Text

_

O Wisconsin Electnc powca cournsr 231 W. MICHIGAN. P.O. BOX 2046. MILWAUKEE, WI 53201 October 13, 1980 Mr. Harold R.

Denton, Director Office of Nuclear Reactor Regulation U. S. NUCLEAR REGULATORY COMMISSION Washington, D. C.

20555 Attention:

Mr.

R.

L. Clark, Chief Operating Reactors Branch 3 Gentlemen:

DOCKET NOS. 50-266 AND 50-301 STATUS OF FIRE PROTECTION MODIFICATIONS POINT BEACH NUCLEAR PLANT, UNITS 1 AND 2 On August 2, 1979, the Nuclear Regulatory Commission issued Amendment Nos. 39 and 44 to Facility Operating Licenses DPR-24 and DPR-27 for the Point Beach Nuclear Plant, Units 1 and 2.

These amendments added license conditions related to the completion of fire protection modifications and referenced the NR2's Fire Protection Safety Evaluation Report (SER) for the Point Beach Nuclear Plant.

By the terms of the license conditions, Licensee, Wisconsin Electric Power Company, is required to complete the modifications identified in Paragraphs 3.1.1 through 3.1.33 and specified in Table 3.1 of the SER.

We have been progressing with these modifications and have described in Enclosure 1, for your information, the status of each of these items.

We have been unable to meet the specified completion dates for some of these items and expect that we will not be able to complete certain other items before the scheduled dates.

Our reasons and justifications for these schedule delays are provided in Enclosure 1 for each applicable item.

We request that the SER be supplemented to reflect the revised schedule dates we have presented herewith.

We also request that you provide the necessary responses to our additiona1 information submittals as soon as possible, so that additional schedule delays may be avoided.

If you have any questions regarding our implementation progress on these fire protection modifications, please contact us.

Very truly yours,

/~~~T:>

Sol Burstein Exec tive Vice President \\

801021o 5 0 o Attachment F

Copy to: NRC Resident Inspector Point Beach Nuclear Plant

ENCLOSURE 1 Page 1 of 5 STATUS OF FIRE PROTECTION MODIFICATIONS POINT BEACH NUCLEAR PLANT, UNITS 1 AND 2 SER ITEM 3.1.1 Emergency Breathing Apparatus - Complete 3.1.2 Smoke Exhaust - Incomplete Delayed delivery of the system exhaust fan caused several months extension of the implementation period for this modification.

Installation is progressing and the modification should be completed by December 31, 1980.

Additional design information requested in SER Section 3.1 was submitted with our September 26, 1979, letter.

We have not received a response to this submittal.

3.1.3 Fire Hose Stations - Incomplete Fire hose station installation is complete.

The fire hose initially obtained was found to be unacceptable and rejected.

Correct fire hose has been reordered.

This modification will be complete upon the delivery and installation of the correct fire hose.

Based upon the present delivery schedule, we expect this modification to be completed by November 30, 1980.

3.1.4 Fixed Water Suppression Systems - Incomplete An installation contract has been negotiated und the systems have been designed.

The contractor began installation work on October 13, 1980.

We expect this modification to be completed by December 31, 1980.

Additional design information requested in SER Section 3.1 was submitted with our June 23, 1980, letter.

We have not received a response to this submittal.

3.1.5 Water Damage Protection - Incomplete A preliminary cable spreading room floor drain system has been designed.

The final requirements and design for this system are dependent upon the overall fire protection system for the cable spreading room.

SER Section 5.3.6 states that further evaluation by the Staff and licensee is required and that the adequacy of the cable spreading room fire protection for safe shutdown cables and equipment will be addressed in a supplement to the SER.

This supplement has not been issued.

Final design and implementation of this modification, if required, will be accomplished within 180 days following the establishment of overall cable spreading room fire protection requirements.

Pago 2 of 5 SER ITEM 3.1.5

' Electrical boxes in the auxiliary feedwater pump (Cont'd) area which require upgrading have been identified.

Doors will be gasketed and conduit connections will be sealed.

We anticipate that this modifica-tion will be accomplished by December 31, 1980.

3.1.6 Waterproofing - Complete 3.1.7 Drain System - Complete 3.1.8 Access for Manual Suppression - Complete 3.1.9 Fire Barriers - Incomplete The penetration seal installer is on-site and fire barrier upgrading work began September 30, 1980.

Implementation completion dates for individual plant building fire barriers will not be met because of the necessity for coordination of the fire barrier upgrading with TMI-2 modification requirements and IE Bulletin 80-11 block wall analyses and upgrading.

We anticipate that total fire barrier upgrading will, however, be completed 4

by the end of the Spring 1981 Unit 2 refueling outage as scheduled.

3.1.10 Ventilation Dampers - Complete 3.1.11 Cur'bs and Barriers - Complete 3.1.12 Fire Detectors - Incompleta The engineering effort required for the specifica-tion and purchase of a suitable fire detector system has been substantial.

Development of a methodology for detector location was required.

This information was submitted for Staff review and approval with our December 20, 1979, letter.

Approval to implement our developed methodology was received with your March 5, 1980, letter.

We anticipate the release of a contract for instal-

-lation of the fire detection system to be accomplished i

by; November 15,-1980.

Installation of Unit 1 containment fire detectors cannot, therefore, be accomplished during the Fall 1980 refueling outage.

We expect that the Unit 1 containment installation can be accomplished during the anticipated Spring

~

1981 Unit 1 steam generator inspection outage.

We anticipate that the entire fire detection system will be installed by the'end of the Spring Unit 2 refueling outage.

Submittal-of the required fire detector performance documentation will be made following detector purchase.

3.1.13 Portable Handlights - Complete

Page 3 of 5 SER ITEM 3.1.14 Cable Separation - Incomplete The locations of cable and conduit crossovers have been identified.

ANI-approved three-hour rated fire seals will be installed at the conduit terminations

.as part of the fire barrier penetration seal work in progress.

We expect this modification to be completed by the end of Unit 2 Spring refueling outage.

Additional design information requested in SER 3.1 is provided as an attachment to this enclosure.

3.1.15 Ventilation System Control Cables - Not Required The subject control cables and junction boxes were shown to be located in a single room on plant design drawings.

Engineering inspection has verified that these cables are located outside of the diesel generator roons and modification is not required.

3.1.16 Hydrant Hose House Equipment - Complete 3.1.17 Hydrogen Hazard Fire Protection - Incomplete The hydrogen header has been' rerouted through the turbine building and the excess flow and manual isolation valves have been installed.

Additional design information requested in SER Section 3.1 was submitted with our September 26, 1979 letter.

We have not received a response to this submittal.

SER Section 5.8.6 states that your evaluation of the effectiveness of Marinite board to retard fire propagation has not been completed.

Hydrogen piping fire barriers have not been installed in the Auxiliary Building for this reason.

The remaining work can be accomplished 180 days following determination of an acceptable fire barrier material.

J.dditional design information requested in SER Section 3.1 was submitted with our September 26, 1979 letter.

We have not received a response to this submittal.

3.1.18 Ventilation Flow Monitoring - Complete 3.1.19 Portable Fire Extinguishers - Complete 3.1.20 Hydrant Gate Valvec - Complete 1

3.1.21 Interior Hose Station Nozzles - Complete 3.1.22 Water Supply - Fire Department Pumper Connection -

Complete

Page 4 of 5 SER ITEM 3.1.23 Carbon Dioxide Hose Reel Nozzles - Complete Additional design information requested in SER Section-3.1 was submitted with our September 26, 1979, letter.

We have not received a response to this submittal.

3.1.24 Diesel Generator Air Intake Structure - Incomplete Although an intake structure has been designed, a functional evaluation of the design determined that it would be a significant impediment to plant operation and maintenance activities.

An alternate approach of reversing ventilation flow through the diesel generators rooms was, therefore, investigated.

An' October 1980 test will be. performed to verify the adequacy of generator cooling and ventilating fan performance with reversed air flow.

Following this test, we expect to select the design approach for this modification and submit the additional design information requested in SER Section 3.1 by November 30, 1980.

The modification can be completed 180 days after acceptance of the submitted engineering approach.

3.1.25 Ventilation Duct Penetration Seals - Complete 4

3.1.26 Auxiliary Building Cable Tray Penetration Seals -

Incomplete This modification is part of the fire barrier upgrading work which is in progress (Item 3.1. 9).

j 3.1.27 Containment Building Fire Stops - Incomplete This modification is part of the fire barrier upgrading work which is in progress (Item 3.1. 9)-

3.1.28 Service Building Penetration Seals - Incomplete This modification is part of the fire barrier

. upgrading work'which is in progress (Item 3.1. 9).

~

3.1.29

-Cable Tray Penetration Seal Qualification - Incomplete The penetration seal installer presently performing fire barrier upgrading work (Items.3.1.9, 3.1.14,-

3.1.26,.3.1.27, 3.1.28)- has an _ inventory of fire tested and ANI-approved seal designs.

We expect that all seals required at PBNP can be provided from this~ inventory.

A copy of the installer's standard seal designs and ANI approval sheets is

provided in Enclosure 2.

This information satisfies theLSER Section 3.1 request for additional design information for the'above listed modifications.

Page.5 of.5 SER ITEM 3.1.30

~ Communications System - Complete 3.1.31

. Emergency Diesel Generators - Remote-Panel'- Incomplete Extensive. engineering. review of this modification has been required to ensure that the modification will not impair emergency diesel generator avail-ability.

The-addition of seismic considerations has caused a prolonged procurement time for the.

r panels.

We expect that this modification can be completed by September 30, 1981.

3.1.32

. Fire Hydrant Inspections - Complete Additional design information requested in SER 3

-Section 3.1 was submitted with our June 23, 1980, letter.

We have not received a response to this submittal.

3.1.33 Control' Room Light Fixtures - Complete Additional design information requested in SER Section 3.1.was submitted with our June 23, 1980, letter.

We have not received a response to this submittal.

W 1

+,-a

=_g,

-T-r-

U q :pe y z 39

y. v, -

f,l J

l i

BURT C. PROO M.CPCU Pressent NOTIFICATION OF ANI/MAERP CABLE A!!D PIPE PENETRATION FIRE STOP SYSTEM ACCEPTAt;CE The following fire stop supplier has successfully completed the "ANI/MAERP Standard Method of Fire Tests of Cable and Pipe Penetration Fire Stops".

This form is provided for information only.

FIRE STOP INSTALLER: INSULATION CONSULTANTS & f1ANAGEMENT SERVICES, INC.

BARODA. MICHIGAN TEST DATE: 8/28/79 ACCEPTANCE CATE: 4/21/80 HOUR RATING: 3 GENEPAL DATA CABLE PENETRATIONS PIPE PENETRATIONS Max. Penetration Size 1A"v 1R" Accepted for Floor 8" Pioe in 12" Sleeve yps Yes Accepted for Wall yes Matarial Yes ICf15 Product 60 Density: 22.4 - 29.2 lbs/cu. ft.

Same as for cable Fire Stop Thickness TRAYS:

5" Product 60 & 1" damming 4" Product 60 & 1" damming Conduits: 4" Product 60 &

(both-sides) 1" dammino (both sides)

Form Material Fiberfrax Hotboard Same as for cable LIMITATIONS Tray Types:

Open ladder only Cable Construction:

No limitations

% Cable Loading:

50%

Tray, 50' Conduit Max. Conduit Sleeve Size:

6" (fiote: % Loading = Total Cross-sectional area of cable / Cross-sectional area of tray / conduit)

Complete details of fire stop installations are to be submitted to American fluclear' Insurers prior to actual installation. ANI acceptance is for insurance coverage related to fire protection of the property and is based on information provided and any information contained hereon is considered confidential and cannot be released to any other person or organization without the written consent of the Supplier and ANI.

M b_

w

' J.J.fANEY - VICE F (ESIDENT, PROPERTY ENGIfiEERING r,..,

3

-,r

, - -=

g,:. # :2

U

.:O;p-E..y,EE:: s r;;;n.*E*7 l

l l

n i

i l -l

0 i

1 BURT C.PROOM.CPCU Pos.o.at NOTIFICATION OF ANI/ttAERP CABLE AND PIPE FENETRATIO!i FIRE STOP SYSTEM ACCEPTA!!CE The following fire stop supplier has successfully ccmpleted the "Atil/MAERP Standard Methoc of Fire Tests of Cable and Pipe Feretration Fire Stops".

This form is provided for information only.

FIRE STOP INSTALLER: INSULATION CONSULTANTS & MANAGEMENT SERVICES, INC.

BAR0DA, MICHIGAN TEST CATE: 8/28/79 ACCEPTANCE DATE: 4/21/80.

HOUR RATING: 3 GENERAL DATA CABLE PENETPATIONS PIPE PENETRATIC'NS Max. Fenetration Size 18"x 38" Accepted for Floor N/A yes Accepted for Wall Yes Material Dow corning Sylgard 170 Silicone Elastomer N/A Density: 81 lbs./cu.ft.

Fire Stop Thickness Trays: 6" Silicone Elastomer &

1" danming N/A Conduit: 4" or less-3" HITACHI HIGHSEAL & 1" Damming or 2" Dow corning 96-081 RTV Silicone caulk & 1" dammina Forn Material FIBERFRAX HOT BOARD N/A LIMITATIONS Tray Types:

OPEM LADDER CMLY Cable Construction:

N0 LIMITATIONS

% Cable Loading:_ 503

Tray, 50:

Conduit Max. Conduit Sleeve Size:

4" (Note: % Loading = Total Cross-sectional area of cable / Cross-sectional area of tray / conduit)

Complete details of fire stop installations are to be submitted to American Nuclear Insurers prior to actual installation.

ANI acceptance is for insurance coverage reltted to fire protection of the property and.is based on information provided and any information contained hereon is considered confidential and cannot be released to any other person or organization without the written consent of the Supplier and ANI.

J.JAARNEY -

E PRESIDENT, PROPERTY ENGINEERING

w..

b 4

r27;p;, ; ' ~ qa:;}, ::L=":mi j

t 3,

l y

BURT C. PROO M.CPCU hesdent

!;0TIFICATI0:10F At;I/f!AERP CABLE Af;D PIPE pef'ETRATION FIRE STOP SYSTEM ACCEPTANCE The following fire stop supplier has successfully completed the "At;I/f!AERP Standard l'ethod of Fire Tests of Cable and Pipe Penetration Fire Stops". This form is provided for information only.

FIRE STOP IfiSTALLER: INSULATION CONSULTANTS 5 MANAGEMENT SERVICES, INC.

BARODA, MICl!IGAN TEST DATE:

3j,23/79 ACCEPTA!;CE CATE:4/21/SO.

HOUR RATIf;G:

3 GE:lERAL DATA CABLE PE';ETRATIONS PIPE PENETRATI0 tis fiax. Penetration Size 36" V 42" 8"

l'in e In 12" Sleeve Acceoted for Floor yns Yes Accepted for Wall yes Material Yes Dow Corning 3-054S Silicone ICMS Leaded Dielectric Gel RTV Foam Density: 15.7-17.5 lbs./cu.ft.

Density: 150 lbs./cu. ft.

Fire Stop Thickness Trays: 9" Silicone Foam 5 1" 12" Dielectric Gel with Damming Silicone fabric boots on Conduit:

4" or 1 css-6" foam 5 each end 5 2" Damming 1" Damming, 6" or larger -

(both ends) 6" foam 5 1" Damming at top 5 2" Damming at base FORM MATERIAL Fiberfrax Hot Board Fiberfrax Durablanket LIMITATIONS Tray Types: Onen ladder oniv Cable Construction:

No Limitations

% Cable Loading:

Snt Tray, 50% Conduit Max. Conduit Sleeve Si::e:

6" (Note: % Loading = Total Cross-sectional area of cable / Cross-sectional area of tray /cenduit)

Complete details of fire stop installations are to be submitted to A:rerican !;uclear Insurers prior to actual installation. ANI acceptance is for insurance coverage reitted to fire protection of the property and is based on information provided and any information contained hereen is considered confidential and cannot be released to any other person or c ga i::ation without the written consent of the Supplier and At;I.

-KJ. 2ARNEY -

PRESIDENT, PROPERTY ENGI!!EERIN'i

w. -

Ll

..I,,

/ \\,l.; [jf

/..\\,f - li

2C;;r r, y.E
.r.E,-

l ',, l,[.

f, \\f i

~ ~.

y,M ' l

,m ;.l ' l i ic i

ll I

y BURT C. PROO M.CPCU President NOTIFICATIO:1 0F ANI/MAERP CABLE AND PIPE PEMETRATICN FIRE STOP SYSTEM ACCEPTANCE The following fire stop supplier has successfully completed the "A;I/l'AERP Standard Method of Fire Tests of Cable and Pipe Fenetration Fire Stops". This form is provided for information only.

