offsite from an acci-dent would be below the EPA's protective action guides.

Also, the quantity of uranium inhaled is below the quantity where chemical toxicity effects are 26

observed.*

Inua, neither radiation doses-nor chemical toxicity from licensed materials is a concern with respect to the need for prompt protective actions.

In the event of such a fire, the licensee would be required by existing NRC regulations to take certain actions.

Among these, the licensee would be required by S20.201(b) to conduct surveys (offsite if appropriate) to determine whether the hRC's limits on radioactivity in effluents to unrestricted areas in S20.106 were exceeded.

A major fire would also require immediate notifica-tion of HRC by telephone and telegraph (S20.403).

If appropriate, the NRC could elect to immediately send an inspector to the site to make any necessary radiation measurements or evaluate the situation.

I With respect to tailing dam failures, rapid emergency response is not needed to avoid doses exceeding protection action guides because dose rates at a spill site are very low.

An appropriate response is to monitor drinking water, especially for radium-226, to be sure that drinking water standards are met.

Gamma ray monitoring of the ground is also appropriate to determine where the tailings have been deposited.

However, ground contamination presents little immediate hazard to the public because the gamma dose rates are low.

Gamma dose rates in contact with tailings should be less than 0.1 mR/hr.

Since the EPA's protective action guides would not be exceeded, a rapid emergency response is not needed.

A clean-up of the spilled tailings would be expected, but this could be done effectively without preexisting emergency preparedness.

2.2.3 UFn Conversion Plants Conversion plants convert yellowcake shipped from uranium mills into uranium hexafluoride (UFs).

Heated liquid UFs is put into 10-ton or 14-ton cylinders.

The cylinders are cooled for several days until the UF8 solidifies.

Eventually, the filled cylinders are shipped to enrichment plants to enrich 4

the uranium in U-235.

There are two NRC-licensed convere un piants:

Kerr-McGee in Oklahoma and Allied Chemical in Illinois.

The uranium is handled in many different chemical forms in UFs conversion plants, but the UFs itself is the only chemical form of uranium that is readily dispersible.

For example, the dispersibility of yellowcake is essentially the

(

  • R. A. Just and V. S. Emler, "Generic Report of Health Effects for the U.S.

Gaseous Diffusion Plants," DOE Report K/0 5050,Section VIII, Part 1, page 6, 1984.

27

a same as that of yellowcake at uranium mills.

Accidents involving yellowcake were previously discussed and found not to require offsite emergency preparedness.

The release of UFs in significant quantity is possible because UFs is o

volatile above room temperature.

The UFs released will react with water in i

the air as follows:

i UFs + 2H O = U0 F2 2 + 4HF + 52.2 kcal/ mole

  • 2 forms a particulate, very soluble in the lungs, which will be carried The U0 F22 away by wind and will settle onto the ground.

The HF is a corrosive acid vapor that can severely harm the lungs if sufficiently concentrated.

The release of 1 kg of UFs combining with 0.1 kg of water results in release of 0.88 kg of (which contains-0.68 kg of uranium) and 0.23 kg of HF.

UO F22 2.2.3.1 Accident History Table 4 lists significant releases of UFs that have occurred from all types of facilities, not just conversion plants.

There have been many releases of UFe.

The releases have caused at least three prompt fatalities and several injuries.

The significant UFs releases have consistently been with UFs heated above its melting point (65 C).

The releases have generally been fairly rapid--lasting from less than a minute to an hour.

The plumes, where they are highly concen-trated, have been visible and immediately irritating to the lungs.

The escape of UFs can be diminished greatly if the leak can be sprayed with water.

Inhalation of uranium due to a UFs release can be verified by measurements The of uranium concentrations in urine taken within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> of the exposure.

uranium from UFs has a biological half-life for expulsion via the urine of 4 to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.** Workers exposed to high concentrations have suffered edema of the lungs, presumably from exposure to HF, and kidney damage due to heavy metal

  • Minton Kelly, Oak Ridge National Laboratory, Sept. 1983.
    • H.W. Babcock and R. C. Heatherton, "Bioassay Aspects of a UFs Fume Release,"

Proceedings of the 12th Annual Bio-Assay and Analytical Chemistry Meeting, AEC Report CONF-661018, 1966, pp 147-159.

28

l Table 4.

Accidents Involving UFs' Releases through 1986 Type of Quantity of Date Facility facility UFs released Cause and consequence 9-2-44*

Philadelphia R & D for 200 kg Rupture or explosion Naval-Yard-thermal accompanied of Iarge tank.

Two diffusion with live workers killed.

Three steam other workers seriously injured, 13 others less seriously injured ornotinjured.

Pre 1949 AEC facility Not Believed to Sudden. leak in a hot identified be 13 kg cylinder.

One worker received injury to respiratory tract,-

eyes, and kidneys.

5-10-60 Babcock &

Fuel Not Leak in heat exchanger

Wilcox, fabrication reported allowed UO F 2 2 to escape Apollo, PA to river water.

60 x MPC at discharge point.

11-17 Union Carbide, Uranium Not Rupture of 10-ton Oak Ridge, TN ' enrichment reported cylinder.

5-25-62 Nuclear Fuel Fuel 15 kg HEU in An overheated 15-kg

Services, fabrication 5 min. 6 kg cylinder ruptured and Erwin, TN metal recovered in released its contents plant in-the building.

3-20-64 Nuclear Fuel Fuel 1 kg in 2 hrs.

Overpressure burst tube

Services, fabrication Half recovered Erwin, TN metal onsite 2-14-66 National Feed 2300 kg in Operator accidentally
Lead, material I hr.

Much removed valve on a hot Fernald, OH production absorbed by 10-ton cylinder, deve-water spray loped lung edema, hospitalized 6 days.

No observed injury to kidney.

6-29-67 Kerr-McGee,

UFs 45 kg in Gasket leaked due to Gore, OK conversion 15-20 min overheating.

7-19-68 Kerr-McGee Fuel 45 kg of 1.6%

Valve accidentally left Cresce,nt, OK fabrication enriched U open during heating.

in 15-20 min

  • Ronald Kathren and Robert Moore, "Acute Accidental Inhalation of U : A 38 year folluw-up," Health Physics, 51, 609, 1986.

29

Table 4.

(continued)

Type of Quantity of Date Facility facility-UFs released Cause and Consequence 11-12-68 Allied UFe 43 kg Valve failure

. Chemical, IL conversion 5-2-73 Goodyear UF 100 kg in Worker broke valve on Atomic processing 20 min 10-ton cylinder.

Oak Ridge, TN (inside) 4-20-74

Numec, Mixed oxide 6 kg, slightly Apollo, PA fuel enriched fabrication 12-2-76 Exxon Nuclear, Fuel Small Worker disconnected Richland, WA fabrication line but had forgotten to close valve.

3-7-78 Portsmouth Enrichment 9500 kg Rupture of dropped hot Gaseous plant in 1/2 to 14-ton UFs cylinder.

Diffusion 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> Plant, OH 12-3-78 GE Fuel not known Block valve opened fabrication l

8-7-79 NFS, Erwin Fuel

<3 kg Accidental venting of l

TN fabrication cylinder to stack, 5-20-80 GE Fuel

<1 kg Pipe flange failure fabrication 9-15-81 GE Fuel

<<74 kg Gasket leak fa' rication o

10-12-91 NFS, Erwin, Fuel 0.05 to 0.1 Release via main TN fabrication kg, HEU scrubber stack.

l 2-25-82 Exxon Fuel

<<25 kg Gasket leak i

fabrication l

12-83 Edlow Inter-Warehouse None Fire in warehouse, national, East St. Louis, IL 1-4-86 Sequoyah UFs 14,000 kg Heating of overfilled Fuels conversion in less than cylinder.

One worker Corp., Gore a minute.

killed.

Several injured OK Between 10%

from HF.

and 50% of the uranium became airborne 30

i poisoning from uranium.

At least two workers were killed.

Persons injured or killed in this manner have all been workers in a room working close to a UFs cylinder.

Two of the cases involving the most serious exposures were reported by Howland.* He reported two fatalities, four serious. injuries, and slight injury to 13 other people.

One of the fatalities showed by autopsy roughly 1000 mg of uranium in the lungs.

Howland concluded that the most serious injuries (observed on the skin, eye, mucous membrane of the upper respiratory tract, esophagus, larynx, and bronchi) were all caused by the action of the fluoride ion on the exposed tissues.

Uranium produced transient urinary-tract changes. A long-term follow-up of three of the workers was reported by Kathren and Mooret.

The three men were estimated to have initial depositions in the icng of 40 to 50 mg of uranium.

Medical and health physics examina-tions of two of the men 38 years after the accident revealed no detectable deposition of uranium nor any physical injury or changes attributable to ura-nium exposure.

The conclusion is that HF and uranium both have adverse effects, but that the HF effects are the more severe.

In the National Lead-Fernald accident, one worker suffered lung edema, presumably from exposure to HF.**

No injury to his kidneys was observed.

He excreted in urine over 1 mg of uranium in the first two days after the acci-dent, suggesting a total intake of roughly 2 to 3 mg of uranium.

The largest release of UFs occurred in 1986 when a cylinder filled with UFs beyond its 14-ton capacity ruptured while being heated at Sequoyah Fuels Corporation in Gore, Oklahoma.

Heating an overfilled cylinder was prohibited by company procedures and the NRC license and was widely recognized in the industry as a dangerous and unacceptable practice.

The cylinder ruptured because of hydrostatic pressure.

The pressure was caused because UFs expands significantly when the solid melts and becomes a liquid, but there was not sough room in the cylinder for this expansion.

There was not enough room becam e the cylinder had been overfilled.

  • Joe W. Howland, "Studies on Human Exposures to Uranium Compounds," in Pharmecoloqy and Toxicoloqy of Uranium Compounds, edited by Carl Voegtlin and Harold Hodge, McGraw-Hill, New York, 1949, p 993.

tKathren and Moore, op. cit.

    • Bab ock and Heatherton, op. cit.

31

/

The rupture was about four feet long and most the contents, approximately 14,000 kg, escaped in less than a minute.

Of the uranium that escaped the cylinder, most was later found to be on the ground near the release point.

The company estimated that 35 percent of the uranium could not be found near.

the release point, but other estimates were that 50 percent escaped.

Thus, the amount of uranium that became airborne would be between about 3300 kg and 4700 kg.

One worker was killed because of pulmonary edema caused by HF.

Several othe?

Tperienced skin burns, irritation to the eyes and mucous membranes, and a fratory tract irritation (

Reference:

NUREG-1189).

No symptoms were found among people exposed offsite.

Bioassay results for 36 workers showed an average uranium intake of about 6.5 mg 6nd a maximum intake of about 28 mg.

Nine of the workers were exposed to uraniurn in excess of NRC's regulatory limit (9.6 mg intake within a week),

but no symptoms of kidney injury were observed.

Another large release of UFe was the 1978 accident at the Portsmouth, Ohio i

gaseous diffusion plant.

In this accident a heated thin-walled cylinder-con-taining 14 (short) tons of natural UFs was dropped 8 to 10 inches and ruptured below the liquid level.* Within one hour, about 9500 kg of UFs escaped.

This is equal to about 6400 kg of uranium.

The release was outdoors.

The air temperature was 32 F, the wind speed was 2 meters /sec, and a mixture of snow and freezing rain was falling.

Snow covered the ground.

About 550 kg of l

uranium were recovered on the ground afterwards.

Agglomeration is likely to have increased the settling.

About 4800 kg of uranium (75% of the release) were estimated to have become airborne and dissipated in the air, much thereby leaving the site.

The site boundary in the downwind direction was at a distance of 2.2 km.

1

  • "Investigation of Occurrence Involving Release of Uranium Hexafluoride from a Fourteen-Ton Cylinder at the Portsmouth Gaseous Diffusion Plant on March 7, 1978," DOE Report ORO-757, June, 1978.

i l

32

Water samples from a drainage ditch located near the release had a peak uranium concentration of 450 mg/1, 10 times the NRC's radiological limit for water to be released to unrestricted areas.*

The reported environmental effects were minimal. Workers who drove l

through the plume showed no detectable uranium in samples of their urine.

Significant ground and water contamination were confined to distances of a few hundred yards from the release point.

Airborne concentrations at the site boundary (2.2 km) were calculated to be not high enough to be harmful for brief exposures.

Another large release of UFs occurred-in France in 1977.t As the result of a handling error a valve ruptured on a container heated to 90-95 C.

The UFs immediately started to spill out onto the ground.

The liquid flow lasted 10 to 15 minutes until the level of liquid in the container had fallen below the valve opening.

Then UFs continued escaping as a gas until the valve was plugged with a wooden peg 30 minutes after the rupture.

Of the 8800 kg of liquid UFs in the container, 7100 kg escaped.

Water and carbon dioxide were used to prevent the escaped UFs from becoming airborne.

However, 330 kg of uranium and 1600 kg of HF were not recovered.

Thus 7% of the uranium and 98% of the HF that escaped the container apparently became airborne.

Weather conditions favored rapid dilution.

It was a warm and sunny afternoon with a windspeed of C m/s.

The French workplace limit for HF of 2.4 mg/m8 was exceeded up to a distance of 1200 meters.

Ground contamination by uranium of up to 10 mg/m2 i

was observed up to 600 meters.

The area on which virtually all the solid uranium compounds settled did not exceed 1000 m,

2 No injuries were observed.

Urine samples were taken from 449 people.

Two workers excreted more than 0.5 mg during the first day, but no physio-logical symptoms were observed.

No symptoms of the HF exposure were observed.

Using the specific activity of natural uranium of 6.77 x 10 7 microcuries/ microgram, the effluent water standard is equiva-lent to 44 milligrams / liter.

TA.J. Docouret, "An Experience of Accidental Release of UFs," Comurtex Plant, Pierrelatte, France.

33

i In addition to gaseous UFs releases, conversion plants have released uranium to rivers.

On Dec.1,1978 the Kerr-McGee conversion plant accident-ally released 750 kg of natural uranium in the form of uranyl nitrate into a river.

The liquid released had a uranium concentration of 1.4 times'the MPC

  1. or water, which would then be diluted by the river water.

2.2.3.2 Accident Source Terms The NRC staff, Sutter at Pacific Northwest Laboratory, and M. Simon-Tov

  • at Oak Ridge National Laboratory have recently analyzed potential accidents at UFs conversion plants to estimate potential releases of UFe.

The largest release postulated by the NRC staff is contained in an Environ-mental Impact Appraisal for the Allied Chemical conversion plant.** The NRC i

staff assumed that the largest release of UFs would be caused by the rupture of a heated 14-ton cylinder.

The staff assumed that 9500 kg of UFs would escape and that the material would hydrolyze.

As a result, 4800 kg of natural uranium would be released with the chemical form UO F, a highly soluble compound.

22 Sutter*** considered a number of possible accidents.

These include:

1.

The rupture of two 14-ton UFs cylinders outdoors in conjunction with a fire fed by 100 gallons of gasoline due to a truck crash 2.

A leak of UFs from a pipe 3.

A tornado strike 4.

Fires 5.

Chemical explosions 6.

Natural gas explosions The accident determined by Sutter to cause the most significant release is the rupture of two 14-ton UFs cylinders along with a gasoline fire.

The initiation is assumed to be a truck accident in which the truck hits the

  • M. Simon-Tov et al., "Scenarios and Analytical Methods for UFs Releases at NRC-Licensed Fuel Cycle Facilities," NUREG/CR-3139, 1984.
    • Environmental Impact Appraisal for Renewal of Source Material License, No. 5U8-526, Allied Chemical Company UFn Conversion Plant, Office of Nuclear Material Safety and Safeguards, NUREG-1071, May, 1984, page 4-28.
      • S.L.

Sutter, et al., op. cit.

34

cylinders, ruptures its gas tank, and catches on fire.

A total release of up to 3800 kg of UFs was calculated.

The amount of material that could be released is limited by the amount of heat available to vaporize the solid UFs.

Heat required to raise the temperature of the cylinder and UFs is neglected.

If the UFs cylinder is not ruptured, the heat is sufficient to raise the temperature of the UFs from 20 to 100*F.

The pressure produced would not be enough to rupture the cylinder.

l Simon-Tov's work was directed toward determining accident scenarios and analysis methods for UFs releases.

His work is the most recent and most comprehensive.

Twenty-five relet.se scenarios are described in his report (Chapter 5).

The scenario most appropriate for this analysis is the rupture of a heated liquid-filled cylinder outdoors.

At a temperature of 100 C, 57% of the liquid UFs could be vaporized.

At 120*C, 65% could be vaporized-(Figure 11,.page 58).

The most important parameter for determining the release is the temperature of the cylinder.

Thus the largest release is from a cylinder just-filled.

Analyses of plausibile fire scenarios involving cooled cylinders show that the UFs cannot be heated sufficiently to cause as large a release as from a hot cylinder.

For the purpose of this regulatory analysis, the release to be evaluated for UFs conversion plants will be one similar to the ones that occurred at the Portsmouth gaseous diffusion plant and the Sequoyah conversion plant.

Those accidents involved the ruptures of hot 14-ton UFs cylinders outdoors.

At Portsmouth, there was a release of 9500 kg of UFs (equivalent to 6400 kg of natural uranium).

It is assumed that 4800 kg of natural uranium becomes air-borne and the remainder settles on the ground due to agglomeration and impaction.

At Sequoyah, the amount of uranium becoming airborne was probably between 3300 kg and 4700 kg. A Portsmouth release was calculated by W. Reid Williams as likely to occur in about 15 minutes.

There would be no advance warning.

Because the release is assumed to be outdoors, no automatic detection or alarm system would detect the release.

Rather, plant personnel are assumed to detect the release and then take emergency measures.

The plume would be readily detectable to the human senses because of the HF and its resulting irritation.

Therefore no monitoring instruments are needed to detect high concentrations.

35

2.2.3.3 Calculations of Doses The release.of UFs presents a chemical rather than radiological hazard.

Exposures lethal due to uranium chemical toxicity or HF burns on lung tissue would not result in radiation doses exceeding 1 rem effective dose equivalent.

Therefore, radiation doses are not calculated.

The release assumed is the escape of 9500 kg of UFs in 15 minutes due to the rupture outdoors of a heated 14-ton cylinder.

The mass of uranium in 9500 kg of UFs is 6400 kg.

Some of the uranium will be removed from the air initially by agglomeration and impac-tion. We assume 4800 kg of uranium becomes airborne.

The corresponding mass of HF is 1620 kg.

Intakes are calculated for atmospheric stability class F with a wind speed of 1 m/s as well as stability Class 0 with wind speed of 4.5 m/s.

The plume is assumed initially to have a centerline near ground level.

The heat from the chemical reaction of UFs combining with the moisture in the air will cause the plume to become buoyant.

Calculations by W. Reid Williams indicate the plume would lift off within 20 to 30 meters and a plume centerline height of about 20 meters would be obtained within 200 to 300 meters.

Thus, we assume a plume centerline height of 20 meters.

