ML20137J012

From kanterella
Jump to navigation Jump to search
Rev 1 to Procedure QI-QP-11.0-10, Shotcrete Application Insp. Related Info Encl
ML20137J012
Person / Time
Site: Comanche Peak  
Issue date: 07/05/1979
From:
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
Shared Package
ML17198A292 List: ... further results
References
FOIA-85-59 QI-QP-11.0-10, NUDOCS 8512020530
Download: ML20137J012 (4)


Text

.

i I

TEXAS UTILITIES GENERATING CO.

INSTRUCTION ISSUE REVISION PAGC x

NUMBER DATE

'CPSES i

QI-QP-11.0-10 1

7-5-79 1 of 3 N//{ Yggf.f/Av

_ 7/f/79 SHOTCRETE PREPARED BY:

APPLICATION DATE INSPECTION 6!~)9 APPROVED BY FATI 1.0

_ REFERENCES 1-A Specification 2323-SS-6, " Excavation for Plant Structures" l-B Specification 2323-SS-9, " Concrete" 2.0 GENERAL 2.1 PURPOSE AND SCOPE p

This instruction establishes the acceptance criteria utilized s,,j by QC Inspectors for inspecting the application of shotcrete to assure compliance with Reference 1-A and 1-B.

-r q

{ *,. : q 3.0 INSPECTION 3

3.1 INSPECTION REQUIREMENTS '

....__L

~

~

3.1.1 Pre-Application Inspection Pour card sign-off completed b'i crafts, engineers and a.

geologist.

b.

Draw simple sketch on back of pour card showing area to be shotcreted and elevation.

Surface to be covered trimmed to line and grade.

c.

d.

Surface clean of loose material and mud.

e.

Surface kept moist from time of cleaning.

G512O20530 851106 PDR FOIA GARDE 8 5-59 PDR

\\

O gg#

TiffTn n A

~ * * "

/

IIGIRUCTION ISSUE s.

TE7AS UTILITIES GEERKEING CO.

NUMIER CPSES s

QI-QP-ll.0-10 1

7-5-79 2 of 3 f.

Surface not frozen.

g.

Rock bolts have,been pull tested if required by geologist.

h.

Non-corrosive grade pins set to depth of application at a maximum spacing of 8 feet in each direction.

1.

Shotcrete workmen qualified to ACI-506.

3.1.2 Application' Inspection a.

QC Inspector will sign for Test Lab representative in

" add-water" block of batch ticket if water is added.

b.

Shotcrete applied by " wet mix" method, c.

Shoterete applied in one layer.

d.

Material placed beyond minimum application line established by grade pins.

e.

Water flows are controlled.

f.

Rebound is removed to line of shotcrete.

g.

Test core sample areas marked.

h.

Curing compound is applied immediately after completion of application.

3.2 DOCUMENTATION The QC Inspector shall verify that* requirements of this instruct-ion have been met by completing Figure 1 and submitting to the Civil Inspection Supervisor / designee for review, processing and filing in accordance with CPSES requirements for "QA Records".

/~s I

j

}iEyAs UTILITIES GENERA INSTRUCTION ISSUE

.G CO.

REVISI "

PAGE g qgg DATE CPSES b

7-5-79 3 of 3 QI-QP-11.0-10 1

' $V FIGURE I fr.*

U$

COMANCHE PEAK STEAM ELEC TRIC S TATION s-rer e,

INSPECTION REPORT Iso

.TLts etSCA.pgp b

fEmiaN2TiQie 9 0 l27&Ilas/ STAuctw4 C(&4narm ti

.1

{*.

s,=. c g at w.

MF Q C (4c-6 R1v. & cpa%4 no

  • La5=r4E G4 is3T (3ui#. e0EMr. 8eG.

O:

s 7

a

2. '.

Q [9 W is O p*? *% 5F2L.LA,r80= O r'.5.'s*,1c rc=

O F$2'neries O P*t',tTr t >*

. ;4 n sne r.c =

.tv.ca 2 ms y.sccre, P

m. ruvo r s l 5.-

O snero. co utro. ut => uc2 tc ire =s sarrescre=,

[.' '

O ws> eno-ccourro. u.sarisucioar iree ustro anoa

  • ^ " -

to l

%e.,2,c mspECriou aTTais;TEs ec

~

m, l

I g

m'

( J' t

2.-

~~~ '

etams towcs sares,ricJ m

atuTL4 aca no i R. CLOSED Q

inatt

,,,,,,,y,,,

es oc waarteron is TUCCO QA

- - - - ~. -.

I DISTRIBUTION LOC ~

i GI-OP-II.0- 10 REV.

O kJ w(!<the b Gee (Ym t%)

6)

NAME OF DATE PREVIOUS REVISION OM.WS DOCUMENT HOLDER ISSUED RETURNED / DESTROYED G-m' 3ATison 1-;/-7il n

2T'r2 S.V. (*lec2 7,M/f fif,qf fej"y,) ff fi,9

' r.x3 neck' (;MhW.",,,,-

744 <jg j_g l;:,,y lj l_y, 2 -000 l Chc V (M'I 54">A'

'f.94-79 pfy p,5 f.y j 4 ;.;, ;

Z-00S RecRGob; won) 7A4%

W Q y,y'gj

~

. ccco 1% wo 7.g.9g l

'r-Co?

6Ai%fl 7 3r.15(,

2-co? O WLG g-3,78 1

3_'

I r.

a4\\1 A % ""

,,,.p.

..e cw,o A. %4

gy l (~

r

~

f 1

=...

-.