'Y i' i ATOMIC ENERGY COMMISSION 9e WASHINGTON. D.C. 30645 May 26, 1967 4* h.
l Dochet No. 50-130 l
\\ M i
i Northam States Pbuer Company 5
i 414 Nicollet Avenue C
Mirineapolis, Mirinesota 55401 o
Attentient W. R. H. Engels Donautive Vice Pasident
(
sQange No.13 No. DPb 11 Gentlement This a fers to your m quest dated Manh 17, 1967, for authorisation of changes in the Technical Specifications of Prwisional Operuting License i
l No. EPhil pursuant to the prwielens of Section 50.59 of the Ma=%'s l
l l
mgulations. The p m posed changes would atthorise deletion of the sepa mte aquimeents on maxima boiler power fmetion and minimum maimulation flow for a given total mactor power, and would incorporate a mquirement for a miniana =11amh1= bumout mtio. 1hese changes are necessary to enable ruanter operation at full power. We have designated this mgasst l
l as Pmposed Change No.13.
We have concluded that Paposed Q1mnes No. 33 does not prueent significant hasards considerutions not described or implicit in the Final Hasards Smenary Report, and that there is zwasonable assumnoe that the health and safety of the public will not be endangerud. A copy of our m lated Safety Evaluation is enclosed.
In view of the foregoing, the Technical Specifications of License No. DPhil i
1, (Appendix A) are hereby changed as set forth in Attachment A to this letter.
i Sincerely yours, l
4 i
&#d I
t Peter A. Morris, Dirmator Division of Reactor Licensing
[
t Enclosurest
- 1. Safety Evaluation i
- 2. Attachment A l
j
{(
g61g5850214 I
PAY 85-S4 PDR I
\\6
d-(
ATDONDff A CHANGE NO.13 '!V TEO9ECAL SPECIFICATIONS LICDISE NO. DPR-ll 1.
In Section 5.6.1 (b), delete:
i
" Boiler Power Maximun Steady State Power Fmetion of 190 Hwt 0.86" 2
In Section 6.1.4 (a), delete:
"High utic Reactor-power / recirculation flow 30 W above 1 Hw(th) per 344 gyn" 3
In Section 6.1.4 (b), adds "High mtio 84 N above 1 N(th) per 443 man with Boiler power / recirculation flow minimun pemissible meirculatlon flow f
of 15000 spa.*
- '!his set point to be selected with appropriate conservative allowanos for safety circuit instrument errors, uncertainties in heat balance measurueents and un-certainties in detector calibation due to control rod and zweirculation flow pengm me utilized.