The following document is a preliminary draft being made
publically available to support a Category 3 public meeting
on January 26, 2018. NRC staff review of this draft document
has not been completed.
NRC DRAFT REGULATORY ISSUE SUMMARY 2002-22,
SUPPLEMENT 1
CLARIFICATION ON ENDORSEMENT OF NUCLEAR ENERGY
INSTITUTE GUIDANCE IN DESIGNING DIGITAL UPGRADES
IN INSTRUMENTATION AND CONTROL SYSTEMS
Summary of Comments on 2018-01-23 Draft RIS_KS R1.pdf
This page contains no comments
RIS 2002-22 Supplement 1
Page 2 of 8
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
OFFICE OF NEW REACTORS
WASHINGTON, D.C. 20555-0001
January XX, 2018
NRC REGULATORY ISSUE SUMMARY 2002-22, SUPPLEMENT 1
CLARIFICATION ON ENDORSEMENT OF NUCLEAR ENERGY INSTITUTE GUIDANCE IN
DESIGNING DIGITAL UPGRADES IN INSTRUMENTATION AND CONTROL SYSTEMS
ADDRESSEES
All holders and applicants for power reactor operating licenses or construction permits under
Title 10 of the Code of Federal Regulations (10 CFR) Part 50, Domestic Licensing of
Production and Utilization Facilities.
All holders of and applicants for a combined license, standard design approval, or
manufacturing license under 10 CFR Part 52, Licenses, Certifications, and Approvals for
Nuclear Power Plants. All applicants for a standard design certification, including such
applicants after initial issuance of a design certification rule.
All holders of, and applicants for, a construction permit or an operating license for non-power
production or utilization facilities under 10 CFR Part 50, including all existing non-power reactors
and proposed facilities for the production of medical radioisotopes, such as molybdenum-99,
except those that have permanently ceased operations and have returned all of their fuel to the
U.S. Department of Energy.
INTENT
The U.S. Nuclear Regulatory Commission (NRC) is issuing a supplement to Regulatory Issue
Summary (RIS) 2002-22, dated November 25, 2002 (Agencywide Documents Access and
Management System (ADAMS) Accession No. ML023160044). In RIS 2002-22, the NRC staff
endorsed Guideline on Licensing Digital Upgrades: EPRI TR-102348, Revision 1, NEI 01-01: A
Revision of EPRI TR-102348 to Reflect Changes to the 10 CFR 50.59 Rule, (Nuclear Energy
Institute (NEI) hereinafter NEI 01-01) (ADAMS Accession No. ML020860169). NEI 01-01
provides guidance for designing, licensing, and implementing digital upgrades and
replacements to instrumentation and control (I&C) systems (hereinafter digital I&C) in a
consistent and comprehensive manner. The purpose of this RIS Supplement is to clarify RIS 2002-22, which remains in effect. The NRC continues to endorse NEI 01-01 as stated in RIS 2002-22, as clarified by this RIS Supplement. This RIS Supplement clarifies the guidance for
preparing and documenting qualitative assessments that licensees can use to develop written
evaluations to address the criteria in 10 CFR 50.59, Changes, tests and experiments. This
RIS Supplement is intended to reduce regulatory uncertainty for licensees applying the
10 CFR 50.59 process and making digital I&C modifications without prior NRC approval. This
RIS Supplement is not directed toward digital I&C upgrades and replacements of reactor
This page contains no comments
RIS 2002-22 Supplement 1
Page 3 of 8
protection systems and engineered safety features actuation systems (ESFAS), since
application of the guidance in this RIS Supplement to such changes would likely involve
additional considerations. This RIS Supplement is also not intended to provide new design
process guidance for addressing software common cause failure (software CCF) or methods for
addressing common cause failure of the reactor protection systems and engineered safety 1
features actuation systems. 2Specific guidance for addressing potential common cause failure of
digital I&C equipment when making design changes to structures, systems, and components
(SSCs) is contained in other NRC guidance documents and NRC-endorsed industry guidance
documents.
This RIS Supplement requires no action or written response on the part of an addressee.
BACKGROUND INFORMATION
By letter dated March 15, 2002, NEI submitted EPRI TR-102348, Revision 1 (NEI 01-01) for
NRC staff review. NEI 01-01 replaced the original version of EPRI TR-102348, dated
December 1993, which the NRC endorsed in Generic Letter 1995-02, Use of NUMARC/EPRI
Report TR-102348, Guideline on Licensing Digital Upgrades, in Determining the Acceptability
of Performing Analog-to-Digital Replacements Under 10 CFR 50.59, dated April 26, 1995
(ADAMS Accession No. ML031070081). In 2002, the NRC staff issued RIS 2002-22 to notify
addressees that the NRC staff had reviewed NEI 01-01 and was endorsing the report for use as
guidance in designing and implementing digital upgrades to nuclear power plant instrumentation
and control systems.
Following the NRC staffs 2002 endorsement of NEI 01-01, holders of construction permits and
operating licenses have used this guidance in support of digital design modifications in
conjunction with Regulatory Guide 1.187, Guidance for Implementation of 10 CFR 50.59,
Changes, Tests, and Experiments, dated November 2000 (ADAMS Accession
No. ML003759710), which endorsed NEI 96-07, Guidelines for 10 CFR 50.59 Implementation,
Revision 1, dated November 2000 (ADAMS Accession No. ML003771157).
The regulations in 10 CFR 50.59(d)(1) state: The licensee shall maintain records of changes in
the facility, of changes in procedures, and of tests and experiments made pursuant to paragraph
(c) of this section. These records must include a written evaluation which provides the bases for
the determination that the change, test, or experiment does not require a license amendment
pursuant to paragraph (c)(2) of this section.
The NRC inspections of documentation for digital I&C plant modifications prepared by some
licensees using the guidance in NEI 01-01 uncovered inconsistencies in the performance and
documentation of engineering evaluations of digital I&C modifications and inadequacies in the
documentation of the technical bases supporting responses to the 10 CFR 50.59(c)(2)
evaluation criteria. This RIS Supplement clarifies the RIS 2002-22 endorsement of the
NEI 01-01 guidance by providing additional guidance for developing and documenting
qualitative assessments adequate for use as bases for licensee evaluations addressing the
criteria of 10 CFR 50.59(c)(2). In particular, this RIS Supplement clarifies the guidance for
documenting licensee determinations that a digital modification will exhibit a sufficiently low"1
1
NEI 01-01, Page 4-20, defines sufficiently low3to mean much lower than the likelihood of failures that are
considered in the UFSAR (e.g., single failures) and comparable to other common cause failures that are not
considered in the UFSAR (e.g., 4design flaws, maintenance errors, calibration errors).
Page: 3
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 12:06:34 PM
In the sentence directly before this one, the limitation regarding not providing new guidance is restricted to RPS and ESF. But in this sentence that limitation is
extended to all SSCs. This contradicts subsequent sections of this RIS which provide new CCF guidance for other non-RPS/ESF SSCs.
Number: 2 Author: KenSc Subject: Highlight Date: 01/23/2018 10:39:52 PM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 9:03:14 AM
ATWS is considered in most FSARs, maybe all. So CCF due to a design flaw is considered in most, maybe all, FSARs.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 9:02:09 AM
RIS 2002-22 Supplement 1
Page 4 of 8
likelihood of failure. This determination then serves as a technical basis supporting the
conclusions that are reached when a licensee evaluates a proposed design against the criteria
of 10 CFR 50.59(c)(2) to determine whether prior NRC staff approval is needed before the
proposed design can be implemented.
In response to staff requirements memorandum (SRM)-SECY-16-0070 Integrated Strategy to
Modernize the Nuclear Regulatory Commissions Digital Instrumentation and Control Regulatory
Infrastructure (ADAMS Accession No. ML16299A157), NRC staff has engaged NEI and
industry representatives to improve the guidance for applying 10 CFR 50.59 to digital
I&C-related design modifications as part of a broader effort to modernize I&C regulatory
infrastructure. The NRC staffs plan for accomplishing this update is outlined in the NRCs
Integrated Action Plan to Modernize Digital Instrumentation and Controls Regulatory
Infrastructure (ADAMS Accession No. ML17102B307). This plan, which is updated
semiannually, provides a comprehensive view of NRC activities associated with improvements
to the digital I&C regulatory infrastructure, including a planned schedule for completion of key
regulatory infrastructure documents. In Section 5 of the NRC staffs Integrated Action Plan
(IAP), the NRC staff outlines how it plans to clarify its previous endorsement of the NEI 01-01
guidance by providing additional guidance for developing and documenting acceptable
qualitative assessments in support of the performance of 10 CFR 50.59 evaluations of proposed
digital I&C modifications. Making available the guidance in this RIS Supplement is described as
a near-term action in the IAP to provide specific guidance for documenting qualitative
assessments that a proposed digital I&C modification will exhibit a sufficiently low likelihood of
failure. The use of appropriately-prepared qualitative assessments is one acceptable way to
document the evaluation of whether a design change can result in more than a minimal increase
in the frequency of an accident or the likelihood of occurrence of a malfunction of an SSC
important to safety previously evaluated in the final safety analysis report. The use of
appropriately-prepared qualitative assessments is also one acceptable way to document the
evaluation of whether a design change can result in accidents of a different type or malfunctions
of SSCs with different results than previously evaluated. The assessment of such malfunctions
includes the need to address the potential for common cause failures, (which is within the scope 1
2
of the IAP), when proposing changes to SSCs that are of lesser importance to safety than that
of reactor protection systems and Engineered Safety Features Actuation Systems. The IAP
also describes a longer-term plan for incorporating the guidance of this RIS Supplement into
durable guidance documents that are now under development. The NRC staff will continue to
engage with stakeholders on the development of new guidance to address the identified issues
and needs.