The equation for uranium intake I is:

X I=QxBxg where Q = the released quantity (4800 kg),

a B = the breathing rate (2.66 x 10 4 m /s), and l

X/Q = the atmospheric dispersion value from Figure 1.

l 36 j

5 Uranium intake due to the airborne release of 4800 kg of uranium Uranium intake (mg) l-Distance F, 1 m/s

-0, 4.5 m/s

-(meters) buoyant buoyant i

200 6

53 300 46 59 500 110 40 700 110 28 1,000 92 17 1,500 62 10 2,000 44 6

5,000 11 1.6 10,000 3

0. 5 15,000 1

0.3 20,000 0.6 0.2 The exposure to concentrations of HF can be calculated similarly.

Expo-I sures due to the airborne release of 1620 kg of HF are shown below.

HF exposure due to the airborne release of 1620 kg of HF 3

HF exposure (mg/m )

Distance F, 1 m/s D, 4.5 m/s (meters) buoyant buoyant t

200 9

77 300 68 86 500 160 59 700 160 41 1,000 140 25 1,500 92 14 2,000 65 9

5,000 16 2.3 10,000 5

0.8 15,000 1.8 0.4 20,000 0.9 0.3 1

r 37

2.2.3.4 Implications for Emeraency Preparedness Of all the accidents considered in this Regulatory Analysis, the rupture of a heated 14-ton cylinder of UFe is clearly-and by far the most hazardous to people offsite. The corrosive effects of exposure to HF and heavy metal poison--

ing due to uptake of uranium are discussed separately below.

Heavy metal poisonina:

We consider the best estimates of the health effects of uranium intake to be those in two DOE reports

  • based on the work of a panel of experts on uranium toxicity.

The effects are summarized below:

Health Effect Intake (ma) 50% Lethality 243 Permanent damage 45 Renal effect (transient) 8.6 No effect 4.5 It is not likely from the calculated results that lethal intakes are actually plausible for outdoor releases of UFs.

In order to calculate lethal intakes it is necessary to assume little or no buoyancy, which is believed to be incorrect, and little or no effort on the part of the exposed individual to escape the plume, which may not be a reasonable assumption.

We conclade that lethal intakes of uranium by people offsite are not really plausible under j

realistic conditions.

Permanent kidney damage, on the other hand, may be possible.

From the intakes calculated above permanent kidney damage could occur as far as 2000 m (1.2 miles) under very adverse weather (F, 1 m/s) and no attempt to escape the plume, Under more typical conditions (0, 4.5 m/s, some buoyancy, and attempted escape) permanent kidney damage would not be expected offsite.

Transient kidney effect appears to be quite plausible.

Under highly adverse conditions (F, 1 m/s) it might be possible as far as five miles away.

Under more typical conditions (0, 4.5 m/s and some escape attempt) transient effect might occur as far as 1 mile away.

  • R. A. Just and V. S. Emler, "Generic Report on Health Effects for the U.S.

Gaseous Diffusion Plants," DOE Report K/0 5050,Section VIII, Part 1, 1984.

38

It is Commission policy for nuclear power plant accidents to plan to avoid acute fatalities.and serious injuries for the worst case accidents.

With this in mind, the recommended protective action distance for rupture of a 14-ton cylinder would be 1 mile.

The protective actions could be movement out of the plume, sheltering in buildings, or ad hoc respiratory protection, depending on practicality and feasibility in the actual situation.

This would avoid acute fatalities and serious injuries for worst-case accidents and transient kidney injury under more typical conditions.

L l

HF:

Estimates of the health effects are from a recent DOE report.* The effects described here are based on concentration as applied to a 15 minute

(

exposure:

Health effect HF concentration (mg/m8)

Lethal (15 min) 3500 Unbearable for 1 min 100 Irritation (15 min) 13 Detectable by smell but no health effects 2.5 From the calculated HF exposures given above, lethal exposures offsite are not plausible.

Levels for permanent injury are not known.

As a consequence we are sub-stituting the concentration of 100 mg/m 3 as the level considered to be "unbear-able" for more than a minute.

Such levels may occur out to about 1500 meters under adverse conditions.

Generally, they would not be expected to occur off-sites under typical conditions (0, 4.5 m/s) if one discounts somewhat the ground level release values.

Irritation appears possible out to at least 5000 meters (3 miles) under adverse meteorology and roughly 1500 m (1 mile) under typical conditions.

Thus the consequences of HF exposure are similar in severity to those from uranium intake.

Consequently the one-mile evacuation suggested for the rupture of a 14-ton cylinder of UFs is appropriate for protection against both uranium and UFs.

  • R. A. Just and V. S. Emler, "Generic Report on Health Effects for the U S Gaseous Diffusion Plants," DOE Report K/D 5050,Section VIII, Part 1, 1984.

39

The U.S. Department of Transportation has a' iso established evacuation guides for HF releases.* For small leaks (drum, small container, small leak from a tank) the DOT recommends isolation in all directions to a distance of 150 feet (45 meters).

For a large spill from a tank (i.e. rail oad tank car) the DOT recommends isolation in all directions to a distance of 300 feet (90 meters) and then evacuation in a downwind direction to a distance of 1.5 mile and a width of 0.8 mile.

The DOT distances, however, are based on a larger quantity of HF.

Thus, the one-mile action distance suggested here is consistent with DOT recommendations.

DOT distances are based on atmospheric stability Class D and wind speed of 4.5 m/s.

DOT states that distances based on those assump-tions have proven to be adequate under actual accident situations.

l 2.2.4 Enrichment Plants At present there are no NRC-licensed enrichment plants, nor are there any immediate prospects for one.

Basically, however, enrichment plants receive UFs from conversion plants and ship UFe, enriched in U-235, to fuel fabrica-tion plants.

Thus the types of potential accidents are similar to those at conversion plants and fuel fabrication plants.

2.2.4.1 Accident History Several large releases of UFs have occurred at enrichment plants, as shown in Table 4.

These have been the result of the ruptures of heated large l

10-ton or 14-ton cylinders.

The largest release was the 1978 cylinder rupture at the Portsmouth, Ohio gaseous diffusion plant, which released 9500 kg of l

UFs.

I l

l

""Hazardous Materials-Emergency Response Guidebook," U.S. Department of r

Transportation report 00T-P5800.4, 1987.

40

2.2.4.2 Accident Source Terms Source terms for two types of accidents are considered:

UFs releases and criticality accidents.

The UFs release for natural uranium is considered to be the same as for the UFs release previously discussed for UFs conversion plants in Section 2.2.3.2.

The UFs releases for enriched uranium are considered to be the same as those for fuel fabrication plants that will be discussed in Section 2.2.5.2.

The criticality accidents is assumed to be the same at the criticality accident for the fabrication plants that will be discussed in Section 2.2.5.2.

2.2.4.3 Calculations of Doses Doses due to a UFs release from the rupture of a 14-ton cylinder of natural uranium are the same as those given in Section 2.2.3.3 for UFs conver-sion plants.

Doses due to UFs releases of low and high enriched uranium are the same as those that will be given in Sectio'n 2.2.5.3 for fuel fabrication plants.

Doses due to a criticality are the same as those given for a criticality at a fuel fabrication plant in Section 2.2.5.3.

t 2.2.4.4 Implications for Emergency Preparedness Offsite emergency preparedness at uranium enrichment plants should be based on chemical toxicity from a large UFs release.

Thus, uranium enrichment plants should be considered a potential chemical haz,rd, not a radiation hazard.

Basically, uranium enrichment plants should have the same level of offsite emergency preparedness as UFs conversion plants.

Currently, enrichment plants, if licensed, would be covered under Part 50 of NRC regulations.

The emergency preparedness requirements in Part 50, which were developed for nuclear power plants, are clearly excessive for enrichment plants.

However, because NRC does not currently license any enrichment plants, the discrepancy is academic.

41

2.2.5 Fuel Fabrication - Uranium Fuel fabrication plants generally receive UFs enriched in the uranium-235 isotope, convert it generally into highly refractory uranium oxides, form the uranium oxides into pellets, and load the pellets into metal-clad fuel elements for shipment to nuclear power plants.

In most cases the uranium-235 is enriched to less than 5%, but at several plants the enrichment exceeds 93%.

However, only one licensed plant (Nuclear Fuel Services, Erwin, Tennessee) currently handles the volatile UFs in highly enriched form.

2.2.5.1 Accident History Among the accidents that have occurred in processing uranium are criti-cality accidents, fires, and releases of UFs.

Since the first successful self-sustaining nuclear chain-reaction there have been no less than 37 occasions when the power level of fissile systems rose unexpectedly because of unplanned or unexpected changes in system reac-tivity.

Of these 37 cases, six cases caused eight deaths, two of which occurred in the early, rushed pace near the end of World War II.

Of these 37 criticalities, eight occurred in fuel cycle facilities (7 in the U.S. and one abroad) and are thus relevant to this analysis.

The remaining 29 occurred in nuclear reactors or critical assembly experiments.

The seven relevant U.S. fuel cycle facility criticalities are listed in Table 5.

One occurred in a licensed facility (Wood River Junction, R.I., 1964).

There are several lessons about criticalities that can be learned from studying these accidents.

Accidental criticalities can occur and occasionally do. When they occur the doses to workers can be very large, sometimes fatal, and sometimes requiring hospitalization.

Radioactive solutions can be ejected and can contaminate workers and the plant area.

No offsite contamination or l

radiation doses have been reported.

l l

42

Table 5.

Criticality Accide ts In Fuel Cycle Facilities through 1986 Contamination Total Contamination Out or D:te Location Process Cause Fissions Duration Personnel Exposures In plant Building June 16 Y-12 Process-Recovery of highly Wash water added to 1.3 x 10's 18 min 8 people. Doses of 461, Small local None 1958 ing Plant, enriched uranium UO (NO ) solution 418, 413, 341, 298, 87, contamination reported 2

3 Oak Ridge, TN by chemical in 55 gal. drum.

29 rads. No fatalities.

methods.

Dec. 30, Pu Process-Recovery of Liquid phases of 1.5 x 1087 I sec 3 people. Doses of Mone None 1958 ing Plant, plutonium from plutonium separated 12,000, 134, 53 rads.

reported reported Los Alamos, NM scrap.

out.

One fatality.

Oct. 16 Idaho Chemical Transfer of highly Solution transferred 4 x 10 "

15 to 19 people. No direct Yes Not 1959 Processing enriched uranium to unsafe geometry 20 min gamma or neutron dose airborne reported Plant, Idaho solution.

(5000 gal tank) because tank was beta Reactor Test shielded, but beta activity Site doses from released radio activity of g

50 rem, 32 rads, and smaller amounts for 17 other people.

Jrn. 25, Idaho Chemical Transfer of highly Solution transferred 6 x 1087 I sec Mone. Shielded None Mone 1%1 Processing enriched uranium to unsafe geometry operation reported-reported Plant Idaho solution.

Reactor Test Site April 7 Hanford Works, Plutonium Plutonium solution 8 x 1087 37.5 hr 3 people. Doses of 110, Mone None 4

1962 Richland WA processing incorrectly siphoned 43, 19 rads.

reported reported July 24, Scrap Recovery Recovery of highly Solution hand poured 1.3 x 1087 2 short 3 people. Doses of 20% of Mone 1964 Plant, Wood enriched uranium into unsafe geometry pulses 10,000, 100, 60 rais.

solution reported River Junction, 1.5 hrs One fatality, splashed RI apart out of tank Oct. 17, Chemical Solvent extraction 3 x 1088 15 min Less than.13 rem.

Air monitors Filters 1978 Processing column (In shielded cell) detected removed Plant, NRIS, ID considerable most activity particles k < 1 hr R2ferences: William R. Stratton, "A Review of Criticality Accidents," AEC Report LA-3611,1%7 and "Recovery of ICPP from Criticality Event of October 17, 1978," 005 Report ACI-362, November, 1978.

t A number of fires,and explosions involving uranium or thorium, which would behave similarly, have been reported.

Uranium metal is pyrophoric.

Uranium metal, heated or in powdered form or heated as a solid will spontaneously ignite if_ exposed to air.

Reported fires and explosions involving uranium or thorium are included in Table 6 below. What is noteworthy is that these fires have had little consequence with regard to either personnel exposure or ground contamina-tion.

Reported offsite contamination levels were generally below the levels that-the NRC allows on equipment to be released for unrestricted use.^

By comparison, the accident record for plutonium, which has a much higher specific activity, is much different.

Plutonium accidents have been charac-torized by extensive radioactive contamination and personnel exposures.

Yet even the most serious of these accidents, the Rocky Flats fire, caused only a small fraction of the plutonium involved to be released.

Of hundreds of kilograms of plutonium involved in the fire, only 0.003 g was released through a damaged exhaust system.** Thus the overall release fraction for plutonium was about 10 8, based on the estimated release quantity compared to the quantity involved in the fire.**

Table 7 lists other accidents involving uranium fuel fabrication, but not including UFs releases, fires, or exposions which were listed previously.

These accidents in Table 7 all involved ventilation systems.

None of the accidents listed in Table 7 caused any offsite doses approaching the 1 rem lower limit of the protective action guides.

  • Surface contamination levels for uranium allowable on equipment to be 2

released fc a unrestricted use are average:

5000 dpm alpha /100 cm, maximum:

2 2

15,000 dpm alpha /100 cm, and removable:

1000 dpm alpha /100 cm.

These values are found in Regulatory Guide 1.86, "Termination of Operating Licenses for Nuclear Reactors," and "Guidelines fur Decontamination of Facilities and Equipment Prior to Release for Unrestricted Use or Termination of Licenses for Byproduct, Source, or Special Nuclear Material," USNRC, July, 1982.

    • H. K. C1 der, "Technology, Safety and Costs of Decommissioning Reference Nuclear Fuel Cycle and Non-fuel Cycle Facilities Following Postulated Accidents," NUREG/CR-3293, Vol. 1, page 3.3, 1985.

44

Table 6.

Fires and Explosions Involving Uranium and Thorium through 1986 Date Facility Release Description 6-27-49 Los Alamos None reported Fire broke out in a drum Laboratory, NM containing uranium metal i

turnings.

10-29-52 Truck in Kansas Considerable Truck carrying uranium l

City, M0 metal burned.

Uranium r

ignited and much was lost.

12-9-52 AEC facility None

. Molten uranium metal was being cast in a vacuum.

i Spill ruptured vacuum.

Uranium then burned.

6-12-53 U.S.

Onsite contamina-Explosion of powdered tion up to 15,000 uranium and CC1 in 4

2 dpm/100 cm.

glovebox.

8-20-56 AEC contractor 100,000 dpm/

Thorium explosion 100 cm2 onsite.

500 dpm/100 cm2 offsite.

9-21-56 Truck in Detroit, None Drum containing thorium MI metal started to burn.

No contamination.

No exposures.

6-23-58 AEC contractor No material Fire in slightly Attleboro, MA loss enriched uranium scrap in perchloroethylene.

t 9-26-60 M&C Nuclear Enriched U Magnesium explosion in Attleboro, MA no exposures, vacuum induction furnace.

9-20-63 Controls, Inc.

None Fire in filter box l

Attleboro, MA detected exhausting enriched L

uranium.

No contamination on or offsite.

l 6-29-67 Kerr-McGee Minor Explosion in ion exchange Crescent, OK column.

9-2-72 United Nuclear Uranium at Flash fire caused by Fuel fabrication 15 times MPC organic contaminants in facility ductworks.

Considerable damage.

3-12-81 Nuclear Metals Minor inplant Fire in scrap packaging Concord, MA contamination building from spontaneous

[

combustion of 10 lbs of e

uranium turnings.

No i

overexposures.

l t

t t

?

45 I

L

Table 7.

Other Accidental Releases from Uranium Fuel Fabrication Plants through 1986 (UFs releases, fires, and explosions excluded)

Date Fac'.lity Release Accident. description 4-2-71 Babcock and Wilcox 10 Microcurie in Contamination outside a Research Facility plant hot cell due to a plug Lynchburg, VA being installed without a sealing bellows.

2-28-73 General Electric, Below MPC HEPA filter failed.

Wilmington, NC 8-24-73 Babcock and Wilcox Decontamination Enriched uranium released Apollo, PA required on and when corroded scrubber offsite.

Release spray nozzle did not was 6.3 microcuries, provide enough scrubbing.

12-8-73 Babcock and Wilcox Offsite release of Inadequate ventilation Apollo, PA natural uranium of calciner allowed j

4 times MPC.

Offsite uranium to escape decontamination through canopy exhaust.

required.

Leak in a roughing filter 9-6-74 Westinghouse UO2 Columbia, SC allowed UO2 power to be discharged directly to the air.

1-24-75 Babcock and Wilcox Enriched uranium Malfunction of scrubber /

Apollo, PA ventilation system.

1-79 General Electric, 62 Kg of low Two cans of powder stolen Wilmington, NC enriched UO2 powder and used in extortion stolen.

attempt.

Thief arrested, convicted and imprisoned.

Powder recovered.

L 46

2.2.5.2 Theoretical Calculations of Releases Criticality accidents, UFe releases, fires, explosions, and tornadoes have been considered in various analyses of accidents in a fuel fabrication plant. The most serious accidents appear to be criticalities and UFs releases, i

Thus, we consider those accidents here.

Criticality Accident:

the NRC staff has developed a set of assumptions on the release of radioactive fission products from a criticality accident occurring in a solution. The assumptions are published in Regulatory Guide 3.34, "Assumptions Used for Evaluating the Potential Radiological Consequences.

of Accidental Nuclear Criticality in a Uranium Fuel Fabrication Plant," July 1979.

Regulatory Guide 3.34 assumes a criticality excursion occurs in a vented vessel of unfavorable geometry containing a solution of 400 g/l of uranium enriched in U-235.

The excursion produces an initial burst of 1018 fissions in 0.5 second followed successively at 10 minute intervals by 47 bursts of 1.9 x 1017 fissions each for a total of 1018 fissions in 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.

The excursion is assumed to be terminated by evaporation of 100 liters of the solution. The amounts of radioactive materials assumed to be released from the solution vessel to the room air are given in Table 8.

Regulatory Guide 3.34 allows credit for removal of fission products by filters in the ventilation system.

In order to escape to the environment the room air must pass through a filter system by means of the building ventilation system.

Even if doors are opened the ventilation system should exhaust the fission products through the filters.

In this analysis the filters are assumed to remove 75% of the iodine but none of the inert gases.

This analysis assumed the ventilation system operates at 5 air changes per hour.

The NRC staff has recently analyzed the potential consequences assuming a criticality accident for Exxon Nuclear in Richland, Washington,* Combustion Engineering in Hematite, Missouri,** and Nuclear Fuel Services in Erwin,

'"Environmental Impact Appraisal, Exxon Nuclear Company, Nuclear Fuel Fabrication Plarit, Richlan6, Washington," Docket 70-1257, NRC Office of Nuclear Material Safety and Safeguards, August, 1981.

