RO 82-016:on 820608,w/plant at 100% Power Fire Main Break Occurred at Const Site.Both Fire Water Storage Tank Levels Decreased Below Tech Spec Limits.Break Isolated & Fire Water Storage Tanks Restored
ML20054H082
Person / Time
Site: Millstone Dominion icon.png
Issue date: 06/08/1982
From: Mroczka E
NORTHEAST NUCLEAR ENERGY CO.
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
MP-2-5202, RO-82-016, RO-82-16, NUDOCS 8206220554
Download: ML20054H082 (1)


Text

IWMFITII!AST IFFII.frIlis P.O. BOX 270

] $N.Nf7Z.117 m m, ve a w eom w ,m.. HARTFORD. CONNECTICUT 06101 (24 W9H g g  ; .1:.,, " "'}'{J[,g June 8, 1982 MP-2-5202 Mr. Ronald C. Haynes Regional Administrator, Region I Office of Inspection and Enforcement 631 Park Avenue King of Prussia, Pennsylvania 19406

Reference:

Facility Operating License No. DPR-65 Docket No. 50-336 Reportable Occurrence R0-50-336/82-016

Dear Mr. Haynes:

This letter provides notification of reportable occurrence 82-016, required to be submitted within one working day following the event pursuant to the require-ments of Millstone Unit 2 Appendix A Technical Specifications paragraphs 6.9.2.g.

and 3.7.9.1.b.

With the plant at 100% power a fire main break occurred at 11:38 on the Unit 3 construction site. This resulted in both fire water storage tanks' levels decreasing below the 200,000 gallon minimum required by Technical Specification limiting condition for operation paragraph 3.7.9.1.b. Level decreased to approximately 60% or 150,000 gallons in each tank before the break was isolated. The break was isolated at 11:55 and at 12:28 the fire water storage tanks were restored to the 200,000 gallon minimum requirement.

Yours truly, NORTHEAST NUCLEAR ENERGY COMPANY h 4

//7d' c' &

/

. J. Mroczka ' /

Station Superintendent Millstone Nuclear Power Station EJM/JJK:mo cc: Director, Of fice of Management Information and Program Control, Washington, D. C. (3)

U. S. Nuclear Regulatory Commission, c/o Document Management Branch, Washington, D. C. 20555 OhKO hohh6 l PDR m -