Applicability to Non-Power Reactor Licensees
The examples and specific discussion in this RIS Supplement and other guidance referenced by
this RIS Supplement (i.e., NEI 01-01 and original RIS 2002-22) primarily focus on power
reactors. Nonetheless, licensees of non-power production or utilization facilities (NPUFs) may
also use the guidance in RIS 2002-22 and apply the guidance in this RIS Supplement to
develop written evaluations to address the criteria in 10 CFR 50.59(c)(2). In particular, NPUF
licensees may use the guidance to prepare qualitative assessments that consider design
attributes, quality measures, and applicable operating experience to evaluate proposed digital
I&C changes to their facilities as described in Sections 4, 5, and Appendix A of NEI 01-01.
However, certain aspects of the guidance that discuss the relationship of regulatory
requirements to 10 CFR 50.59 may not be fully applicable to NPUFs (e.g., 10 CFR Part 50,
Appendix A and B are not applicable to NPUFs).
Page: 4
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 12:07:45 PM
The first paragraph on Page 3 says this RIS is not applicable to RPS/ESF. But this paragraph implies it would not be applicable to any equipment of equal or
greater importance to RPS/ESF. Importance can be determined by the PRA. Equipment of equal or greater importance would typically include load sequencers,
and accident monitoring instrumentation and controls for manual actions credited in the TAA. So the original statement that says this RIS is not applicable to
RPS and ESFAS should be expanded to encompass these additional systems.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 9:06:19 AM
RIS 2002-22 Supplement 1
Page 5 of 8
SUMMARY OF ISSUE
Section 3.2.3 of the NRC staffs evaluation of NEI 01-01 (Attachment 1 to RIS 2002-22) states:
The staffs position regarding documentation of 10 CFR 50.59 evaluations is
accurately reflected in the second paragraph in Appendix A to the submittal,
which states: The 10 CFR 50.59 questions should be answered in sufficient
detail, either by reference to a source document or by direct statements, that an
independent third party can verify the judgements. The staff has reviewed
Appendix A, Supplemental Questions for Addressing 10 CFR 50.59 Evaluation
Criteria, and Appendix B, Outline for Documenting 10 CFR 50.59 Screens and
Evaluations, and, based on the foregoing, concludes that the guidance therein is
acceptable for licensees to use in performing and documenting their
10 CFR 50.59 evaluations.
This RIS Supplement emphasizes the staffs paragraph above.
Specifically, this RIS Supplement provides additional guidance on what is needed to ensure that
licensees adequately perform and document qualitative assessments used to provide an
adequate basis for a determination that a digital modification will exhibit a sufficiently low
likelihood of failure, which is a key element in 10 CFR 50.59 evaluations of whether a change
requires prior NRC approval. Digital hardware being introduced in a nuclear facility modification
is typically expected to be more dependable than the equipment it is replacing. However, there
are no established consensus methods for accurately quantifying the reliability of software. NEI 96-07 Revision 1, Section 4.2.1 states: If a change has both positive and adverse effects, the
change should be screened in. The 10 CFR 50.59 evaluation should focus on the adverse
effects.
In general, digital I&C modifications may include a potential for an increase in the likelihood of
equipment failures occurring within modified SSCs,1including common cause failures, that can
2
lead to the failure to perform a design function. In particular, digital I&C modifications that
introduce or modify identical software within independent trains, divisions, or channels within a
system, and those that introduce new shared 3 resources, hardware, or software among multiple
4
non-safety related control functions (e.g., controllers, communication networks or video display
units), may include such a potential. The qualitative assessment can be used to support a
conclusion that there is not more than a minimal increase in the frequency of occurrence of
accidents or in the likelihood of occurrence of malfunctions [10 CFR 50.59(c)(2)(i) and (ii)]. The
qualitative assessment can also be used to support a conclusion that the proposed modification
does not create the possibility of an accident of a different type or malfunction with a different
result than previously evaluated in the UFSAR [10 CFR 50.59(c)(2)(v) and (vi)]. NEI 01-01
describes that for 10 CFR 50.59 evaluations, the likelihood of failure is normally demonstrated
qualitatively (i.e., through reference to reasonable engineering practices and engineering
judgment), particularly for systems or components that rely on software, because there are no
well-established, accepted quantitative methods to demonstrate the likelihood of failure from
sources such as software design errors.
For digital I&C modifications, an adequate basis for a determination that a change involves a
sufficiently low likelihood of failure may be derived from a qualitative assessment of factors
involving system design features, the quality of the design processes employed, and an
Page: 5
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 12:08:20 PM
We typically view "failure to perform" as "no function at all". But equally important is performing a design function erroneously. This is too often forgotten by
digital designers. It should be clearly stated.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 9:15:39 AM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 9:17:29 AM
A failure of shared resources among safety control functions can also introduce unanalyzed malfunctions.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 9:13:15 AM
RIS 2002-22 Supplement 1
Page 6 of 8
evaluation of relevant operating experience 2 of the software and hardware used (i.e., product 1
maturity and in-service experience). A licensee may use a qualitative assessment to record the
factors and rationale for concluding that there is an adequate basis for determining that a digital
I&C modification will exhibit a sufficiently low likelihood of failure. In doing so, a licensee may
consider the aggregate of these factors. The attachment to this RIS Supplement, Qualitative
Assessment Framework, provides guidance for performing and documenting this qualitative
assessment.
This RIS Supplement does not change the NRC staff positions in RIS 2002-22 endorsing NEI 01-01. Specifically, RIS 2002-22 states:
Because there is currently no acceptable way to quantitatively establish the
reliability of digital systems, [NEI 01-01] gives considerable attention to the
qualitative assessment of the dependability of and risk associated with I&C
systems. The guidance in the submittal [NEI 01-01] identifies qualitative
approaches within existing endorsed guidance with regard to software issues,
including software-related common-cause failure issues, without proposing
alternatives to the existing guidance. Therefore, the guidance in [NEI 01-01]
does not propose to alter, or offer less conservative guidance for, the existing
licensing process for license amendment requests to implement digital
replacements.
There is no change in NRC staff position regarding its endorsement of the guidance in NEI 01-01 for addressing digital I&C modifications under the 10 CFR 50.59 process. However, this
RIS Supplement clarifies the staffs previous endorsement in RIS 2002-22 of the guidance in
NEI 01-01 pertaining to the performance and documentation of adequate technical evaluations
and adequately documented qualitative assessments to meet the requirements of
10 CFR 50.59. Specifically, the guidance in this RIS Supplement clarifies the NRC staffs
endorsement of the guidance pertaining to Sections 4, 5, and Appendices A and B of NEI 01-01.
The attachment to this RIS Supplement provides a framework for preparing and documenting
qualitative assessments considered acceptable to serve as a technical basis supporting the
responses to key 10 CFR 50.59(c)(2) evaluations.
Clarification of Guidance for Addressing Digital I&C Changes under 10 CFR 50.59
NEI 01-01 supports the use of qualitative assessments, engineering judgment, and industry
precedent when addressing whether frequency of occurrence of an accident or the likelihood of
occurrence of a malfunction of an SSC important to safety would be more than minimally
increased (evaluation criteria 10 CFR 50.59(c)(2)(i) and (ii)). NEI 01-01 also supports the use of
such qualitative assessments when addressing whether a possibility for an accident of a
different type or a malfunction of an SSC important to safety with a different result than any
previously evaluated in the UFSAR would be created (evaluation criteria 10 CFR 50.59(c)(2)(v)
and (vi)). This RIS Supplement describes the importance of documenting how the
implementation of key design attributes, quality of the design processes, and an evaluation of
relevant operating experience is being credited as the basis for making engineering judgments
that the likelihood of failures of SSCs that are introduced by a proposed digital modification is
low. Such qualitative assessments are used to provide an adequate basis for determining that
the likelihood of failure for proposed modifications is low. The guidance in NEI 01-01 provides a
road map to relevant standards and other sources of detailed guidance. The attachment to
this RIS Supplement clarifies how the aggregate of the proposed digital I&C system design
Page: 6
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 10:01:37 AM
SECY 93-087 and BTP 7-19 constitute current NRC policy on digital CCF. The current policy does not allow a conclusion that the likelihood of a CCF is
sufficiently low to require no further consideration based on these qualitative factors alone. The current policy is clear that these qualitative factors facilitate a
conclusion that the CCF is beyond design basis, but not that it requires no further consideration. Another way of looking at this is that the current policy is that
qualitative factors do not allow a conclusion that the likelihood is comparable to other sources of CCF that are not considered in the FSAR. How can a RIS be
used to change previous NRC policy.