    • "Environmental Assessment, Combustion Engineering, Inc., Nuclear Fuel Fabrication Plant, Hematite, Missouri," Docket 70-36, NRC Office of Nuclear M.sterial Safety and Safeguards, November, 1982.

47

Table 8.

Amounts of Radioactive Materials Released to Room Air Due to a Criticality Accident (101s fissions initially and 1.9 x 1017 fissions every 10 minutes for 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />)

Radioactivity in Curies Half-life Radionuclide in hours 0-0.5 hr 0,5-8 br Kr-83m-1.8 22 140 Kr-85m 4.5 21 130 Kr-87 1.27 140 850 Kr-88 2.8 91 560 Kr-89 0.05 5900 36,000

.te-133 125.

4 23 Xe-135m 0.26 310 1900 Xe-135 9.1 50 310 Xe-137 0.06 6900 42,000 Xe-138-0.24 1800 11,000 I-131 192.

0.3 1.9 I-132 2.3 38 240 1-133 21.

5.5 35 I-134 0.88 160 980 I-135 6.6 17 100 Source:

Regulatory Guide 3.34, Table 1, July,1979.

The values for radiciodines in Table 1 of the guide were reduced by a factor of 4 to account for retention in the solution water.

Tennessee.* In each case the radionuclide releases from Regulatory Guide 3.34 were used.

Low-enriched UFs: The Exxon and Combustion Engineering analyses ** also considered releases of UFs, as did a recent analysis for the General Electric fuel fabrication plant in Wilmington, North Carolina.t The worst-case accident in the Exxon and Combustion Engineering analyses was assumed to involve the release of UFs as might occur from valve or line failure of a heated cylinder being unloaded. Assuming that a full cylinder of UFs (2500 kg) at elevated

    • 0p. cit.

t"Environmental Impact Appraisal, General Electric Company, Wilmington Manufacturing Department," Office of Nuclear Material Safety and Safeguards,"

NUREG-1078, June, 1984, page 69.

48

b b

temperature started to leak and that no additional heat was supplied after cylinder failure, the NRC staff estim?ted that about 22 percent of the material would be released before the UFs would be cool enough to solidify and have a vapor pressure low enough so that the release would stop.

The NRC staff esti-mated that such a release would last for 15 minutes, and 540 kg of Ufs would be released. This has a uranium content of 360 kg.

The staff assumed the uranium released would react with water in the air and form highly soluble UO F2 2 of a respirable particle size.

High-enriched UFs:

In evaluating the need for offsite emergency prepared-ness at Nuclear Fuel Services, Erwin, Tennessee, the NRC staff concluded that the UFs accident to be considered was release from a 15-kg cylinder cor.taining high enriched uranium.* This is largest cylinder used at the site for highly j

enriched UFs.

An accident in 1962 breached one cylinder.

Of the 15-kg contents, 6 kg was recovered but 9 kg was not recovered and presumably much of the material escaped from the plant.

2.2.5.3 Calculations of Doses Potential radiation doses due to criticality accidents and UFs releases previously calculated by the NRC staff for Combustion Engineering Exxon, and Nuclear Fuel Services are summarized in Table 9.

Criticality accident:

To calculate the dose due to a criticality accident, the Exxon analysis assumed a wind speed of 1 m/sec, atmospheric stability class F, and a building wake factor of 1.0 beyond 500 meters (i.e. no building wake assumed).

The building ventilation rate is assumed to be 30 air changes /hr.

The whole body doses were calculated to be 0.004 rem at 3600 m (the nearest residence) and 0.009 rem at 2000 m (the nearest industrial site).

The doses to the thyroid were calculated to be 1.7 rem at 3600 m and 4.5 rem at 2000 m.

If one assumed only 25% of the iodines would pass through the filter system, the thyroid doses would be 0.4 rem at 3600 m and 1.1 rem at 2000 m.

The NRC analysis for the Combustion Engineering plant made sirilar assump-tions. The whole body dose at the nearest residence (800 m) wouid be 0.27 rem.

The thyroid dose at 800 m would be 1.7 rem.

If the filters rr.duced the iodine concentrations by 75%, the thyroid dose would be 0.4 rem.

~

t

49

Table 9.

Offsite Doses Calculated for Fuel Fabrication Plants Criticality UFs-low enrich.

UFs-high enrich.

Key Analysis Assumptions Effective DE Thyroid DE Effective DE Bone DE Effective DE NUREG-1140 Building size:

250 m2 0.5 to 1.1 to 0.2 to Wind:

F, 1 m/sec 2.6 rems at 8.2 rems 1.5 rem Release height:

ground 100 m at 100 m at 100 m (child's thyroid)

Combustion Building size:

0 0.27 ren 1.7 rems 0.05 rem 0.82 rem Engineering Wind:

F, 1 m/sec at 800 m at 800 m at 800 m at 800 m Release height:

stack Exxon Building size: 0 0.009 rem 4.5 rems 0.11 rem 1.7 rems Wind:

F, Im/sec at 2000 -

at 2000 m at 2000 m at 2000 m g

Release height:

ground 1 rem NFS, Erwin Building size: 0 5 rems Wind:

G, 0.5 m/sec at 1000 m at 1000 m Release height:

same level as residence

This analysis calculated an effective dose equivalent due to the airborne release from a criticality as 0.5 to 2.6 rem at 100 m.

The dose from prompt gammas and neutrons from excursions after the first one should be added to that dose, but those doses have not yet been calculated.

We calculated the thyroid dose to a child due to the radioiodine release from a criticality accident to be 1.1 to 8.2 rems at 100 m.

Low-enriched UFs:

For the UFs release, the Exxon plant analysis assumed a ground level release and calculated a dose to the bone of 1.7 rem at 2000 m.

The whole body dose was calculated to be 0.11 rem.

In the analysis the NRC staff published for the Combustion Engineering plant, the release was assumed to be through a stack.

The bone dose was calculated to be 0.82 rem at 800 m.

The whole body dose was calculated to be 0.05 rem.

For purposes of this Regulatory Analysis uranium intakes and HF concentra-tions have been calculated.

Radiation doses were not calculated since they are of lesser concern.

The release was assumed to be 540 kg of UFs at ground level.

The uranium content is 364 kg.

Atmospheric dispersion values from Figure 1 were used.

Uranium intakes are shown below for ground level releases.

Buoyant releases are not calculated because there may not be enough material to create buoyancy.

Uranium intakes due to a ground level release of 540 kg of UFs Uranium intake (mg)

Distance (meters)

F, 1 m/s D, 4.5 m/s l

100 320 43 200 150 16 300 90 9

400 42 3

500 24 2.2 1000 14 1.4 l

1500 6

0.8 1

2000 4

0.5 5000 0.5 0.1 1

High-enriched UFs:

For the Nuclear Fuel Services P: ant, the NRC staff previously calculated the effective dose equivalent at 1000 m due to the release of 15 kg of UFs, high-enriched, to be 1 rem.

For a 9 kg release of hiQh enriched uranium, we calculated an effective dose equivalent of 0.2 to 51 l

L 1.5 rems at 100 m, a uranium intake of 0.3 to 2.6 mg, and exposure to HF at a concentration of 1.0 to 7.8 mg/m.

A building size of 10 m x 25 m, neutral 3

buoyancy for the plume, ground level release, 5-minute release duration, 1.5%

U-234 with sobbility Class D for uranium and F,1 m/s and D, 4.5 m/s meteorology were the assumptions.

2.2.5.4 Implications for Emergency Preparedness The implications of criticality accidents and UFs releases are discussed separately below.

Criticality accident:

Using what are believed to be reasonable assump-tions, at 100 m effective dose equivalents of 0.5 to 2.6 rems for F, 1 m/s and D, 4.5 m/s meteorologies were calculated compared to a 1 to 5 rem protective action guide.

A child's thyroid dose of 1.1 to 8.2 rems was calculated compared to a 5 to 25 rem protective action guide. The calculated doses exceed the lower end of the range where protective actions should be considered out to about 200 to 250 m.

Low-enriched UFe release:

For the release of 540 kg of low-enriched UFe, lethal intakes (242 mg) offsite do not seem plausible.

Intakes sufficient to cause permanent kidney injury (45 mg) are calculated for adverse meteorology with no buoyancy to about 500 meters, although consideration of buoyancy might easily eliminate calculated permanent injury under any conditions.

Transient kidney effects might occur to 1000 meters under worse case meteorology and to perhaps about 300 meters under more typical meteorology.

There would be no observable effects at 400 meters for typical meteorology.

Therefore, in keep-ing with the Commission's policy on nuclear power plant emergency preparedness, t

avoiding fatalities and serious health effects for worst case and protective action guide doses for more probable events, a response distance of roughly l

400 meters is recommended.

f l

High-enriched & :

For the release of 9 kg of high-enriched UFs during F, 1 r's meteorology, the dose at 100 m is 1.5 rems effective dose equivalent and the uranium intake is 5 mg.

For 0, 4.5 m/s meteorology the dose at 100 m is 0.2 rem and the uranium intake is 0.7 mg.

Buoyancy is not considered in l

either case since the quantity of material is so small. Protection actions to reduce dose may be appropriate during F, 1 m/s meteorology to a distance of 150 m.

l 52

r t

2.2.6 Fuel Fabrication - Plutonium t

There.is currently no plutonium fuel-fabrication being done in the U.S..

I but accidents for facilities fabricating plutonium fuel have been analyzed in

'i NUREG-0002, "Final Generic Environmental Statement on the Use of Recycle Plutonium in Mixed 0xide Fuel in Light Water Cooled Reactors," 1976, usually called "GESMO." Because of the quality and thoroughness of that report, we

[

will.directly quote relevant sections for this analysis.

l 2.2.6.1 Accident Histoy *

"A sumary of operational accidents in U.S. Government facilities, from I

1943 to 1970, is given in WASH-1192.

For some facilities and operations having a general resemblance to the various mixed oxide fuel cycle steps (in the areas of fuel reprocessing, fuel fabrication, and scrap recovery) there have been a number of accidents.

Those which involved the possibility of environmental release include the following:

Five solution criticality events (1958--2 events; one each in 1959, 1961, and 1962) in reprocessing or-recovery operations involving highly enriched f

uranium or plutonium.

All were of small consequence in terms of property damage or releases of radioactivity to the environment, but one fatality

[

and several high radiation exposures occurred among operating personnel, i

Chemical explosion in evaporator (1953), related to fuel reprocessing.

(

Explosion and fire in plutonium purification facility (1963),

I t

'I

]

Metallic fuel fire (reactive metal) in process dissolver (1960), related to fuel reprocessing.

Spontaneous fire in radioactively contaminated, combustible waste (1951).

l l

  • From GESMO, pages II-45 to II-48.

The references given in GESMO are not included here to save space.

The reader wanting the references should refer to the original GESMO.

I 53 i

t

Two fires at the Rocky Flats plutonium fabrication and recovery facility, (1957) and (1969).

The 1969 fire caused $45 million in property damage.

Both fires are attributable to spontaneous ignition of plutonium metal which is not involved in the mixed oxide fuel cycle.

Fire around an anion exchange column, fuel reprocessing plant (1964).

"Some of these accidents occurred during the early years of operations with new facilities and newly developed technologies.

All were investigated and corrective actions were taken (e.g., design changes) to make the events unlikely of recurrence.

Such corrective actions have been carried forward, where applicable, into design practices for new facilities, both government and commercial.

During the past decade, criticality accidents have disappeared from the accident scene, and fire or explosion involving reactive metals has become the predominant major accident in government facilities.

"On a comparable basis, accident experience in commercial facilities to date include:

A solution criticality accident in recovery operations involving highly enriched uranium, fatal to operator (1964).

A series of dissolver "fires" (reactive metal), fuel reprocessing plant (1967-1968).

Final HEPA filter bank failure (inadequate mechanical support), fuel reprocessing plant (1968).

Fire in plutonium contaminated wastes, fuel fabrication facility (1973).

There was no detectable release of plutonium to the environment.

About Explosion in plutonium glovebox, fuel fabrication facility (1972).

5.6 pCi of alpha activity was released via the stack.

54

"The measured and estimated quantities of long-lived alpha activity released from the Rocky Flats plant during its first 20 years of operation are summarized in Table II-12....

"The specific and extensive modifications made to all plutonium handling facilities at Rocky Flats subsequent to the 1957 fire (especially the substitu-tion of flame resistant filters for those formerly used, and the addition of fire protection in the filter banks and plenums) were clearly responsible for the vastly improved containment of alpha activity during the 1969 fire.

The new plutonium recovery facility now under construction at Rocky Flats (as a replacement for older facilities) is being built under criteria that should provide even greater assurance that the facility will be able to confine plu-tonium releases to exceedingly small values, even under severe abnormal circum-stances--in.:1uding natural events, such as tornados."

"Table II-12 LONG-LIVED ALPHA ACTIVITY RELEASED FROM ROCKY FLATS Date Circumstances Quantity 1958-1968 Leakage of Pu conteminated machine oil 5.3 Ci to soil at stored at the Rocky Flats site drum storage area 1957 Fire in Bldg. 771 resulting in major 60 pCi, airborne, damage to filter system mostly during fire 1969 Fire in.,1dg. 776 0.2 pCi, airborne, over 6-day period during and after fire 1953-1970 Normal effluent releases (cumulative)

< 41 pCi, airborne 91 pCi, liquid effluents 1

55

2.2.6.2 Accident Source Term *

"A wide spectrum of credible accidents for these plants has been analyzed and their potential consequences estimated.

"Some incidents, such as punctures or tears of gloves or other glovebox malfunctions, are expected to occur as part of the normal operation.

Other more serious accidents--such as glovebox window breakage--will occur far less often, although the offsite consequences from such accidents are judged to be insignificant, they are included in the estimate of aftborne effluents result-ing from normal operations.

Upper limit accidents that may occur include a criticality incident, an explosion, or a fire....

Criticality "There have been no criticality accidents to date in process operations where undermoderation is a primary method of control, and few in aqueous or moderated systems.

The number of fissions has been estimated to be 10s: in an accidental criticality.

In calculating the effects, it is assumed that all of i

the noble gases krypton and xencn and 25% of the iodine formed by the fissions would escape.

In addition, it is assumed that 500 grams of Pu would become air-borne in a glovebox by the accidental criticality cxcursion.

The ventilation filters are assumed to remain intact because a criticality is not an explosive The decontamination factor of three HEPA filters in series has been process.

assumed to be 2 x 10, lower by a factor of 50 than the decontamination factor 7

assumed for normal operating conditions.

[Pu release = 0.29 pCi alpha) Calcu-lations show that the maximum offsite individual dose commitment results from absorption of fission product iodine in the thyroid and amounts to 360 mrem.

This is comparable to the dose to the closest theo?etical resident from a cri-fabrication plant.

The slightly different fission ticality accident at a U02 product yield and the presence of small amounts of plutonium particulate do not l

significantly alter the effects of a Pu0s criticality accident relative to f

those of a UO criticality accident.

"From GESHO, pages IV D-37 to IV 0-39.

56 l-

e n vg,

L Fire; 7*

"Unlike'a criticality excursion or an explosion, a fire usually is not

-an' instantaneous event _and v9ry often starts from a small flame sourcc.

The i

design,2 construction,1and operation.of' fuel fabrication plants considers'in-detail the possibility of a fire and equipment and procedures for fire preven-

. tion.

Repulstory Guide 3.16 presents methods acceptable to the NRC for a fire protection' prograw chat should prevent, detect, extinguish, limit, or control fires and explosions and their hazards and damaging effects.

Licensee must operate within these or acceptable eauivalent constraints.

Under these condi-tions, the probability of a fire of the magnitude considered in this statement is considered highly unlikely.

In general, operators have time to react to'and extinguish 4 mall fires.

The process materials, oxides of uranium and plutonium, are_not themselves flammable.

The final filters are protected against fire by water spray systems installed in the duct some distance upstream of the fincl i

filters.

Hist deflectors or collectors are installed between the water spray system and the filters to remove large drops of water.

The water from the sprays collects in the bottom of the ducts and flows to a fire-water collection tank.

This tank is either a safe geometry tank or a fixed poisen-controlled tank to preclude the possibility of a criticality' accident as a result of a fire.

"The final HEPA filters are located some distance from the gloveboxes.

This separation distance ano the water spray' system should be sufficient to i

. protect the filters against the effects of an explosion or fire, but the fire or explosion'is assumed to destroy the local filters on-the gloveboxes.

Plutonium and uranium oxides reach the final filters.~

Based on an~ assumed room volume of 1,000 m3 and an air loading of 100 mg/m3 for plutonium oxide particulate, 100 grams of plutonium would reach the filters.

Each of the filters is expected to remove 99.9% of the particulate reaching it, so that a total of 0.1 mg of Pu passes through the filters. [53 pCi alpha]

r Explosion "An explosion might occur in a mixed oxide fuel fabrication plant at loca-tions where an explosive mixture of vapors in air could be present.

There is a potential for the existence of combustible gases at the sintering furnance and in the clean scrap reduction operation.

In addition, flanaable solvents are 57

used in the dirty scrap recycle operation and may be used for cleaning fuel rods and during cleanup and maintenance operations.

These operations are essentially the only ones that have a potential for supporting an explosion.....

"The consequences of an explosion are similar to those of a fire.

The

-amount of plutonium reaching or passing through the filters is estimated to be

~

the same as that estimated for the fire (53 pCi alpha] and would have the same relatively minor offsite consequences."

[End of quote]

2.2.6.3 Calculations of Doses For the accidental releases above, GESHO assumed the nearest resident was at 500 m.

GESHO used a chi /Q of 1.3 x 10 4 for Pasquill Stability Category D, wind speed 3 m/s, and 10 meter release height.

GESMO assumed the plutonium to be soluble.

The following dose commitments were calculated for GESMO:

1 l

Type of accident Dose commitment (rem)

Criticality 0.36 (thyroid)

Fire 0.02 (bone)

Explosion 0.02 (bone)

I l

Using the standard assumptior.3 in this Regulatory Analysis, doses would be slightly higher than those in GESMO.

2.2.6.4 Implications for Emergency Preparedness The GESMO analysis concluded that the design of plutonium fuel fabrication plants is adequate to prevent releases that would cause doses exceeding protec-tive action guides. Thus special emergency preparedness would not be needed offsite.

In addition, GESMO (page II-10) concluded there was little threat from the ingestion pathway.

r "A study of indigenous and experimental animals kept for long periods in areas heavily contaminated with plutonium indicates that direct uptake of plu-tonium was small.

Plutonium uptake by plants from soil and growth media has o

been investigated in the field and in the laboratory under a variety of condi-tions.

The concentration of plutonium in plants on a dry weight basis was never 58

~ ~ - - _ _ _ _

more than one thousandth of that in the growth medium, and only about one ten thousandth of that in the soil.

The fraction of available plutonium absorbed from the gastrointestinal tract of animals grazing on contaminated vegetation is less than one ten thousandth the total intake of the element and measurements of plutonium transfer from the blood stream to milk suggest a further reduction in plutonium concentration by another factor of at least 10.

