05000395/LER-1982-051, Forwards LER 82-051/03L-0.Detailed Event Analysis Encl

From kanterella
(Redirected from ML20064F265)
Jump to navigation Jump to search
Forwards LER 82-051/03L-0.Detailed Event Analysis Encl
ML20064F265
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 12/30/1982
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20064F268 List:
References
NUDOCS 8301060293
Download: ML20064F265 (2)


LER-1982-051, Forwards LER 82-051/03L-0.Detailed Event Analysis Encl
Event date:
Report date:
3951982051R00 - NRC Website

text

4

/

SOUTH CAROLINA ELECTRIC & GAS COMPANY POST OppiCE 764 CotuustA. south CAROLINA 29218 d

o. w.oixou.;R.

Vice PRESIDENT M

er 30, 19M n

7 NucLEan OPEnAvioNS s

ca Mr. James P. O'Reilly, Director

?-

U.S. Nuclear Regulatory Commission 9f Region II, Suite 3100 c,

101 Marietta Street, N.W.

cf Atlanta, Georgia 30303

SUBJECT:

Virgil C.

Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Thirty Day Written Report LER 82-051

Dear Mr. O'Reilly:

Please find attached Licensee Event Report #82-051 for Virgil C.

Summer Nuclear Station.

This Thirty Day Report is required by Technical Specification 6.9.1.13.(b) as a result or entry into Action Statement"a'or Technical Specification 3.11.1.3,

" Radioactive Effluents, Liquid Waste Treatment," on December 2, 1982.

Should there be any questions, please call us at your convenience.

Ver trul

yours, l

T

/

0. W.
xon, r.

HCF:0WD:dwr Attachment cc:

V.

C.

Summer A.

R. Koon T.

C. Nichols, Jr.

G.

D. Moffatt G.

H. Fischer Site QA j

0. W.

Dixon, Jr.

C.

L. Ligon (NSRC)

H. N.

Cyrus G. J. Braddick H. T.

Babb J.

L.

Skolds D.

A. Nauman J.

B. Knotts, Jr.

M.

B. Whitaker, Jr.

B.

A. Bursey W.

A.

Williams, Jr.

I&E (Washington) 0.

S. Bradham Document Management Branch R.

B.

Clary INPO Records Center M. N. Browne NPCF File

. OFl}CIAL COPY r301060293 821230 PDH ADOCK 05000395 M~ db S

PDR

s r

Mr. James P.

O'Reilly LER No.82-051 Page Two December 30, 1982 DETAILED DESCRIPTION OF EVENT On December 2, 1982, with the Plant in Mode 1, Surveillance Test Procedure (STP) 145.002 was performed unsatisfactorily on the Waste Evaporator.

The liquid radwaste treatment system is required to be OPERABLE per Technical Specification 3.11.1.3,

" Radioactive Effluents, Liquid Waste Treatment".

PROBABLE CONSEQUENCES There were no adverse consequences resulting from this event as the system was in compliance with the Technical Specification Action Statement.

CAUSE(S) OF THE OCCURRENCE The distillate pump of the waste evaporator package is equipped with an external thermal cut-out switch that is wired into the pump motor circuitry as a start permissive.

The leads for the thermal cut-out switch were found pulled out of the pump junction box, which inhibited the pump start.

The cause for the damaged assembly is unknown.

IMMEDIATE CORRECTIVE ACTIONS TAKEN The Licensee took the following corrective actions:

1) the thermal cut-out assembly was replaced;
2) the circuitry was megged to ensure circuit continuity; and 3) the applicable Surveillance Test Procedure was performed satisfactorily on December 13, 1982.

ACTION TAKEN TO PREVENT RECURRENCE The Licensee plans no further action for this event other than the normal surveillance testing.