I have heard some people say that the current NRC policy is only applicable to new plants. If that is true, which I don't believe it is, then how can the NRC create
a new policy for operating plants that is different than for new plants. This directly contradicts the commissioners direction in (SRM)-SECY-16-0070 that the
guidance for new plants and operating plants should be the same.
Number: 2 Author: KenSc Subject: Sticky Note Date: 01/24/2018 12:10:01 PM
Dave, You told me that "sufficiently low" could only be reached with 4 factors, the fourth being an evaluation of the "what if" malfunction results. This
contradicts your explanation of this RIS. If your interpretation is confused, the industry's interpretation is also going to be confused.
RIS 2002-22 Supplement 1
Page 7 of 8
features, quality of the design processes, and equipment and software operating experience
that are applied to the proposed design using such standards and guidance can be documented
by licensees when preparing qualitative assessments to support conclusions within a
10 CFR 50.59(c)(2) evaluation that a license amendment is not needed.
In addition, this RIS Supplement clarifies the applicability of some aspects of the NRC policy
described in Item II.Q of SRM/SECY 93-087, Policy, Technical, and Licensing Issues
Pertaining to Evolutionary and Advanced Light Water Reactor Designs, (ADAMS
No. ML003708056), in regard to the application of 10 CFR 50.59(c)(2) criteria for digital I&C
modifications.
To assist licensees in documenting adequate qualitative assessments for evaluating the
10 CFR 50.59(c)(2) criteria, the attachment to this RIS Supplement also clarifies the NRC staff
position on the content, rationale, and evaluation factors that can be addressed and evaluated
within licensee-developed qualitative assessments. Specifically, the attachment describes how
such qualitative assessments can be documented to clearly demonstrate an adequate technical
basis for the conclusion that the change does not require prior NRC staff approval.
BACKFITTING AND ISSUE FINALITY DISCUSSION
This RIS Supplement clarifies but does not supersede RIS 2002-22, and includes additional
guidance regarding how to perform and document qualitative assessments for digital I&C
changes under 10 CFR 50.59.
The NRC does not intend or approve any imposition of the guidance in this RIS Supplement,
and this RIS Supplement does not contain new or changed requirements or staff positions.
Therefore, this RIS Supplement does not represent backfitting as defined in
10 CFR 50.109(a)(1), nor is it otherwise inconsistent with any issue finality provision in
10 CFR Part 52. Consequently, the NRC staff did not perform a backfit analysis for this RIS
Supplement or further address the issue finality criteria in 10 CFR Part 52.
FEDERAL REGISTER NOTIFICATION
The NRC published a notice of opportunity for public comment on this RIS in the Federal
Register on July 3, 2017 (82 FR 30913). The NRC received comments from 13 commenters.
The NRC considered all comments, some of which resulted in changes to the RIS. The
evaluation of these comments and the resulting changes to the RIS are discussed in a
publicly-available memorandum that is available in ADAMS under Accession
No. ML17296A852.
CONGRESSIONAL REVIEW ACT
This RIS is a rule as defined in the Congressional Review Act (5 U.S.C. §§ 801-808). However,
the Office of Management and Budget has not found it to be a major rule as defined in the
Congressional Review Act.
PAPERWORK REDUCTION ACT STATEMENT
This RIS provides guidance for implementing mandatory information collections covered by
10 CFR Part 50 that are subject to the Paperwork Reduction Act of 1995 (44 U.S.C. 3501 et.
This page contains no comments
RIS 2002-22 Supplement 1
Page 8 of 8
seq.). This information collection was approved by the Office of Management and Budget
(OMB) under control number 3150-0011. Send comments regarding this information collection
to the Information Services Branch, U.S. Nuclear Regulatory Commission, Washington, DC
20555-0001, or by e-mail to Infocollects.Resource@nrc.gov, and to the Desk Officer, Office of
Information and Regulatory Affairs, NEOB-10202, (3150-0011) Office of Management and
Budget, Washington, DC 20503.
Public Protection Notification
The NRC may not conduct or sponsor, and a person is not required to respond to, a request for
information or an information collection requirement unless the requesting document displays a
currently valid OMB control number.
CONTACT
Please direct any questions about this matter to the technical contact(s) or the Lead Project
Manager listed below.
Timothy J. McGinty, Director Christopher G. Miller, Director
Division of Construction Inspection Division of Inspection and Regional Support
and Operation Programs Office of Nuclear Reactor Regulation
Office of New Reactors
Technical Contacts: David Rahn, NRR Wendell Morton, NRO
301-415-1315 301-415-1658
e-mail: David.Rahn@nrc.gov e-mail: Wendell.Morton@nrc.gov
Norbert Carte, NRR David Beaulieu, NRR
301-415-5890 301-415-3243
e-mail: Norbert.Carte@nrc.gov e-mail: David.Beaulieu@nrc.gov
301-415-3724
email: Duane.Hardesty@nrc.gov (Specifically for non-power reactors)
Project Manager Contact: Tekia Govan, NRR
301-415-6197
e-mail: Tekia.Govan@nrc.gov
Note: NRC generic communications may be found on the NRC public Web site,
http://www.nrc.gov, under NRC Library/Document Collections.
Attachment: Qualitative Assessment Framework
This page contains no comments
Qualitative Assessment Framework
1. Purpose
Regulatory Issue Summary (RIS) 2002-22 provided the NRC staffs endorsement of Nuclear
Energy Institute (NEI) Guidance document NEI 01-01, Guideline on Licensing Digital Upgrades:
EPRI TR-102348, Revision 1, NEI 01-01: A Revision of EPRI TR-102348 To Reflect Changes
to the 10 CFR 50.59 Rule. NEI 01-01 provides guidance for implementing and licensing digital
upgrades, in a consistent, comprehensive, and predictable manner, as well as guidance in
performing qualitative assessments of the dependability of digital instrumentation and control
(I&C) systems.
The purpose of this attachment is to provide supplemental clarifying guidance to licensees to
ensure that, if qualitative assessments are used, they are described and documented
consistently, through an evaluation of appropriate qualitative evidence available. Following the
guidance in RIS 2002-22 and NEI 01-01, as clarified by the guidance in this RIS Supplement,
will help licensees document qualitative assessments in sufficient detail that an independent
third party can verify the judgements, as stated in NEI 01-01. This RIS supplement guidance
1
presumes that the qualitative assessment will be performed after all technical work (e.g. failure
modes and effects analysis, 2and revised design documentation) is complete and that the
proposed modification has already been determined to have a potential adverse effect (i.e. it
has been screened in as described in NEI 96-07).
If the qualitative assessment determines that a potential failure (e.g., software common cause
failure [CCF]) has a sufficiently low likelihood, then the effects of this failure do not need to be
considered in the 10 CFR 50.59 evaluation. In particular, this qualitative assessment provides
a means of addressing software CCF.
This RIS Supplement includes guidance that licensees may use to develop adequate bases for
3
determining that (1) a digital modification will exhibit a sufficiently low likelihood of failure, or, (2)
4
if a digital I&C modification failure can be postulated, the effects of that failure will not result in a
new type of accident or a malfunction of structures, systems, and components (SSCs) with
different result than previously evaluated in the updated final safety analysis report (UFSAR).
The determination of whether a modification will exhibit a sufficiently low likelihood of failure is a
key element in 10 CFR 50.59. Licensees need to understand the possible effects of failures of
a digital I&C modification to ensure that such effects will not create a possibility for an accident
of a different type or a malfunction of an SSC with a different result than previously evaluated in
the updated final safety analysis report.
The sections that follow provides one approach, acceptable to the NRC staff, for describing the
scope, form, and content of a qualitative assessment.
2. Regulatory ClarificationApplication of Qualitative Assessments to Title 10 of the
Code of Federal Regulations, Section 50.59
After determining that an activity is safe and effective through appropriate engineering and
technical evaluations, the 10 CFR 50.59 process is applied. 10 CFR 50.59 provides a threshold
for regulatory review, not the final determination of safety, for the proposed activities.