FIRE STOP INSTALLER:

It:SULATION C0f;SULTANTS & MAf;AGEMENT SERVICE, li;C.

BRIDGMAii, MICHIGAN TEST DATE:

2/24/77 ACCEPTANCE CATE: 7/27/77 HCUR RATING:

3 GENERAL DATA CABLE PENETRATIONS PIPE FENETDATIONS Max. Penetration Size Ji' x 56L' 60" pipe sieeve Accepted for Floor vre YE5 Accepted for Wall yc yES Material Silicone foam 4as dispensed by ICMS Sare as cabie, clus, i5u= leaceo Silicone Foam Injection Unit.

foam, or insulated boot-type Den;:ty: 17-23 lbs/cu.f t.

seal.

  • Cow Ccrning 3-6548 RTV Silicene Fire Stop Thickness Trays: 10 inches minimum 8 inches minimum (l" damming-9" foam)

(l" damming-7" foam)

Conduits: 8 inches minimum

/1" dmino-7" feard Form Material Carborundum Company's Fiberfrax-Bulk Fiber, Durablanket and Hot Board LIMITATIONS Tray Types: Onen ladder-solid bottom Cable Construction:

No limitations

" Cable Loading:

50%

Tray, 50 Conduit Max. Conduit Sleeve Size: C (Note: % Loading = Total Cross-sectional area of cable / Cross sectional area of tray / conduit)

Complete details of fire stop installations are to be submitted to Arrerican Nuclear Insurers prior to actual installation. ANI acceptance is for insurance coverage related to fire protection of the property and is based on information provided and any information contained hereon is censidered confidential and cannot be released to any other person or organization without the written consent of the Supplier and ANI.

J.3 n

s os J.J. CARNEY - VICE PRESIDENT, PROPERTY ENGINEERING s..

,7 g.,:.:s

,m c.-.,;

.._y.

a.,--

-- - 3

ek GLOSSARY - INDEX s

Nv' PENETRATION TYPES C

Conduit E

Electrical G

Gap H

HVAC M

Mechanical S

Structural PRODUCT TYPES 01-19 Silicone Products 20-29 Leaded Products 30-39 Refractory Preducts 40-49 Coating Products 50-59 60-69 70-79 80-89 90-99 Specialty Products SPECIFIC PRODUCT TYPES SILICONE PRODUCTS 01 Silicone Foam 02 ICMS Product 60 03 Silicone Caulk 04 170 A & B 05 Silicone Sheeting Material 06 Dielectric Gel LEADED PRODUCTS 20 Leaded Silicone 21 Leaded Dielectric Gel REFRACTORY PRODUCTS l

30 Fiberfrax Damming Material 1

is A

A

=

3<.

,p INDEX C0101 Fire Seal - Conduit Penetration - 6" Seal - Wall C0102 Fire Seal - Conduit Penetration - 6" Seal - Floor C0103 Fire Seal - Conduit Penetration - 7" Seal - Wall C0104 Fire Seal - Conduit Penetration - 7" Seal - Floor CG105 Fire Seal - Conduit Penetration - Continuous Conduit - Wall C0106 Fire Seal - Conduit Penetration - Continuous Conduit - Floor C0107 Fire Seal - Conduit Penetration - Conduit & Sleeve Seal - Wall C0108 Fire Seal - Conduit Penetration - Conduit & Sleeve Seal j

C0109 Fire Seal - Conduit Penetration - Exterior of Barrier - Wall 1

C0110 Fire Seal - Conduit Penetration - Exterior of Barrier - Floor f

CO211 Fire Seal - Conduit Fenetration - ICMS Product 60 - Wall CO212 Fire Sea) - Conduit Penetration - ICMS Product 60 - Floor C0313 Fire Seal - Conduit Penetration - Silicone / Adhesive - Wall C0314 Fire Seal - Conduit Penetration - Silicone / Adhesive - Floor C0315 Smoke & Air Seal - Conduit Penetration - Silicone / Adhesive - Wall l

C0316 Smoke & Air Seal - Conduit Penetration - Silicone /AdSesive - Floor Fire & Radiation Seal - Conduit Penetration - 150 Lb. Density - Wall C2017 C2018 Fire & Radiation Seal - Conduit Penetration - 150 Lb. Density - Floor C2019 Fire & Radiation Seal - Conduit Penetration - 150 Lb. Density Conduit & Sleeve Seal - Wall C2020 Fire & Radiation Seal - Conduit Penetration - 150 Lb. Density Conduit & Sleeve Seal CO221 Fire Seal - Conduit Penetration - Continuous Conduit - ICMS Product 60 - Wall 00222 Fire Seal - Conduit Penetration - Continuous Conduit - ICMS Preduct 60 - Floor

1 CONCRETE BARRIER CONDUIT Ag

/.k.

  • 4

~

b 6

o ELECTRICAL p

CABLE p

/

a:

4..:" 5ghh!.h 1" FIBERFFAX

.c hjlj'

+c'!4 @.:

DA?D!ING OR EQUAL 7.'

(BCTil SIDES) 4 y,

~:..'/.

N:)? Yi g.

  • G 6" DEPTil

~

' /.

9ILICONE FOAM P

b.

INSULATION CONSULTANT & MANAGEMENT SERVICE

'0" Typical Detail Drawing 7'ra Fire Seal Conduit Penetration 6" Seal - k'all es 5 w q_

c~=0 p)2 n" gg an oa t u-l a-30 cart 5-6-60 Datt 5-1-80 oarc sc^

0*G w

..'t.

'N T 4 C0101 y

n n rr ervis.n s ev n

a=:.-

l

1 ELECTRICAL CABLE f

WH v

- u mw Y

CONDUIT tm

.b b:

w k

If EY 6" DEPTH

  • 4' lli

![

SILIQ0NE FOAM k

6 n

h Nf3);f,h;ff:

  • d
  • b g

,q

>m:-

p-p s\\

p 6w 1" FIBERFRAX DA!!!!ING A

(OR JUAL) b g

CONCRETE N

O BARRIER p

w

.g

')

4 i

l INSULATION CONSULTANT & MANAGEMENT SERVICE

'0" Typical Detail Drawing I'ILE Fire Seal Conduit Penetration 6" Seal - Floor av gw c_

c.= o ing a 7f 7-am cart 4-14-80 cart 5-6-00 D^rt 5-7-60 c^rt scatt NTS owG ec C0102 y

e e.,r

.,v,,-

~,

1 CONCRETE BARRIER

.. x' A

CONDUIT

..g

, [>

4*

ELECTRICAL A

9;.

CABLING 6

1" FIBERFRAX

v. *i E

DAMMING-OR EQUAL

/ f.

(

(BOTH SIDES) 4 Yj

{:,.. ' ~ '.S*

~.

7" DEPTil SILICONE FOAM

/>

.P

  • 1 INSULATION CONSULTANT & MANAGEMENT SERVICE Typical Detail Drawings TirLE Fire Seal Conduit Penetration 7" Seal - Wall St QQQ two LG 4PP g 7-am ca rt 4-14-60 oAft 5-0-oO cart 3-i-cy part i

scnt Nrs oom C0103

=f e

n. rr ww.m.

~.

1 ELECTRICAL CABLING w

hamp CONDUIT

)

p-

.1 g

s 6

Sa Q

N 7" DEPTH

,k), 5.Nh )

y SILICONE FOAM 4

1. W 6
  1. . 0

'a,, -

b

.:t+

V 4.,

b*- [0:+::$

5 f

3 6

e g

CONCRETE 3

Q ;>(%

O m' BARRIER W

d

1" FIBERFRAX N

A DMOIING

'g*

(OR EQUAL) b 9

A

,s, p

v g

v

~

4 INSULATION CONSULTANT & MANAGEMENT SERVICE

'0" Typical Detail Drawing

Id Fire Seal Conduit Penetration

(

7" Seal - Floor 1

ew ye cmo y,, g

. A" y,e7 '

oa't 4-14-8t o*Tt 5-6-80 o^tt 5-7-60 cart kaa NTS tm

  • C0104 5'

m narr erv,s.rws av c-

.g i

l l

T CONCRETE BARRIER CONTINUOUS

.A ONDUIT

  • ./

b

  • 7' ELECTRICAL
  • /

e FABLING

  • p.
.,.j p'

j 1" FIBERFRAY.

DM0!INC-OR EQUAL

.?:.,.

(BOTli SIDES)

.p 4

.. :S!

    • P*

7" DEPTH SILICONE FOM1 P.

9 -

INSULATION CONSULTANT & MANAGEMENT SERVICE

'0" Typical Detail Drawing T'TLE Fire Seal Conduit Penetration Continuous Conduit - Wall av 7g co yg

.= yg7-

[

od't4-16-60 cart 5-6-80 D*'t 5-7-80 Dart scatt NT9 D*G W y

n

,.vr m.wws e,

c-C0105

T l

1 I

i ELECTRICAL l

CABLING

/

CONTINUOUS CONDUIT j

SLEEVE

?.t

. I y,. i 7" DEPTH

.A

yj

[

/;.)

SILICONE FOAM

8. l Vg.

f[h k$$ 0*

.p*

4

?:g

'A.

Mm ils$

l o

\\

q CONCRETE g

'g.

A BARRIER b-1" FIBERFRAX DAM 1ING N.

' C>.

~

(OR EQUAL)

%V v

~/

INSU! A ' TON CONSULTANT & MANAGEMENT SERVICE roR rypical Detail Drawing mLE Fire Seal Conduit Penetration Continuous Conduit - Flaor ev qwt C"D ff.G TE7-

^"

cart 4-10-60 cart 5-6-80 D*'t 5-7-80 D

ut NIS _

N*

C0106

.,n m m.-m e

.~

-e

.m ---

1 CONCRETE BARRIER SLEEVE

,b,Y

  • b**b-

/

CONDUIT dif!. !:-.....

l ELECTRICAL

,D

.. d! M..gS$?.3'.

CABLING

/:.sfl.f[jf. $('.;?.$.~'kN.

)

h NU;?'p.-....s' c.

..;ty;,

iW

  1. l:N; d.$..':h S /

$.$5 5 0.5 D. f

!.y~.p - a

.e h' 6" DEPTH

/I;d

g A

N SILICONE FOAM S

9

',.A.*

.b 1" FIBr.RFRAN DND!ING-OR EQUAL (BOTH SIDES)

INSULATION CONSULTANT & MANAGEMENT SERVICE

'O' Typical Detail Drawing T8fLE Fire Seal Conduit Penetration Conduit & Sleeve Seal - Wall Bv 3yC Cam 0 MG AN gg AN oart *-14-6v cait 5-o-60 Dart 3_7_ge cart o

N NTS D"G W C0107 ll wr m.~.

T i

i l

6" DEPTH SILIC0!!E FOAM h

+

M V

D SLEEVE 3

.../

vgr..

e

-u

.1,

  • 6 f.2 $$^e:.Y&ns,. <

).:Q.WS-

.:d

$p!1%.:.f.9.*?.!.. W @.?

.-m s

i N..jeg.g. 7$j f.

691 j'

.U.f.i't.i.jf.j:1?i ?:

%~

. h:..f.

p

...s c 4,.

9"

.f.....'. '!(.d,tb

@.1 D,@$.i E$.

C0!iCRETE

%$w,iE;Q-~y 9.i@ A *.

4

~ BARRIER 4

d

.g i.~{6x gg n

a g

s%

y:.

,f

%,.r;)]

4 N

y 1" FIBERFRAX g

4 DA>011!;G b.

g (OR EQUAL) w(

8.

ELECTRICAL P,

DAFO!I!!G 4

C0!iDUIT INSULATION CONSULTANT & MANAGEMENT SERVICE

'0" Typical Detail Drawing TITLE Fire Seal Conduit Penetration Conduit & Sleeve Seal 8'

~3 w c,,.

C"o

/AG

"" (E7' 0475 4-14-80 cart 5-6-8L cart 5-7-80 ca rt xea NTS oas **o C0108

=

4

-.... ~,

4

T CONCRETE BARRIER k

ELECTRICAL

. h ',

CABLING

'7,*.**,

.p CONDUIT

  • .A*.

y 650 psp; 1" FIBERFRAX

' M,:OT6'TS

.A.

\\ DA.T!ING-OR EQUAL j

(ALL LOCATIONS SHOWN)

/;r

~

/

l, 4.'.6

.s*3*

~~

4 6" DEPTH SILICONE FOAM INSULATION CONSULTANT & MANAGEMENT SERVICE Typical Detail Drawing

(

TITLE Fire Seal Conduit Penetration l

Exterior of Barrier - Wall av gut c-*o n,,2 am yg7-a~

cart a-la-go cart 5-6-80 cart 5-7-80 D^'E scaa NIs o=c w C0109

-l-...

m.. ~

c,

T ELECTRICAL CABLING v

.m r:

CONDUIT l

U E

~

k.

j 6" DEPTH

/~

6

.' 'Qgg?

W' SILICONE FOAM A

p

.h( s.

..q

/

s

.a

/

?.

1 5

s 7.

e

  • *s N

CONCRETE

.4s

(,.,* j ',

N

.g*

BARRIER

%s~

J k.

s'.g,p k*

1" FIBERFRAX N

DAMMING (OR EQUAL) 4 4

./

i l

I i

INSULATION CONSULTANT & MANAGEMENT SERVICE

'0" Typical Detail Drawing Fire Seal Conduit Penetration Exterior of Barrier - Floor es 5we c~ a sg ;-

s"yfg 7-an omit t.-15-go cart 5-6-80 D^'t 5-7-80 DE

%^' t NT4 D*G 'O Col 10

1 CONCRETE BARRIER X

CONDCIT

.g N.*

ELECTRICAL CABLING

- y 4

?

/

.g 1" FIBERFRAX Ikf:k;f)I,kj..Ji DAFD!ING-OR EQUAL 3, l 7,~

(BOTH SIDES)

?3

.A.

/

/

-b' b.

4" DEPTH A

ICBIS PRODUCT 60 INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing mLE Fire Seal Conduit Penetration IC115 Product 60 - Wall av 7%

c-o fata

    • yE 7-Am l

oart 4-15-80 CE 5-6-80 D^7E 5-7-80 o^'t I

scatt NTS~

0*G W CO211 l-u' e

n..e

.ev.e.n..e c.

1 ELECTRICAL CABLING 4

NNO v

d 6

CONDUIT 8 N

-)

h..

%/

(;jy 9.:.

O 5

y

  • 4 CONCRETE g**

Il P,

t,{

4-g s

d.,.

.g

  • N-(>

j 7

b b.

g

  • b 4" DEPTH 4

Y 1" FIEERFRAX DA:D1ING-OR EQUAL ICMS PRODUCT 60 (BOTH SIDES)

'N

,/

j 1

l i

l 1

l INSULATION CONSULTANT & MANAGEMENT SERVICE r0R Typical Detail Drawings TITLE Fire Seal Conduit Penetration ICMS Product 60 - Floor cs.o ng c am ygg am 8'

TuJ L cart 5-6-RO DE 5-7-80 DE o^ rt f,_75_go scnt 3is owc w CO212 w?

.o

-..r

.rv~.

cu.

c..

I i

j i

i CONCRETE BARRIER W

  • O CONDUIT 4-

.5.-

k, b.

'O-ELECTRICAL A

a CABLING N

4

/

b

(

f.

4 ffhf.[:.

m

/ b 1" FIBERFRAX DM011NG-OR EQUAL d'

BOTH SIDES)
  1. ~

/.QA 2" DEPTil SILICONE CAULK

.O INSULATION CONSULTANT & MANAGEMENT SERVICE

'0" Typical Detail Drawing "M

Fire Seal Conduit Penetration Silicone / Adhesive - Wall sv gwt c-=o gc

.= ygf An oE4-16-80 o^rt 5-6-80 o^rt 5-7-80 cart O LE NTS M 'o C0313 af

e..

,,v,<,,w..

c.

T ELECTRICAL CABLING n,

r..

SLEEVE 7*

1 b

!jbf YA*-

i_h'..

2" DEPTH d

b y!F 4 0 SILICONE CAULK 3

A

.p.

m P.

  • bl

. 'k p

1" FIBERFRAX

    • '[.

h,,,.,d*.

DAID!ING (OR EQUAL)

O p.