Consumption of animal products by man will introduce another reduction-factor of at least 10 4 in the plutonium concentration entering the systemic circulation, except in the very young infant where the factor may approach 0.01.

It appears, therefore, that the possibility of transfer of plutonium from soil to man by way of the food chain is negligible."

2.2.7 Spent Fuel Storage

  • Spent nuclear power plant fuel may be stored in pools of water, in dry storage casks, in drywells, or dry vault storage.

Each of these methods is discussed in this section.

2.2.7.1 Accident History There have been no accidents associated with spent fuel storage that have had any significance for offsite radiation exposure. Radioactive material has escaped to storage pool water when casks containing damaged fuel elements were opened.

However, these events have no significance for offsite emergency preparedness.

  • Source terms in this section were developed with the assistance of Fritz Sturz, Advanced Fuel and Spent Fuel Licensing Branch, Office of Nuclear Materials Safety and Safeguards, NRC.

59

A 2.2.7.2.,ccident Source Term Pool storage:

Pool storage for spent' fuel storage in pools, possible accidents and their effects are discussed in a generic environmental impact statement, NUREG-0575.*

The accidents considered are:

1.

The rupturing of fuel pins due to the drop of a fuel' assembly 2.

A tornado driven utility pole strikes the pool at the worst possible angle and ruptures a 45 foot row of assemblies 3.

Fires and explosions 4.

A criticality accident 5.

High radioactivity in the pool water 6.

Rupture of a waste tank or piping 7.

Lowering of the water level in the pool 8.

Loss of the ability to cool the pool water Of these accidents, the generic environmental impact statement for pool storage estimated that the most serious of these accidents is the rupture of a large number of fuel assemblies by a' tornado-driven missile.

The statement calculated the release of radioactivity to be 19,000 curies of krypton-85 and l

0.00006 curies of iodine-129.

(Actually, I-129 is of only academic interest.

Due to saturation, the 5-rem thyroid dose used as the protective action guide cannot be reached.)

A more recent NRC report on pool storage evaluated accident consequences for the General Electric fuel storage facility in Morris, Illinois.** The most serious accident was considered to be the drop of a fuel storage basket in the water of the storage pool.

The maximum drop would be about 7 m.

While experience with similar drops indicates that only minor damage to a fuel

  • NUREG-0575, Generic Environmental Impact Statement on Handling and Storage of Spent Light Water Power Reactor Fuel, pp 4-17 to 4-22, Volume 1, August 1979.
    • NUREG-0709, "Safety Evaluation Report related to the Renewal of Materials License SNM-1265 for the Receipt, Storage, and Transfer of Spent Fuel Pursuant to 10 CFR Part 72 - Morris Operation - General Electric Company -

dom +t Nos. 70-1308 and 72-1," July, 1981, Chapter 7.

60

assembly would result, the calculations assumed that all the fuel rods in four PWR fuel bundles would rupture and that all the plenum gases would be released to the pool water.

The release was calculated to be about 6000 Ci of Kr-85 and 0.00008 Ci of I-129.

Several other types of accidents were also analyzed for the GE-Morris facility.

A loss of basin water was considered to be not credible, an earth-quake was estimated to cause minimal offsite radiological consequences, a tornado-driven missile was estimated to cause the same release as the fuel-basket drop, and a criticality was estimated to cause minimal offsite doses.

I Dry cask storage:

The accident assumed for this analysis is the removal of the lid of a dry cask in which all the fuel rods have been damaged.

The gaseous activity in the gap between the fuel and cladding is assumed to be released.

From NUREG-0575* 10% of the krypton-85 and 1% of the iodine-129 activities are assumed to be in the gap.

The cask is assumed to hold 24 PWR spent fuel assemblies.

The fuel is assumed to be less than 5% by weight uranium-235.

The fuel burnup for this analysis is assumed to be 33,000 megawatt-days per metric ton of uranium.

The fuel is assumed to have been removed from the reactor core 5 years earlier.

Using these assumptions the activity released from a cask would be 8,000 curies of krypton-85 and 0.004 curies of iodine-129.

Drywell and dry vault storage: While the number of fuel rods may be larger than assumed for dry cask storage above, it is reasonable to assume that a single accident would not damage a larger number of fuel rods than assumed above for dry cask storage.

Therefore, the dry cask storage source term is also appropriate for drywell and dry vault storage.

2.2.7.3 Calculations of Doses Dose estimates previously published by the NRC staff for the pool releases described above are given in Table 10.

  • NUREG-0575, op. cit., Volume 1, p. 4-18.

61

Doses for the dry cask storage accident described above calculated in this analysis are also shown in Table 10.

The effective dose equivalent for F, 1 m/s meteorology would be 0.003 rem and the child's thyroid dose would be 0.04 rem.

For D, 4.5 m/s meteorology, the child's thyroid dose would be 0.005 rem.

2.2.7.4 Implications for Emergency Preparedness The doses shown in Table 10 are below the EPA's protective action guides for taking protective action after an accident.

Therefore offsite emergency preparedness is not necessary for spent fuel storage either in dry casks or in pools.

2.2.8 New Fuel Storage New fuel will at times be stored prior to being loaded into a nuclear power plant core.

Stored new fuel does not require any offsite emergency preparedness because of its minimal hazard.

By comparison with spent fuel storage just discussed, no fission products are present.

Thus no volatile radioactive materials are present, and no driving force, such as decay heat, is present to cause the uranium fuel to escape its cladding and become airborne, i

l 2.2.9 Reprocessing of Spent Fuel Spent fuel reprocessing is the mechanical and chemical processing of spent nuclear fuel to extract enriched uranium and plutonium from the fuel elements so they can be used in new fuel elements.

Radioactive fission products are removed from the spent fuel and processed into high-level radioactive waste.

Currently, no reprocessing plants are licensed by NRC to operate in the U.S., nor are there any near term prospects for licensing any reprocessing plants.

However, the Nuclear Fuel Services reprocessing plant in West Valley, New York, operated as a commercial plant under NRC license for many years, and reprocessing plants have been operating in the U.S. weapons program for over 40 years.

In addition, reprocessing plants are operating in several foreign countries.

62

Table 10.

Calculated Releases and Doses from Spent Fuel Storage Accidents-Kr-85 Skin Effective Dose Thyroid Reference Accident Release Dose Equivalent I-129 Release Dose Storage in pools:

Tornado driven 19,000 Ci 0.06 rem Not calculated 0.00006 Ci 0.03 rem Generic Environmental missile followed at 275 m at 275 m-Impact Statement, by calm NUREG-0575 Storage in pools:

Drop of

e. fuel 6,000 Ci Not 0.016 rem 0.00008 Ci 0.0004 rem i

GE-Morris SER, storage basket calculated at 150 m

'at 150 m NUREG-0709 Dry cask, drywell, Removal of cask 8,000 Ci Not 0.003 rem 0.004 Ci 0.005 to or dry vault lid with all fuel calculated at 100 m 0.04 ren storage: NUREG-1140 elements ruptured within 100 m c}

(child)

I f

2.2.9.1 Accident History The Nuclear Fuel Services reprocessing plant was plagued by many small releases into ground water, surface water, and air as well as unusually high occupational radiation exposures.

However, the plant never had an accident of significance for offsite emergency preparedness.

Several criticality accidents, as listed in Table 5, have occurred in spent fuel reprocessing or in processes similar to tFose that would be used in spent fuel reprocessing plants.

No other accidents of significance offsite are known to have happened in spent fuel reprocessing.

2.2.9.2 Accident Source Terms

  • Accident source terms for a reprocessing plant were analyzed in GESMO, and are quoted below.

"Upper level accidents that may occur at separations facilities or Pu02 conversion facilities include:

Criticality High level radioactive waste concentrator or calciner explosion Plutonium product concentrator explosions Criticality Accident "A criticality accident is unlikely in a separations facility or Pu02 conversion facility, because equipment and process limitations are designed to prevent such incidents.

Safe spacing is assured in storage basins by physically spacing the fuel elements in storage racks in a safe array.

Process systems and controls are designed to prevent an unsafe condition.

Nevertheless, a criticality accident of 1018 fissions is assumed.

This yield is approximately an order of magnitude greater than the yield that has been experienced for Pu systems in past accidents.

It is further assumed that all noble gases and 50%

^From GESM0, pages IV E-39 to IV E-42.

64

of the halogens (or halides) are discharged from the plant stack.

The dose commitments would be essentially the same for UO2 fuel or M0X fuel.

Waste Concentrator Explosion Accident "During operation of the separation facility solvent extraction process, solvent degradation-products are generated and may be carried over into the waste streams.

Under extreme conditions in early pilot plant operations, these nitrated degradation products (red oil) have caused concentrator explo-sions.

However, red oil explosions can be prevented by installing equipment to eliminate the accumulation of organic materials in the waste, and by con-trolling the process temperature in the concentrator.

"Concentrators are installed in highly shielded cells, having a volume of 3

about 100,000 cu ft (3,000 m ).

In the unlikely event of an accident, the explosion is estimated to disperse about 150 gallons (600 litors) of high level radioactive waste solution into the cell in the form of a finely divided mist.

A substantial portion of the mist would rain out or plate out on the a

cell surfaces. Droplets remaining in the air (10 mg/m ) would be carried through the ventilation ducts to the high efficiency filters.

Moisture sepa-rators upstream of the filters would knock out most of the mist.

"The plant ventilation filters are located some distance from the separa-tion plant process cells.

Most of the explosive energy would be expended in destruction of the concentrator.

Pressures developed by the explosion would be dampened by expansion into the cell and would be further attenuated in the ductwork.

The final filters are not expected to be affected.

"It has been estimated that plateout of the droplets on the cell walls and floors and removal by the filtration system will result in a reduction in the fraction of material released to 3.6 x 10 8 Material leaving the final filter has been estimated to be 30.5 mg of high level radioactive waste solution in the form of an aerosol.

"Table IV E-16 identifies those nuclides that would contribute significantly to the offsite dose, and summarizes the offsite bone dose commitment that might result from this hypothetical accident.

The maximum offsite dose commitment to an individual is estimated to be about 2.6 mrem (bone) for UO2 fuel, and about 6.9 mrem (bone) for MOX fuels.

65

"Table IV E-16 WASTE CONCENTRATION EXPLOSION EFFECTS Radioactivity Released Accident Bone in Accident Dose Contribution Nuclide Half Life mci mrem UO Fuel M0X Fuel 00 Fuel.

M0X Fuel-2 2

Pu 0.02 0.15 0.01 0.06 242Am-

'458y 0.007 0.05 0.02 0.17 242Cm 162d 0.76 12.3 0.04 0.60 244Cm 18y 0.05 3.25 0.07 4.38 90Sr 29y 2.80 1.62 1.92 1.14 106Ru ly 2000.

3400.

0.02 0.04 144Ce 284d 27.

23.

0.04 0.03 Other F.P.

1. 5
1. 5 0.48 0.48 Total 2.6 6.9 "Table IV E-17 shows the radionuclide releases and the bone dose commit-ment to the maximally exposed offsite individual....

Table IV E-17 "PLUT0NIUM PRODUCT EVAPORATOR EXPLOSION EFFECTS Radioactivity Released Accident Bone in Accident Dose Contribution Plutonium mci mrem Fuel M0X Fuel 00 Fuel MOX Fuel Isotope Half Life U02 2

238 86y 1.02 2.11 5.94 12.27 239 2.4 x 104y 0.08 0.04 0.51 0.28 240 6,540y 0.11 0.13 0.76 0.88 241 13y 2.94 4.01 3.98 5.42 Total 11.2 18.9 End of Quote b

66 w

Plutonium Concentrator Explosion Accident ~

"The postulated explosion of a plutonium concentrator in the reprocessing plant is typical of upper level accidents by which plutonium could be released to a cell or glovebox area. ~ Typically, the plutonium processing equipment tends to be smaller, and installed in smaller rooms (cells or gloveboxes) than the waste concentrator previously discussed.

The release rate is derived by assuming that the room (cell or glovebox) atmosphere contains the same mass of aerosol 3

(10 mg/m ) as the atmosphere of the waste concentrator cell.

For a 1,000 m3 plutonium concentrator cell volume, the postulated accident would release about 2.2 mg of plutonium.

2.2.9.3 Calculations of Doses l

1 1

The doses below for these accidents are taken directly from GESMO, page IV E-40.

"Maximum Offsite Individual Dose Commitment (rem)

Accident PWR MOX Fuel Criticality 0.056 (thyroid)

Waste Concentrator Explosion 0.0069 (bone)

Pu Evaporator Explosion 0.019 (bone)

Fire 0.0135 (bone)

End of Quote 2.2.9.4 Implications for Emergency Preparedness According to the GESMO analysis accidents at reprocessing plants would not cause doses in excess of protective action guides.

This is primarily due to lack of strong driving forces and extensive containment systems.

Thus special emergency preparedness is not needed offsite.

2.2.10 Research with Nuclear Fuels These facilities perform research and development related to nuclear power plant fuel manufacturing and testing.

They use special nuclear materials 67

in-forms ranging from powders to solutions, although larger quantities are usually in the form of fuel pellets.

The work takes place in laboratories and glove box trains.

Processes such as blending, crushing, milling, sintering, grinding, and solvent extraction may take place.

2.2.10.1 Accident History A number of the accidents previously discussed for other parts of the fuel cycle are relevant to research with nuclear fuels.

For example, if the facility handles large quantities of enriched uranium, criticalities as listed in Table 5 could occur.

In addition, fires and other types of accidents such as those listed in Tables 6 and 7 could occur.

Since these types of accidents have been discussed previously, they will not be discussed further here.

2.2.10.2 Accident Source Terms Sutter* has analyzed nuclear fuel research facilities and concluded that the potential accidents are criticality accidents, spills and leaks, tornados, earthquakes, fires outside the facility, fires inside the facility, explosions, and fuel handling accidents.

If large quantities of material are handled a criticality accident may be a possibility.

If this is the case, the releases and offsite doses would be the same as those discussed in Section 2.2.5.2 for criticalities at fuel fabrication plants.

The other possible accidents of significance would be a major fire in the facility such as a fire in a glove box train.

If the fire does not break the glove box filters and the final HEPA filters, the release to the environment would be negligible.

However, if both sets of filters are breached a consider-able release is plausible.

Assuming 13 glove boxes are in the train, 2 kg of material is present in each, and 0.1% becomes airborne due to the fire, a release of 0.026 kg would be calculated.

This would be uranium or plutonium, whichever was being processed, although at this time no licensees are handling such quantities of plutonium.

  • Sutter, Op. cit.

68

2.2.10.3 Calculations of Doses Doses due to a criticality would be the same as discussed previously.

A fire involving low enriched uranium (solubility class Y) would result in an effective dose equivalent within 100 m of 0.007 rem for F, 1 m/s meteorology and 0.001 rem for more typical D, 4.5 m/s meteorology.

Inhaled quantities are well-below levels where chemical toxicity is observed.

The dose calculations assumed that the building size was 25 m x 10 m, the release was at ground level, and the release duration was 30 minutes.

If plutonium-239 were the fuel rather than uranium, the effective dose equivalent from the fire would be about 67 rems for typical D, 4.5 m/s meteor-ology and 500 rems for conservative F, 1 m/s meteorology.

The dose calculations for uranium and plutonium consider an insoluble class Y compound.

However, the plutor,ium dose was calculated assuming that plutonium facility would have the same containment capability as uranium facilities would be expected to have.

Since superior containment is provided for plutonium, the offsite doses presented here are probably larger that could actually be by quite a large margin.

For example, we assume 0.1% release for the involved plutonium.

By comparison the actual release for the Rocky Flats fire discussed previously was 10 8, a hundred-thousand times lower.

2.2.10.4 Implications for Emergency Preparedness Criticality, as discussed previously, may require some emergency prepared-ness.

Other accidents at facilities handling uranium would not seem to require emergency preparedness.

Plutonium processing, on the other hand could cause large doses offsite if not contained.

We therefore conclude that for plutonium research and development activities the need for offsite emergency preparedness should be evaluated on a case by case basis.

2.3 Byproduct Material Facilities There are six types of byproduct material licensees that handle large enough quantities of radioactive material not in sealed form so that need for offsite emergency preparedness should be considered.

These are:

radio-pharmaceutical manufacturing, radiopharmacies, sealed source manufacturing, 69 y

university research laboratories, waste warehousing, and fabrication of depleted uranium products.

.2.3.1 A Generic Overview We will consider each of these types of facilities separately rather.than.

as a single group.

The reason-is that we wish to determine whether accident scenarios and release fractions developed for each type can be generalized into a single set of accident scenarios and release fractions.

But first, we will consider certain common or generic characteristics of byproduct material licensees.

(

2.3.1.1 Accident History The accidents involving release of byproduct material from all types of facilities handling byproduct material are listed below in Tables 11 and 12.

The reason for combining all types of facilities in these tables is that the experience of one type of facility may be relevant to other types of facilities.

Fcr example, a fire or explosion in a glovebox or hot cell is an accident that could happen at almost any type of major byproduct handling facility.

The rele-l vant accidents listed in Tables 11 and 12 will be discussed in later sections, f'

Overall, accidents involving byproduct material have led to small offsite l

doses.

Releases have always been below the EPA's protective action guide lower limit of 1 rem. 'Thus, no emergency protective' actions have ever been necessary to protect people offsite from airborne releases of radioactivity.

2.3.1.2 Release Fractions for Accident Source Terms

  • l The release fractions selected are given below along with the reasons for selecting them.

l Noble gases (1.0):

Kr and Xe were assigned a release fraction of 1 because they are always gases at room temperature, they do not plate out, they are not retained by filters, and they do not react chemically to form less volatile compounds.

  • This section prepared with the assistance of Mark Halverson, Pacific North-west Laboratory, who compiled the references upon which the releese fractions are based.

70

Table 11.

Fires and Explosions Involving Release of Byproduct Materials through 1986 Date Facility Release Description 4-23-50 Lawrence Radiation Minor Multistory research build-Lab, S.F., CA ing destroyed by fire.

2-21-55 AEC Contractor Minor Spontaneous ignition fire broke out in nitric acid saturated rags and paper in a contaminated waste storage area of a chemical process laboratory.

l 10-8-59 Mound Laboratory, Po-210 Explosion in drybox l

Miamisburg, OH contamination disperses Po-210.

Lab tech (Fuel R&D) in laboratory.

combined acetone wash with 1

39 Ci released nitric acid solution.

onsite 11-10-60 Laboratory at None An overheated oil both Univ. of Calif.,

started a fire in a process-Berkeley, CA ing cave handling curium.

No exposures and no contami-nation outside cave.

12-29-60 University of Some Fire caused loss of some Alabama radioactive materials.

(Laboratory) 4-5-61 U.S. (location 1 mci.

Minor Radiochemistry building unspecified) contamination fire.

9-25-64 AEC 2.5 g of Shipping container contractor americium explosion.

4-20-69 Babcock and Co-60 A bag of Co-60 contaminated Wilcox contamination paper was put in nonradio-of incinerator active trash and burned in of 10 mR/hr incinerator.