10 CFR 50.59 establishes the conditions under which licensees may make changes to the
facility or procedures and conduct tests or experiments without prior NRC approval.
Attachment
Page: 9
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 9:38:55 AM
Licensees will often conduct these evaluations prior to investing in revised design/analysis documentation.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 9:37:49 AM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:00:39 PM
Dave, This is an OR statement. Therefore, this does not say that a failure must be postulated, as you told me.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 9:40:15 AM
RIS 2002-22 Supplement 1, Attachment
Page 2 of 27
Evaluations must address all elements of proposed changes. Elements of a change can have
positive effects on SSC failure likelihood while other elements of the change can have adverse
effects. As derived from the guidance in NEI 96-07, positive and negative elements can be
considered together if they are interdependent. This means that if elements are not
interdependent, they must be evaluated separately.
When discussing 10 CFR 50.59 criteria, the words met or satisfy mean that a yes or
affirmative answer has been achieved and an amendment is required.
2.1 Likelihood Justifications
Qualitative assessments are needed to document the bases to support a conclusion that a
proposed digital I&C modification has a sufficiently low2 likelihood of failure, consistent with the
UFSAR analysis assumptions. This conclusion is used in the Title 10 of the Code of Federal
Regulations (10 CFR) 50.59, Changes tests and experiments, written evaluation to determine
whether prior NRC approval is required.
The staff notes that when performing digital modifications under 10 CFR 50.59, some licensees
have experienced challenges in preparing qualitative assessments needed to support
conclusions for responding to the criteria in 10 CFR 50.59(c)(2)(i), (ii), (v), and (vi).
The ability to provide an adequate basis for a determination that the digital modification will
exhibit a sufficiently low likelihood of failure is a key element of 10 CFR 50.59 evaluations to
determine whether the change requires prior NRC approval. To support the 10 CFR 50.59
process, methods are needed to evaluate the digital system likelihood of failure (e.g., based on
the dependability of the modified digital components) that could result in a malfunction of an
SSC important to safety. For digital equipment, however, there may not be well-established,
accepted quantitative methods that can be used to estimate their dependability or likelihood of
failure. Therefore, for digital SSCs, 1an adequate basis for determining sufficiently low likelihood
2
of failure may be derived from a qualitative assessment of factors involving the inclusion of key
system design features,3 the quality of the design process used, and an evaluation of relevant
operating experience (i.e., product maturity and in-service experience). The qualitative
assessment reaches a conclusion through engineering judgment that there is an adequate basis
for concluding that the digital modification will exhibit a sufficiently low likelihood of failure by
considering the aggregate of these factors.
Likelihood Thresholds for 10 CFR 50.59(c)(2)(i), (ii), (v), and (vi)
A key element of 10 CFR 50.59 evaluations is demonstrating that the modification will exhibit a
sufficiently low likelihood of failure. For digital modifications, particularly those that introduce
software, there may be the potential increase in likelihood of failure, including a single failure.
2 NEI 01-01, Page 4-20, defines sufficiently low to mean much lower than the likelihood of failures that are
considered in the UFSAR (e.g., single failures) and comparable to other common cause failures that are not
considered in the UFSAR (e.g., design flaws, maintenance errors, calibration errors).
3 System design features are used to address anticipatable and quantifiable threats (e.g., the qualification of a piece
of equipment to meet the plant seismic criteria ensures that the likelihood of failure from seismic event is sufficiently
low). Defense-in-depth and diversity are system design features to address anticipatable but non-quantifiable threats
(e.g., software CCF). These deterministic measures must be implemented under the appropriate quality processes.
Page: 10
Number: 1 Author: KenSc Subject: Highlight Date: 01/23/2018 10:53:30 PM
Number: 2 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:04:51 PM
Dave, you told me that to reach a conclusion of "sufficiently low" the licensee must postulate a CCF and then demonstrate acceptable results. What you told me
is not reflected here. This postulate may be your interpretation, but others will interpret this differently. This RIS is supposed to resolve the current industry
confusion, not create more confusion.
RIS 2002-22 Supplement 1, Attachment
Page 3 of 27
1
2
For redundant SSCs, this potential increase in the likelihood of failure creates a similar increase
in the likelihood of a common cause failure.
The sufficiently low threshold discussions have been developed using criteria from NEI 96-07,
Revision 1, and NEI 01-01. They are intended to clarify the existing 10 CFR 50.59 guidance
and should not be interpreted as a new or modified NRC position.
Qualitative Assessment
The determination that a digital I&C modification will exhibit a sufficiently low likelihood of failure
can be derived from a qualitative assessment of factors involving system design attributes, the
quality of the design processes employed, and the operating experience of the software and
hardware used (i.e., product maturity and in-service experience). The qualitative assessment
documents the factors, rationale, and reasoning for determining that the digital I&C modification
exhibits a sufficiently low likelihood of failure by considering the aggregate of these factors.
The determination of likelihood of failure may consider the aggregate of all the factors described
above. Some of these factors may compensate for weaknesses in other areas. For example,
for a digital device that is simple and highly testable, thorough testing may provide additional
assurance of a low likelihood of failure that helps compensate for a lack of operating
experience.
Qualitative Assessment Outcome
3
There are two possible outcomes of the qualitative assessment: (1) failure likelihood is
sufficiently low, and (2) failure likelihood is not sufficiently low. NEI 01-01, Section 44.3.6,
5
states, sufficiently low means much lower than the likelihood of failures that are considered in
6
the UFSAR (e.g., single failures) and comparable to other common cause failures that are not
considered in the UFSAR (e.g., design flaws, maintenance error, calibration errors). [Note: 7
This sufficiently low threshold is not interchangeable with that for distinguishing between
events that are credible or not credible. 8The threshold for determining whether an event is
credible or not is whether it is as likely as (i.e., not much lower than) malfunctions already
assumed in the UFSAR.]
Criteria
A qualitative assessment outcome of sufficiently low supports a no or negative answer for
10 CFR 50.59(c)(2)(i), (ii), (v), and (vi) as follows:
Does the activity result in more than a minimal increase in the frequency of occurrence of an
accident previously evaluated in the UFSAR?
Sufficiently low threshold - The frequency of occurrence of an accident is directly
related to likelihood of failure of equipment that initiates the accident (e.g., an increase in
the likelihood of a steam generator tube failure has a corresponding increase in the
frequency of a steam generator tube rupture accident). Thus, an increase in likelihood
of failure of the modified equipment results in an increase in the frequency of the
accident. Therefore, if the qualitative assessment outcome is sufficiently low, then
Page: 11
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:05:43 PM
This is technically incorrect. Single failures, by definition, are random non-systematic failures. An increase in the likelihood of a single failure, does lower system
availability, but it does not increase the likelihood of a CCF.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 9:44:37 AM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 10:18:38 AM
Should be NEI 01-01 Section 4.4.6.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 10:18:44 AM
Number: 5 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:11:14 PM
Note that this is an AND condition. Therefore, to achieve "sufficiently low" the failure likelihood must be comparable to other failures not considered at all in
the FSAR. If the failure likelihood is only comparable to failures considered as beyond design basis events, then the failure must also be considered a beyond
design basis event. The current NRC policy is that only deterministic attributes of 100% testing and internal diversity facilitate a conclusion that the failure
likelihood is comparable to to other failures not considered at all in the FSAR, and therefore requires no further consideration.
Number: 6 Author: KenSc Subject: Highlight Date: 01/24/2018 1:06:26 PM
Number: 7 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:16:44 PM
This note says that if a failure is "not credible" it may still require further consideration. This is sure to confuse licensees, because we have never analyzed non-
credible events. I don't know the basis of this sentence but it is wrong. An event that is not as unlikely as events not considered in the FSAR, as either design
basis or beyond design basis, are credible. This is why we analyze both design basis and beyond design basis events (i.e., because they are credible, not because
they are not credible).
Number: 8 Author: KenSc Subject: Highlight Date: 01/24/2018 10:03:46 AM
RIS 2002-22 Supplement 1, Attachment
Page 4 of 27
there is a no more than a minimal increase in the frequency of occurrence of an accident
previously evaluated in the UFSAR.
Does the activity result in more than a minimal increase in the likelihood of occurrence of a
malfunction of a structure, system, or component (SSC) important to safety4 previously
evaluated in the UFSAR?