CONCRETE m i BARRIER

.J 4

INSULATION CONSULTANT & MANAGEMENT SERVICE

'0" Typical Detail Drawing TITLE Fire Seal Conduit Penetration Silicone / Adhesive - Floor av 7ye c""

MtC

'" 7/.E C

^"

cart 4-16-80 cart 5-6-80 D*'E;-7 on

^'E vna N'TS OwG %

C0314

,.,,1 w

v,..~,<

~.

i CONCRETE BARRIER d

CONDUIT

.g

- l

..p ELECTRICAL CABLING 1" FIBERFRAX h

.9.-

DAID11NG (OR EQUAL)

,h' 8

P.',. d f

e

-+

-q..:.-

P-2" DEPTH SILICONE CAU T INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing I'TM Smoke & Air Seal Conduit Penetration Silicone / Adhesive - k'all er zy c~o gx nn gg. 7-n" o^fE 4-14-8C. 0* rt 5-6-80 D^ rt 5-7-80 cart suu y~ 79 ons %

C0315 j

=

-.... ~

l

T l

ELECTRICAL 6

CABLING 27 2" DEPTil j

i l

-w SILICONE CAULK

'N 7

N Ng%

1" FIBERFRAX DAEING (OR EQUAL) t

[

P..

-CONDUIT

1..

..a.

,P p

,4

b..b. '

. 4..',

b' '

O

'h CONCRETE

. N..-

.>4 BARRIER 4 '. 'f..b..6 s.

4 b,

4

~

J

~

2 INSULATION CONSULTANT & MANAGEMENT SERVICE

'0" Typical Detail Drawing

' ' I" Smoke & Air Seal Conduit Penetration Silicone / Adhesive - Floor av 7g co wa A

ygg-Am cart 4-14 80 cart 5-6-80

"'E 5-7-80 D^tt watt NT4 D*G W co3m

4

'*cacT,-

o,knIta 1y

.. <t n

a

enovi,

)

-s

~

.... g

alcaz n

y

c1gz,

/:

..'u m,...v..

.m iso "-

byolo,;gsin.

E DEPTH)

.a

..a-T

  1. UlAlloy fo~so,,,,, & M4y ENEgy Vicy ro Det.g,
  1. uVfng

,,, F1rg Audja

Sea, udug netr on

]3 lb Oensjgy ~ g,ull e* WQp ci,,o f4%

f s

car, n~jy~00 car, 3'6 OAyg

~I'do m

s,r7 C2017

+

^

  • r, au o,

~

v ELECTRICAL CABLING v

/

CONDUIT b*

150 LB. DESSITY 4

EADED SILICONE

h wh (FULL DEPTH)

".A

' j.

n[:f-)d;J.k sm...g.pj.S f, g

is,is a

.a

- u P

)h

'g.>

A

.{f.,.jli l:lol:gt.s; Tw 5.b "

f y

4

'4

  • CONCRETE

[0" f ":.

.d BARRIER vg.p -

>b,4

...b.

l

. y ',/

N-4 humus e

INSULATION CONSULTANT & MANAGEMENT SERVICE Typical Detail Drawing roa TITLE Fire & Radiation Seal Conduit Penetration 150 Lb. Density - Floor c~=0 %

"" JA 7"

' ^"

e, gy cart 4-16-80 D^'t 5-6-80 0^tt 5-7-80 0^'t scxt NTS C2018

~

" ^~

.. ~,

i

\\

t CONCRETE BARRIER e

'g SLEEVE

'b 4

N A

CONDUIT

'.. ' 'f

/

r

  • 4-

.:.q '..r-

'.,:3;;@dh.; f. hS

.hI' d

ELECTRICAL h

CABLINC J$

\\;...-} IN$hk'

}..

4i ~ if$ ny. ; M d

^Y

[,-Q,$!

r[$f.(M.fE l

4 s.

?.'W.*,:.

.. iG -Jy 150 LB. DENSITY

@. B;. 2.?
.;c...._ dd LEADED SILICONE
4. l.9.(,:l...g.7'$gi:l'i.

W I

~.

(FULL DEPTH)

a[./:f;. W

.y 5"

d

.g;p,. f.!F :-

g-4;

)

'A, i

l l

i 1

l INSULATION CONSULTANT C MANAGEMENT SERVICE i

FOR Typical Detail Drawing TITLE Fire & Radiation Seal Conduit Penetration - 150 Lb. Density Conduit & Sleeve Seal - Wall j

0' 7 W C.,

chm 0 Ag @

AN gg AM l

o^'t 4-16-80 D^'E 5-6-60 D^'E 5-7-80 D^rt I

x^' E N'TS D*G **

I l

C2019 w

V I

I 1

SLEEVE v

g Y vh v

bd l

97,;'?

TF ;:<,

. ch

'!:S:h:-

150 LB. DENSITY j

S:::t;q: :y%.:.$k 4.5.:? '

h kj:

1 Pd;i !"..i>:"#F.:N ?!?:".s. :' 'y$..

- i

r;
6:t

.t :i.$.....:

f.U:

p.: *h.!NW:yy}.h.SE.'

b

"$. <N.Nr'Of91S*:?

..,..,i, 1%, [i;;$@Y.$ 9'".::f5..:!5 4 * *4 CONCRETE

c,::yr.:e

,n 3.t, y BARRIER

2. ::

y,.

  • ?..v

..w'<$'.. if;

. ?.
ll.%'?

g%

.?.:V.%.

i=?

...i;...

-... :.::9:

.. n, irigi'):

yc. ::.A 3::%*q\\.5't.3

1f;..-

5i,,.y.v M..w '.

s i

'.4

-l' g N 4.

6 A

ELECTRICAL CABLING g

CONDUIT

.I 8

INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Tvpical Detail Drawing i

TITLE Fire & Radiation Seal Conduit Penetration - 150 Lb. Density Conduit & Sleeve Seal l

e, gg cmo 4

"" TRT omrt 4-16-60 cd'E 5-6-80 0^rt 5-7-30 cart SCAL {

NTS D*G %

C.,3020 e..,

,.n,.--

n..

1 1

6" CONCRETE BARRIER SLEEVE CONTINUOUS CONDUIT

.j p.4 p '. ' 8)

ELECTRICAL CABLING y

i U

1" FIBERFRAX DAID11NG OR EQUAL (BOTH SIDES) 4 Y

/

/

,p,.Q.-

P 4" DEPTH ICMS PRODUCT 60 s

INSULATION CONSULTANT & MANAGEMENT SERVICE

'0" Typical Detail Drawing tiru Fire Seal Conduit Penetration Continuous Conduit ICMS Product 60 - k'all j

MLO

^* JEJ

^*

8' U w c_

C"*0

E

^'I 5-10-R0

^'E 5-10-R0 D

5-10 4n sc^d NTS o*G

  • C0221 wt e

e.n

.co..n..,

em.

T ELECTRICAL CABLING N

n h

CONTINUOUS CONDUIT kJ

., ' \\p=

SLEEVE

~

/

a' Th tss

.Q

'ir..

.A 6" CONCRETE j

eiJ BARRIER d

@fjj h

f n

q;;.

p

'hid 1

~

!ES$i):.."

D,*

Q.A g.9.-

.n - a.

N 4" DEPTH IC1!S PRODUCT 60 4

1" FIBERFRAX DA!CIING (OR EQUAL)

.)

i i

1

)

l 1

l INSULATION CONSULTANT & MANAGEMENT SERVICE j

Typical Detail Drawing Fire Seal mu Conduit Penetration Continuous Conduit IC11S Product 60 - Floor A8*

APP Cwa 0 g'&

BT 7g cart 3-10-30 DAtt 5-10-80 DE 5-10-80 D^tt ows %

scat

.; rg CO222

. ~.

i GLOSSARY - INDEX PENETRATION TYPES C

Conduit E

Electrical G

Gap H

HVAC M

Mechanical S

Structural PRODUCT TYPES 01-19 Silicone Products 20-29 Leaded Products 30-39 Refractory Products 40-49 Coating Products 50-59 60-69 70-79 80-89 90-99 Specialty Products SPECIFIC PRODUCT TYPES SILICONE PRODUCTS 01 Silicone Foam 02 ICMS Product 60 03 Silicone Caulk 04 170 A & B 05 Silicone Sheeting Material 06 Dielectric Gel LEADED PRCDUCTS 20 Leaded Silicone 21 Leaded Dielectric Gel REFRACTORY PRODUCTS 30 Fiberfrax Damming Material

A

/

s I

INDEX E0101 Fire Seal - Electrical Penetration - Multiple Trays - Wall E0102 Fire Seal - Electrical Penetration - Multiple Trays - Floor E0203 Fire Seal - Electrical Penetration - Multiple Trays - ICMS Product 60 - Wall E0204 Fire Seal - Electrical Penetration - Multiple Trays - ICMS Product 60 - Floor E0105 Fire Seal - Electrical Penetration - Cabling Thru Blockout - Wall E0106 Fire Seal - Electrical Penetration - Cabling Thru Blockout - Floor E0207 Fire Seal - Electrical Penetration - 5" Barrier - ICMS Product 60 - Wall E0208 Fire Seal - Electrical Penetration - 5" Barrier - ICMS Product 60 - Floor E0209 Fire Seal - Electrical Penetration - 7" Barrier - ICMS Product 60 - Wall E0210 Fire Seal - Electrical Penetration - 7" Barrier - ICMS Product 60 - Floor E2011 Fire & Radiation Seal - Electrical Penetration - 150 lb. Density - Wall E2012 Fire & Radiation Seal - Electrical Penetration - 150 Lb. Density - Floor E2013 Fire & Radiation Seal - Electrical Penetration - 250 Lb. Density - Wall E2014 Fire & Radiation Seal - Electrical Penetration - 250 Lb. Density - Floor E0ll5 Fire Seal - Electrical Penetration - Barrier Extensions - Wall E0116 Fire Seal - Electrical Penetration - Barrier Extensions - Floor E0ll7 Fire Seal - Electrical Penetration - Typical Seal Repair - Wall E0118 Fire Seal - Electrical Penetration - Typical Seal Repair - Floor E0119 Fire Seal - Electrical Penetration - Piping & Tray Thru Barrier - Wall E0120 Fire Seal - Electrical Penetration - Piping & Tray Thru Barrier - Floor E2021 Fire & Radiation Seal - Electrical Penetration - Piping & Tray Thru Barrier 150 Lb. Density Leaded Silicone - Wall E2022 Fire & Penetration Seal - Electrical Penetration - Piping & Tray Thru Barrier 150 Lb. Density Leaded Silicone - Floor E0223 Fire Seal - Electrical Penetration - Piping & Tray Thru Barrier 10!S Product 60 - Wall E0224 Fire Seal - Electrical Penetration - Piping & Tray Thru Barrier IQ1S Product 60 - Floor

i CONCRETE BARRIER 1" FIBERFRAX DA01ING ELECTRICAL (OR EQUAL)

CABLING

.y

  • p.

ll V

/

./

.:.:.. v?"*.:.{:$5:
  • [>.

..$':.,:=

\\

  • ?. ":l:.:
r..:/ !::*:

h::: *

  • 9

. :.u N.I, i,i},.Y[k.Y.5 ![: f.i$

!.::,. '.1.@.'.':. :...f'.;
*:::.:.'I:':,:,'g'.. * * ",b,*!.'::':..-

il.$0..E.f *. :i'-},*."f,I:':'[(:

Fi 1" FIBERFRAX II:.**:~5!!*55 2.!.,,*-['ji,'.5. 55.

DA!?!ING

~!.!':*.:h. i#:'.S :... 12 t.if.'te, 'ii' (OR EQUAL)

. :... :*..l"f.iV,'.I:t.;* * :1.: :,* :.$*:':::*

5::'., ::.. C.;

^ :{.!:

.t :::.::,::... U"":::.

!.5.'":',( 2'!NI:'*,,., II.h::

4

/

.*t.

9" DEPTH 5:'.I.5'er,:, 'fid'*i. 3'. IM A.

  • !..j /.5 :;'i M,

SILICONE FOAM 5:,':'.;:::...:::./.,*':v,i'.' *,., *.-

-.-)

4 i

\\

'..:.: :: y\\-.:y:.;, ;..:Q:: '

  • Q, j
  • l/ *

/> *,

CABLE TRAY INSULATION CONSULTANT & MANAGEMENT SERVICE

'0" Typical Detail Drawing W

Fire Seal Electrical Penetration Multiple Trays - Wall g 7-lam am av g w q, cs o pg ca'i4-24-80 0^'t 5-6-80 D^tt 5-7-80 joart utt NTS DWG NO E0101

?!

'ae wn narr envises av con am am

,a.

bN CABLr TRAY s

~

4 D

pf -]- (l,

~ R

,s 4~

4, e

x-y-

t

.Aj4

,/

O-

.i:i e.3 v

c

~

,/

V,

^

5...c 1s, 4'.%.h'JhE3:..%.'.

/

,f w

t!)M w

T g

4 e/

. ;...N2.a.::,:.::o

%.P "1.W:E:,bl,qsa s n

~

.O h)ly{#.

r!#'ki$.IkN!fdk{.k:$:.

Ej

.I.'U.:

JNs$

.g-9" DEPTH 58/R{V!$p!$'E%f.

M SILICONE FOAM g*

h.

d ::. : i. ':-. b?. 4:):rMg N

s.Wq@:!$Y:@;:$h?.~..yi,;',h.I: :

2.*,b,.5??!&f..\\e:

.. : 'h:! 'ip:.jj::yI'!4*. E!) *h:,

Q.:p d:!d,..i~::*?::!.:'*:.t...s. Wi?.::ll:. ;:f'vi:l.A'.'s;f;8:": $?i

  • Q
p fi u.~..:.

Y. Q y:.g: :.l.ib.,!...

  • =

.~:i. ?.:s..%.W,:::j.u'. a,%:* ::;.:s.:.ff,rf 4:.y:.,..,,

J.:.., 4Y.:.)......':

s. C0NCRETE .,.... ' k. ;. 5 k :f :.IIi . N. p...,,. N x\\sge, 4;**.s.;*:.$ \\ s' '.w.:..J... ' *EB.'if.I-h. A . e e, - 'Y%gTe.;EI'- . QP. p

s h

s s% N

  • M",

g ge 1" FIBERFRAX 4 b-DASDfING N (OR EQUAL) ELECTRICAL i CABLING W' INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Tvpical Detail Drawing TITLE Fire Seal Electrical Penetration Multiple Trays - Floor av ywt cs o gg 7A T-a" Dl DA'l 4-2 r, n r ~ on Ol r _, n _ a n DA'l scAtt N79 owG % "I e. w narr arvrs cws av em 4= am e.. E0102

CONCRETE BARRIER 1" FIBERFRAX DASD11NG BETWEEN q CABLES (BOTH SIDES) ELECTRICAL .A CABLING . 4' - b* / . P ,.e.; _... -?; A Ml![. d i' ?. .? ? 5 1" FIBERFRAX I Y' DA'D1ING-OR EQUAL (BOTH SIDES) 1 l / -+ p'i) 5" DEPTH {,. lj ICMS PRODUCT 60 ,3 e.. {p. ~ CABLE TRAY INSULATION CONSULTANT & MANAGEMENT SERVICE '08 Typical Detail Drawing TITa Fire Ecal Electrical Penetration Multiple Trays TritS Prodort 60 - Wall ^# 7[J' AN chm 0 gg 8, 7 g g o^" 4-26-80 0^'E 4-27-80 ^'t 4-30-80 " w.a E0203 yf m n.n misin $ e, em i

o ELECTRICAL g CABLING c; r sYq rY ar &,/ m w wa _ ~ 9;-1-/ / b. M

  • /

.M "Au / c.1 L 5" DEPTH / jbM O f ICMS PRODUCT 60 af gp#p,je. y.'- ~ 4 q'Nv, jgt .d \\ :~s " F WM g CONCRETE . q,N BARRIER N A ss N - 4 ,b .p s s g/ 's .~ s s% b c / "s" Q 'd 1" FIBERFRAX / DAMMING CABLE TRAY 3 (OR EQUAL) N i l INSULATION CONSULTANT & MANAGEMENT SERVICE ) FOR Typical Detail Drawing TITLE Fire Seal Electrical Penetration Multiple Trays TrMS Produc t 60 - Floor j a" er 7gt c>.ao fyg 7fT~ DATE 4-2(3-80 Dd'E4-27-80 D^'t 4-30-80 D^rt x^d NTS D"G

  • E0204 T

eae mn Da ff ofV'tm$ gy cwn app app p ae a

l CONCRETE BARRIER 1" FIBERFRAX DAFDlING-OR EQUAL i (BOTH SIDES) f .o 4 'y~ 3 ELECTRICAL ,y I ? f CA3 LING 'O.... - { . '.. d...,......, fM 9" DEPTH

W SILICONE FOAM I
6....