8-30-76 Hanford Site -

300 Ci Am-241 Explosion of an ion Plutonium Worker seriously exchange column containing Plant contaminated.

100 g (300 Ci) of Am-241.

Negligible 1 to 5 Ci deposited on a release to worker's skin and clothing.

environment.

5 mci remained on body after initial washing.

Inhalation uptake by lung estimated at 0.05 mci.

71

Table 12.

Accidental Releases of Byproduct Material Except Fires and Explosions through 1986 Date Facility Release Description 7-25-58 Los Alamos H-3, minor H-3 gas escaped.

Scientific Lab.,

Los Alamos, NM 8-24-62 Phillips Petroleum I-131 leaked Leaky shipping cask contaminated Co., Idaho Reactor from cask.

truck and cask.

Test Site, Idaho Dose of 5 R/hr Falls, 10 on surface 1-23-64 Hanford Laboratory, Sr-90 While workers were replacing Richland, WA an agitator on a waste storage tank, convection currents carried contaminated vapor from the open top of the tank to the environment.

1-15-67 Babcock and Wilcox, Ir-192 onsite Technicians cut into an Ir-192 Apollo, PA pellet in hot cell.

Ventilation j

imbalance allowed Ir-192 to j

escape to working area.

4-4-67 Savannah River H-3 released An electric welder malfunctioned Laboratory, through stack.

causing the failure of a seal Aiken, SC Minor tube which released H-3 tostack.

9-27-68 U.S. (location Low level A cask of canned waste was not reported) waste dumped into an underground contamination caisson.

Radioactive dust escaped contaminating the cask, its truck, and workers.

5-5-69 U.S. Naval Ammuni-Minor quantity Released to atmosphere tion Facility of Kr-85 8-6-70 Lawrence Radiation H-3 acci-Automatic safety devices Laboratory, dentally failed.

Berkeley, CA discharged through 100-ft stack 9-17-73 Rocky Flats, H-3 released Water not known to be contam-Golden, C0 to water inated with H-3 released to plant waste stream.

5-2-74 Savannah River H-3, 50 g Failure of a pipe fitting Laboratory, allowed H-3 to be discharged Ailen, SC through stack.

72

Table 12.

(continued)

Date Facility Release Description 1978 American Atomics 287,000 Ci "Normal operating losses," Some calendar Corp, Phoenix, AZ of H-3 food prepared nearby contained year H-3 in concentrations above EPA drinking water standard of 0.02 uCi/t (4 mrem /yr for 2 liter / day consumption).

(This was not an accidental release, but is included because of the large quantity of material released.)

9-1-80 New England Nuclear, Am-241 inside Airborne Am-241 while renovating N. Billerica, MA plant contaminated gloveboxes.

7-24-81 New England Nuclear, 3.2 Ci of S-35 Released during opening of l

N. Billerica, MA 2 capsules containing 30 Ci i

of S-35.

11-19-81 Tech / Ops, Ir-192 Ir-192 surface contamination 12-12-81 Burlington, MA surface found in lab.

Escape path from hot cells not discovered.

8-27-82 Consolidation Coal Up to 0.5 Ci A stuck well logging source Company, Library, of Am-241 in was cut by a drill bit during PA drilling mud recovery operations.

Because the leak went unrecognized, some Am-241 activity was tracked into homes and businesses.

2-8-83 Gulf Nuclear, Inc.

Am-241 inside A 20 Ci Am-241 sealed source was Webster, TX plant accidentally cut open on a cut open on a lathe during machining.

Six employees were exposed.

9-13-83 Shelwell Services, Cs-137 on 2 Ci Cs-137 sealed source cut Inc., Hebron, OH workers shoes open on lathe.

Some CsC1 powoer and clothing spilled out.

Shop contaminated.

15 homes contaminated by Cs-137 from workers shoes and clothing.

73

Volatile and combustible compounds (0.5):

A release fraction of 0.5 was assigned to volatile and combustible elements and compounds, for example, hydrogen, phosphorous, sulfur, iodine, bromine, and chlorine.

Releases of these materials would be expected to be less than 100% due to these factors:

(1) some of the compounds of the elements may form some nonvolatile compounds (ash) in a fire, (2) some of the compounds of the elements will plate out and deposit on internal surfaces, (3) some of compounds of the elements will be subject to retention by filters, (4) not all containers possessed by a licensee would be likely to be breached in an accident, (5) at any particular time the actual inventory may be below the licensed possession limit, and (6) some

. particles formed may not be respirable.

Consideration of site specific factors could cause considerable reductions in the release fractions for specific facilities.

With respect to I-131, experimental releases from a fire with the I-131 in a flammable solvent were 65%.

If the container was subsequently heated afterwards with a prorane torch the release reached 83%.* Other factors as mentioned above would reduce the quantity that would actually escape the

~

building.

The elements listed above could be used in nonvolatile and noncombustible forms, for example, the chlorine in sodium chloride.

For those situations, the licensee would have to apply for a site-specific release fraction based on the chemical forms used.

Carbon (0.01):

Carbon compounds are generally combustible.

However, most of the carbon would be emitted ai carbon dioxide.

Carbon dioxide is relatively inert and is not significantly deposited in the lungs or on surfaces.

Thus, carbon dioxide containing radioactive carbon is of little biological significance compared to other forms of carbon. We have assumed that the release fraction for carbon in forms other than carbon dioxide is 0.01, the value given below for semi-volatile compounds.

Semi-volatile compounds (0.01):

These include compounds of the elements selenium, mercury, cesium, polonium, tellurium, and ruthenium.

Releases of Cs-137 at 1000 C have been measured at 1%/hr,* 1.5%/hr,** and 4.2%/hr.t

  • A. E. Albrethsen and L. C. Schendiman, "Volatilization of Fission Products from High-Level Wastes," BNWL338, Pacific Northwest Laboratory, 1967.

I

    • W. J. Gray, "Volatility of a Zinc Borosilicate Glass Containing Simulated High-Level Radioactive Waste," BNWL-2111, Pacific Northwest Laboratory, 1969.

tD. Walmsley et al, "Volatility Studies of Glasses for the Fingal Process, AERE-R-5779, England, 1969.

74

Additional removal by filter retention and condensation was measured at 35 to 93% removal, and an additional 30% removal by deposition was measured.*

Polonium-20 is generally found in a liquid, with a bismuth metal slug, or bound to ceramic microspheres.

These forms of polonium-210 should generally have a relatively low release fraction.

Based on the assumption of a 30-minute fire, an assumed release fraction of 0.01 is believed to be reasonable for semi-volatile compounds.

Unknown form (but not generally volatile or combustible) (0.01):

For use in screening analyses in which the chemical form of a radioactive material is not known, a release fraction of 0.01 is assumed.

This value does not apply to Kr, Xe, H, C, P, or S, which were assigned different values above.

It does not apply to V, Pu, Am, or Cm, which are assigned a reinase fraction of 0.001 on the basis of their general form as nonvolatile powders as explained below.

It also does not apply to Co, Ta, and Ir, which are assigned a release fraction of 0.001, as explained below.

The 0.01 release factor for unknowr. form should be used only for screening.

For specific fccilities, the actual chemical form of the radioactive material could be used to determine an appropriate (generally lower) release fraction.

Nonvolatile powders (0.001):

Release fractions for nonvolatile compounds are given as the fraction of material released which is of respirable size.

Most experiments report total release fraction.

To convert these to respirable release fraction, the release of particles larger than 10 microns was excluded from the respirable release fraction.

Most reported experiments provide enough information to allow this determination, but some do not.

For experi-mants providing no information on particle size, it is necessary to estimate respirable release fractions from total release fraction; by assuming that the respirable proportion will be similar to that reported in similar experiments.

A release fraction of 0.001 was assigned to nonvolatile compounds in powder form.

The mechanism is not volatilization.

Rather it is entrainment of the particles in an airstream.

Even finely ground powders will generally contain less than a few percent of the powder in respirable size.

The frac-tion of particles of respirable size is kept small by the difficulty in pro-ducing all small particles and subsequently by agglomeration and weathering,

  • R. K. Hilliard, "Fission Product Release from Uranium Heated in Air," HW-60689, Hanford Atomic Products Operation, 1959.

75

processes which cause micron-sized particles to stick to surfaces, to larger particles, anci to themselves.

Particles larger than respirable size (>10 microns aerodynamic median diameter) quickly settle out of the air, and if inhaled seldom are deposited in the lungs.

The release fraction of 0.001 is suggested by a number of experiments generally designed to maximize the release.* The experiments usually found releases of respirable size particles of about 0.001 or less.

In a few special cases designed to produce maximum releases, values above 0.001 were found.

These conditions were for highly ground powders on certain flammable surfaces such as rubber or plexiglass, for high velocity air flow, or for highly pres-surized releases in which all the material is violently thrown into the air, which is then sampled before significant settling can occur.

Such conditions are not considered representative of realistic accident conditions.

Uranium metal and plutonium metal (0.001):

These materidls are pyrophoric.

The release fraction of 0.001 is representative of experimental measurements described in Section 2.3.7.2.

Nonvolatile solids (0.0001):

For nonvolatile compounds in solid form rather than powder form, a release fraction of 0.0001 was assumed to reflect the lower amount of material that would be of respirable size.

This value could be applied to cobalt, iridium, and tanalum in solid form on a case by case basis.

Nonvolatile elements in flammable liquids (0.005).

A release fraction of 0.005 was assigned to nonvolatile compounds in flammable liquids.

Experiments with strontium in a flammable solvent yielded a release frac-tion of 0.002 from a fire.**

Releases of uranium in flammable solvent averaged 0.00026, releases of cesium averaged 0.0024, releases of cerium averaged 0.0065, and releases of zirconium also averaged 0.0065.**

When the container in those experiments were

  • J. Mishima, L. Schwendiman, and Radasch, "Plutonium Release Studies III.

Release from Heated Plutonium Bearing Powers," BNWL-786, Pacific Northwest

(

Laboratory, Richland, WA,1968.

J. Mishima and L. Schwendiman, "Fractional Airborne Release of Uranium (Representing Plutonium) During the Burning of Contaminated Wastes," BNWL-1730, Pacific Northwest Laboratory, Richland, WA, 1973.

S. Sutter, Johnson, and J. Mishima, "Aerosols Generated by Free Fall Spills of Powders and Solutions in Static Air," PHL, HUREG/CR-2139, PHL-3786, 1981.

    • S. L. Sutter et al, "Fractional Airborne Release of Strontium During the Combustion of 30% Normal Tributyl Phosphage in a Kerosine Type Diluent,"

BNWL-B-358, Pacific Northwest Laboratory,1974.

76

subsequently heated with a propane torch uranium releases were 0.003, cesium releases averaged 0.006, cerium releases averaged 0.0074, and zirconium averaged 0.004.*

For UO2 powder in gasoline, release fractions were 0.0012 when airflow was 1.8 m/s.**

Of this, 66% was less than 10 micron AED*** for a respirable release fraction of 0.0008. When airflow increased to 8.9 m/s, the release fraction increased to 0.013,* but only 7%** was smaller than 10 microns, thus the respirable release fraction was 0.0009, about the same as with the lower airflow.

In other experiments on burning of kerosene-based solvent releases of Ru-106 were below 0.1% and releases of uranium and plutonium were much lower.t Nonvolatile compounds in nonflammable liquids (0.001):

Nonvolatile compounds in nonflammable liquids are assigned a release fraction of 0.001.

Several studies have measured releases in these circumstances.

In general, release of these compounds can be expected to be small until the liquid is dried.

After drying release fractions generally remain small because the material normally cakes on the substrate or binds into particles too large to be respirable.

2.3.1.3 Quantities Requiring Consideration of Emergency Preparedness Table 13 lists the quantities requiring consideration of emergency preparedness based on the quantities needed to deliver a 1-rem effective dose equivalent offsite.

The quantities Q in Table 13 were calculated using the 4

following equation:

9

  • RF (Hy4 + GCi + HCSi) 1 4
  • J. Mishima and L. C. Schwendiman, BNWL-B-274, 1973, op. cit.
    • J. Mishima and L. C. Schwendiman, BNWL-1730.
      • J. Mishima and L. C. Schwendiman, BNWL-1732, tD. Whitney Tharin, Jr., "Burning of Radioactive Process Solvent, Savannah River Laboratory Report OP-942, Aiken, South Carolina, 1965.

77

4 1

Table 13. Quantities of Radioactive Materials Requiring Evaluation of the Need for Offsite Emergency Preparedness.

(Based on 1 rem effective dose equivalent'outside the building.)

Dose conver--

sion factor Radioactive (rems /uCi.

Solubility -Release Quantity Quantity material inhaled)*

class **

fraction

_(weight)

(curie) 0.5 20,000 H-3

.00012 0.01 (non CO )

50,000 C-14

.0021 2

Na-22

.0076 D

0.01 9,000 Na-24

,0012 0

0.01 10,000 P-32

.015 W

0.5 100 P-33

.0023 W

0,5 1,000 0.5 900 S-35

.0025 Cl-36

.022 W

0.5 5,000 K-40

.012 D

0.5 50,000 K-42

.0014 0

0.01 9,000 Ca.0065 W

0.01 20,000 Sc-46

.029 Y

0.01 3,000 Ti-44 1.0 Y

0.01 100 V-48

.010 W

0.01 7,000 Cr-51

.00033 Y

0.01 300,000 Mn-54

.0067 W

0.01 10,000 Mn-56_

.00037 0

0.01 60,000 Fe-55

.0027 D

0.01 40,000 Fe-59

.015 0

0.01 7,000 Co-60

.22 Y

0.001 5,000 0.01 20,000 Ni-63

.0063 Cu-64

.00027 Y

0.01 200,000 Zn-65

.02 Y

0.01 5,000 Ge-68

.051 W

0.01 2,000 Se-75

.0084 W

0.01 10,000 1.0 6,000,000-Kr-85 Rb-86

.0066 0

0.01 20,000 Sr-89

.041 Y

0.01 3,000 Sr-90 1.3 Y

0.01 90 Y-91

.048 Y

0.01 2,000 Zr-93

.32 0

0.01 400 Zr-95

.024 0

0.01 5,000

  • This column is also roughly equal to the maximum dose in rems per curie released because the maximum intercept fraction is 10 8 and the inhalation pathway dominates the dose for most materials.
    • Solubility classes for materials in the lung as defined in ICRP Publica-tion 30.

D = days, W = weeks, and Y = years.

78

Table 13.

(continued)

Dose conver-sion factor Radioactive (rems /uCi Solubility Release Quantity Quantity material inhaled) class fraction.

(weight)

(curie)

Nb-94

.41 Y

0.01 300-Nb-95

.0057 Y

0.01 10,000 Mo-99

.0039 Y

0.01 30,000 Tc-99

.0082 W

0.01 10,000 Tc-99m

.000032 0

0.01 400,000 Ru-103

.0089 Y

0.01 10,000 Ru-105

.00045 Y

0.01 70,000 Ru-106

.47 Y

0.01 200 Ag-110m

.08 Y

0.01 1,000 Cd-109

.11 0

0.01 1,000 Cd-113m 1.5 0

0.01 80 In-114m

.088 D

0.01 1,000 Sn-113

.011 W

0.01 10,000 Sn-123

.032 W

0.01 3,000 Sn-126

.087 W

0.01 1,000 Sb-124

.025 W

0.01 4,000 Sb-126

.012 W

0.01 6,000 Te-127m

.021 W

0.01 5,000 Te-129m

.024 W

0.01 5,000 I-125*

.79 D

0. 5 7

I-129*

saturates 0.5 infinite I-131*

1.1 D

0.5 5

Xe-133

1. 0 900,000 Cs-134

.046 D

0.01 2,000 Cs-137

.032 D

0.01 3,000 Ba-133

.0078 0

0.01 10,000 Ba-140

.0037 0

0.01 30,000 Ce-141

.0089 Y

0.01 10,000 Ce-144

.37 Y

0.01 300 pm-145

.025 W

0.01 4,000 Pm-147

.026 W

0.01 4,000 Sm-151

.03 W

0.01 4,000 Eu-152

.22 W

0.01 500 Eu-154

.28 W

0.01 400 Eu-155

.041 W

0.01 3,000 Gd-153

.024 0

0.01 5,000 Tb-160

.025 W

0.01 4,000 Ho-166m

.77 W

0.01 100 Tm-170

.026 W

0.01 4,000 Yb-169

.008 Y

0.01 10,000 Hf-172

.32 0

0.01 400 Hf-181

.015 0

0.01 7,000 Ta-182

.044 Y

0.001 20,000

  • Child's. thyroid.

79

Table 13.

(continued)

Dose conver-s1on factor Radioactive (rems /uCi Solubility Release Quantity Quantity material inhaled) class fraction (weight)

(curie)

W-187

.0006' D

0.01 70,000 Ir-192

.0028 Y

0.001 40,000 Au-198

.0032 Y

0.01 30,000 Hg-203

.0073 W

0.01 10,000 T1-204

.0024 0

0.01 50,000 Pb-210 14.

0 0.01 8

Bi-207

.02 W

0.01 5,000 Bi-210

.19 W

0.01 600 Po-210 8.5 W

0.01 10 Ra-226 8.5 W

0.001 100 Ac-227 6600.

0 0.001 0.2 Ac-228

.3 0

0.001 4,000 Th-227 16.

Y 0.001 700 Th-228 250.

W 0.001 5

Th-230 320.

W 0.001 3

l Th-232 1600.

W 0.001 0.7 Pa-231 1300.

W 0.001 0.9 U-232 15.

W 0.001 8

U-233 140.

Y 0.001 8

U-234 130.

Y 0.001 8

U-235 120.

Y 0.001 (4100 kg) 9 U-238 120.

Y 0.001 (30,000 kg) 10 Np-237 490.

W 0.001 2

Pu-236 160.

W 0.001 7

Pu-238 460.

W 0.001 (0.12 g) 2 l

Pu-239 510.

W 0.001 (32 g) 2 Pu-240 510.

W 0.001 2

l Pu-241 10.

W 0.001 100 Pu-242 490.

W 0.001 2

Am-241 530.

W 0.001 2

Am-242m 510.

W 0.001 2

Am-243 520.

W 0.001 2

Cm-242 18.

W 0.001 60 C:n-243 350.

W 0.001 3

I Cm-244 280.

W 0.001 4

l Cm-245 540.

W 0.001 2

l Cf-252 120.

W 0.001 9

0.01 10,000 Any other beta gamma emitter 0.01 1,000 Mixed fission products 0.001 10,000 1

Mixed corrosion products Contaminated equipment, 0.001 10,000 beta gamma i

Irradiated material, 0.01 1,000 any form 80 t

Table 13.