Sufficiently low threshold - The likelihood of occurrence of a malfunction of an SSC
important to safety is directly related to likelihood of failure of equipment that causes a
failure of SSCs to perform their intended design functions (e.g., an increase in the
likelihood of failure of an auxiliary feedwater (AFW) pump has a corresponding increase
in the likelihood of occurrence of a malfunction of SSCs - the AFW pump and AFW
system). Thus, the likelihood of failure of modified equipment that causes the failure of
SSCs to perform their intended design functions is directly related to the likelihood of
occurrence of a malfunction of an SSC important to safety. Therefore, if the qualitative
assessment outcome is sufficiently low, then the activity does not result in more than a
minimal increase in the likelihood of occurrence of a malfunction of an SSC important to
safety previously evaluated in the UFSAR.
Does the activity create a possibility for an accident of a different type than any previously
evaluated in the UFSAR?
Sufficiently low threshold - NEI 96-07, Revision 1, Section 4.3.5, states, Accidents of
a different type are limited to those as likely to happen as those in the UFSAR.
Accidents of a different type are caused by failures of equipment that initiate an1accident
2
of a different type. Only failures of equipment that are as likely to happen as those in 3
4
the UFSAR can create a possibility of an accident of a different type. If the qualitative
assessment outcome is sufficiently low, then there are no failures introduced by the
activity that are as likely to happen as those in the UFSAR that can initiate an accident of
a different type. Therefore, the activity does not create a possibility for an accident of a
different type than any previously evaluated in the UFSAR.
Does the activity create a possibility for a malfunction of an SSC important to safety with a
different result than any previously evaluated in the UFSAR?
Sufficiently low threshold - NEI 96-07, Section 4.3.6, states, Malfunctions with a
different result are limited to those as likely to happen as those in the UFSAR. A
malfunction of an SSC important to safety is an equipment failure that causes the failure 5
6
of SSCs to perform their intended design functions. Only failures of equipment that are
as likely to happen as those in the UFSAR can create a possibility of a malfunction
4 NEI 96-07, Revision 1, Section 3.9, states, Malfunction of SSCs important to safety means the failure of SSCs to
perform their intended design functions described in the UFSAR (whether or not classified as safety-related in
accordance with 10 CFR 50, Appendix B).
Page: 12
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:18:10 PM
This contradicts previous statements in this RIS and in NEI 01-01 which state to require no further consideration in 50.59, the failure likelihood must be
"comparable to other common cause failures that are not considered in the UFSAR". This is quite different than "as likely as those failures that are
considered".
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 10:12:30 AM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:20:41 PM
Yes, but the sentence above says that even if you have not reached the "sufficiently low" threshold, there are no new accidents introduced unless the failure is
"as likely" as other failures assumed in the FSAR. This is different than your definition of "sufficiently low" and therefore quite confusing. "Sufficiently low"
should be removed from this paragraph, because "sufficiently low" is not required by the statements of consideration for this question, as it is for Question 6.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 10:05:54 AM
Number: 5 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:29:07 PM
This contradicts previous statements in this RIS and in NEI 01-01 which state to require no further consideration in 50.59, the failure likelihood must be
"comparable to other common cause failures that are not considered in the UFSAR". Since NEI 01-01 is inconsistent in this regard, this RIS should
resolve the inconsistency by making it perfectly clear that unless the failure likelihood is "sufficiently low" (i.e., comparable to other malfunctions
not considered in the FSAR) it does require further consideration. It should be clear that this threshold is different than the unlikelihood threshold
in Question 5. A simple chart would help that very simply and clearly shows the different likelihood levels, with "failures in the FSAR" having
higher likelihood than failures "not in the FSAR".
Number: 6 Author: KenSc Subject: Highlight Date: 01/23/2018 10:57:32 PM
RIS 2002-22 Supplement 1, Attachment
Page 5 of 27
with a different result. If the qualitative assessment outcome is sufficiently low, then
there are no failures introduced by the activity that are as likely to happen as those in the
UFSAR. Therefore, the activity does not create a possibility for a malfunction of an SSC
important to safety with a different result than any previously evaluated in the UFSAR.
2.2 Additional Considerations for 10 CFR 50.59 evaluation of criterion (c)(2)(vi)
The 10 CFR 50.59 evaluation of criterion (c)(2)(vi) can be viewed as a five-step process that
stems from NEI 96-07, Revision 1, Section 4.3.6, which states: The possible malfunctions with 1
2
a different result are limited to those that are as likely to happen as those described in the
UFSAR. This section provides excerpts from NEI 96-07, Revision 1, and NEI 01-01 and
groups them into five steps to more clearly describe the considerations for addressing
10 CFR 50.59 criterion (c)(2)(vi). The section should not be interpreted as creating new or
revised NRC positions:
Step 1: Develop a list of ways (i.e., failure modes of SSCs important 3 to safety that are affected
4
by the proposed modification) in which SSCs can fail to perform their intended design functions.
intended design functions described in the UFSAR (whether or not classified as
safety-related in accordance with 10 CFR Part 50, Appendix B.) [NEI 96-07, Rev. 1,
Section 3.9, Definition of Malfunction of SSCs, page 18.]
Step 2: Perform a qualitative assessment of the likelihood of occurrence of each failure 5 mode to
6
determine which ones are as likely to happen as those described in the UFSAR.
- For digital systems, reasonable assurance of adequate quality and low likelihood of
failure is derived from a qualitative assessment of the design process and the system
design features. [NEI 01-01, Section 5.3.1, page 5-14]
7
8
If the qualitative assessment outcome is not sufficiently low, then perform Steps 3, 4, and 5 to
evaluate the results of these failures against 10 CFR 50.59 criterion (c)(2)(vi).
Step 3: Determine the malfunction results.
- The key issue is the effect of failures of the digital device on the system in which it is
installed. [NEI 01-01, Section 4.4.6, page 4-19]
- Another way to determine the appropriate level of detail is to consider the level at which
design functions are described in the UFSAR. If the relevant design functions are
assigned at the system level, then it is appropriate to evaluate the effects of malfunctions
at this level. [NEI 01-01, Section 4.4.6, page 4-19]
- If failures of the digital device cause the system to malfunction (i.e.,
9 not perform its
design function), then the evaluation
11 needs to determine if 10
the result of the system
malfunction is 12 bounded by or different than those previously evaluated. [NEI 01-01,
Section 4.4.6, page 4-19]
Page: 13
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:32:10 PM
This statement in NEI 96-07 contradicts NEI 01-01 which says to require no further consideration the failure likelihood must be "comparable to other
common cause failures that are not considered in the UFSAR"; this is different than 'as likely as those that are considered'. Since these are
different likelihood thresholds, this RIS needs to resolve this inconsistency between NEI 96-07 and NEI 01-01.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 10:13:32 AM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:33:22 PM
Needs to also include ways in which SSCs can erroneously perform. Some may argue that "failure" encompasses "erroneous" but erroneous is too often
overlooked by digital designers.
Number: 4 Author: KenSc Subject: Highlight Date: 01/23/2018 10:58:55 PM
Number: 5 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:33:49 PM
This should say "which ones that are not as unlikely as failures not considered in the FSAR" or "which one whose likelihood is not comparable to other
common cause failures that are not considered in the UFSAR."
Number: 6 Author: KenSc Subject: Highlight Date: 01/24/2018 10:22:20 AM
Number: 7 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:36:31 PM
"as likely as those described in the FSAR" contradicts "comparable to other common cause failures that are not considered in the UFSAR", which is your
definition of "sufficiently low". These are two different thresholds. So it is not clear when Steps 3-5 are needed. This RIS is supposed to bring clarity to the 50.59
issue, not more ambiguity.
Dave, you told me that steps 3-5 are always needed to reach "sufficiently low"; here it says they are needed only when you have not reached "sufficiently low".
So I think you are also confused about what this RIS actually requires; I know I am certainly confused.
Number: 8 Author: KenSc Subject: Highlight Date: 01/23/2018 11:00:26 PM
Number: 9 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:37:33 PM
Clarify that "end result" means "plant level". This is another key ambiguity in NEI 96-07 and NEI 01-01, that has caused much industry confusion, that this RIS
needs to resolve.
Number: 10 Author: KenSc Subject: Highlight Date: 01/24/2018 10:28:29 AM
Number: 11 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:42:45 PM
"Bounded" is in NEI 96-07 and NEI 01-01, but it is never defined. This is a key area of industry confusion. This RIS is supposed to address key areas of industry
confusion, so it should define this term.
Number: 12 Author: KenSc Subject: Highlight Date: 01/24/2018 1:41:41 PM
RIS 2002-22 Supplement 1, Attachment
Page 6 of 27
- NEI 01-01, Section 5.2, page 5-10 states that, reanalysis of design basis events is 1
permitted using best estimate conditions and realistic assumptions 2Unless already
incorporated into the design and licensing basis, best-estimate methods cannot be
used for evaluating different results than those previously evaluated in the UFSAR. For
failures in which likelihood is not sufficiently low, the results of these failures are to be
analyzed using methods consistent with the plants design and licensing basis.