'y-T: [if

f :

~ 1 T p.~: i'l-3 .. / i: f / s 4 it .r

9F.~

gg:.:..- P'. INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing W Fire Seal Electrical Penetration Cabling Thru Blockout - Wall 8' TLo c. ("*o ,MLg ^~ y g O*'E 4-24-80 cart 5-6-80 DA't 5-7-80

  1. fE SCA E0105

,,'t NT4 me P4e w Da't stygnogg g, gg,

r-9" DEPTH p ELECTRICAL SILICONE FOAM CABLING \\ ..J h5 h- ,srr....Ut,. i-vg'g,g 70 - .y' LCL , $.h'.Wf:i N* i-p.

z. < g u.

gy?? .p* ~. I" FIBERFRAX '$< v.2f y'. . p. "EISb i'I br$5.h. 'if.e.E. 5 CONCRETE DAlD!INO 4 g (OR EQUAL) 7 t7 2$ ~ T$' fM ~ BARRIER

f48 'kh.p. f p

n - b. u.s i a p g. INSULATION CONSULTANT & MANAGEMENT SERVICE Typical Detail Drawing itTLE Fire Seal Electrical Penetration Cabling Thru Blockout - Floor B' 3*w C. C#0 AM ^" JRT ^" cart 4 24-80 DE 5-6-80 (* ' t 5-7-80 D^tE scatt NTS 0*G w "I ea. e narr erva.n.a sv cm an >= E0106 Q

5" CONCRETE BARRIER TAPCON FASTENER.e (OR EQUAL) ?; N 1" FIBERFPR 7, y A - (BOTH SIDES) AMMING-OR EQlIAL k O __- s ,- g ___ :5 g;} b' hh ~ b? h; ?> N' ELECTRICAL I CABLING i' !?y 3 ,n a y 3 gs:- / b.., #, b it 4 'P ' >- 5" DEPTH / b . *. ICMS PRODUCT 60 1 1 INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing titu Fire Seal Electrical Penetration-5" Barrier IC!!S Product 60 - Wall er zwe cno ws anygf an 081t 4-26-80 cATE 4-2 7-80 D^rE 4-3 0- 80 Gatt watt N~ Tg owG w E0207 "l ...jn n.rr evim , av r. .= l.

5" DEP111 ICMS PRODUCT 60 --- ELECTRICAL g O CABLING C1 / } .J.$i ' i.g h > '.y" h. -.WI'1.$. n 5N H .,x q~ ,p 2.- kh w..d!

7.. !$F h.

gj /* 5" CONCRETE s., ( BARRIER / + b. ~~ ,q' .\\f 's.p, s .p., F- ~ Agpl. f.' 9 '. ' ' ~q p .y. 1" FIBERFRAX DAD 11NG (OR EQUAL) 1 INSULATION CONSULTANT & MANAGEMENT SERVICE rom Typical Detail Drawing tiitt Fire Seal Electrical Penetration 5" Barrier TDtS Product 60 - Floor CHao g, a,o g(( AP# BY ggg o^" t.- 2 5-80

  1. 't 5-6-80 0^'E 5-7-80 c^'E scatt N' rs D*G W E0208

= ,. n uv,w, n.,

7" CONCRETE BARRIER S 1" FIBERFRAX .N, g DASD11NG-OR EQUAL 2 7,". p (BOTH SIDES) g .r s 3 E h i ELECTRICAL fl $h CABLING w. ? 3 3 3 02i 5" DEPTH (y ICMS PRODUCT 60 n. fh ' * ,F INSULATION CONSULTANT & MANAGEMENT SERVICE 'O' Typical Detail Drawing mu rtre seal Electrical Penetration 7" Barrier ICMS Product 60 - h'all es 3g cno g.s "" TE T DATE 4 2 6 _ g g DATE 4_2 7.g g DATE 4_39.gg DATE I N NTc D*G % l

    • /

eae m ,natt osv.Sms av cw; am; a. g E0209 I-I

t 5" DEPTH ELECTRICAL k ICMS PRODUCT 60 C CABLING f j / r.e.t d I. ~.. ? j(4 jf 9:f by svi x k.., v... " a $$ Ey S Q' :, Qfg;klN .,..di.t K .;a __ gitiq='..n mm MO ^ I.' N . f(th!((g.-k?> g

gg Lgqp '

7" CONCRETE g-p'i g, yl:f 4' BARRIER F b . g ' ~q. ' g. e.- m ;q.,. .g p- , A-1" FIBERFRAX D' ~ dam!ING (OR EQUAL) INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing mtt Fire Seal l Electrical Penetration ( 7" Barrier TCMS Product 60 - Finor av APP 7g c-o e .*7pf 0 0E4-27-80 0E 4-30-8n 0^'E ..' 4-2 6-80 scatt me owc m E0210 ? n n.rr ervi..n s n, r

ELECTRICAL CABLING ~b 'N. 3. ..w..s' w h 5$1y...

f. h El y.

. pM ;,4 g.g./ 4 ..:.d TYY fjh!hh. '7 A bh /' / adk.was4. ${N l?*N$$ul$p L ?... ;$}!} gd$$ LwO ^ @*$. 150 LB. DENStry ^" s ..e .g' LEADED SILICONE Sj Viv - t v yn f *. '" kh .M 9 Af.. p gg@7. ' CONCRETE E, BARRIER ',7 - .p. .p l i t =-- l INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing title Fire & Radiation Seal Electrical Penetration 150 Lb. Density - Wall 8' Tus t. C" AJ ^" JET ^" DATE 5-7-80 Ud'E Datt 4_2 5_ Ao o.rt 5-6-80 D LE N'TS C'"G N E2011 . lcm. m n.., m,wws

CABLE TRAY ELECTRICAL Aw'<-c-CABLING c,c i-8 nw /. fg?, .A p. w py ,p P . (;;M glinEh2T$g;iffi'?V,-ian -n w f.tdE M 5.M s '. 6. gg;.jN p. - ^ s i thgfBBW. se a.* 9...P d g.Q;:)gl.y,'js mw- " i ? .dr' }$}($9fs .,I. -4E 3. g. .0M.p CONCRETE (kHQ,+:1. i l

. {n#..

BARRIER i 2 .h 'T.t.&p.,yr. ppd lihyy; V. p. .:1.fb;jf "p~ g >%* c>. k A. n u a 4 150 LB. DENSITY d~ g>$.., LEADED SILICONE .p s ./ p' Nm INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing TITLE Fire & Radiation Seal Electrical Penetration 150 Lb. Density - Floor e,

yg ts o g a n y g 3-Aw ca't 4-2 5-8 0

E

e. A n d'ES-7 An

^'E scatt y^ rg owc m ^ E2012 eae e natt osvoorwA ev re.s app a,....

ELECTRICAL CABLING p' h CABLE TRAY .. 'A. 9 ,/ NSs.

r.. '

b W ..~ .p .a .a#H n $$fik p ?b $j '. ":9:ig(h)Y;,d.fhjp. ~ i-l'/,$, * ' ";- 1 "' 5kk;jf ..- fh 250 LB. DENSITY '-a j 'l LEADED SILICONE b .-r :.. ). bNjQ. - l: * ? I 5 N .x if$.D.. ye"

  • y

' }~ A 'Q, CONCRETE

  • P BARRIER P'

I l INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing N Fire & Radiation Seal Electrical Fenetration 250 Lb. Density - Wall av ywe c ao fag,

    • 7 Et care 4_25-80 Da'E 5-6-80 D^'E 5-7-80 cart N

NTS D*G W E2013 "I eae m

nart, emww<

sv c a.

4 CABLE TRAY er-o-: ELECTRICAL W CABLING f e- $ W ue? J $. em4:i%-..-M)2.id.f S,- ..* AT >Me; fj.2 ;p ':' k .ihib' hfI :p 5 li$$.fh.E E.s. ~N, a..'..(W . !:Y <, 250 LB. DENSITY \\5 Q.iWi~'I'-s ' 1$ $pJ' v ~ LEADED SILICONE

s. y,),kh!h-

!!hI.h$b "'h y6'?- l h (60% FILL DEPTH) !caidvs.i.y:M:iMii a. u9;.>, e-

w;gEh:5

'kIi.reffb. (YkIkkfhhh ii.?O::i '.* g f g' h

.ycunn 7-MM..S.. h.. 5.-

w .; p. s k m G %9 yg / CONCRETE .7-g BARRIER N p- ./ lusf f INSULATION CONSULTANT & MANAGEMENT SERVICE N# Typical Detail Drawing I" Fite & R,diation Seal Electrical Penetration 250 lb. Density - Floor AP yyQ CHED gg A.Py g 8v oatt4_25 80 cart 5-6-80 0E 5-7-80 0^'t scau y rs D*G

  • E2014 uf n

n.tr erv wws nr c.

e ELECTRICAL CABLING "J" RUNNER i EXTENSIONS .i CABLE TRM d. <! 1., ?

  • A. GI.+

dE235$ ]V[T.2).m .x '~. YSE .i - ' c. $jI.k,::;;.h d? ff y au N }' [.h OR EQUAL (BOTH SIDES) 1" FIBERFRAX DA.T1ING (f,hhf l0,f, N, j 5: .g y,.

  • . ift /

fg,.. ...g5 N 'h,: hf.. -,::.:... 'k' 9" DEPTH Y,*b SILICONE FOAM l0.4 'I:k,. d .c'i f;.. " ' ,4 , p / CONCRETE ,s BARRIER INSULATION CONSULTANT & MANAGEMENT SERVICE 'O' Typical Detail Drawing TITLE Fire 3eal Electrical Penetration Barrier Extensions - L'all aw e<7wt c~o rgs .w yg c^'t 4-26-60 Datt 5-6-60 DE 5-7 -80 DATE Wa NTS DaG m E0115 wl n e.., uv,s.n s e.

CABLE TRAY 9" DEPTH SILICONE FOAM _.p! .Ih k ELECTRICAL .. k }W.y,N; ' p.$'., rf::co i,zr n :- CABLING .gWM~ J ~ %h-

$ yf. zr-2 ':-

g.:r.[.w~,.f$, gy,4:,. S' n %$4':,.jk. :.. [ 4-- f-! Tt &P 2*ia.G..:.4. / ~k-gh.c.i.f;.%,f_ p@i-n::;s.v.p%p::.y,: 4. .:b. Y.... -a n, n;:m e:n $k pq 1..

. :d is; adem;:.3=qe pe, w-mnwei.v i-

"J" RUNNER .? Rll0.? %'!ST6.$:$ EXTENSIONS %Bh,?Mi5.s:.5MBN i a T-e.v:s.:.c.% .y e. p M.E.q$s:.:. $'..:9.~:g.nz. 'kt: x s;:. $i!# M.y >.p.. h ~r2;?Hi%@QQ?!id.t:% N MSE sj@:.Sii'42b *.7 ..p- "4ii :::: N s G.g.y'g.m ,'. g p' Pis il 4 N, N Q, CONCRETE 1" FIBERFRAX ,h BARRIER DA?0!ING (OR EQUAL) / j e i l 1 1 lNSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing TITLE Fire Seal Electrical Penetration l Barrier Extensions - Floor 8, Ty( C*.u D f,ay A" J E 'T' aart e-2o-ot cart 2-o-co oart 2-i-co cart 1 K AL L N' T(i D"G NO E0ll6 n n.n .,v.< m. n..

CONCRETE BARRIER sm q. g: ELECTRICAL CABLE k ~-i.0h- , _ :.0: ': ?i *E. } /@:$n.2;$$l ii.R;i ... ) 3 / .G i j l:p ?...nj .'i ^ k'. .I g.ng..... I:y .Q :*: . y.-:-l N

. @ v:is,-
...::f.i?]"\\!]:fE

/). sij r*y I l ..? - f ',(,L'iI ".'

  • 9" DEPTH iF -

SILICONE FOAM )7,.*y 4 NEWLY INSiALLED CABLE 3" DEEP 1" FIBERFRAX DMO!ING REPAIRED AREA OR EQUAL (BOTH SIDES) INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Tvpical Detail Drawing I'I" Fire Seal Electrical Penetration Typical Sesi Repair - Wall n" aw c~o y;, y g g-er 3 w c, oa " 4-27-80 D* 't I. - 2 8-8 0 DE 4-30-Rn Dart scatt ymq onc m E0117 T n n.,, .rvic,%< e, c-

r NEWLY INSTALLED ELECTRICAL CABLE

  1. CABLING d

N, ~ es e.m s;, 9- ..a is.i ..3 s%i$ _ 'f. 1 w.'. s. fJ. l{lf.igy:.2.3E.. ;'if 6$) 3" DEEP D:!A Ai 4 P 9" DEPTH -. "i "...$$,'.f..>jE.V,jfl ../5.W.'i. REPAIRED AREA C 7 .p:.::$ '? g Si. .[.

  • P

.i 4,% h. ig....,r.~.:s$..w:.,.'x.. wr. e:q:i'7 ' d..p; SILICONE FOAM 4. l. . w e .w . m...m..:.,. 9.i]-l.f:lel.:li;.%<: t?iG(.E :.;... 5 O' Q.N.B.'@ hiss 78.P M i34.5 Y ... : di itspf >* t

$4E 3

is$w 9.y . Nf W.':''.h I t :ik.:t.Q

  • ?Rls4.*'.'h'.y:(: ;,. h:~ $$2.I hE.y.d3

.[

  • A Cj:.: ~:*..

r. Y':i@e:g,.s.: F,#:.';Cr@*.j*:*4::: ;;s gc;g Q V .y.,....#. a. U -~:K. '/S. >. s e i p.,[ "rIS.. gir.:n. h, : .5 "S'i v.ei;.".g:r.*:::2 1" FIBERFRAX 'Ekj.';; P. CONCRETE DA:NING "',g O BARRIER (OR EQUAL) A ,-. h, 1 l l i l i i 1 l lN5ULATION CONSULTANT & MANAGEMENT SERVICE l '0" Typical Detail Drawing Fire Seal Electrical Penetration Typical Seal Repair - Floor 8v y y Q, CM.D pgG am g y 4" cart 4--2 B-80 C^'E

i-fi-R o D^'E 5-7 an oa'E M.Att g7q OwG NO u,'

o nan en.s m s n. c a= .= E0118

't CONCRETE BARRIER / .b ELECTRICAL CABLING . 4., / + t>. ~ a f CABLE TRAY .p.f.j,.h ,.e ily;.0: :Qj, ' [ ....1 h 0,. 'l N !.}!

~

e MECHANICAL ( 'y '" PIPING v.,.- ,..dj ..;jjh 1" FIBERFRAX ,..gp , 4.h. DA>011NG-OR EQUAL gi;;is.5 p (BOTH SIDES) 9" DEPTH SILICONE FOAM INSULATION CONSULTANT & MANAGEMENT SERVICE Typical Detail Drawing TITLE Fire Seal Electrical Penetration Piping & Tray Thru Barrier W11 gg amyg A= ev ywq c> mo oa rt 5-10-80 0^'t 5-10-80 0^'t 5-10-80 0^tt scaa we owo w l m narr en=mc . av rw-am

== .a. E0119 l

MECHANICAL PIPING CABLE TRAY / p$k$k ..uf.5 r.i.EN'g:... ~ f , f.... - 82 gjl'p.. A LECTRICAL if $ %.92 _MM ^ 3 v.. em ww w A d; !.. ~ pr Aw k. h,p$;.g.$.yf pi.h$'I @M MM p .s w g .1, pyh" '. p;' IN$ .!h kh %"f@k i - % g:~- y.'.,*.,*t d*' ',r '*.i g "$. p * ~ BARRIER CONCRETE y

  • .b h'

r.Mjf A... I.cirst:)fggj.?hy .>*l*.... Afgby @ O ig s,'s,,9)Q' 's .*.b .k..* . b- >Q". 1" FIBERFRAX N g DAMMING (OR EQUAL) .g, *%. N ) q I ~ 9" DEPTH y SILICONE FOAM INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing TITLE Fire Seal Electrical Penetration Piping & Tray Thru Barrier Floor es yg c"=c g n"y>y - cart 5-9-80 M's5-10-80 0E 5-10-8n 0^'t scatt r' q owc w ~ E0120 w n n.n .n,,s.n s n, n. l

ELECTRICAL CABLING iks Ag CABLE TRAY p.,'. [: pp ' [ ~ r - 3.), * 'M,l. -MECHANICAL 2 M e,, I',,'".. 4 7 PIPING !'f. f!hI ' f' i '%..,' A,.443.@' f 04: ,,g, c:'( ^ ..c.ni,.:.:,N/d g,:y.:? jpf,[h ', ' ' . M.

