_-

6 e

SAXTON NUCLEAR EXPDtIMENTAL CORP 0rGTION Application for Reactor Construction Permit and Operating License Docket No. 50-lh6 W &nghe, Amendment No. 10 - Supplement No. 2 llhjh Applicant submits the following enclosures pertaining to Phase 1 of the 1.

Saxton Nuclear Experimental Corporation's five-year research and development programs

" Addendum No. 1 to the Safeguards Report for Phase 1 of the Saxton (a)

Nuclear Experimental Corporation Five-Year Research and Development Program,"

It is requested that Saxton be authorized by amendment dated December 20, 1962.

of its existing provisional operating license or other appropriate authorization to conduct the Phase 1 experimental program in accordance with changes and ad-ditions described in Addendum No. 1 to the Phase 1 Safeguards Report.

" Proposed Revision of Supplement No.1 to the Saxton Technical (b)

It is requested that Supplement No.1 to the Saxton Technical Specifications. "

Specifications be revised or amended as proposed to provide for changes and additions to the Phase 1 experimental program as described in Addendum No.1 to the Phase 1 Safeguards Report.

i Applicant further requests that the Saxton Technical Specifications be 2.

amended so as to express the min 12 cum burnout safety factor in terms of the DNB correlation currently in use by the Westinghouse Atomic Power Division (hereinafter referred to as the W-2 correlation) rather than the WAPD correlation used for the 1

The burnout safety factor, based on the W-2 current Technical Spscifications.

correlation, for operation with rod control is 2.91 under steady-state conditions l

at 20 MWt, compared with a facter of 2.2 for the sa e conditions usint; the WAPD l

correlation.

Accordingly, it is requested that the minimum burnout safety factor contained in paragraph 6(k) of the existing Saxton Technical Specifications be revised to read as follows:

" Minimum burnout safety 1' actor (W ? correlation) 2.91" SAXTON NUCLEAR EXPERIMETAL CORPORATION (S E A L)

By

/s/

R. E. Neidig President Attest:

/s/

R. E. Sypher Secretary Sworn and subscribed to before me this 20th day of Deccuer 1962.

/f

[

Ti e. 4

/e/ Martin A. Kohr (S E A L)

Notary Public 2 910424 y),01' Muhlenberg Township, Berks County My Ccel_?rien Expires Fet. b, 1966 CiOK91-17 PDR

_