- An example of a change that would create the possibility for a malfunction with a
different result is a substantial modification or upgrade to control station alarms, controls,
or displays that are associated with SSCs important to safety that creates a new or
common cause failure that is not bounded by previous analyses or evaluations. [NEI
96-07, Section 4.3.1, page 55.]
- If a feedwater control system is being upgraded from an analog to a digital system, new
components may be added that could fail in 3ways other than the components in the
original design. Provided the 4end result of the component or subsystem failure is the
same as, or is bounded by, the results of malfunctions currently described in the UFSAR 5
6
(i.e., failure to maximum demand, failure to minimum demand, failure as-is, etc.), then
this upgrade would not create a malfunction with a different result. [NEI 96-07, Section
4.3.6, page 54; also see NEI 01-01, Section 4.4.6, page 4-19.]
Note that [for criterion7
(vi)] new types of malfunctions are not the issue. NEI 96-07,
Revision 1, states that a new failure mechanism is not a malfunction
8 with a different
result if 9the result or effect is the same as, 10
or is bounded by, that previously evaluated in
the UFSAR. [NEI 01-01, Section 4.4.6, page 4-19]
Step 4: Identify the associated malfunctions and results previously evaluated in the UFSAR.
- the evaluation needs to consider the level of detail that was previously evaluated in the
UFSAR (i.e., component versus division/train versus system level failures). [NEI 01-01,
Section 4.4.6, page 4-19]
- Another way to determine the appropriate level of detail is to consider the level at which
design functions are described in the UFSAR. If the relevant design functions are 11
12
assigned at the system level, then it is appropriate to evaluate the effects of 13
malfunctions
at this level. [NEI 01-01, Section 4.4.6, page 4-19]
14
Step 5: Compare the newly created results to the results of malfunctions previously evaluated
15
in the UFSAR. If the created results are not bounded by the previously evaluated results,
then an LAR is required.
17 16
- Once the malfunctions previously evaluated in the UFSAR and the results of these
18
malfunctions have been determined, then the types and results of failure modes that the
proposed activity could create are identified. Comparing the two lists can provide the
answer to the criterion question. [NEI 96-07, Rev. 1, Section 4.3.6, page 55]
- A new failure mechanism is not a19malfunction with a different result if the result or effect
is the same as, or is 20 bounded by, that previously evaluated in the UFSAR. [NEI 01-01,
Section 4.4.6, page 4-19]
Page: 14
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:38:25 PM
This is new NRC policy that clearly contradicts the quote in this paragraph from NEI 01-01, which is previously endorsed by NRC. It is not clarification of
previous policy. It also contradicts SECY 93-087 and BTP 7-19. A RIS cannot change previous NRC policy.
Regardless, "best estimate" methods are used in most, maybe all, FSARs for ATWS, SBO and fire. So they are used in the FSAR, therefore even with this new
policy, as worded here they can be used to evaluate CCFs when the CCF is considered beyond design basis (i.e., significantly less likely than other malfunctions
considered in design basis events).
Number: 2 Author: KenSc Subject: Highlight Date: 01/23/2018 11:02:45 PM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 10:33:15 AM
Clarify that "end result" means "plant level".
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 10:31:39 AM
Number: 5 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:39:54 PM
These are failure modes or component level effects. They are not the "end result". The ambiguity in this RIS is evidence that this is point of confusion, which this
RIS needs to resolve.
Number: 6 Author: KenSc Subject: Highlight Date: 01/24/2018 10:34:02 AM
Number: 7 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:40:37 PM
Clarify that "end result" means "plant level".
Number: 8 Author: KenSc Subject: Sticky Note Date: 01/24/2018 10:44:51 AM
What does it mean to be "bounded". This RIS needs to provide guidance, because this is a particular area for frequent industry inconsistency.
Number: 9 Author: KenSc Subject: Highlight Date: 01/24/2018 10:34:29 AM
Number: 10 Author: KenSc Subject: Highlight Date: 01/24/2018 10:44:57 AM
Number: 11 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:56:53 PM
This is not clear. All design functions are assigned at the system level. But the effects of system level failures can be assessed at the plant level. The plant level is
where "bounded" should be defined. Clarity is needed here because this is clearly an area of frequent industry inconsistency.
Number: 12 Author: KenSc Subject: Highlight Date: 01/24/2018 10:46:06 AM
Number: 13 Author: KenSc Subject: Highlight Date: 01/24/2018 1:56:32 PM
Number: 14 Author: KenSc Subject: Sticky Note Date: 01/24/2018 10:47:45 AM
define "bounded"
Number: 15 Author: KenSc Subject: Highlight Date: 01/24/2018 10:47:34 AM
Number: 16 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:48:27 PM
This paragraph uses "results" to refer to two different things. Therefore "results" has two different meanings. This RIS needs to clarify that the results of concern
for 50.59 are the plant level results. Then this RIS needs to define what it means to have "bounded" plant level results. Without these clarifications you are just
promulgating industry confusion, not resolving that confusion.
Number: 17 Author: KenSc Subject: Highlight Date: 01/24/2018 10:48:19 AM
Number: 18 Author: KenSc Subject: Highlight Date: 01/24/2018 10:48:24 AM
Number: 19 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:49:35 PM
"bounded" is used in three quotes on this page. But it is never defined here or in NEI 96-07 or NEI 01-01. A definition is clearly needed, because this is pivotal
concept for the correct 50.59 decision.
Number: 20 Author: KenSc Subject: Highlight Date: 01/24/2018 10:51:10 AM
RIS 2002-22 Supplement 1, Attachment
Page 7 of 27
3. Producing Qualitative Assessments that Support a Sufficiently Low Likelihood
Conclusion
The qualitative assessment framework described herein may be used to develop and document
the technical basis supporting a conclusion that a proposed digital modification satisfies each of
the likelihood thresholds outlined above. The resulting qualitative assessments may then be
used as part of the reasoning and rationale serving as the basis for a 10 CFR 50.59 evaluation.
The NRC staff has determined that proposed digital I&C modifications having all the
characteristics listed below are likely to result in qualitative assessment results that support a
determination that a license amendment is not required by 10 CFR 50.59:
[Note: The term design functions, as used in this RIS Supplement, conforms to the
definition of design functions in NEI 96-07, Revision 1.]
1. Digital I&C design-functions replacing I&C design-functions that:
a) Do not create a CCF vulnerability due to the integration of subsystems or
components from different systems that combine design functions that were not
previously combined within the same system, subsystem, or component being
replaced, and 1
b) Do not create a CCF vulnerability due to the incorporation of 2new shared resources
(such as power supplies, controllers, and human-machine interfaces) with other
design functions either explicitly (or implicitly) described in the final safety analysis
report as updated (UFSAR) as functioning independently from other plant system
functions, or modeled in the current design basis to be functioning independently
from other plant design functions, and
c) Do not affect reactor trip or engineered safety feature initiation/control logic design
functions.
Integration, as used in this RIS clarification refers to the process of combining software
components, hardware components, or both into an overall system, or the merger of the
design function of two or more systems or components into a functioning, unified system
or component. Integration also refers to the coupling of design functions (software/
hardware) via digital communications. Modifications can result in design functions of
different systems being integrated or combined either directly in the same digital device
or indirectly via shared resources, such as digital communications or networks, common
controllers, power supplies, or visual display units. Such integration could be
problematic because the safety analysis may have explicitly or implicitly modeled the
equipment performing the design functions that would be integrated on the basis that it is
not subject to any potential source of common cause failure.
2. Digital I&C modifications to SSCs that do not result in a CCF vulnerability due to a
reduction of any aspect of independence (or separation), single failure tolerance, or
diversity credited in the UFSAR (including a reduction in diversity due to hardware or
software resources shared among non-safety related control functions); and
3. Digital I&C modifications to facility SSCs, where a malfunction due to a design defect is
precluded through: (a) simplicity (as demonstrated through 100 percent testing or a
combination of testing and input/output state analysis); or (b) a demonstration of
Page: 15
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:50:32 PM
The same software in different systems could be considered a "shared resource", but it is not when assessing single failures. So change to "shared hardware
resource".
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 10:56:17 AM
RIS 2002-22 Supplement 1, Attachment
Page 8 of 27
1
2
adequate internal or external systematic diversity, or where a design defect is assumed,
postulated to be triggered, and demonstrated to result in no new malfunction or a 3
4 5
malfunction that is bounded at the level previously evaluated in the safety analysis.