  • LEADED SILICONE k-4'

...g .p 4 CONCRETE BARRIER 1 l ) i i 910 INSULATION CONSULTANT & MANAGEMENT SERVICE Foa Typical Detail Drawing taitt Fire & Radiation Seal Electrical Penetration Piping & Tray Thru Barrier 190 t h. Onneir* in,ded 911icone 'a'all e, qg cwao }Q aq A" ^" cart S-12-RO D^ rt q_yg_an cart Dait c _ 3.,_on sc^d NTS 0*G % E2021 y e n.n mic n. n..

v i !!ECHANICAL l PIPING l 150 LB. DENSITY LEADED SILICONE di- ~ . kN ' CABLE TRAY t C.' h.,.,^ * '.. +. Y y .bSN (Ih;..:., ?.:a+cw p.g h.)4 ' M N ' F ELECTRICAL , ngl 9.f.f' Bi ( g,,%g-CABLING M_ f @g dj y q s4. p 33..k.hg,.np (~* g,, l , g-k..i. :vi{ugTv.cp g CONCRETE 2 A BARRIER - ',yn n... . > - ? i r a,5.. 2 s 4 O. <l e 15 ~.; 9-1 4' W:.w.,N..' Nia S Y.

m$ M

/. k.. l M k ~ 1 J 'x y-I Y-l> i l I ) INSULATION CONSULTANT & MANAGEMENT SERV 'OR Typical Detail Drawing ma rire c. venetration seal Electrical Penetration Piping & Tray Thru Barrier 130 lb. Density Leaded Silicone - Floot 4 gd AN yg 7'- AN l chm 0 ev7 9 Q c'TE 5-12-600^rt 5-12-80 0E 5-12-80 0^tt 'i.L E NTc DwG NO ~ E2022 =? n nn m sin $ m r.w.

6 ELECTRICAL CABLING .A, _ CABLE TRAY / W * 'Q. f MECHANICAL

  • s\\

PIPING g.:/ E g / 1" FIBERFRAX O DAMMING-?R EQUAL (BOTH SIDES) g g /< i ,a 5" DEPTH g ICMS PRODUCT 60 p-s- 9.. --+ 6" CONCRETE BARRIER

p.. v.

TAPCON FASTENERS (OR EQUAL) INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing Tira Fire Seal Electrical Penetration Piping & Tray Thru Barrier ICMS Product 60 - h'all Svgg{ CHR0 p Q aPD gg APP oarE 5-12-80 D*'E 5-12-80 auf 3-12-80 MfE scatt NTS N* E0223 "? .a. n non wvieuw< n a ..e...

MECHANICAL 5" DEPTH PIPING IC11S PRODUCT 60 Y /' CABLE TRAY _ J., N [. g h g{, [ f .t + -ELECTRICAL y ygA y CABLING ,'y ' gE ~ h?@l ' j, id& fi w ,g.'.l N4 . 8. 5 ff ) 6', 'T' 6" CONCRETE g. p. BARRIER 3j Ny+ ( !/.. f ,s \\ 1" FIBERFRAX DA5011SG 4 w (OR EQUAL) INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing Fire Seal Tira Electrical Penetration Piping & Tray Thru Barrier IC21S Product 60 - Flonr a,* av ygp c-mo g@ ae. yg ^'E Datt 5-12-80 OAYE 5-12-A0 D5-1' an o*G % so.t 'er q E0224 u,' n nor wv.<in s av ew 4

..e L s. (, ? 5 GLOSSARY - INDEX X V PENETRATION TYPES C Conduit E Electrical G Gap H HVAC M Mechanical S Structural PRODUCT TYPES 01-19 Silicone Products 20-29 Leaded Products 30-39 Refractory Products 40-49 Coating Products 50-59 60-69 70-79 80-89 90-99 Specialty Products SPECIFIC PRODUCT TYPES SILICONE PRODUCTS 01 Silicone Foam 02 ICMS Product 60 03 Silicone Caulk 04 170 A 6 B 05 Silicone Sheeting Material 06 Dielectric Gel LEADED PRODUCTS 20 Leaded Silicone 21 Leaded Dielectric Gel REFRACTORY PRODUCTS 30 Fiberfrax Damming Material

i icx. D~ s INDEX H0101 Fire Seal - HVAC Penetration - Wall H0102 Fire Seal - HVAC Penetration - Floor H0203 Fire Seal - HVAC Penetration - ICMS Product 60 - Wall H0204 Fire Seal - HVAC Penetration - ICMS Product 60 - Floor H0305 Fire Seal - HVAC Penetration - Silicone / Adhesive - Wall H0306 Fire Seal - HVAC Penetration - Silicone / Adhesive - Floor H0107 Fire Seal - HVAC Penetration - Barrier Extension - Wall H0108 Fire Seal - HVAC Penetration - Barrier Extension - Floor 1 H0209 Fire Seal - HVAC Penetration - ICMS Product 60 - Wall H0210 Fire Seal - HVAC Penetration - ICMS Product 60 - Floor 1

T .p { ,. $7 p./ ' s HVAC DUCT 3* Aw.5',.t . :.u j f ~- \\ s s h? 'M,i,!,i.yI524i95:.IydliM #. "...:: i;illM ll..k:.pr!: l/- hi$'h.h,{ibb'M: ? a:.n%. E!:n jyfil:g..q;gg:..lih,{' Ov. x.jf1: I I i 1" FIBERFRAX 6[Ng:ff.J.if. gc#+::-$hd" i'. A DAFDIING-OR EQUAL i l$ "" 9.5A.'th.'$pipd.i$ (BOTH SIDES) L.. 1: '*QGlny:$ylN l b f !b... we:.i:w;9.y X

..: gi.

i,.'::.h.Ib .N. ' .O 7" DEPTH J 3.g,i,'@!.Q.? .g-SILICONE FOAM '::g g:::a. P., ,.p) p p .p CONCRETE 4 4 BARRIER 4 4 s= INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawihg N Fire Seal HVAC Penetration Wall ev xx c~o gs nn y an oa'E 4-17-80 cart 5-6-80 DE 5-7-80 0^tt ut NTS D*G w H0101 7

  • ae e

natt etwo s e, c 4.-

v J HVAC DUCT ( I 4

4..:.h);
x g..

"ky,Q:n I "O,., c:e/,$:: '4 '. f,(d:. Ulic.h+ Di 7" DEPTH

s 4

.. g:.. r.to,,s.j. i?:. m %h...h'.'. d.: ';*.v:. ?$;s'. k'.lr4 :., N.lg $S : -..

.J k..sig***ig.W '
?

SILICONE FOAM Y, i? d V

.:4 ;;; :.;* ::.. h+lf l

1 $ Oiy,.f. i;.. H Q)w.}'.*:ji "p?ijf@.@i%jt .e,. it - {.y @ 9;'/: h,:5 V. fl M}} T D. Ik O '...k'b 5:5 :, h ' ~.sl.} CONCRETE ' 7/f55%.hb;S m. "$* jfp#l#;{%,$(!!:,j@f26:' 3h BARRIER Z C- ' - 4! ff.pl.,5,@n.ii: ,2 N s NU

  • 4 -

n u. .s a v. 4 ...,; : ;..~.,,;.,. .Gt 4

:';<?l;.).:}.g.

,',4 A 1" FIBERFRAX DA3211NG p'. (CR EQUAL) 9-P. P INSULATION CONSULTANT & MANAGEMENT SERVICE 'O' Typical Detail Drawing TITLE Fire Seal HVAC Penetration Floor ev yy( cwao p,afg Am 7 g am OAft 4-17-6(i cart 5-6-du 0'TE 5-7-6U. oart scAtt SIS DwG No H0102 n on,. ~,. e...,

O l 1 i .O A'. O-HVAC DUCT l g-.a. ../ b .s.... 1:c w / >4[: ..h j

jjl 1" FIBERFRAX

?,t. .. r, /, DAMMING-OR EQUAL ~_ .d \\ (BOTH SIDES) if \\ l h / ':) J 4" DEPTH j s F5'* ICMS PRODUCT 60 .1 G -:w. ex .A*p.. E!l. / (@%;'p.p...* ( l CONCRETE 4 .,,. b. .~ BARRIER -y. 4 N l INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Draiing TITLE i Fire Seal ) i l HVAC Penetration ICMS Product 60 'Jall I ev gg t cw=o ga am 7 g am DE 4-17-80 C^tt 5-6-80 D=TE 5-7-80 0*ft "E NTS D*G W H0203 e ~n .<v.. m. c,

0 t HVAC DUCT r 1 4. \\ 1" FIBERTRM ' *'~ " '9"M

  • 4 f,.a

?$r'NsiDEgy p ,, h. I

  • J.,

G7 .g.. o \\ "5ki?f. ',y,.f,j. ;cqw9r-h k 1 6

  • /

f.. CONCRErg RIER p I. 4 f..O. g C> ,,, DEPTH IC!S PRODUCT 60 p a. 2 i INSULATION CONSULTANT & MANAGEMENT SERVICE Foa Typical Detail Drawing Fire Seal HVAC Penetration ICMS Product 60 - Floor e, gw e cno g; s" grgy-a" CA TE WE WE OATE 4_j7_gn z _ g, _ g n y_, scatt NTS D"G

  • H0204

= c..

l" FIBERFRAX DA> MING-OR EQML (BOTH SIDES) .A N L. ..O I O 4 m HVAC DUCT ? I l b d .i$$ CONCRETE \\ c'VM BARRIER 4 N N ty> ; ~ [>* .N 2" DEPTH FIRE N RETARDANT CAULK g 4 s INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing TITLE Fire Seal HVAC Penetration Silicone / Adhesive - Wall ev ru3t co wa w 747- = D" 4 4-18-8C D*'E 5-6-80 0E 5-7-80 Da'E l i W NTS H0305 e.. m e... .rv== av c--

IIVAC DUCT t t N 2" DEPTil. SILICONS CAULK O ' .o sy. g)$g% [ NCRETE BARRIER A g, 6 1" FIBERFRAX . [* d DAMMING (OR EQUAL) I .b 4-P' 1 I l l I l l 4 1 t INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing mLE Fire Seal f HVAC Penetration Silicone / Adhesive - Floor BvgyQ CHmD 74 4, AN g AM DATE 4-17-6(i DATE 5-6-80 DATE 5-7-80 Da'E SCALE NTg Dw; % j, H0306 vAe no,oATE

  • (vistONS Sv cus! Am A.

HVAC DUCT t, .p. q. /

' g

. :i .g l

f. -

/ , s. L 1" FIBERFRAX E' i ' b j} DA>Di1NG-g f h. G if OR EQUAL l-(BOTH SIDES) 2 '. ir" s i E*Nh5 )

f:hfl 9" DEPTH
pif, 4
  • h g

SILICONE FOAM a p i.t ' 'V. p, / / . t.. 6" CONCRETE BARRIER "J" RUNNER EXTENSIONS i INSULATION CONSUL 7 f.NT & MANAGEMENT SERVICE roR Typical Detail Drawing N Fire Seal HVAC Penetration Barrier Extensicn - b'all an av ywe c-o gg am 7g ca'i 4_1g_an o^'E

_4,qq DATE g_7 qq part

%A* L N' TC DwG NO H0107 m.,,,,... e.

? A HVAC DUCT / 1 \\ N / I 9" DEPTil _1 .w.4,h.. SILICONE FOAM 44. E'h bf [N'kN;g#61 7 ff* [ '7{'NT. dli-iU*l3YO;:. hef gj<Y G - !s [ [ 'h'.5l$f@d.I5[$5['$$hh'i$,f,,,h.:h@h* fj?;. "J" RUNNER 'p 'h. ""S ' "S + - Q:.I?;^ '.N'&"4 - QP *

  • i'$g NA. ih'?$

L* ?"-I %. {YU;'i(;;, p:.' w .. :, y ' d$;y% $c..-:<7. ~ $ q'; m --t.' % g[' duI.S($$lj, ".2.7k;.p s 'j 21,./ w A g ,v::r.t 7.. Q.'. 6" CONCRETE BARRIER Tiger - Sg m 94.qo . Ry.4 y 4 4., Yh a 1" FIBERFRAX DASD11NG (OR EQUAL) l [ l INSULATION CONSULTANT & MANAGEMENT SERVICE roe Typical Detail Drawinc Fire Seal HVAC Penetration Barrier Extens'ons - Floor 8v 7yQ CaaD pg ase gg an D^TE o*'t 4_1s_gr R't s_6_po Daft ;_v_an scaa yre owG aso H0108 ~.

i i T l 1 HVAC DUCT i [ 1" FIEERFPAX l ( DA*2fING OR p EQUAL (BOTH , pp SIDES) \\L A P N.'ih s,qn\\ 4 h, 3 .$i 'rt. [

9. i.,,,. ',!.f.:

I:h.{$$.'f#E I \\pi!c;:3 !!::/#.!,j.5-Y $ ;K..; 4" DEPTH f

k. s.~ *'hh, ICMS PRODUCT 60 J

1:t %y. i.%

.ix).-{60'. /

l 1

.~.. -

,O** O

  • h 6" CONCRETE BARRIER l

i v. 4 + .p l r I l l IN5'JtATION CONSULTANT & MANAGEMENT SERVICE 'O' Typical Detail Drawing Fire Seal HVAC Penetration ICMS Product 60 - k'all es 3wg cm.o np

  • " g cart 41880 cart 5-6-80 D' it 5-7-80 D*'t wat t y7s uwc w H0209 r...

~ ~.. ~.

'l HVAC DUCT \\ 4" DEPTH ICMS PRODUCT 60 D. . $ f ;h....41;if bd;?.. l 'd,',', ".,, gjj$$#, ,q p 'y n-6" C0!; CRETE 4 6,a*'. BARRIER u .a - p. "4 ,4.g. ,,s', O-1" FIBERFRAX DAM!I!;G (OR EQUAL) ~ INSULATION CONSULTANT & MANAGEMENT SERVICE Foa Typical Detail Drawing mLE Fire Seal HVAC Penetration ICMS Product 60 - Floor e, ywe c~.0 .,og, se g ^" ca'E 4_19_An o^tt s _ r,_8 0 o^rt q_7_gg cart K^il NTq DwG 8eo Hon o m., ~ ~.

, $h N, 4' GLOSSARY - INDEX PENETRATION TYPES C Conduit E Electrical C Cap H llVAC M Mechanical S Structural PRODUCT TYPES 01-19 Silicone Products 20-29 Leaded Products 30-39 Refractory Products 40-49 Coating Products 50-59 60-69 70-79 80-89 90-99 Specialty Products SPECIFIC PRODUCT TYPES SILICONE PRODUCTS 01 Silicone Foam 02 ICMS Product 60 03 Silicone Caulk 04 170 A & B 05 Silicone Sheeting Material 06 Dielectric Gel LEADED PRODUCTS 20 Leaded Silicone 21 Leaded Dielectric Gel REFRACTORY PRODUCTS 30 Fiberfrax Damming lbterial .s

/d \\ h. ,,,A 4 .s ? T%' INDEX M0101 fireSeal-MechanicalPenetration-Wall M0102 Fire Seal - Mechanical Penetration - Floor M0103 Fire Seal - Mech nical Penetration - Insulated Piping - Wall M0104 Fire Seal - Mechanical Penetration - Insulated Piping - Floor M0105 Fire Seal - Mechanical Penetration - Multiple Piping - Wall M0106 Fire Seal - Mechanical Penetration - Multiple Piping - Floor M0107 Fire Seal - Mechanical Penetration - Barrier Extensions - Wall M0108 Fire Seal - Mechanical Penetration - Barrier Extensions - Floor M0209 Fire Seal - Mechanical Penetration - ICMS Proouct 60 - Wall M0210 Fire Seal - Mechanical Penetration - ICMS Product 60 - Floor M0211 Fire Seal - Mechanical Penetration - Insulated Piping - ICMS Product 60 - Wall M0212 Fire Seal - Mechanical Penetration - !nsulated Piping - ICMS Product 60 - Floor M0213 Fire Seal - Mechanical Penetratien - 6" Barrier - ICMS Product 60 - Wall M0214 Fire Seal - Mechanical Penetration - 6" Barrier - ICMS Product 60 - Floor M0215 Fire Seal - Mechanical Penetration - 4" Barrier - ICMS Product 60 - Wall M0216 Fire Seal - Mechanical Penetration - 4" Barrier - ICMS Product 60 - Floor M2017 Fire & Radiation Seal - Mechanical Piping - 150 Lb. Deasity - Wall M2018 Fire & Radiation Seal - Mechanical Penetration - 150 lb. Density - Floor M2019 Fire & Radiation Seal - Mechanical Penetration - 150 Lb. Density w/Marinite - Wall M2020 Fire & Radiation Seal - Mechanical Penetration - 150 lb. Density w/Marinite - Floor M2021 Fire & Radiation Seal - Mechanical Penetration - 250 Lb. Density - Wall M2022 Fire & Radiation Seal - Mechanical Penetration - 250 Lb. Density - Floor M0323 Fire Seal - Mechanical Penetration - Silicone / Adhesive - Wall M0324 Fire Seal - Mechanical Penetration - Silicone / Adhesive - Floor 1