(continued)

Dose conver-sion factor Radioactive (rems /uCi Solubility Release Quantity Quantity material inhaled) class fraction (weight)

(curie)

Irradiated material-solid, noncombustible 0.001 10,000 Mixed radioactive waste, beta gamma except I-125 and I-131 0.01 1,000 Packaged waste, beta gamma

  • 0.001 10,000 Any other alpha emitter 0.001 2

Contaminated equipment, alpha 0.0001 20 Packaged waste, alpha 0.0001 20 "Type B packages assumed to have no release and no need for emergency preparedness, where Q = the quantity of material 1, curies 4

RF

= release fraction of material 1.

(Release fractions are for a g

severe facility fire, which has been identified as the accident wit'h the largest plausible release fractions.)

H

= the effective dose equivalent from material i for the inhalation yg pathway, rems / curie released.

HGCi =

the effective dose equivalent from material i for the ground contamination pathway, rems / curie released.

HCSi =

the effective dose equivalent frem material i for the cloudshine pathway, rems / curie released.

For all materials of greatest interest for fuel cycle and other radio-active material licensees, the dose from the inhalation pathway H will yg dominate the dose.

81 1

n.

z+r o'

y$ was calculated by assuming a maximum plausible intercept fraction for H

non-depositing (non particulate) materials of 10.s.

Thus, Hgg = 10 s x DCF where DCF = dose conversion factor, rems / curie inhaled.

This intercept frac-tion was found to be the intercept fraction that would be calculated a Gaussian plume dispersion model, a distance of 100 meters on the plume centerline, atmospheric stability class F, 1 m/s wind speed, release duration of 30 minutes, building size of 10 m by 25 m, no other obstructions to spread the plume, and no plume rise due to buoyancy.

According to this model intercept fractions would exceed 10 8 at distances closer than 100 meters from the release point.

Such larger intercept fractions are not used because they are not considered physically realistic.

Larger intercept fractions require the assumption that the smoke from a fire will not rise over the heads of people closer than 100 meters and that the people would stand in dense smoke for the full duration of the release. These assumptions are not considered realistic.

Next, a deposition model was added to the meteorological model described above.

A deposition velocity of 1 cm/sec was assumed.

This reduces the j

intercept fraction at 100 meters to 0.9 x 10 8, but adds a dose contribution from ground shine.

Exposure to ground shine for 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> was assumed.

Table 13 includes all radionuclides listed on 20 or more of NRC's approxi-mately 9,000 licenses.

A quantity for I-129 is not included because satura-tion would prevent the thyroid from absorbing enough I-129 to reach the 5-rem l

protective action guide dose.

Table 13 also includes all beta gamma emitters listed on more than one but less than 20 licenses if the quantity that might deliver an effective dose equivalent exceeding 1 rem is less than 10,000 curies.

l Table 13 also includes all alpha emitters listed on more than one but less than 20 licenses if the quantity that might deliver an effective dose equivalent exceeding 1 rem is less than 2 curies.

The quantities in Table 13 are differeat from quantities previously pub-lished in NUREG-0767, "Criteria for Selection of Fuel Cycle and Major Materials Licensees Needing Radiological Contingency Plans," and Federal Register Notices with orders (46 FR 12566) and an Advance Notice of Rulemaking (46 FR 29712).

The main reasons are:

(1) dosimetric models from ICRP Publications 26 and 30 have been used instead of the older models from ICRP Publication 2 and 82

4 (2) release fractions have changed as a result of further study.

Meteorological models are slightly different, but this has a small effect in most cases.

The intercept fraction for inhalation of a material that does not deposit on the ground is 10 8 in both cases.

For particulates, which do deposit on the ground, the dose per curie released can be as much as 11% lower for radionuclides with negligible external dose to about 5 times higher for radionuclides whose major dose pathway is groundshine from material deposited on the ground.* The values in Table 13 include consideration of groundshine.

Quantities ~re also given for certain frequently occurring mixtures of a

radionuclides.

Mixed fission products are assigned the generally applicable release frac-tion cf 0.01 and a quantity of 1000 curies.

This value is typical for fission l

products, assumes that short-lived iodines will not be present, and assumes that no single nuclide will account for more than perhaps 5 to 10% of the activity.

In particular, Sr-90 is likely to be the dominant contributor to dose and is assumed to be no more than 5 to 10% of the activity.

Mixed corrosion products are assumed to be tound to surfaces and thus assigned the smaller release fraction of 0.001.

Cobalt-60 is likely to be the dominant nuclide The quantity assigned is 10,000 curies.

Contaminated equipment, beta gamma is likewise assumed to have a lower release fraction of 0.001 due to bonding to surfaces.

The activity assigned is 10,000 curies.

Sr-90 is assumed to be less than 10% of the activity.

Irradiated material is assigned the same values as mixed fission products because the forms and nuclides are likely to'be similar.

However, solid noncom-bustible irrgdiated material is assigned a lower release fraction of 0.001 and an activity of 10,000 curies.

Mixed radioactive waste, beta-gamma, except I-131 and I-125 is assigned an activity of 1000 curies.

Iodine-131 and iodine-125 are assumed not to dominate the hazard due to their short half-lives.

If significant quantities of iodine would be in the waste, their quantities should be calculated separately.

Packaged waste, beta-gamma is assumed to have one-tenth the release fraction of unpackaged material due to an assumed protection provided by the packaging.

The quantity assigned is 10,000 curies.

  • See Table 5.5 of NUREG/CR-3657 for contributions of each pathway.

83

- +

Contaminated equipment, alpha is assumed to have one-tenth the release fraction of alpha emitters in general due to bonding onto surfaces.

An activity is 20 curies is assigned.

Packaged waste, alpha is assigned an activity of 20 curies because the packages are assumed to provide some protection against release.

Type B packaged waste is assumed to have no significant release because Type B packages are constructed and tested to survive various types of severe accidents including fires.

2.3.2 Radiopharmaceutical Manufacturing These plants produce radionuclide-labeled compounds for medical d.iagnosis and treatment.

Some handle only one or two radionuclides, while othe'.'s handle many.

The radionuclides of most significance are:

H-3, C-14, P-32, S-35, Sr-90, Mo-99, I-125, I-131, and Cs-137.

2.3.2.1 Accident History Of the accidents listed in Tables 11 and 12, two were at radiopharma-ceutical manufacturing plants.

Those are the 1980 inplant contamination with Am-241 and the 1981 release of 3.2 curies of sulfur-35.

Both occurred at New England Nuclear in N. Billerica, Mass.

Doses offsite in both casts would be well below EPA's protective action guides.

2.3.2.2 Accident Source Terms Sutter analyzed potential accidents at radiopharmaceutical manufacturing facilities, ir.cluding loading dock fires, major facility fi9es, tornadoes, earthquakes, spills and leaks, explosions, cyclotron accidents, and fires in waste storage areas.

Fires were seen to have the largest potential releases, and in particular a major facility fire involving all the radioactive material in a building was seen theoretically to yield the largest potential release.

Release fractions for radioactive materials are based on the assumption that alnost all the licensed material is involved in the fire, that storage containers (except sealed sources) are ineffective in protecting the material and limiting releases, 84

f I

and that the fire burns long and intensely.

For these conditions to be met it is likely that the building containing the material would be woodframe or some other combustible,rjdterial, that no automatic sprinkler system or other fire prevention systeciould operate, and that the local fire department would be ineffective in ' fighting the fire. -The entire building and its contents are assumed to be consumed in the firt.

Tabie 14 lists the maximum quantity auth-orized for possession by any licensee and the selease fraction for each radio-nuclide involved in a major facility fire.

Table 14.

Radiopharmaceutical Manufactur.ng:

Maximum Possession Limits, Release Fractions, and Doces Due to a Major Facility Fire Maximum licensed Radioactive possession Releasc-Effective doso material limit (C1) Licensee fraction ~. aquivalent, rem **

H-3 150 000 NEN*

O.5 0.1 to 10.

5 C-14 500 NEN-Boston 0.01*** O to 0.01

'~

P-32 500 NEN 0;5 0.04 to 4.

S-35 1,000 NEN '^

0. 5 0.01 to 1.

s Ca-45 50 NEN-0.01 0 to 0.003 Cr-51 100c NEN 0.01 0

Fe-55 200 NEN' O.01 0 to 0.005 Ni-63 1,000 fiEN 0.01_

0.001 to 0.06 Se-75 100 NEN 0.01 0 to 0.008 Kr-85 10,000 NEN

1. 0 0 to 0.002 Rb-86 50 ^ NEN 0.01 0 to 0.003 Sr-90 500 NEN 0.01 0.05 to 5.

Mo-99 2,000 NEN/Squibb 0.01 0.001 to 0.08 Ru-103 25 NEN 0.01 0 to 0.002 Sn-113 100 NEN 0.01 0 to 0.01 1-125 100 NEN/Mallinckrodt

0. 5 0.3 to 30. (child's thyroid)

I-131

'00 Mallinckrodt 0.5 5 to 500. (child's thyroid)

Xe-133

),900 NEN

1. 0 0 to 0.001 Cs-134 25 NEN 0.01 J to 0.01 Cs-137 500 NEN 0.01 0.002 to 0.2 Ce-141 50 NEN 0.01 0 to 0.004 Yb-169 50 NEN 0.01 0 to 0.004 Tm-170 25 NEN 0.01 0 to 0.006 Au 198 200 NEN 0.01 0 to 0.008
  • NEN = New England Nuclear, North Billerica, Mass.
    • zero in the dose column indicates a dose of less than one millirem.
      • Non-carbon dioxide release fraction.

85

2.3.2.3 Calculations of Doses A range of doses due to release of radionuclides in a major facility fire was calculated to reflect uncertainty in the doses calculated.

The upper end of the range represents the worst-case conditiohs - maximum release fractions, F, 1 m/s weather, and no plume buoyancy.

From Figure 1 it can be seen that more typical weather (0, 4.5 m/s) reduces doses by a factor of almost 8, that assum-ing buoyancy during F, 1 m/s weather reduces doses by a factor of 37, and that assuming both 0, 4.5 m/s weather and buoyancy reduces doses by a factor of 68.

Furthermore releases may be smaller than assurned because of many possible mitigating factors.

We therefore present in Table 14 a range of doses to reflect these uncer-tainties.

The upper end of the range is the worst-case described above and the lower end of the range is that value divided by 100.

The range is considered likely to encompass the dose likely to be received by a person on the plume centerline due to a severe accident.

From Table 14 it can be seen that in only one case is the potential dose significantly larger than the upper end of the EPA's protective action guide range - I-131 at Mallinckrodt.

2.3.2.4 Implications for Emergency Preparedness The radioactive materials possessed by radiopharmaceutical manufacturers might present a potential hazard from H-3, P-32, S-35, Sr-90,1-125, and I-131.

1-131 exceeds the EPA's protective action guides by the largest margin with a dose of 5 to 500 rems to a child's thyroid within 100 m and 0.2 to 20 rems at 1000 m.

All other materials would drop below the lower end of the protective action guide range within 350 to 400 m.

2.3.3 Radiopharmacies and Hospitals Radiopharmacies act as receivers and distributors of radiopharmaceuticals for use by hospitals and medical research facilities.

They are not production In facilities, and thus minimal handling of radioactive materials takes place.

general, either a hospital will have its own radiopharmacy, or, as is currently taking place in the industry, a large metropolitan area will have one or more 86

)

L private radiopharmacy firms serving as central distribution points for the hospitals and research facilities in the area.

A radiopharmacy receives shipments of radiopharmaceuticals from vendors either as bulk quantities or as prepackaged diagncstic kits.

With prepackaged kits, the pharmacy merely holds the material until it is required for use by the hospital.

For bulk quantities, the primary bulk material consists of Mo-99/Tc-99m generators.

The radiopharmacy prepares individual doses by pipetting dose size aliquots into a syringe, which is then transported to its final destination.

This loading of Tc-99m is usually conducted in a fume hood.

If other bulk materials are handled, such as iodine-labeled compounds, they may be dispensed in glove boxes.

2.3.3.1 Accident History There are no known accidents at radiopharmacies or hospitals with any offsite significance.

The events that have been reported are small spills in the laboratory that were cleaned up in a routine manner or surface contamination on packages.

2.3.3.2 Accident Source Terms Sutter considered several classes of accidents and concluded that a major facility fire would result in the largest releases.

The fire is assumed to consume the entire building and the roof is assumed to be breached providing a direct path to the atmosphere for airborne contamination.

Table 15 lists the maximum quantity licensed for possession by any licensee and release fractions for a major facility fire.

2.3.3.3 Calculations of Doses Doses for a major fire at a radiopharmacy or hospital are shown in Table 15.

Ooses from all radionuclides are far below the EPA's protective action guides.

A zero for the effective dose equivalent indicates that dose is less than 1 millirem.

87

k ible 15.

Radiopharmacy:

Maximum Possession Limits, Release Fractions, and Doses Due to a Major Facility Fire Maximum licensed Dose Radioactive

. possession Chemical Release equivalent, material limit (Ci) forms fraction rem H-3 0.05 Ci In vitro test kits 0.5 0

C-14 0.05 In vitro test kits 0.01*

O Cr-51 0.15 Labeled serum, 0.01 0

sodium chromate Co-58 0.15 Cyanocobalamin 0.001 0

(vitamin B12)

Fe-59 0.15 Chloride, citrate, 0.01 0

sulfate Se-75 0.1 Labeled compound 0.01 0

Sr-90 0.5 Nitrate, chloride 0.01 0 to 0.006 Mo-99/Tc-99m 75.

Mo-99/Tc-99m 0.01 0 to 0.004 generators (liquid) 1-125 0.15 Na I, fibrogen, 0.5 0.001 to

'7 diagnostic kits 0.1 (child's thyroid) 1-131 0.75 Na I, labeled 0.5 0.007 to organic compounds 0.7 (child's thyroid) l l

Xe-133 1.

Gas or saline 1.0 0

Note:

sealed sources are not included.

Reference:

Sutter report.

  • Non-carbon dioxide releast fraction.

l l

1.3.3.4 Implications for Emercency Preparedness l

No offsite radiological emergency preparedness is needed for radiopharmacies and hospitals because doses outside the buildings are far below the 1-rem lower limit protective action guide.

2.3.4 Sealed Source Manufacturing Sealed source manufacturers produce encapsulate radioactive materials into sources of alpha, beta, or gamma radiation or self-luminous devices for use in watches, compasses, and aircraft instrumentation.

88

b

Means of producing sealed sources vary, but in general consist of receiving the bulk radioactive material in a shipping container, dispensing the material in an appropriate containment in the required amounts, and placing the material in a capsule which_is welded or brazed.

Thus, little actual chemical processing occurs; rather, the operations are r. ore of a redistribution and repackaging-process.

In some cases the radioactive material-is put through a series of steps to convert it to microspheres prior to encapsulation, and this operation does involve some chemical processing.

The production of tritium light source usually requires that the gaseous tritium be transferred to a glass ampule, although in sos;a cas~es a tritiated paint is produced for application to watch i

or compass dials.

The majority of the time, the radioactive materials are in a form not readily airborne.

These could be pellets, metallic wafers or foils, platinum gauzes, etc.

Plastic microspheres of controlled particle size encase some i

isotopes.

These are generally spherical, 10 to 250 microns in diameter.

2.3.4.1 Accident History Several of the accidents listed in Tables 11 and 12 are relevant to sealed source manufacturing.

They are:

the 1959 drybox explosion involving Po-210 at

}

Mound Laboratory, the 1960 processing cave fire involving curium at the Univer-i sity of California-Berkeley, the 1967 cutting of an Ir-192 pellet in a hot cell at Babcock and Wilcox, the 1981 escape of Ir-192 from a hot cell at Tech / Ops, the 1983 accidental cutting open of an Am-241 sealed source at Gulf Nuclear, and the 1983 accidental cutting open of a Cs-137 sealed source at Shelwell Services, Inc.

None of these accidents involved a large proportion of the radioactive material at the facility.

All except the Gulf Nuclear and Shelwell Services accidents involved filtered hot cells.

In all cases the airborne release to the environment was small.

2.3.4.2 Accident Source Terms Sutter analyzed a number of types of accidents including glove box or hot cell fires, container or piping leaks, spills, explosions, tornadoes, and major facility fires burning down the entire building.

The major facility fire produced by far the largest releases.

I f

89 i

Table 16 lists the maximum licensed possession limits for any licensee and release fractions for each radionuclide.

The release fractions shown in Table 16 can be assumed for an intense fire of 30 minutes duration in which the building is breached.

2.3.4.3 Calculations of Doses As discussed previously a range of doses is presented in Table 16 due to a major facility fire. The highest doses represent a conservative worst case.

The lower end of the dose range (a factor of 100 lower) represent a severe but not worst-case accident during typical meteorology with some consideration It is clear that a few radionuclides are of signifi-given to plume buoyancy.

cant concern:

Po-210, plutonium, Am-241, and Cm-244.

Doses exceeding the All of these upper end of the protective action guide range seem plausible.

are alpha emitters for which inhalation is the exposure pathway.

Tritium, strontium-90, I-125, Cs-137, Tm-170, Cm-242 and Cm-243 might also be able to exceed the lower end of the protective action guide range.

l 2.3.4.4 Implications for Emergency Preparedness Emergency preparedness should be considered for certain sealed source manufacturing facilities handling large quantities of materials.

Those facili-ties potentially exceeding 1 rem are:

3M, Monsanto, Tech / Ops, and Safety Light.

In addition, it may be possible for effective dose equivalents to exceed the protective action guide value of 5 rems at distances as great as 1000 m.

l This could potentially occur for Po-210 at 3M and plutonium, Am-241, and Cm-244 at Monsanto.

It is possible that these two plants would need more emergency preparedness than the others.

2.3.5 University Research Laboratories At university research laboratories, radioactive materials are received generally from radiopharmaceutical manufacturers and used in many laboratories covered under one license.

They are received at and distributed from a central I

90

Table 16.

Sealed Source Manufacturing: Maximum Possession. Limits Release Fractions, and Doses Due to a Major Facility Fire Maximum Effective licensed dose Radioactive posession Release equivalent, material limit (Ci)

Form Licensee fraction rems H-3 100,000 Ci volatile Safety Light 0.5 0.06 to 6.5 C-14 50 Amersham 0.01*

O to 0.001 Co-60 20,000 75% metallic Automation 0.0001 0.004 to pellets Ind.

0. 4 25% sealed sources Kr-85 1,500 noble gas 3M 1.0 0

Sr-90 3,000 1000 Ci in 3M 0.01 0.3 to 33.

solution in 0.1 liter of 0.1 N hcl also, sealed sources Sb-124 50 Monsanto 0.01 0 to 0.01 I-125 100 5 Ci in K0H 3M 0.5 0.7 to 70.

liquid (child's 5 Ci on resin thyroid) beads Cs-137 10,000 Tech / Ops 0.01 0.03 to 3.

Pm-147 3,500 800 Ci in 3M 0.01 0.008 to solution in 0.8 0.1 liter of 0.1 N hcl also, sealed sources Yb-169 100 5 Ci liquid 3M 0.5 0.004 to Yb chelate 0.4 Tm-170 5,000 Tech / Ops 0.01 0.01 to 1.