Licensees may evaluate digital I&C modifications to SSCs associated with reactor protection
systems and ESF actuation systems using the qualitative assessment clarification in this RIS
Supplement with the following four considerations: (1) the proposed modification is not part of
the actuation/control logic portion of reactor protection systems and ESF systems, (2) the
proposed modification is not an extension of an ESF actuation, such as emergency power bus
load sequencers, (3) the design function will continue to be accomplished and the proposed
design will continue to satisfy applicable NRC requirements, and (4) any new input or output
devices do not communicate with the actuation logic portion of6reactor protection systems or
ESF actuation systems 7using digital data communications. This would include possible
changes to individual, non-shared channel inputs to reactor protection systems logic, reactor
protection systems power supplies, or output actuators (relays/breakers). Proposed
modifications beyond these types would likely require a license amendment.
4. Qualitative Assessment
4.1. Quantitative vs. Qualitative
A quantitative assessment is one capable of representing the SSC by a mathematical model,
such as apportioning the reliability and availability goals among parts of the system, assigning
probabilities to each failure mode of concern, and reconciling the calculated estimates of
reliability and availability with the overall SSC goals. A qualitative assessment identifies
possible ways in which an SSC can fail, and identifies appropriate precautions (design changes,
administrative procedures, etc.) that will reduce the frequency or consequences of such failures.
For example, a licensee may be able to rely on a qualitative assessment of a particular digital
controller even if it is difficult to demonstrate that the controller uses an error-free operating
system and error-free application-specific system software logic commands. Specifically, it may
8
be possible to demonstrate qualitatively that the controller has a set of specific attributes that
9
allow its installation without prior NRC approval. One acceptable set of attributes is that (1)
software for that controller has been prepared using a high-quality software development
process, (2) the controller was tested thoroughly during acceptance and post-installation tests,
and (3) the particular controller has been used in tens of thousands of hours of successful
operation at other locations under similar plant conditions and for similar purposes, and there
has been no evidence of operational failures due to software defects.
The qualitative assessment conclusion makes use of engineering judgment. As stated above,
NEI 01-01 describes that for 10 CFR 50.59 evaluations, the likelihood of failure is normally
demonstrated qualitatively (i.e., through reference to reasonable engineering practices and
engineering judgment) particularly for systems or components that rely on software, because
there are no well-established, accepted quantitative methods to demonstrate the likelihood of
failure from software design errors. When applying engineering judgment, the following
principles and general considerations may be followed:
- The technical qualifications of the personnel performing such evaluations will be appropriate
for the evaluation preparation and reviews.
- The evaluation process follows the applicable corporate engineering or plant engineering
procedures for performing such engineering evaluations or calculations.
Page: 16
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:51:59 PM
This contradicts previous sections which say that the malfunction must be analyzed only if the likelihood is not "sufficiently low" based on a qualitative
assessment. Here you say that analysis is needed to reach the "sufficiently low" threshold. This is quite confusing. Dave, this supports the interpretation that you
shared with me. But the RIS itself is contradictory in this area.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 10:59:25 AM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:55:56 PM
These words are very unclear. What does it mean to be evaluated "at the level previously evaluated". The plant level effect of all malfunctions are evaluated in
the FSAR. Sometimes the words in the FSAR stop at the system level, because the plant level is clearly unaffected. But that does not mean that the plant level is
not evaluated; of course it is. See previous comments.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 1:52:46 PM
Number: 5 Author: KenSc Subject: Highlight Date: 01/24/2018 1:52:50 PM
Number: 6 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:57:53 PM
Even if you hardwire a signal from a digital device, the digital device itself can create an erroneous signal that could adversely affect RPS/ESF. Digital data
communication creates an additional communication independence vulnerability. But it has no effect (positive or negative) on functional independence. "using
digital data communication" should be deleted.
Number: 7 Author: KenSc Subject: Highlight Date: 01/24/2018 11:02:46 AM
Number: 8 Author: KenSc Subject: Sticky Note Date: 01/24/2018 1:58:52 PM
Per previous NRC policy, all of these attributes facilitate a conclusion of sufficiently low likelihood to be analyzed using "best estimate" methods. Not sufficiently
low likelihood to require no further consideration. This RIS should not be changing NRC policy.
Number: 9 Author: KenSc Subject: Highlight Date: 01/24/2018 11:07:41 AM
RIS 2002-22 Supplement 1, Attachment
Page 9 of 27
- The basis for conclusions relying on engineering judgment are clearly documented in the
evaluation/analysis.
- A sound technical basis or rationale for the judgment (e.g., recognized engineering
principles, standards, trend evaluations, and empirical data; previous engineering
experience, calculations, or evaluations; demonstrated industry practices, etc.) is
established.
- The level of detail used to justify the engineering judgment may be commensurate with the
safety significance and complexity of the design function affected in accordance with
licensees procedures.
- The level of detail permits another technical reviewer with similar expertise, and without
recourse to the author, to understand the author's rationale.
- Simplified models and estimation techniques can provide supporting bases for engineering
judgement.
4.2. Overview of Design Information that Supports Qualitative Assessments
Technical information is needed to support a conclusion that a proposed digital I&C modification
will exhibit a sufficiently low likelihood of failure. As described in greater detail below, an
adequate basis for determining sufficiently low likelihood of failure may be derived from a
qualitative assessment of factors involving the inclusion of key system design features, the
quality of the design process used, and an evaluation of relevant operating experience (i.e.,
product maturity and in-service experience). The qualitative assessment reaches a conclusion
through engineering judgment that there is an adequate basis for concluding that the digital
modification will exhibit a sufficiently low likelihood of failure by considering the aggregate of
these factors. Section 5 of this Attachment provides further discussion regarding technical
information supporting qualitative assessments.
4.3. Qualitative Assessment Categories
Consistent with the guidance provided in NEI 01-01, this attachment specifies three general
categories of proposed design-related characteristics (described in Table 1 of this document)
that can be used to develop justifications that demonstrate a sufficiently low likelihood of failure
for a proposed modification. The aggregate of the three qualitative assessment categories form
the technical basis for developing justifications based upon the likelihood of failure (i.e., single
failures and CCF) of a digital I&C modification to a system or components. The aggregate of all
three categories below needs to be evaluated to demonstrate that there is an adequate basis for
concluding that the proposed modification will exhibit a sufficiently low likelihood of failure such
that the criteria described in Section 2 of this attachment can be addressed:
- Design attributes:
NEI 01-01 Section 5.3.1 states:
To determine whether a digital system is sufficiently dependable, and
therefore that the likelihood of failure is sufficiently low, there are some
important characteristics that should be evaluated. These characteristics,
discussed in more detail in the following sections include. . .
This page contains no comments
RIS 2002-22 Supplement 1, Attachment
Page 10 of 27
Hardware and software design features that contribute to high
dependability (See Section 5.3.4). Such [hardware and software design]
features include built-in fault detection and failure management schemes,
internal redundancy and diagnostics, and use of software and hardware
architectures designed to minimize failure consequences and facilitate
problem diagnosis.
Consistent with the above-quoted text, design attributes of 1the proposed modification
can prevent or 2limit failures from occurring or mitigate the consequences of such
possible failures. The qualitative assessment documents and describes hardware and
software design features that contribute to high dependability. Design attributes focus
primarily on built-in features such as fault detection and failure management schemes,
internal redundancy and diagnostics, and use of software and hardware architectures
designed to minimize failure consequences and facilitate problem diagnosis. However,
design features external to the proposed modification (e.g., mechanical stops on valves)
may also need to be considered.
During the design process, it is important to consider both the positive effects of
installing the digital equipment (e.g., elimination of single-point vulnerabilities (SPVs),
ability to perform signal validation, diagnostic capabilities, etc.) with the potential
negative effects (e.g., software CCF, etc.).
Within the concept of defense-in-depth, acceptable justification for concluding an 3
accident of a different type will not be initiated could include, if supported by the facts,
that the postulated new accident is only possible after a sequence of multiple unlikely
independent failures. This type of justification is summarized and documented as part of
the qualitative assessment.
- Quality of the Design Process:
Section 5.3.3 of NEI 01-01 states:
For digital equipment incorporating software, it is well recognized that
prerequisites for quality and dependability are experienced software
engineering professionals combined with well-defined processes for
project management, software design, development, implementation,
verification, validation, software safety analysis, change control, and
configuration control.
Consistent with the guidance provided in NEI 01-01, Quality Design Processes means
those processes employed in the development of the proposed modification. Such
processes include software development, hardware and software integration processes,
hardware design, and validation and testing processes that have been incorporated into
the development process. Although in many cases this development process would be
documented and available for referencing in the qualitative assessment for proposed
modifications to safety-related equipment, for commercial- grade-dedicated or
non-safety related equipment it may not be readily available. In such cases, the
qualitative assessment may place greater emphasis on the design attributes included
and the extent of successful operating experience for the equipment proposed.
Page: 18
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:00:28 PM
Limiting and mitigating do not reduce the likelihood of the failure. They can only be used to demonstrate that the failure has an acceptable plant level end
result.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 11:09:58 AM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 11:12:29 AM
This paragraph is not related to design attributes that reduce the likelihood of failure. It is about tolerating the failure. This paragraph should be deleted or
moved.