<9 1Gk Y i T M2125 ' Fire & Radiation Seal - Mechanical Penetration - 150 lb. Density Dielectric Cel - Wall M2126 Fire & Radiation Seal - Mec'hanical Penetration - 150 lb. Density Dielectric Gel - Floor M3027 Fire Seal - Mechanical Penetration - Booted & Refractory Material - Wall M3028 Fire Seal - Mechanical Penetration - Booted & Refractory Material - Floor M0529 Smoke & Air Seal - Mechanical Penetration - Booted One Side - Wall M0530 Smoke & Air Seal - Mechanical Penetration - Booted One Side - Floor M0631 Fire Seal - Mechanical Penetration - Booted-Dielectric Gel - Wall M0632 Fire Seal - Mechanical Penetration - Booted-rielectric Gel - Floor M0633 Fire Seal - Mechanical Penettation - Dielectric Gel - Wall M0634 Fire Seal - Mechanical Penetration - Dielectric Cel - Floor M3035 Fire Seal - Mechanical Penetration - Insulated Piping - Booting and Ref t:ctory Riterial - Wall M3036 Fire Seal - Mechanical Penetration - Insulated Piping - Booting and Refractory Material - Floor M0537 Smoke and Air Seal - Mechanical Penetration - Insulated Piping - Booted One Side - Wall M0538 Smoke and Air Seal - Mechanical Penetration - Booted One Side - Floor M0139 Fire Seal - Mecnanical Penetration - Reflective Insulation - Wall M0140 Fire Seal - Mechanical Penetration - Reflective Insulation - Floor M0141 Fire Seal - Mechanical Penetration - Blank Sleeve - Wall M0142 Fire Seal - Mechanical Penetration - Blank Sleeve - Floor M2043 Fire & Radiation Seal - Mechanical Penetration - Blank Sleeve - Floor M2044 Fire & Radiation Seal - Mechanical Penetration - Blank Sleeve - Wall M2005 See Brayton Point File

V i i l CONCRETE BARRIER .4 .,A d

  • 4

_ PIPE SLEEVE p A 31ECHANICAL PIPING . d 'g;$$?/ A" ' {'f:$y;gi-1" F13ERFRAX DA>EIING } -OR Eyl'AL (BOTH SIDES) m...i.- ., $.$ / [ .;,,th * # /:.gIl.lk[E,.... ~ 7" DEPTH Q SILICONE FOA>! /. '.h. 4 _y y.. 's.' ' 9 IN!ULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing mLE Fire Seal

lechanical Penetration Wall 9.gg{

CHa0 py y aN g 4M cart e - 1,- 0 0 cart

-o-ot cart 3-7-go cart satt N' T S D*G W
  • f0101 w

s., c..

1 MECHANICAL PIPING a 7" DEPTH y SILICONE FOAM + E O f

n

?*h*cj1):M.. G h ',':i h $b-i. PIPE SLEEVE .d.I.) .'? 6-i.@... 3 =. :. - 6!,M. g:-j .b b.

ii
.N?k
'.y$

??

  • V P,

.'T 9.. I,iid '. '. ~. g>*'.,g djp .D y5. CO'; CRETE k,- g,., BARRIER w \\ I d 1" FIBERFRAF ,q'*' 4 DA'DtING l (OR EQUAL) .g r J l l INSULATION CONSULTANT & MANAGEMENT SERVICE l Typical Detail Drawing W Fire Seal Mechanical Penetration Floor e, q u e c~.0 MLS '" T2r care 4-17-60 omit 5-o-80 oart5-7_go oart ~ SCA t m;+c owG 8eo t M0102 = .,v..~. c

1 A e .A CONCRETE BARRIER A o. A - PIPE SLEEVE A 4 PIPING ~ INSULATION 7 V / MECHANICAL g PIPING ., 3 (G '- p. . i. / /. i. ;.*E....'J ' / 1" FIBERFRAX / dam!ING-OR EQUAL ... J..Dl'. (BOTH SIDES) 4 ..:, 2 *n ....i..',j_. -' 7" DEPTH / } ':0,:2 -~ SILICONE FOA'1 ,.j- ,/ V a - y./.. ...p. s eb INSULATION CONSULTANT & MANAGEMENT SERVICE Typical Detail Drawing Fire Seal Mechanical Penetration i Insulated Piping - Wall es 3g cmo tr " '" JbT~ c^'E 4-17-8C DATE $_6_gg DA rg 5-7-80 D^'t w ^ owc w scatt urg Mol03 n...n... .n .n c.. I

1 IECllANICAL j PIPING i 1 PIPING i INSULATION i / PIPE i j SLFEVE b. .v.5 '.. 5.: $@h:. 7" DEPTH Y-3.* 'E$hi SILICONE FOAM ..iiiit. M.h:$

    • y*

2h.l:;.0

  • di.$...?.

. ~.c

g..

'.b .Q44; . !.k0 ?:'$ li b b. O* C CONCRETE f, y ef S,h.:.y(?,- [:;.:;p ..,6,l:,' p*. BARRIER

1::?;.'.

qtt. -s A. 3,2-}6: i': 9 9',' y

.t

+ pp.. y. ..u.. ~ ..Ca y

  • b*

1" FIBERFRAX A. ' 'i- \\' ~.. DMD11NG g (OR EQUAL) k .b. ~ f ~J INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing - N Fire Seal Mechanical Penetration Insulated Piping - Floor er yg e, c ao gus am ygy-am cart 4-17-80 DE 5-6-80 DarE 5-7-80 D^rt v*Lt NIS D*G w M0104 w' m...-., r...

r..

1 t e

  • A CONCRETE 7

BARRIER N ,^. ",A p* / 1" FIBERFRAX

  • @d DA3SIING-OR EQUAL (BOTH SIDES)

A ~ .; "if d ' p ~~ lhi ji 4B.;;ls .' r. M MECilANICAL .^ PIPMG j f,l'I/ !!!,.,.j}ij$)* Is.!;4F' r 4:.ce - / ..e7.~ . ;?@ y- .c A ..; l: 5 . _g/h 7" DEPTH ...g:f.if /- SILICONE FOA>! -g.sp,i .:s.I

Y.

A A, - INSULATION CONSULTANT & MANAGEME}T SERVICE FOR Typical Detail Drawing Fire Seal Mechanical Penetration Multiple Piping 'a'all Bf 7y( CHRD gtj g 7"' APP APP cart 4_17_80 oaTE $_6_ gg oart 5_7_gn D*TE N NTS 0*G % M0105 u? m.~., r

1 C 7" DEPTH SILICONE FOAM O4 D. MECHANICAL PIPING

5@.L1
,

/ 7-

,I$$i d

.:s .b ::. y y,:<:.. - . :. h.. 4 W &l. Ni.

h' ?

h ) f,:5.d.r.).:-%$ ,D, i. CONCRETE BARRIER

. c.o

.?;

L.

6 1::.sy t. st -c e

p:i:r.

' i;x. .g C: n

  • fv.'.u

, p- + l: ;gp::'. . l>. ' g-t A. k.l.f. : :

.' 6 n :.

ow .O'.. W. 55*$.9d 1: .a%. ,p.,. .p. s,%q 'y

  • 7 p

4 'J 1" FIBERFRAX ~DAMtING (OR EQUAL) INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Tvpical Detail Drawing flTLE Fire Seal Mechanical Penetration Multipic Piping - Floor BY qwQ CMac pg 7g AN AN can 4 p 90 Datt 5_A_go o'rt s_7_so 0471 scau NTs ocw M0106 ~.

1 .~, 'O-6" CONCRETE BARRIER u .W 4 - "J" Rt'NNER EXTENSIONS 57. A 4f y A- '!ECHANICAL PIPING -f $,s t;:- E 1" FIBERFRAX 4 DA>S!ING (Ok EQUAL) e 7" DEPTH SILICONE FOAM ' na. .n . a 144. NJ '>d. 1" FIBERFRAX ., j DA?S!ING ,4. (OR EQUAL) l lN5ULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing N Fire Seal Mechanical Penetration Barrier Ext nsions - b'all B, y w c_ cmo m, 3 sn gg 3-an cart 4-13 m cart 5-6-80 0^rt 5-7-e0 0^rt watt

i. E ~
  • owo w

~ ' '-- ; Ma107

I l 7" DEPTil 1 SILICONE FOAM -- MECHbICALPIPING D e / / . 1f J ~6. )p!; 4 ...v , S,. g@~f[:, ,6 cgg "J" RUNNER EXTENSIONS h*.-

u. s} es" '

.h> .9 gg? h. N '1 mr& 6 5 y k -c 4 .N ys 4 6" CONCRETE BARRIER 1" FIBERFRAX N;.'4 ., p DxenNa (OR EQUAL) Q b ) i t INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing 7" Fire Seal Mechanical Penetration Barrier Extensions - Floor l m 3, s" 7gy e-qwe c~=0 ca.t 4-16-80 D' 't 5-6-80 D' 4 5-7-80 D^'E scea yre ow; w M0108 w M

1 T J 9 i 7 CONCRETE BARRIER p,' PIPE SLEEVE l .h -MECHANICAL PIPING / 4 4 1" FIBERFRAX DA*! MING 4,./ '/ OR EQUAL (BOTH SIDro 4 4" DEPTH / 4 ICMS PRODUCT 60 s / p P. .A'y p /' ~1 INSULATION CONSULTANT & MANAGEMENT SERVICE Foa Typical Detail Drawing ) ritu Fire Seal Mechanical Penetration ICMS Product 60 - Wall g ap, 4pe Ov TyQ Cw=D fj,, g DE 4-10-60 D^rt 5_6_go cart 5-7-80 cart i D 'E NIS owc % M0209 = r..

1" FIBERFRAX DMI'!ING-OR EQUAL ~~ MECHANICAL PIPING (B01H SIDES) i, PIPE SLEEVE g. N 4" DEPTH ICMS PRODUCT 60 g m. b' Tx / g. x ^ ss .2. .b'- 4 Q f. N; th(W;. i -:.:y i:' p-4 q-CONCRETE

n. -

5

  • e BARRIER g,

N BiE(n

  • 3 p

9 a \\ p>. T A ~4 l. ', V, 4.. '.V 4 [ O' J \\ l i 1 INSULATION CONSULTANT & MANAGEMENT SERVJCE 'O' Typical Detail Drawing N Fire Seal Mechanical Penetration l ICMS PRODUCT 60 - Floor AN AP 8v gy( CHmD g.3 gg oart 4-17-80 D' " 5-6-80 D*'E 5-7-80 D*'E m NTS o*G

  • M0210 w,

~~4 ~. r.. l i

/ ~ I .p. .g -CONCRETE BARRIER e p

  • . a *.

-PIPE SLEEVE .g b. - PIPING INSULATION ,/ p/ A. .j MECHANICAL PIPING y i'l / / k'

  • 1" FIBERFRAX DASD11NG-

/ y OR EQUAL (BOTH SIDES) 4 c / ,g _.y k-/7 4" DEPTH f . '., ' *o ICMS PRODUCT 60 s.. ' b t \\/.',, * ,. d ' b'

  • b..

j

  • h l

\\ INSULATION CONSULTANT & MANAGEMENT SERVICE 1 Typical Dett 11 Drawing '0" tita Fire Seal Mechanical Penetration Insulated Piping TCTS Prn<loct 60 - tJn11 C"D kl.S '" 32 T~ e' ~3w c_ art oarc 5_7_gn cart 5_g_gn catt 4_1s_gn O*G NO SCAtt MTC M0211 ~ ~.,

3 i 1 1" FIBERFilAX DA?P11NG OR EQUAL (BOTH SIDES) 1 PIPING INSULATION 2 ) PIPE SLEEVE b- .N ~ V

  • A

~ ?

  • b*

C> h**, S. I CONCRETE BARRIER a 2 - {j , 6,' ' b.'. ', g, '. / A' a '" DEPTH i ICMS PRODUCT 60 ~

q.,n.

,,,A 4 + 6 q- ...7., s... y 3

  • g*,

s MECHANICAL PIPING h b,

  • se

'sd i 1 ~ INSULATION CONSULTANT & MANAGEMENT SERVICE 'OR Typical Detail Drawing r:Ttt Fire Seal Mechanical Penetration Insulated Piping trMs Product 60 - Floor n" es ~gm c~=0 fyg n" g y-oa rt 4.is_an cart 5-6_gn oart 5_7_so cart sua wq o-c m MO212 w e..

6 6 j .b. .a 6" CONCRETE BARRIER O O. PIPE SLEEVE s . V . 'y .i / .id. .: lpje'.hi. ' 7' MECHANICAL PIPING V..'l?;i a" " ....;.p 1" FloERFRAX DA'211NG

e..i.

OR EQUAL (BOT.i SIDES) OM 4 4" DEPTil / ICMS PRODUCT 60 /. b.. b. . a. 4- ? INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing Tita Fire Seal Mechanical Penetration 6" Barrier Tr.ts o ndrict 60 - a l l r es gwe c"o fyp, s" yg T* ^" c^'t 4_16_9n o^'t s_A_9n s 7_9n o^'t o^rt scia ...,.c owo % M0213 = ~... -... r.... c..

o !!ECHANICAL PIPING } ~i J 1" FIBERFRAX DNetING OR EQUAL (BOTH 1; IDES) N .g h PIPE SLEEVE m.- ) v N . J:g.-j d. 6" CONCRETE

  • [

BARRIER f-I.' a. ,a....a- . n, u e 9 b ,\\ 7.'~ d 6 4 !:.~1: '=. 4 + . n. . a. \\ 6 A 3, ( 4" DEPTH ICriS PRODl'CT 60 b INSULATION CONSULTANT & MANAGEMENT SERVICE s '08 Typical Detail Drawing Md Fire Seal Stochanical Penetration 6" Barrier ICMS Product 60 - Floor ywe cr <o y);s nw g g y-e- see catt 4-18-80 cart 5-6-80 od't 5-7-60 Dart N "TS owG w M0214 w' r.

e 1 t O A' p 4" CONCRETE BARRIER .b.d s y / ~ O 1" FIBERFRAX DA>S!ING .d, *,. OR EQUAL (BOTH SIDES) i v .:.4 EII !!ECHANICAL PIPING 2 9-A/ 4 / s s .4-4" DEPTH y p7s... ICMS PRODUCT 60 ~. w y. 'A. g. 3.. @/ s'. '. '. ..p .A TAl'COS ANCHORS OR EQUAL i i INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing TITLE Fire Seal Mechanical Penetration 4" Barrier TC'S Product 4 0 - k'a l l 3[ 7-nn 3 e c~o y nn es cart cart 0^tt enn 3_3g_qn 5_ f,_ g n 5_7-qn W NTS D*G S M0215 w n, .e. n c..

o TAPCON ANCHORS (OR EQU^.L) MECHANICAL PIPING 1" FIBERFRAX DA'O!ING f ] OR EQUAL (BOTH SIDES) ,, / 4" DEPTH 9* ICMS PRODUCT 60 g .S b lll.*.:"-. h ~

  • c' 4" CONCRETE BARRIER

.4f.; G;, ' ;'.i 4:{:.;. j'-.b- \\ E,.$ O '.. ' O,. '..A*'.O' q y

n g..

o-x .?- 4 ,r ? INSULATION CONSULTANT & MANAGFMENT SERVICE '0" Typical Detail Drawing mLE Fire Seal Mechanical Penetration 4" Barrier T etfC Product 60 - Floor B* qw( CHuD yQ AW g g Aw DATE 4_]6_gg DATE 5_g_pg DATE 3_7_pp DATE KALE NTS DwG No M2016 w' r.. - ~.,.. 9

1 A

  • O CONCRETE

,5 ,d dARRIER ,y., PIPE SLEEVE ~' .- 6 p.., p. r' "t h MECHANICAL .,8E ~ PIPING g Y .? Q ..d' h f" LEADED SILICONE 150 LB. DENSITY ?!- jEi#'7-(100 FILL DEPTH) ?gy%,g; 7" MINIMUM g 4

c. l.Q "

<'fl5?.- . 4.. 4' . A.,, s @N,'>..',',*# i TAPCON FASTENERS CR EQUAL 1" FIBERFRAX DMDilNG OR EQUAL t-(BOTH SIDES) P ) 5 DMD!ING AND se FASTENERS . {'.. INSULATION CONSULTANT & MANAGEMENT SERVICE l j 23 1 ,0, Typical Detail Drawing N Fire & Radiation Seal !!cchanical Piping 150 lb. Density - Wall an \\ ev y w g c~no y an ggt-cart 4-18-80 cart 5-o-80 0*rt 5-7-60 cd'E scaLt NfS D*G W M2017 w ~,,.

i i MECHANICAL PIPING 1 I } PIPE SLEEVE .A '.. *:h

g..

iii:.ii! i

..;.a:...