Ta-182 200 metallic or Tech / Ops 0.01 0 to 0.001 carbide Ta-183 2,000 metallic or Tech / Ops 0.01 0 to 0.001 carbide Ir-192 50,000 solid metal Tech / Ops 0.0001 0.001 to or sealed 0.1 source T1-204 50 Monsanto 0.01 0 to 0.001

  • Non-carbon dioxide release fraction, 91

-f T

Table 16.

(continued)-

Maximum Effective itcensed dose Radioactive posession

. Release equivalent, material limit (Ci)

Form

. Licensee fraction-rems Bi-210 200

- metal slugs 3M

-0.001 0 to 0.03 Po-210

.4,000 up to 1500 Ci 3M 0.01

1. to 100.

in 40 liters-(per of.2M HNO ;

1500 Ci) 3 up to 2500 Ci 0.001-0.2 to 20.

in waste (per primarily as 2500 Ci) microspheres Np-237 0.1 Monsanto 0.001 0 to 0.04 Pu-238, 236, 199 g 250 Ci as Monsanto 0.001 0.75 to 75.

239, 240, unsealed (per 241, 242 powder oxide 250 Ci)

Am-241 6,000 250 Ci as Monsanto 0.001 1.2 to 120.

unsealed (per powder oxide; 250 Ci).

remainer as sealed l

sources Cm-242 600 Monsanto 0.001 0.1 to 10.

Cm-243 10 Monsanto 0.001 0.03 to 3.0 Cm-244 600 Monsanto 0.001 1.5 to 150.

Cf-252 10 mg solid pellet Monsanto 0.001 0.006 to 0.6 i

receiving area.

Solid waste is usally stored at a central location prior to disposal.

Thus, the central receiving and waste storage areas have the largest radioactive material inventories.

License limits are low, and actual inven-r tories are usually fractions of the limit.

The laboratories are scattered in different locations on a campus; up to 500 locations can handle radioactive materials at a single licensed facility.

Several laboratories may be located in one building.

The generally low quantities of material licensed and the diffuse operations reduces the risks associated with these facilities.

r i

92

-,n e

_. - _ + _

2.3.5.1 Accident History There.have been no accidents at facilities of this type.with significance for offsite protective actions.

Releases have generally been very small.

2.3.5.2 Accident Source Terms The accidents considered by Sutter are spills and leaks, tornadoes, explo-sions, fires, waste incinerator error, and patient related accidents.- Again, fires are'seen to yield the greatest releases.

However a major facility fire involving the entire inventory is not reasonable because of the diffuseness of l

the operations.

The fire with the~ maximum potential release is seen as being l

a major fire at the shipping and receiving department of the University.

Sutter concluded on the basis of information submitted to NRC by licensees that, at most, 10% of the authorized possession limits would be involved.

Table 17 lists the maximum possession limits for any licensee and the release fractions for a major fire at the shipping and receiving area.

t Table 17.

University Research Laboratories: Maximum Possession Limits Release Fractions, and Doses Due to a Major Fire Radioactive Maximum licensed Release Effective dose material possession limit (Ci) fraction equivalent, rems H-3 3000 0.5 0.002 to 0.2 C-14 10 0.01*

0 P-32 5

0.5 0 to 0.04 S-35 5

0.5 0 to 0.01 Ni-63 1

0.01 0

Sr-90 0.5 0.01 0 to 0.005

+

Mo-99/Tc-99m 10 0.01 0

I-125 8

0.5 0.06 to 5.5 (child's thyroid) 1-131 1

0.5 0.01 to 1. (child's thyroid)

Xe-133 10 1.

O Po-210 10 0.01 0,009 to 0.9 Ar-241 0.5 0.001 0.003 to 0.3 Cm-244 1

0.001 0.003 to 0.3 Cf-252 0,1 0.001 0 to 0.01

  • Non-carbon dioxide release fraction.

f r

93

[

2.3.5.3 Calculations of Doses A range of calculated effective dose equivalents is shown in Table 17.

The largest potential doses are from I-125, Po-210, and Am-241.

The range reflects the likelihood that release fractions will be considerably below those shown in the table and a range of possible meteorology.

2.3.5.4 Implications for Emergency preparedness Offsite emergency preparedness does not appear necessary for university research laboratories because potential effective dose equivalents are low.

2.3.6 Waste Warehousing and Burial In waste warehousing, radioactive material in containers (drums) is stored for a period of generally not more than six months.

Drums may be opened in the waste warehousing operation.

They are stored and then transported to a licensed waste burial ground.

2.3.6.1 Accident History Accidents involving waste warehousing and burial have been minor, such as very small releases, leaking containers, and containers having surface contami-nation above regulatory limits.

There have been no offsite airborne releases of significance.

2.3.6.2 Accident Source Terms Warehousing.

Since most radioactive waste is in metal drums, the potential for accidental releases is low.

An event of significant magnitude to breach the drums would be required to make material airborne.

Accidents considered are tornadoes, earthquakes, fires, and explosions.

l A major facility fire is seen as yielding the largest releases.

The activities of radioactive materials becoming airborne were estimated by Sutter.

These activities are listed in Table 18.

94

Table 18. Waste Warehousing Airborne Releases and Doses Due to a Major Facility Fire Radioactive Quantity Release Effective dosa material present (Ci) fraction equivalent, rem H-3 6200 0.5 0.004 to 0.4 C-14 160 0.01*

O to 0.004 P-32 160 0.5 0.01 to 1.

S-35 120 0.5 0.002 t 0.2 Cr-51 60 0.01 0

I-125 280 0.5 4 to 400 (child's thyroid)

I-131 20 0.5 0.4 to 4b. (child's thyroid)

  • Non-carbon dioxide release fraction.

l i

Burial. Accidents during waste burial were analyzed in a draft environ-mental impact statement.* A major trench fire of two hours duration was deter-mined to be the accident with the largest potential airborne release.

Dropped and ruptured containers were determined to cause smaller releases.

The reader is referred to the referenced environmental statement for the details of the assumed releases.

2.3.6.3 Calculations of Doses Warehousina.

A range of effective dose equivalents outside the building due to a major warehouse fire are also shown in Table 18.

The range represents the uncertainty in doses that might result from a severe accident.

Burial.

Doses calculated for a major trench fire are given in NUREG-0782 as 0.006 rem whole body and 0.03 rem to the lungs.

While these doses were not calculated by exactly the same calculational techniques as others in this report, they are so low that there seems to be no need to recalculate them.

  • 0ffice of Nuclear Material Safety and Safeguards, Draft Environmental Impact Statement on 10 CFR Part 61 "Licensing Requirements for Land Disposal of Radioactive Waste," NRC Report NUREG-0782, Volume 2, Section 6.2.2, 1981.

i l

95

2.3.6.4 Implications for Emergency Preparedness Since potential accident doses for waste burial are far below the EPA's protective action guides, burial does not seem to require special offsite emergency preparedness.

For warehousing, the radioiodines I-125 and I-131 may make some special emergency preparedness appropriate.

2.3.7 Depleted Uranium Products

  • Depleted uranium is used to make a number of products: radiation shields for radioisotopes and x-ray machines, aircraft counterweights, armor piercing bullets, and artillery shells.

Among the processing operations performed are:

reduction of "green salt" (uranium tetrafluoride) to metal; melting and casting of the metal; welding; extrusion, cutting and etching; and machining.

Since uranium metal turnings and powders will burn, fires are a potential accident of concern.

2.3.7.1 Accident History Table 6 listed fires and explosions involving uranium and is relevant to fabrication of depleted uranium products.

The releases and offsite contamina-tion that resulted were negligible in all cases.

2.3.7.2 Accident Source Terms Three potential scenarios during three operations suggest themselves as potentially resulting in the largest airborne releases of uranium.

First, a large quantity of molten uranium is handled during the melting and casting operation.

Second, moderate quantities of divided uranium scrap, which can be more readily ignited than bulk pieces, can be stored outdoors under water in containers.

Finally, large quantities of uranium in the form of depleted uranium munitions are stored by the military.

Up to about 700 kg of molten uranium could be poured during a casting operation.

If an operational or equipment failure resulted in the release of

  • This section prepared with the assistance of Dr. Jofu Mishima, Pacific Northwest Laboratories.

96

the molten uranium and the loss of the inert gas cover, the uranium would oxidize rapidly and a fraction would be made airborne.

Carter and Stewart (1970) experimentally measured the airborne release from molten uranium and measured airborne release rates ranging from 0.005% to 0.3% depending upon the conditions - ignition and burning, melting, or partial disruption of liquid into droplets.* The potential airborne release from this scenario range from 0.04 kg to 2 kg of uranium.

Casting operations occur in enclosed facilities and some of the airborne material will be lost due to natural processes such as gravitational settling or deposition on surfaces during its transport to the release point from the facility.

Many such facilities are equipped with particle removal devices such as filters which further reduce the emission.

Scrap metal such as turnings can be stored under water in metal cans.

Prezbindowski (1983) analysed such an event postulated to occur outdoors.**

190 kg of uranium turnings in a 30 gallon metal drum were assumed to ignite and oxidize to completion.

The airborne release was estimated to be 0.1%

resulting in 0.190 kg being released to the environment.

The potentially most serious accident would involve a fire in a munitions storage bunker (igloo) holding a large quantity of various types of munitions (depleted uranium, high explosive, etc.).

It is postulated that 12,000 rounds of a 105 mm depleted uranium cartridge could be present.

Each cartridge would hold 3.3 kg of uran.ium resulting in a total of 40,000 kg of uranium.

Other types of combustibles such as wooden crates and pallets, paper based packing materials, etc. would also be present.

If the material present were ignited, the fire would initially spread slowly until sufficient flammable vapors could be generated and flashover occurs.

Once flashover occurs, the entire contents of the enclosure are involved.

The fire soon becomes oxygen limited due to the limited accessibility of air.

Eventually, the cartridges themselves would be ignited and, if containment is lost, the fire would burn more vigorously due to the greater availability of oxygen.

Igloos are designed to vent in a perferred direction which does not involve adjacent structures.

The flanmable vapors released may well burn

  • R. F. Carter and K. Stewart, "On the Oxide Fume Formed by the Combustion of Plutonium and Uranium," Inhaled Particles III, Unwin Brothers Limited, The Gresham Press, England, 1970.
    • D. L. Prezbindowski, "Uranium 0xide Facility Safety Analysis Report,"

UNI-M-157-DR, United Nuclear Industries, Richland, Washington, 1983.

97

outtide the facility due to the high vapor generation rate reducing radiant heat transfer to the materials inside.

There are two types of cartridges cases used for depleted uranium munitions -

metal and combustible.

The depleted uranium portion of metal cased cartridges were ejected from and unaffected by the fire _in a large-scale, outdoors test.*

Depleted uranium from combustible-cased munitions in similar tests were not ejected from the fire and were almost completely oxidized (83% and 85.2%).**

Collection and analysis of the residual material did not indicate a loss of uranium and air samples taken during part of the burning and all of the recovery period did not show any significant airborne release ***

Experimental studies measured the rate of oxidation and airborne release during oxidation at elevated temperatures (400 C to 1200 C) of the depleted uranium portion of large-caliber munitions in air and a 50% air-50% carbon dioxide mixture.

The maximum airborne fractional release rate measured during the outdoor test using combustible materials as the heat source was 2.2 x 10 6/ min by weight.

The material was primarily U 0s.

About 50% of the mate-ial 3

had a by weight aerodynamic equivalent diameter of 10 microns or less.

The three depleted uranium specimens oxidized an average of 44% during the three hour test.

The velocity of air passing around the samples was 2.23 m/s (5 mph).

Similar but lower rates were measured in laboratory studies at various tempera-tures and atmospheres.

For the worst case accident involving depleted uranium it is postulated that 40,000 kg of depleted uranium are involved in an igloo fire and that it i

is completely oxidized.

It is also assumed that the material is combustible-cased although the igloo limit is for metal-cased.

Based upon the experimental studies reported by Elder and Tinkle,**** the material would be completely

  • R. L. Gilchrist, G. B. Barker, and J. Mishima, "Radiological and l

Toxicological Assessment of an External Heat (Burn) Test of the 105 mm Cartridge, APFSDS-T, XM-774," PNL-2670, Pacific Northwest Laboratory, Richland, Washington, 1978.

    • C. D. Hooker et al, "Hazards Classification Test of the Cartridge, 120 mm, APFSDS-T, XM-829," PNL-4459, Pacific Northwest Laboratory, Richland, l

Washington, 1983.

      • J. C. Elder and M. C. Tinkle, "0xidation of Depleted Uranium Penetrators and Aerosol Dispersion at High Temperatures," LA-8610-MS, Los Alamos Scientific Laboratory, Los Alamos, NM, 1980.
        • J. C. Elder and M. C. Tinkle, "0xidation of Depleted Uranium Penetrators and Aerosol Dispersion at High Temperaturas," LA-8610-MS, Los Alamos t

Scientific Laboratory, Los Alamos, NM, 1980.

98

oxidized in 400 min.

At the rate of 2.2 x 10 8/ min, 35 kg would be made air-borne of which half are respirable particles.

The total airborne release of respirable depleted uranium thus would be 18 kg.

2.3.7.3 Calculations of Doses The effective dose equivalent for an 18 kg release of depleted uranium was calculated to be in the range from 0.001 to 0.06 rem.

Heavy metal poisoning of the kidneys is not a factor because the uranium would not be in soluble form.

2.3.7.4 Implications for Emergency Preparedness No special offsite emergency preparedness is necessary for depleted uranium products because doses are below protective action guides.

2. 4 Summary of Facilities to be Covered Fuel Cycle:

The accident with the greatest potential hazard appears to be release of a large quantity of UFs.

The release of a large quantity of UFs

-presents a chemical toxicity hazard.

The greatest potential hazard is at UFs l

conversion plants where hot 14-ton cylinders are handled outside.

NRC licenses two such plants.

The rupture of a hot cylinder is quite plausible and could lead to multi-ton releases of UFs.

The release would begin instantly.

In such a case evacuation to several kilometers downwind would be appropriate for very calm weather conditions.

The plume is easily detectable by sight and by smell at levels well below levels likely to cause injury.

Thus people downwind would be able to see the plume coming and would be able to judge for themselves when they have reached an area of safety.

In an actual accident the release could be greatly diminished by spraying the release point with water or carbon dioxide.

This is probably the most effective action that can be taken to mitigate offsite consequences.

The release of low-enriched UFs could also occur from smaller 10-ton cylinders and could occur inside a building, which would prevent escape of much uranium.

For the 9 such facilities licensed by NRC the appropriate response would be similar to that above but would be limited to distances of perhaps about half as great.

99

t The release of high-enriched UFs from hot cylinders may not require offsite response due to the small cylinder size used.

from cold cylinders does not require a response because The release of UF8 the quantities released would be quite small.

With regard to the heating of cold cylinders in a fire and subsequent release, a response similar to that for hot cylinders may be' appropriate, but additional warning time would generally be available.

For a criticality accident, the lower end of the protective action guide range could be exceeded for a person standing outside on the plume centerline out to a distance of about 250 meters from the release point assuming adverse weather conditions.

The calculated doses are based on the assumption of a pulsating criticality lastlag 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> and the person standing outside on the plume centerline for the entire 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.

Three additional licensees might be in this category.

An appropriate emergency response to a criticality accident during adverse meteorology would be immediate sheltering and closing win' dows up to a distance of 250 meters downwind.

This response should be accomplished within about 3 or 4 minutes after the criticality occurs.

The initial pulse is likely to be the largest one.

Plume travel time to 250 meters would be about 4 minutes for low wind speeds and 1 minute for average wind speeds.

There would be some added delay due to holdup in the liquid solution and the building atmosphere.

After l

the immediate sheltering response, evacuation could be considered as an alter-native to further sheltering.

Preparedness for such a response is recommended for the area within 200 to l

250 meters from high-enriched uranium and plutonium processing.

Plutonium facilities (none currently operating) may also need special off-site emergency preparedness due to airborne releases of plutonium.

However, the GESMO analysis discussed in Section 2.2.6 would indicate that extensive i

preparedness may not be appropriate.

Byproduct material and plutonium licensees:

A total of about 48 Part 30 or Part 70 licensees were identified who were authorized to possess one or more radionuclides in unsealed form in excess of the quantities in Table 13 of this analysis (i.e., effective dose equivalent could exceed 1 rem offsite or thyroid dose could exceed 5 rems).

However, some of the licensees have little or no need to possess as much as they are authorized to and some can do an evaluation to show releases would be smaller than assumed. We estimate that 100 f

most of the licensees will elect to lower their authorized possession limits or perform an evaluation rather than submit a plan.

Thus, the total number of affected licensees is likely to be about 10 exceeding the limit for plutonium and 7 exceeding the limit for other materials, specifically Am-241, Po-210, I-125, I-131, H-3, P-32, Sr-90, Cm-242, and Cm-244.

In all cases a fire would be the accident of concern.

The appropriate emergency response would be to evacuate people from the immediate vicinity (at least 100 meters) so as not to interfere with firefighting and to shelter or evacuate everywhere else where smoke can be smelled.

These actions should be l

taken within a few minutes.

2.5 A Protective Action Strategy The most important characteristic of the accidents discussed is that there is likely to be little or no warning time before releases start.

The most important accidents, UFs releases and fires, are likely to be controlled within roughly half an hour in a majority of cases.

Thus releases are often likely to stop or be greatly reduced within a half hour.

r 2.5.1 The Initial Response Quick decisions and prompt actions are necessary.

The goal should be to make decisions on protective actions and start implementing those decisions within 5 or 10 minutes of discovering the accident.

The heart of an effective protective action strategy is quick protective action decisions because accidents of concern are likely to happen so quickly that decisions on protective actions must be immediate to be effective.

Thus, the licensee's initial notification of police and fire offic.ials should include a recommendation on what protective actions are appropriate and the distances to which the protective actions are appropriate.

This can only be done if the literisee has thought in advance about what he would recommend.

f 1

The appropriate protective actions for an airborne release are:

(1) sheltering in buildings with the windows closed, and (2) leaving the imme-diate vicinity.

Sheltering with windows closed should provide, on the average, roughly a factor of three protection against the. inhalation of radioactive mate-rials.

Inhalation is the dominant exposure pathway for all the radioactive materials of concern.

A factor of three protection will result in a substan-tial dose reduction and will meet the EPA's objective of reducing dose for those people who would receive doses exceeding the protective action guides.

Ad hoc respiratory protection could reduce exposures by an additional factor of three.

Ad hoc respiratory protection means breathing through cloth such as a towel, a crumpled handkerchief, a bed sheet, or a blanket.

Leaving the vicinity can result in the complete elimination of exposure if it can be done before the release starts.

The later the movement starts, the less the benefit.

This action should not be confused with evacuation to great distances.

The movement could be as little as 50 or 100 yards in a cross wind direction to get out of the direct downwind plume.

In general, the licensee should recommend both sheltering and leaving the vicinity to the offsite response organization responsible for public health and safety.