...A. 4 3 ' A' iy;9 .W" M: Y,ik ' ? r'.h{h. b'k4 >- .v'si p: 150 LB. DENSITY c Y .:n .n

g p'

, b t.EADED SILICONE p i,$ F (1007. FILL DEPTH) r$: .g5i: q

b..

a v.l.y g.:d... ?' V' ,C. Q . s:

t. );?.

wi. cc. .9 f.y;!.:. ,* O f 9 CONCRETE g 4 BARRIER b. r ~ I e INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Dettil Drawing j I' 7" Fire & Radiation Seal j Mechanical Penetration l 130 Lb. Density - Floor 1 gyt CH8C pg yg[ 8' am AP9 o*'E 4-18-30 cart 5-6-80 od't 5-7-80 0*'t x^t t NTS o*G % M2018 w m.,,,.... ..,.i

Y t g CONCRETE BARRIER j

  • P *,' p,"

~ DASS!ING OR' EQUAL 1" FIBERFRAX g,, e.;h'} (BOTH SIDES) p ...p:-.e... '*'i o H.+ M ~l..f.h -W.5;~ ' ):n...' 5fi,j;f.W.NhS,IM.'

fi,-

E4..: d MECHANICAL PIPING R$p#" @.E.:.! En= i.G.:' /

i#"

150 LB. DENSITY .:Y,917: .../.i.ik.4i.? '~ LEAD FILLED ?':' SILIC0NE l /:.c.:WifIf,{j,$:h'dl'e..j'f! E:H f -Y5h'.fi .,,d .fjpf. (100% FILL DEPTH)

d. U.: ~. ;.f6;...'@l.'fhE. A, 7" MINIMUM l

5 .= . f;.:- n$,f{.* *:.%.%:~... * .?ll.' s ::

yg:,

.'.b-

a

.'p.,. l> TAPCON FASTENERS 7" OR EQUAL L l 23 (1( S If[ INSULATION CONSULTANT & MANAGEMENT SERVICE se Dar=in g & Anchors t FOR Tvpical Detail Drawing TITLE Fire & Radiation Seal Mechanical Penetration l 150 Lb. Density w/Marinite - Wall 1 er g t,3 c., c-o pg-a gg am i 0^'E 4 17_9n 0^'E oa'E C^rE s _ r,_ a n

_7_on SCA E ymq owG No L

j M2019 l e e." .ev..~,s c..

I 1 i MECHANICAL PIPING a E. .6.e N 1/2" MARINITE BOARD 4 (BOTH SIDES) 31*01:: S.5l.'fh'55{-s.:,...i l: h.. TAPCON FASTENERS k

?,. U

."..::.#$.;.;p:2...:.': (OR EQL'AL) c Q ..w: :.:;:.:y

.?:P.T

.-?.I., CONCRETE BARRIER f 4 g>...l..-

2
aw::....:

..y.28.:l

s.!y;;:* D.

. i.:..:.:.::.:.w..:i 2 p .D;. : :.n

.?:1:9 :%.:..

..+

s.
...i

.. :.:...'.v,. r..

!:Q*l:*Q b 4

.. i:. -... b. .b .:c:.v.,.t :.',\\:: :.: .::;:y.: ; ....u.~....

.v.

s 150 LB. DENSITY Nf':!.y)if,.*A LEAD FILLED Y:-. :M ~ . i... @ d$yl SILICONE D. *. (1007. FILL DEPTH) M r J r X INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing TITLE Fire & Radiation Seal Mechanical Penetration 150 lb. Density w/Marinite - Floor n' TLa C C"O % ^"J8 DE l-17-80 DE 5-6-80 0E 5-7-80 DE N NTS~ D"G W "? -.e <v. ~ r M2020

T i A CONCRETE BA:.RIER i .6 ~ PIPE SLEEVE

  • O'

....,/ / MECHANICAL PIPING J. p ?ls' ..h b .j.f %/ yf... f" 'ly?

  • 1" FIBERFRAX

/ OA>D11NG (OR EQUAL) g> .:id$ '

y -'

250 LB. DENSITY LEAD FILLED 4 SILICONE p > ' ' I> .y ,P.. (60% FILL DEPTH) g 3 r' F INSULATION CONSULTANT & MANAGEMENT SERVICE i Tenical Detail Drawikg FOR Fire & Radiation Seal Mechanical Penetration 250 lb. Density - Wall 1 1 am CMa0 gfsp am y g Bv ggt GE D^'t 5-7-an DE 5-6 90 oE 4-18-80 oow l' __ watt yrc: 32n:; j s.

1 1 l MECHANICAL PIPING t x 7 PIPE SLEEVE f . $a, h.. . a O s' yi:n g pen'-i 250 LB. DENSITY M LEAD FILLED SILICONE ~

/:.::!:/

.s..... N D (60'.' FILL DEPTH) j:f:? ql,,, E.>'

y.t.i.

Es39y:/ 5 \\ .61g5 l f.:. .A %.c

G 7:i..p;5.t

-G 1 .= CONCRETE O.. O k BARRIER w.b s 1" FIBERFRAX b q. Q D.tT!ING (OR EQUAL) O ~ b l g r ,s 1 i i l E INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawi.ng TITLE Fire 6 Fadiation Seal Mechanical Penetration 250 Lb. Density - Floor CP *O Qg Apo p 7-Apr 8' gy{ cart 4_jg_gg cart 3-6-RO E 5-7-80 0^'t $ CALL NTQ (?frG Ps0 ~~ M2022 = r.. a. ~

i r CO:: CRETE f BARRIER 2" DEPTH FIRE ,p RETARDANT CAULK ]" FIBERFRAX R b', L MECHANICAL (BOTil SIDES) PIPING A*IN/ y s 7 PIPE SLEFVE / 4 4 P-

  • P l

1 't A INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawidg Fire Seal Mechanical Penetration Silicone / Adhesive - Wall fgg

    • ggy-er gg c-o am cart 4-Ig_ge o^ 't 5-A-80 o^ 't 5-7 an od't SC4LL NTS o*G %

w M0323 , ~. ~. r..

4 i MECHANICAL PIPING 1 h i J PIPE SLEEVE D 4 s. g 4 g' (is; / Sa ) 2" DEPTH FIRE .y,A g g .;.,T RETARDANT CAULK g, w Q 3, s 4 1" FIBERFRAX D/J011NG g' A O. (OR EQUAL) A 5 u ,A.'d CONCRETE BARRIER / b . 'w . ' o. + O 4 l4 ,4 7 w L ? INSULATION CONCULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing flTLE Fire Seal Mechanical Penetration Silicone / Adhesive - Floor es ~g w e cmo gy yg sw sw cnit 4-18-80 DATE 5-6-60 care 5-6-80 o*TE ..,,..,,,...,,'at NTS N* M0324 e.+, ..rv,.,~,

T LEADED DIELECTRIC GEL b 2" DEPTil \\ ROLLED S.1LICONE COATED IWt!ING 4.- y...

  1. . 6..

9 s e TYPICAL E ~ 4 BOTH SIDES 7 I SILICONE /

  1. ~

FABRIC BOOT L- \\ 31ECH AN ICAL,_,,, rD j hge. ' PIPING ff A ~ ,f~. SLEEVE ..d 4 ~ N -f 'b. CONCRETE BARRIER / P.. STAINLESS STEEL BANDING 's ? INSULATION CONSULTANT & MANAGEMENT SERVICE ro* Typical Detail Drawing Tita Fire & Radiation Seal 5techanical Penetration 150 lb. Density Dielectric Gel tJall es 3wc_ c~=0 ty p nn 7,cr nw enic 5-5-80 cart 5-6-30 cart 5-9-60 cart I* M2125 L

V MECHANICAL PIPING STAINfESS STAINLESS STEEL BA'; DING L: STEEL BANDING 'i \\ 'n. H PIPE g/ V SLEEVE 7 2" DEPTH

  • A-

\\ f ROLLED SILICONE COATED DA>E ING I t 7 4 i-

s 4.- 3
  • .. '. k

( CONCRETE ( p ,7.";. BARRIER LE b' t + Ah LEADED s!,' , 4' ',' Y DIELECTRIC GEL l / ( l 4 1 s. 4 1, N -y '. 1 3. P. s y s 4 's TYPICAL s i I BOTil SIDES 's I 's a I ~ ~ _. ' l L l E INSULATION CONSULTANT & MANAGEMENT SERVICE 'O' Typical Detail Dravidg TITLE Fire & Radiation Seaf Mechanical Penetration 130 lb. Density Dielectric Gel Finor aP e, 7 g e_ cs c yg any i om:t 5-5-80 C^ M 5-8-80 D^'t

o 80 cart scau N^ T4 C*G
  • M1116

.~ ee..*, e o< e.. sw s rw r s,

1 CONCRETE BARRIER s' 6\\ SILkCONE \\ FABRIC BOOT s \\ b \\ .u TYPICAL i F BOTH SIDES h 3 I h I i 1 !!CCHANICAf i PIPING / PACKED FIBER-FRAX DAM > LING OR EQUAL (14" DEPTH) 4 .c U PIPE SLEEVE / i' N ~ STAINLESS j STEEL BANDING l 't i h 5 Ch " Sed f gNWflfI INSULATION CONSULTANT & MANAGEMENT SERVICE 23 so Damming Depth roR Typical Detail Drawing flTLE Fire Seal Slechanical Penetration Booted & Refractory Material - iJall n" e, 3 g c~o g,x ." g cart 5-5-80 D^rt 5-8-80 0t 5_9_go cart nun E NTS N 'O ~.

1 MECHANICAL PIPING l STAINLESS [ STEEL i BANDING SILICONE FABRIC BOOT bl'. J Y J b* \\} 7* d PACKED FIBER-FRAX DAMhTNG OR EQL'AL g d (14" DEPTil) 'g. CONCRETE ,a asARRIER ,4- / ..Q ,. [. PIPE SLEEVE j 4 a \\,N .b Q-t A i 's -Q TYPICAL \\ i BOTil SIDES I 's I e , ~~~_..J s t E Damming Depth TA d=phh < 05INSULATION CONSULTANT & MANAr.s. MENT SERVICE l 23 ge '0" Typical Detail Drawing TITLE Fire Seal Mechanical Penetration Booted & Refractory Material - Floor 8' T uJ C. C""D MLC l "" J'E7- ^" 4 carc 5-5-80 c^" 5 A ao ' o^ ' t 5-9-90 wt SCALL NTg DwG NO A407q

.$r 9 9/ o %$1b t) //// A '%g*,} l /// "I f/gy>+/g,9' NNNN*/ 4r /Y y //// _ EEm e 1,e~ TEST TARGET (MT-3) a -g ,k,, 5 lh-ca l,l 'h # l Iib 1.8 1.25 IA i 116 i 6" = MICROCOPY RESOLUTION TEST CHART +

  • Ek

' //)/ .p

l '%$>&Q? //// th l 9 '*"N$, .N i \\\\V' IMAGE EVALUATION TEST TARGET (MT-3) i 1.0 l;m un e tu p=2 e as l l,l h,* bN I gs 1.25 1.4 1.6 i V i MICROCOPY RESOLUTION TEST CHART fff /// b $Y?,,l .g+p, f . /b p. e w.w

  • w ed.
-w s.

1 CONCRETE BARRIER O* STAINLESS STEEL $ANDING\\

  • I

.g - p. E .d h MECHANICAL PIPING I N'b PIPE SLEEVE J p. 4.' 4 4 b. SILICONE -g FABRIC BOOT i ) INSULATION CONSULTANT & MANAGEMENT SERVICE FM Typical Detail Drawing TITLE Smoke & Air Seal Mechanical Penetration Booted One Side - k'all er $we c~.0 zg3 ^~ py se oa't 5-5-go omrt 5-8-80 oE5-9-80 o^'t scut y7c owc w M0529 l w e.. h

4 MECHANICAL PIPING SILICONE FABRIC BOOT t / STAINLESS STEEL BANDING / h* b- / O. k '.A P. A g 'I CONCRETE g A*,k BARRIER Y.% 4 t p .O PIPE SLEEVE d N 'p / 't. f INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing I'I'E Sno'ge & Air Seal Mechanical Penetration Booted One Side - Floor l er gto (- ca"o Mtg ^* JAT ^" ( oart 5-5-80 0^'t 5-8-80 DATE 5-9-80 D^fE I x^d NTS D*G W Mos30 l o. . ~... ~ l

+ t CONCRETE BARRIER "\\ \\ g t g v ---- TYPI CAL .y-e j ,4 fr i BOTH SIDES 1 { ?'. ,g'fri l s g gi I Eb E s l pfe, % MECHANICAL PIPING 5 f .r ' IfQ ' 5 DIELECTRIC GEL Q-3) 1 l7 ,s ; . s. \\ / -.y..- 4 ~ h. PIPE SLEEVE P-STAINLESS STEEL BANDING SILICONE FABRIC BOOT i. 1 INSULATION CONSULTANT & MAN 4GEMENT SERVICE Typical Detail Drawin'g TITLE Fire Seal Mechanical Penetration Booted-Dielectric Gel - Wall es ggg e c~o Aqg ^" f g n" cart

-;-ou cart 5-8-80 Da'E 5-9-80 D*'t v a.,

-c xm

1 MECHANICAL PIPING S II.1 CONE FABRIC BOOT s i t / s / STAINLESS STEEL BANDING V. cu'! h m j l.1 <w# ) s[ 1. '. /1% r 'V 'f7, PIPE SLEEVE 1 2 s (J ~s 3 f l b 6 f p , "I

  1. '1 f 7 CONCRETE
  • A Q

BARRIER

  1. .,y.rgy y

O. S,J- ./ J sr DIELECTRIC GEL e 1 L- 's r& -Q*l' b t .f g I f 4 fgi, -', a g. s.; ~ \\ k TYTICAL 's l 8 BOTH SIDES l ', ~ ~ ~...a 1 T r I INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing "M Fire Seal Mechanical Penetration Booted - Dielectric Gel - Floor yg s"ggy er yx c~ o nn cart 5_5_go cart 5-8-80 0E 5-9-80 arc x^'t NTS Xw M0632 w c..

1 CONCRETE BARRIER L. i O/b V. p,..>d.. g 7, f, MECHANICAL PIPING g,[fY / y- , t 4/s.b' -(f / y -DIELECTRIC GEL i ( ~ QJ t.nj&.9 f,, y [ p', p 5 PIPE SLEEVE 4 E ,. yP O i l 1 l s i INSULATION CONSULTANT & MANAGEMENT SERVICE " '0" Typical Detail Drawing W Fire Seal Mechanical Penetration Dielectric Gel - k'all er 7g c-ao ny ancqy Am OE 5-6-80 DE 5-8-80 Od'E 5-9-80 0'fE W NTS 0*G

  • M. 06 3 3 w

n. . ~.

MECHANICAL I'IPING b i P-PIPE St.EEVE n., s 6 f(h . 0 E J(f $f. uz \\jp-l 'S u z *r

  • f(

4.- 1 .r f 73{ () P.'. .g' '. 'f 2 1 ~, D / s. ' 'l; ty.7 ,O P CONCRETE s b BARRIER g- ,a Q. .q u. DIELECTRIC k 9',A ._ _4 CEL d 4 es 9 / t t INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing TITLE Fire Geal Mechanical Penetration Dielectric Gel - Floor

e. qwq fgg_

n"yty-c~~o omit 5-6-so cart 5-8-9n ot s o-go o^'t x^'t

  • Tc o*G **

,, n,.g,,

1 CONCRETE BARRIER SILIC0y: '[# FABRIC BOOT s 's TYPICAL Y,'. ' ( 20TH SIDES j ,o i p.. g i g i i n' l 1 HIGH TEMP / / CE!!ENT g / / / / / j MECHANICAL PIPING 4 4 PIPING INSUL- / ATION / \\ 4 N STAINLESS STEEL BANDING PACKED / FIBERFRAX DA!2ilNG OR EQL'AL (14" DEPTH) E 5 Changed g, y'g INSULATION CONSULTANT & MANAGEMENT SERVICE j 23 J 80 Dammine Denth roe Tvolcal Detail Drawinn tirLE Fire Seal Mechanical Penetration Insulated Piping 'hti. - Wall nno t !.,- e o, r, - a,- es gwe c~~o pg

  • " 727~

oE 5-6-80 0E 5-8-80 C^rt 5_o_gg cart $CAtt NTR CNG W M3035 .. ~, r... .~. j l

V P1 PING INSULATION MECHANICAL PIPING llICH TEMP CEMENT l SILICONE g l FABRIC BOOT s' 5 N STAINLESS STEEL

  1. V BANDING PACKED E,

p# FIBERFRAX A DAE11NG OR EQUAL A 6 (14" DEPTH) .b O ..q p-CONCRETE BARRICR 9.. =. s w ~ PIPE SLEEVE p {K 1 - q-A l s.- 9 l p,- g ~N N g \\, l TYPICAL 's, BOTH SIDES e t L a { J{ Changed 6g INSULATION CONSULTANT & MANAGEMENT SERVICE /w Daeming Depth '0" Typical Detail Drawing tira Fire 6eal Mechanical Penetration Insulated Piping Booting 5 Refractory Matl. - Floor zwg c~.0 p,qq

a.,,j u

an Dart J-t)-oD cart 3-5-ou Dart 5-9-80 cart %Att N' T 9 0*G NO ~ M3036 r..

1 = C0" CRETE BARRIER I 4 PIPING INSULATION SIL/ CONE a g'. FABRIC BOOT .D w MECHANICAL PIPING PIPE SLEEVE 4 O. ,\\7 3 a 6 STAINLESS STEEL BANDING i Y I INSULATION CONSULTANT & MAN AGEMENT SERVICE '0" Typical Detail Drawi.ng ritu dmoke o Air Seal Mechanical Penetration Insulated Piping Booted One Side - Wal1 cno y angg an e, qwe oa'i 3-6-60 cart 5-6-60 cart 5-0-80 0t scatt 3;79 c=c m MO517 .~

1 . PIPING INSL'LATION STAINLESS MECHANICAL PIPI;iG STEEL BANDING / h y / l I SILICONE FABRIC BOOT E O# ] f O g.- g \\ ,h. '/ CONCRETE BARRIER p..p (. <1 t.'7 r ~s- - + 6 .y. 4 PIPE SLEEVE q. g' y* m y ,,) 't h INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Draw 4ng TITLE Smoke & Air Seal Mechanical Penetration Booted One Side - Floor 3g c~ 0 pg s" g ev s" cart 5-6-80 0E 5-8-80 0E 5-Q-80 0*TE SCA NiS D*G m ,.,'E M0538

1 CONCRETE BARRIER 1 PIPE SLEEVE J . >? b. ECHANICAL PIPING '. ' 4. *... .u... Nil /i;G.gpy$$b?" h h * ~.rj It7 1" FI3ERFRAX L DA>C11NG gkN' p f g; ..i!....- ?.' ' '

  • 4 ' K

- + ,,9 p' SILICONE FOAM \\ REFLECTIVE INSl'LATION P e INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail DrawirtI; N Fire Seal !!echanical Penetration Reflective Insulation - k'all e ;rw t c~o g(q, amyg cart 5-10-80 Daft 5-10-80 0^'t 5-10-8( D*'E scau "T C, D*G W M0139 we ~v,

1 MECHANICAL PIFING REFLECTIVE ISSULATION i )() A. PIPE SLEEVE t .?' 9 ts . p r ,.c w /,, /. y 3-

e. x; a

s. f lfM. Q 44 y, p' ' ' j s %g 9 . 6 ;. CONCxETE sAsa1Es f.. j. q e DePru + sgmE d h g g u.- p; L 1" FIBERFRAN ym DA}DIINC s (OR EQUAL) y/ INSULATION CONSULTANT & MANAGEMENT SERVICE ro" Typical Detail Drawing flTLE Fire Seal Mechanical Penetration Reflective Insulation - Floor

e. qwe c~~o fqc.

"" JW c^tt 5-9-80 0^rt 5-10-60 D^ rt 5-10-60 o^tt m MTs M0140 o, e..

1 CONCRETE BARRIER J 9 1" FIBERFRAX p DAM'!ING OR EQUAL (BOTH SIDES) . s., .,;jf;' .W.kIf,, f 5.: '$d fhk ...~C. JN l@#E" \\ 7" DEPTH i f;$ffSf-[.,)g; '- SILICONE FOAM yi 9!Qst:.' " ~' w !..IjikY' Q.' + - S 4 k b .A SLEEVE Q I t I 1 i INSULATION CONSULTANT & MANAGEMENT SERVICE 'C' Typical Detail Drwing W Fire Seal Mechanical Penetration Blank Sleeve - Wall 1 y@ '" 32f~ B' T w C. C"O omit 5-6-30 cart 5-7-60 cart 5-9-60 oart EAI .TR DwG #80 L M0141 ,,,,s.r... .m c.,

I SLEEVE s. 2 ,/ k%WA%.h Y.s$. /

.~.3QT N!OG

/ Gj$(WsE;QW;!jj;. d, hi'.4.y$$'ID.15'N$ff.I*I$ T;.'h '?.O.t'* i. d g/4b;4:b:.' d.. y-'.j.u;.(;. CONCRETE dj6.['iME[)[' y%8-gf:lp'Qy .p. l- {' BARRIER G A; ;'a; n 56.:.: >. I ~ % :r O 'lG.@..j~g.vQ.i!.:-}%17 f \\ gii ~1.'g..:? s.%..,c., N. :'.d g - a.c.'..~y.

e p:.s.

b 6 Pt,3.q g S u. / 4 f q i 1" FIBERFRAX I A + Dxrt1NG (OR EQL'AL) D 7" DEPTI! SILICONE FOM! l l l i i INSULATION CONSULTANT & MANAGEMENT SERVICE ron Typical Detail Drawing TITLE Fire Seal Mechanica1 Penetration Blank Sleeve - Floor y)g n" 7gy-n" es ywL c~o cart 5-6-80 D*'t 5-7-80 o^'E 5-9-80 o^tt wau N' TS D*G W M0142 c.,

T 1L SLCEVE .. b...s...-

Lm l.rj );l[;.

.g .*s-- %. ~. )'4s [. 42lCW@,.3Nb *;sm!9.,n MW pi.e.6./,,.9,4fesi!.@]M., 1,$. M's 3... e.iN..[1, m-A G 9: t A..?. :.i:: "*.:,1.;':gy ;G:*.....v .e< ny;. %, A .[ A.f** .'. % e ?'!:7 C .( *.:.*;,. '::p..... u,g.,, e,*;i:,,~!i'XN.1Q;g ; v. " r-i:!&e- ~ .~ $4,;.:c

4..-

a

n. :!(.

. C; :'. '..'.?:'.,'. #,3;:...L.15,.?:. RM gy,j:,; t e...:; A.;.;,Mi..e .e. . c,5 .o *

. :.?; -

,.&...,.'i.;;;;J.;:...L. : .?...Q' M..'.f,'; e .?. -?- ..,, ".:hT'. *. '"h '$.s a ; s':d ' 5 ;-[*.'..., - .S&. 3.: '..%g.:;t '; 2

?
  • CONCRETE
.
;':::ga; -"

s" ~M:f90/jd..:.:n.'0.'. BARRIER . ;;f. 4 I "(sd-.~22 4, e > 4:.;;f.~f:.!t.ht ; l

  • '* i :: 4 tl9:

' ::. s +,.., + N N. g-s'.; W;; 1 d.~~ ) A* 4 130 LB. DESSITY LEADED SILICONE (Fl*LL DEPTH) i l INSULATION CONSULTANT & MANAGEMENT SERVICE '0" Typical Detail Drawing W Fire & Radiation Seal Mechanical Penetration Blank Sleeve - Floor gQ are are By yy( CMD D' u s o_80 can s_ l o_ r,n can 5 10 gg oan sou =:Ts owo m gg4 3 a,.-- e,,

t \\ \\. CONCRETE BARRIER b f 1" FIBERFRAX DAICIING OR EQUAL (BOTH SIDES)

  • U-D A: p

. Jh.Nd$ 150 LB. DENSITY

  • b r '.:: n;;-di@';![K.

-e, ds E jpi LEADED SILICONE 0 .t e > ,2p. er.:::. r s0 (FULL DEPTH) df.[j%db3!Eff.S[ ~ 7" MINI!IUM DEPill Q . J:- WO ?:iMFME,MEj.j3k; ?f \\ Mf.M,Y.'re.>#j:,.J ?: 0 HWCid,P);?.?. _ i . W$ '.Y. O: '9A 'i' E.p.:a;.- M, s. x. v.e :.: !lj:'..,9f*';,

-c u

wih.tr.ii.T ; O . g' 1,-g:W* m.i. n;...;y, ';w 94,'p. n~. c. i-5Y'g:. - SLEEVE W;3 X, M 'g LAPCON FASTENERS, (OR EQUAL) Q

  • Q' D

5 1 22 4 J . INSULATION CONSULTANT & MANAGEMENT SERVICE Damming & Anchors y 'm 80 FOR Typical Detail Drawing TITLE Fire E Radiation Seal !!echanical Penetration Blank Sleeve - k'all av yt.g.,3 c, crao 7g g a T4'T' ^" ca7E 5-6-80 D^ rt 5-7-80 ot 5-9-80 DA'E sc^d NT9 D*G W 7, e a e m narr miswws I s.- es, a, M2044

a CLOSSARY - INDEX 'Q " PENETRATION TYPES C Conduit E Electrical G Gap H liVAC M Mechanical S Structural PRODUCT TYPES 01-19 Silicone Products 20-29 Leaded Products 30-39 Refractory Products 40-49 Coating Products 50-59 60-69 70-79 80-89 90-99 Specialty Products SPECIFIC ?RODUCT TYPES SILICONE PRODUCTS 01 Silicene Foam 02 ICMS Product 60 03 Silicone Caulk 04 170 A & B 05 Silicone Sheeting Material 06 Dielectric Gel LEADED PRODUCTS 20 Leaded Silicone 21 Leaded Dielectric Cel REFRACTORY PRODUCTS 30 Fiberfrax Damming Material t

A b i ,r-y '4 - p i s fSDEX G0101 Fire Seal - Seismic Gap - Floor - Wall - Ceiling l G0102 Smoke, Air & Water Seal - Seismic Gap - Wall - Floor - Ceiling l G3003 Fire Seal - Seismic Gap - Refractory Material - Wall - Floor Ceiling L 4 4 4 I 4 1 1 i e

e 7" DEPTH SILICONE FOAM l k i FLA>D!ABLE 1 d JOINT l l FILLER .r { .wl4::(- ..eSi?(?,$',, e' 'r*:l *- ...:e.se::

y.,.

@Eh,,.. j.l. %:.*.s.,f.fe,:.i.'.d :N."U/ *S:li \\*- s. e!: 4:gp,:/Ij:-l ..:.,c.:.....!. 98: ..i:.: ?: .Z.......*. ::t:.:...f,t 4.'s.;. t. ,::::, y.s::. !.::a.t

..f,.<.:3:.c.yu~:,g.:..v
: :..~

~ .:.;p

si
n..

.>. R:.5..*TEf..W:c;;..M..t.'y:: i*9.;:c..k..': l};'i::.Y

.y?%

..... 9 '.**. dl'.m$.'b$@5h .$} ;E$k

  • 5f:\\ $.::,Y:::::c.,.:.]::::

. : ::i:.' i c.4....:.. w '::...::W ; 1 i::;@: :- h,*::...;;;:ft:;;L::; \\ ~ * : Y :...:f.'s '.:&a,h1 *

<l+;4: J.,

. h.: * * '.L

.e..

l:::'..... - 't * '*..; * :I. k;;.. t.

f:i".C
..L :. - :-

?:.:: 6::,y;; :~;;.... '. 1 ;#.. M.y.:d..).: n$..b.:&$ A* WiR .lL

c..:..' *..

}::: .e.- s.

,::::y4:id...,

4 b

  • cr.
$:. a:.x'<.w.: : g:e o.

?. : a :P;S:'ns. EE. .; ' '. f::(:h&n.e.: d d m> ' '.c.3 0 5$::, $,... CONCRETE 1&I.:i s -c y:. BARR1ER .\\)ly:.0 ,.::. n.-

i?
  • i.W. -
1.:d::.::
:,yg;!.?, a,s. :.x..i
... a..

....'.\\.:.*t

s

.c.g.;c.:f.y ~

L-:'n i$$..$

g. h. = .: < y.. E.r.EG.: A ff

)::i=

N J INSULATION CONSULTANT & MANAGEMENT SERVICE a roa Typical Detail Drawing TITLE Fire Seal Seismic Gap Floor - Wall - Ceiling es qx cmoyh sw3g sw c^'E a_v on 5-6-80 E 5-7-80 o^'t ^'t sc4 E NTS o*G w G0101 =? m w .n...n.,s n., o,. w.

9 SILICONE j V FABRIC f SHEE"ING CONCRETE B;.RRIER s h 4 s ,7 ' , f 3".,, ) #.#,.

u.,.

.;n: hip;*L08 V'.*' r-i p f.:,l,,C.y.x' w.sx., :t *n!4;'.:t..;l:.2 ~q 1L= / .~.~T v :, i y ';:y'., ;e rn : *. &.!j,..a. i sv - b-J Jh b.. j'5 f~ Q t ~

y.. g..y>
: y 4..; t.+ -,:,,.

. ; ! f. ;. r,,r.- .t : ,..c, w- .. g. ; m g.. r e o.:. p y.. :- s. 4 a y*- b g .a 4. s. p g g. SILICONE / ADHESIVE (OR EQUAL) J 4 W 3 INSULATION CONSULTANT & MANAGEMENT SERVICE Typical Detail Drawing TITLE Smoke, Air & Water Seal Seisnic Gap Wall-Floor-Ceiling 8v ygg CM*C gtp am yg aN oa rt 4-21-60 cart 5-6-80 D* ' t 5-7-80 DE sc^ E NT("; D*G W G0102 w' n n.n wv un. n

9 SILICONE FABRIC SHEETING (BOTH SIDES) 'e s-1 W: h '*f,u 3, M-p 4,..?t's ' *f' ^.' >f&,. 5*x. f,,'.c,. l-y. e. ' I ... + f,- Q.g,,. -na.a. s$m.,. V* b. g.,.

/-la!5f+

-b'-

J...m.,..+,.1.

.... y,. ;.--:.,;.,s.-^ k,,.QY: % &.H.'.li J t ..... 2:.:-:.. - ..s. i.

l ' e 2,:c; 7 c y 2. M )

Nk"" :, f 's' O f _ Q. ~_ p_ >- a }y

9..

w[q r p-f-p a

2. -

5 V,,r==er + A -- p s 7 $qcS y% _ -gfQJ .O w & ],0w~' 'm%W .4 .p. 4 . C>. - ..d. 6.t~ 4 q.... Y $CTMc / CONCRETE g BARRIER SILILONE/ ADHESIVE (OR EQUAL) i PACKED FIBERFRAX MATERIAL (OR EQUAL) INSULATION CONSULTANT & MANAGEMENT SEf ' ICE rom Typical Detail Drawing tira Fire Seal Seismic Gap Refractory Material Wall-Floor-rgilinc er 7 w q_ &=o (p,L,g_

    • 7g J

oart 5-9-80 D^'E 5-10-80 DE 5-10-An D*TE scau ne owc w ' ~ G3003 u.' n e.,, .,m,n.,s n,.

4 i sN i INDEX i 4 l S0101 Fire Seal - Structural Penetration - Corrugated Wall S0202 Fire Seal - Structural Penetration - Corrugated Wall ICMS Product 60 f 4 I i i I 6

n l ) 6" CORRUGATED WALL 1, SHEET METAL / (\\ STRUCTURAL 2 N BEAM !.I / S1 h'. / / k.: [ ('[j[.'I f3 1" FIBERFRAX f DAFSIING-OR EQUAL _) M. s (BOTH SIDES) e g q >:a ~ 4" DEPTH ICMS PRODUCT 60 / ~x i I e INSULATION CONSULTANT & MANAGEMENT SERVICE FOR Typical Detail Drawing Tiru fire Seal i Structural Penetration Corrugated Wall ICMS Product 60 CHED QQ .M g AN 87 7y{ ca rt 5-10-80 od't5-10-80 3rt 5-10-80 o^'t l sc^d NTS D*G W S0202 uf n n.rr wv..n < n, c.

CORRUGATED WALL i. SilEET METAL j s k STRUCTURAL <g i 8 TAM $:3 f.n:??Ei 3:1.V [d 2 5 l Y

f. '

ik / .J ff "9:. 1" FIBERFRAX sj DMD!ING-OR EQUAL E4 (BOTH SIDES) fll. IL 'i

$: f-

\\f/ 7" DEPTil SILICONE FOMI v ( s INSULATION CONSULT ANT & MANAGEMENT SERVICE FOR Typical Detail Drawing TM Fire Seal Structural Penetration Corrugated Wall 7WC CHuD ff g [g[ lAN O' AN E 5-10-80 D^ 't 5-10-80 D^7E ;-10 A0 l Dart D scia aq owc m S0101 c.., u...,~., n.. r..}}