Both are suitable options that meet the EPA's protective action objec-tives.

The decision on which to use should be left to the offsite response organization.

The offsite response organization would then make its decision on what to do based on the practicality of the actions at the particular time and place of the accident.

In many instances a combination of the two protec-tive actions may be appropriate, for example, moving spectators out of the f

areas and sheltering nearby residents in their homes.

l The next question is, what areas should be involved? The first considera-l tions are common sense and practicality.

The recommendation should be that people should move out of dense smoke or fumes, either by leaving the vicinity or sheltering indoors.

The areas and actions involved should to a large extent be determined by practicality.

Simply put, what is it practical to do in a very short time?

But to what distances are actions appropriate? We suggest distances below, but again practicality should be considered.

If protective actions can be taken over larger areas than sug p sted, it would be appropriate to take those actions.

Conversely, if there were not enough time to take actions for 102

the entire distance, then the area where actions would be taken could be reduced until it was small enough to handle in the time available.

It is also possible that the emergency would occur so quickly that no protective actions could be taken.

This possibility is inherent in any type of emergency response.

The emergency plan and emergency response capability do not guarantee any particular outcome will be achieved.

They merely assure that people will act quickly and efficiently to do whatever they can reasonably do to help.

Appropriate action distances are suggested below, keeping practicality in mind.

It is considered impractical to base distances on measurements of source terms and meteorological conditions.

There would not be nearly enough time, nor is such assumed precision necessary or appropriate.

Thus, we will base estimated distances on assumed releases.

It would not be practical or appropriate to assume a very-worst case conservative release.

The Commission's policy is that, "Emergency planning should be based on real-istic assumptions regarding severe accidents."*

For an accident involving a quantity or material 10 times the amount requiring a plan we recommend a response distance of about 100 meters.

The 100-meter distance is selected based on the following factors:

1.

Isolation areas of this size are commonly used by emergency personnel.

2.

Doses exceeding the lower end of the protective action guide range would generally not be exceeded beyond this distance for the largest plausible releases and average meteorology (D, 4.5 m/s) or for adverse meteorology (F, 1 m/s) with releases of more likely size (one-tenth the assumed maximums).

4 i

  • U S.. Nuclear Regulatory Commission Policy and Planning Guidance - 1985,"

l NUREG-0885, Issue 4, 1985, page 6.

103

3.

The upper end of the protective action guide range is unlikely to be exceeded beyond that distance even under very adverse but realistic cir-I cumstances (i.e., considering plume buoyancy, people not.likely to remain in smoke, possible wind shifts, or other factors that may occur).

If the quantity of material involved in the accident is about 100 times the quantity requiring a plan the appropriate distance would be about 500 neters.

The 500-meter distance is selected based on the following factors:

[

1.

A 500-meter distance is still a practical size area for providing a reasonable response.

2.

A distance of 500 meters provides approximately a factor of 10 dilution in concentration compared to 100 meters.

(See Figure 1 curves for D, 4.5 m/s wind speed and F,1 ir/s wind speed.)

3.

For most accidents,.the lower end of the protective action guide range would not be exceeded beyond that distance.

4.

For worst-case accidents the upper end of the protective action guide range is unlikely to be exceeded under realistic circumstances.

Using similar logic, the distance appropriate for accidents involving 500 times the quantity needing a plan would be about 1500 meters, or about a mile.

In no situations would distances beyond one-mile be recommended for action because actions over larger areas would be too difficult to undertake within the time available.

The same type of considerations could be applied to UFe releases.

For less than 50 kg of UFe at risk a distance of 100 meters would be appropriate.

For 500 kg of UFe at risk a distance of 500 meters would be appropriate, and for a 14-ton cylinder, one mile would be an appropriate distance.

We have intentionally not defined an emergency planning zone for either the plume exposure pathway or the ingestion pathway as is done for nuclear power plant emergency planning.

104

The purpose of the planning zone for nuclear power plants is to identify a jurisdictional area in which emergency response organizations should be involved in the planning.. For fuel cycle and other radioactive material licensees, the response would be under the direction of the local fire and police departments just as similar industrial accidents are handled.

It is only necessary to identify the organizations that will be notified and will respond rather than a geographical area for which planning would take place.

2.5.2 Locating Contamination I:

After the release has ended, it would be necessary to begin radiat lon surveys to locate contamination offsite.

The primary responsibility for these surveys rests with the State radiological protection department.

The State, at i-its request, can obtain technical support from the U.S. Department of Energy, which has radiological assessment teams that can be called to the site.

However, since the licensee initially is likely to have the only trained personnel equipped with radiation detection instruments it would be expected

[

that they would initially make measurements in an attempt to provide an early estimate on the degree of contamination.

2.5.3 The Assessment Phase Soon after the release has ended, usually within half an hour to an hour, the assessment phase of the emergency response should begin.

The public will be concerned about whether the danger is over, whether they were exposed, whether they are contaminated with radioactivity, wht,her their homes are contaminated with radioactivity, and what should they do.

The news media will want to know what happened.

Both the licensee and the NRC must be prepared to respond to such concerns promptly or suffer damaged reputations, ill-will, and possibly lawsuits.

As discussed above, field measurements to locate ground contamination will be underway.

105

The question of whether people were exposed can only be answered with abundant field measurements.

Generally, direct measurements of radioactive material concentrations in the plume will not be possible because of a lack of time to prepare and a lack of ability to locate and follow the plume.

Never-theless, plant personnel should attempt such measurements with available instru-mentation to the extent possible because if they are fortunate enough to get data, the data will be valuable.

The answers of whether or to what degree people were exposed are likely to be best answered by measurements of ground contamination and bioassay measure-ments.

Ground contamination measurements will allow a direct determination of whether there was a release.

They will also allow a quick rough order-of-magnitude estimates of the time-integrated exposure to people in the areas.

In addition, the "Emergency Planning and Community Right-to-Know Act of 1986" requires that releases of radioactive materials in excess of certain quantities must be immediately reported to the National Response Center.

Quan-tities requiring an immediate report were proposed in the Federal Register (52 j

LR8172)onMarch 16, 1987.

As soon as the licensee knows that a reportable quantity has been released, an immediate notification of the National Response Center is required.

Failure to comply could result in a fine of up to $25,000 and jail if the failure were willful.

3.

VALUE/ IMPACT 3.1 Alternatives Three alternatives have been identified:

(1) adopting a regulation containing the proposed requirements, (2) imposing the requirements by license condition rather than by regulation, and (3) imposed no new requirements with regard to emergency planning.

The first two alternatives would have essentially the same value and costs.

Those values and costs are discussed below.

The third alternative, no new requirements, would have essentially no value or l

Costs.

l l

106

..e 3.2 Value of the Proposed Action Value can be expressed in terms of risk reduction.

Consider a release in which the effective dose equivalent at a distance of 100 meters is 5 rems, assuming Class F atmosphere stability and a wind speed of 1 meter /sec.

The area over which the 1 rem protective action guide would be exceeded would be 0.006 square miles.

If this area contained people at the average population density of the continental United States (72 people / square mile) it would contain on the average about half a person.

However, the facilities under consideration are usually located in built-up A survey of potentially affected licensees shows that typical popula-areas.

tion densities are about 3,000 people / square mile.* Thus perhaps about 20 people would typically be in the area.

Generally about 80% of people are in the build-ings so about 4 people would be outdoors and 16 would be indoors.

The average dose to a person outdoors in the area was calculated to be about 3 rems.

(This value was calculated for an open field; doses in urban areas would be less, but we ignore that factor.) In addition, doses to people in buildings would be half this dose because of protection provided by the building.

The total collective dose for the urban area thus might be 40 person rems.

Protective actions that would be available to these people are primarily evacuation and sheltering.

Evacuation would be the more effective if it could be done promptly before the plume arrived.

Sheltering would often be more practical because it can be done faster and most people are already inside.

Very roughly the dose savings, due to protective actions for this adverse meteorology could be put at 20 person-rem, about half the potential dose.

Assuming that the chance of death due to cancer due to doses of several rems is in the range between zero to 10 4 cancer deaths / rem.

The expected number of lives saved due to the protective actions would be less than 0.002 for adverse meteorology and roughly 0.00002 lives averaged over all meteorology.

  • J. P. McBride, "Economic Consequences of Accidental Releases from Fuel Fabrication and Radioisotope Processing Plants," NUREG/CR-0222, 1979, Appendix A.

107

=.

,, ~...

... ~.

Our estimate of the frequency of a major release is less than 10 4/ year.

Insurance statistics available from insurance companies dealing in commercial structures indicate fire losses in unsprinklered commercial and industrial facilities to be 0.006/ year.

Sprinkler failure rates are estimated to be 0.038 should a fire occur.** The fire loss rate for a sprinklered facility should thus be roughly 2 x 10 4/ year.

It is now assumed that additional site specific factors will reduce the probability of a release to roughly 10 4/yeur.

Examples of such factors would be:

material kept in fireproof storage thus preventing significant release, filter system does not fail thus preventing release, or firemen extinguish fire before radioactive material is heated hot enough for a significant release, and many more.

Thus protective actions could be expected to save 0.00000002 lives per year per facility.

If a life is given a value of ten-million dollars, the value of protective actions at a typical site in an urban area is $0.20 per facility per year or 1

less.

Now consider a release in which the effective dose equivalent at a distance of 1000 meters is 5 rems assuming Class F atmospheric stability and wind speed of 1 meter /sec.

At this level early injuries have still been avoided.

The area over which the 1 rem protective action guide would be exceeded would be 0.15 square miles.

For a typical built up site this area would contain about 450 people.

The average dase to a person outdoors in the area was calculated to be about 3 rems and to a person indoors was calculated to be 1.5 rems.

The total collective dose assuming some people are indoors as previously discussed might be 800 person-rem.

The dose savings due to protective actions could be about half of this or 400 person-rem.

Lives saved due to these protective actions could be up to 0.04 life for adverse meteorology and 0.04 life for average meteorology.

With the frequency of s major release at 10 4/ year, protective actions might perhaps save up to 0.000004 life per year per facility.

    • National Fire Protection Association, Fire Protection Handbook, 14th edition, Table 14-19, page 14-5.

108 L

P If a life is given a value of ten-million dollars, the value of protective actions in a densely populated urban area is $4 or less per facility per year.

3.3 Cost For the smaller class of accidents, those exceeding 1 rem offsite but not 5 rems at 1000 meters, the licensee is considered to have a 50 page plan telling what he would do in the event of emergencies such as fires.

-Cost data were obtained from two radiopharmaceutical manufacturers.

Both licensees calculated the cost of the onsite contingency plans required by order.

The manufacturer with a small program and limited facilities estimated the initial set-up cost $84,000.

Annual operating costs were estimated to be

$18,000.

Labor accounted for 1/2 to 2/3 of the cost in each category.

Labor was given a value of $30/ hour with no overhead charged.

The main equipment costs were for radios, extra monitoring equipment for emergency use, and extra respirators.

The largest annual expense is for training.

Other operating expenses are for audits, drills, and equipment replacement and maintenance.

To place all expenses on an annual basis the initial set-up cost was divided by 10, assuming a ten year useful life of a plan.

Thus annual costs are estimated to be $26,000/ year / facility for this radiopharmaceutical manufac-turer with a small program.

A second radiopharmaceutical manufacturer with one of the largest programs that would be covered by the regulation reported that the cost of establishing their on-site radiological contingency plan was more than $550,000.

No annual operating costs were given.

Assuming a 10 year plan life and operating costs of $18,000/ year (the estimate of the other manufacturer) the total annual cost is $73,000/ year /

facility for large facilities.

Costs to NRC to review and inspect plans have been estimated to be

$4,000/ year / facility.

3.4 Value/ Impact of Alternatives The costs of emergency preparedness are expected to exceed the benefits in terms of protecting public health and safety as shown below, t

?

109 a

. Table 19.

Comparison of Costs and Benefits of Special-Emergency Preparedness Size of Licensee Cost Benefit Small - Possessing 5 times quantity in Table 13

$30,000/yr

$0.20/yr Large - Possessing 50 times quantity in Table 13

$77,000/yr

$4/yr 4.0 STATUTORY CONSIDERATIONS 4.1 NRC Regulatory Authority The Atomic Energy Act gives NRC authority to adopt regulations for protect-ing public health and safety.

This proposed rule would be justified under j

that authority.

4.2 Agreement State The question is whether NRC's Agreement States would adopt offsite emer-gency preparedness requirements similar to NRC's.

The NRC's Office of State Programs intends to make this requirement a matter requiring compatability.

Thus, NRC would require that Agreement States adopt requirements similar to NRC's.

i 4.3 Environmental Impact Appraisal The NRC's regulations [10 CFR S 51.5(b)] require that substantive and significant amendments (from the standpoint of environmental impact) of regula-tions require an environmental impact statement.

[

To make the finding that amendments are not substantive and significant from the standpoint of environmental impact, NRC regulations (10 CFR S 51.5(c)(1)]

require the preparation of a negative declaration and an environmental impact appraisal.

l The environmental impact appraisal must include [10 CFR S 51.7(b)]:

t (1) A description of the proposed action.

110

s (2) A summary description of the probable impacts of the proposed action on the environment.

(3) The basis for the conclusion that no environmental irr. pact statement need be prepared.

The proposed action is a rule to require emergency proceduNs for off-site releases.

A description of the proposed requirements is contained in Section 1.1, "Description of the Proposed Action."

A summary description of the probable impacts of the proposed action on the environment is contained it Section 3.2, "Value of the Proposed Action."

l The basis for the conclusion that..o environmental impact statement need I

be prepared is that the benefits to : ublic safety are neither substantive nor significant as described in Section 3.2, "Value of the Proposed Action,"

and summarized in Table 24.

5.

CONCLUSIONS The conclusion of this Regulatory Analysis is that accidents at fuel cycle and other radioactive material licensees pose a very small risk to the public.

Serious accidents are infrequent and would generally involve relatively small radiation doses to few people located in small areas.

This is not to say that radiation doses large enough to exceed guides for taking protective actions ca'nnot occur.

It may be possible to have an accident at some licensed facilities which would cause offsite doses exceeding protective action guides.

However, offsite radiation doses large enough to cause an acute fatality or even early injury from an airborne release are not considered plausible.

For a licensee possessing 5 times the amount of material in Table 13, we conclude that protective actions in an urban area might save up to 0.00000002 lives per year per facility.

Perhaps about 20 to 30 licensees have a possibil-ity of such an accident or worse.

For these facilities we recommend there should be notification of local authorities.

However, no special facilities, equipment, or other resources for responding are considered necessary, 111

For a licensee with 50 times as much releasable material as in Table 13, we l

conclude that protective actions in a built up area might save up to 0.0000004 lives per year per facility.

There may be 2 or 3 licensees with a capability of an accident this severe.

The cost of this preparedness may not be justified in terms of protecting public health and safety.

Rather we would justify it in terms of the intangible benefit of being able to reassure the public that if an accident happens local authorities will be notified so they make take appropriate actions.

Although emergency preparedness for fuel cycle and other radioactive material licensees cannot be shown to be cost effective, the NRC feels that such preparedness represents a prudent step which should be taken in line with the NRC's philosophy of defense-in-depth, to minimize the adverse effects which could result from a severe accident at one of its facilities.

112

groa==

u s =veumuuuron co u.o=

i e + r ~ven m4-, *. noc, v.< e..

M">'E BIBLIOGRAPHIC DATA SHEET us. st uctiosi o~ t i

..a NUREG-1140 TsTLE A%o $VST1T LE 3 LievtSLA%E A Regulatory An sis on Emergency Preparedness for Fuel Cycle and 0 r Radioactive Material Licensees Final Report

. o.ri i.ogoo,a vio woor-f t

November f

1987

..v1-o

<s,

\\

6 gg ageomy issygo poNTH

~

VGAR Stephen A. McGuire Januaryf 1988 7 s tasomwiwo onGaggat EON N AME ANo M AILi%o a t $$,iac.wer le c.or, 8 eaOstCT!Tpwoma v4sf huwtER Division of Reactor Accide Analysis

/

Office of Nuclear Regulatcr

.esea rch

^o a ' a v"" "

U. S. Nuclear Regulatory Comm sion Washington, D. C.

20555 io seio..so o.o.

.,,0

~,...~o..,L

~o.oc,.u,,

e, c,

p, n,io,..,0.,

Same as 7, above.

f Final e et a'Co Covin t o,roce em. ensest v

>> sve,a v n r..

~ovii o ni,a.c r a..

Potential accident' for 15 types of f uel cyc1 d ather radioactive material licensees were analyzed. The most pcttntially hazardous acci t, by a large margin, was determined to be the sudden rupture of a heated trulti-ton cylinder UF. Acute fatalities offsite are probably not 6

credible. Acute pennanent injurias may be ssi e for many hundreds of meters, and clinically observable transient effects of unknown lu te onsequences may be possible for distances up to a few miles. These effects would be sed by e chemical toxicity of the UF. Radiation doses would not be significant. The mos potential hazardousaccidentduetorabiationexposure was determir.ed tc be a large fire at c tain facili es handling large quantities of alpha-emitting radicraclides (i.e., Po-210 u-238, Pu-23 Am-241, Cm-242, Cm-244) or radioiodines (I-125 and T- 01). However, acute talities or inj

'es to people offsite due to accidental releases c' " ese materials do not,eem plausible. T only other significant accident was identifie; ss a long-term pulsati criticality at fue cycle facilities handling high-enriched uranium or plutonit.m. An importa feature of the most ricus accidents is that releases are likely to start without prior ning. 1he releases wo usually end within about half an hour.

Thus protective actions would ve to be taken cuickly t e effective. There is not likely to be enough tirne for duse proj ions, corrplicated dtcision king during the accident, or the participation of personnel in the irmediate vicinity o the site. The appropriate response by the facility is to imme tely notify local fire, polic and other emergency personnel and give them a brief predeter ned messoge recomrrending protec ve actions. Emergency personnel are generally well qualified respond effectively to small acc.nts of these types.

14 oGGUW8 %T A N A L V $.$ - e E l vfrO AQ$

$CA.DToA$

ig Agaigag, git y STATlWENT fuel cycle licens emergence prepar ness Unlimited radioactive mate al licensee radiation expo re

....ev.,, c L, u,,,c.1,o.,

<r..,,,

,,on,.....wn n-Unc1assified

,r..,,,,,,

Unclassified ir %vwsta oo, ages is,n ca

  • V. S. COv(eg,(gf pa tst ;g; crf !C( s1995.?O2 297:60337

~

UNITED STATES

,csf etass ua,t NUCLEAR REGULATORY COMMISSION rosTaoj,gg$s ram WASHINGTON, D.C. 20555

. PERMIT NE O $7 0FFICIAL BUSINESS -

PENALTY FOR PRIVATE USE,4300 120554078877 1 1 A *< 1 C F I C 41511 US NTC-0ACM-ADV OIV 7F PUH SVPS POLICY & DUP VGT BR-POP N:JREG n-537 WASHINiTON PC 70535 e

if

.