RIS 2002-22 Supplement 1, Attachment
Page 11 of 27
- Operating Experience:
Section 5.3.1 of NEI 01-01 states, Substantial applicable operating history reduces
uncertainty in demonstrating adequate dependability.
Consistent with the above-quoted text, relevant operating experience can be used as a
means to help demonstrate that software and hardware employed in a proposed
modification have adequate dependability. The licensee may document information
showing that the proposed system or component modification employs equipment with
significant operating experience in nuclear power plant applications, or in non-nuclear
applications with comparable performance standards and operating environment. The
licensee may also consider whether the suppliers of such equipment incorporate quality
processes such as continual process improvement, incorporation of lessons learned,
etc., and document how that information demonstrates adequate equipment
dependability.
These categories are not mutually exclusive and may overlap in certain areas. Adequate
qualitative assessments for SSCs fully address each of the above categories. Qualitative
assessment documentation for the proposed modification to SSCs is retained in accordance
with the licensees design engineering procedures, procedures implementing
10 CFR 50.59(d)(1), and NRC-approved QA program.
Table 1 provides acceptable examples of design attributes, quality of the design processes, and
documentation of 1 operating experience. This listing is not all inclusive, it merely provides
2
examples. Licensees may consider additional design attributes, quality of the design
processes, and documentation of operating experience in their qualitative assessment and need
not use these specific examples.
Page: 19
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:21:12 PM
It needs to be clarified that any one or more of these examples, or even all of them, may not be sufficient for any specific application. We don't want licensees
to point to these examples and say "look, we have this, so we reached a "sufficiently low" conclusion.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 2:18:47 PM
RIS 2002-22 Supplement 1, Attachment
Page 12 of 27
Table 1Qualitative Assessment Category Examples
1
2
Categories Acceptable Examples for Each Category
Design Attributes * Design criteriaDiversity (if applicable), Independence, and
Redundancy.
- Inherent design features for software, hardware or
architectural/network Watchdog timers that operate independent of
software, isolation devices, segmentation, self-testing, and self-
diagnostic features. 3
- Basis for identifying that possible triggers are 4non-concurrent.
- Sufficiently simple (i.e., enabling 100 percent testing or
comprehensive testing in combination with analysis of likelihood of
occurrence of input/output states not tested).
- Unlikely series of eventsEvaluation of a given digital I&C
modification would necessarily have to postulate multiple independent
random failures in order to arrive at a state in which a CCF is
possible.
- Failure state always known to be safe, or at least the same state as
allowed by the previously installed equipment safety analysis.
Quality of the * Justification for use of industry consensus standardsfor codes and
Design Process standards not endorsed by the NRC.
- Justification for use of the other standards.
- Justification for applicability of standards used.
- Use of Appendix B vendors. If not an Appendix B vendor, the
analysis can state which generally accepted industrial quality program
was applied.
- Use of Commercial Grade Dedication processes per guidance of
EPRI TR-106439, Annex5 D of IEEE 7-4.3.2, and examples within
6
EPRI TR-107339.
- Demonstrated tolerance (e.g., through qualification testing) to
withstand environmental conditions within which the SSC is credited
to perform its design function (e.g., EMI/RFI, Seismic).
- Development process rigor (adherence to generally-accepted
commercial or nuclear standards.)
- The use of custom software using code for application software will
typically call for extensive evaluation or testing or both to demonstrate
dependability, where there is inadequate information to conclude that
a quality design process has been used.
Operating * Wide range of operating experience in similar applications, operating
Experience environments, duty cycles, loading, comparable configurations, etc.,
to that of the proposed modification.
- History of lessons learned from field experience addressed in the
design.
- Relevant operating experience: Architecture of the referenced
equipment and software along with the design conditions and modes
of operation of the equipment should be substantially similar to those
of the system being proposed as a digital I&C modification.
Page: 20
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:22:16 PM
Delete "acceptable" because this implies that any one or more of these may be sufficient.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 2:21:40 PM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:26:28 PM
Non-concurrent triggers is never enough. You must also demonstrate that the triggered failure is self-announcing. This facilitates corrective actions before the
same defect is triggered in another component. Without self-announcing, triggered defects can remain hidden. Therefore, multiple triggers for the same defect
can occur in other places and thereby accumulate to become CCFs.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 2:23:37 PM
Number: 5 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:27:37 PM
I think you mean 107330
Number: 6 Author: KenSc Subject: Highlight Date: 01/24/2018 2:27:22 PM
RIS 2002-22 Supplement 1, Attachment
Page 13 of 27
- High volume production usage in different applicationsNote that for
software, the concern is centered on lower volume, custom, or
user-configurable software applications. High volume, high quality
commercial products with relevant operating experience used in other
applications have the potential to avoid design errors.
- Evaluation of the operating experience for specific versions of
operating system software designed by high quality commercial grade
equipment vendors may be one of the only means by which a degree
of assurance of reliability may be judged. For some applications and
custom-developed software, operating experience may be the most
reliable justification that the software is acceptable. It may be
necessary to delay implementing major application software use and
software revisions until the software version has sufficient operating
experience.
- The operating system and application level software may need to be
considered. In some cases it may be necessary to address vendor
software that creates the configuration files as well as the
configuration file itself.
4.3.1 Design Attributes to Reduce the Likelihood of Failure
Many system design attributes, procedures, and practices can contribute to significantly
reducing the likelihood of failure (e.g., CCF). A licensee can account for this by deterministically
1
assessing the specific vulnerabilities through the 2introduction of failure modes (e.g., software
CCF) within a proposed modification and applying specific design attributes to address those
vulnerabilities (see Table 1 above). An adequate qualitative justification regarding the likelihood
of failure of a proposed modification would consist of a description of: (a) the 3identified 4
vulnerabilities of the proposed modification, (b) the design attributes used to address the
5
identified vulnerabilities, and (c) a clear description explaining why the chosen design attributes
and features are adequate.
Changes in control system design need to be evaluated for potential vulnerabilities to CCF. In
addition, there are some SSCs that have few applicable requirements (e.g. no diversity or
redundancy requirements). These SSCs may have been implemented in a manner (i.e.,
relatively independently) such that only individual SSC malfunctions or failures were considered
in the UFSAR. If these individual SSCs are combined with (e.g., controlled by a common digital
component, employ the same software in separate digital devices), or are coupled to each other
(e.g., by digital communication), then the potential for malfunctions with a different
6 result or
accidents of a different type 7would be evaluated under 10 CFR 50.59.
4.3.1.1 Diversity and Common Cause Failure
Diversity is one example of a design attribute of an SSC that can be used as part of the bases
for demonstrating an SSC modified with digital technology will exhibit a low likelihood of a loss
of design function due to a potential common cause failure. The design of certain SSCs is
required to include
8 diversity to the extent practical. (For example, for protection systems,
9
diversity is to be used to the extent practical to prevent loss of the protection function.
(10 CFR Part 50 Appendix A, Criterion 22.)). Some licensees have already followed staff
guidance, such as NUREG-0800, Chapter 7, Branch Technical Position 7-19, in establishing the
Page: 21
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:29:08 PM
I think you mean "postulate" failure modes, not introduce them.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 2:28:39 PM
Number: 3 Author: KenSc Subject: Highlight Date: 01/24/2018 2:31:15 PM
Number: 4 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:33:19 PM
In both cases here, I think "identified" should be "postulated". You cannot reach a 'sufficiently low" conclusion if any vulnerabilities remain (i.e., if any are
"identified").
Number: 5 Author: KenSc Subject: Highlight Date: 01/24/2018 2:31:21 PM
Number: 6 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:39:23 PM
This is clear criteria for "screen in". So why don't you clearly say that, rather than tip-toe around the edges. The industry has made too many errors screening
digital mods out. This is not the only screen-in criteria, but it is certainly the most important for digital mods and the simplest to understand. You have said in
one sentence what Appendix D has not said in 50 pages. If this one sentence includes the words "screen-in" we will resolve the most prevalent historical
inconsistency in 50.59 evaluations.
Number: 7 Author: KenSc Subject: Highlight Date: 01/24/2018 2:34:44 PM
Number: 8 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:02:58 PM
Clarify that this refers to functional diversity (e.g., temperature and pressure trips for the same accident), not implementation diversity (e.g., both implemented
using 7300 or Spec 200). Implementation diversity is not required in the protection system by 10CFR Part 50 Appendix A. Implementation diversity is only
required by 50.62 for ATWS, which is a beyond design basis event for which "best estimate" methods are permitted.
Number: 9 Author: KenSc Subject: Highlight Date: 01/24/2018 11:16:14 AM
RIS 2002-22 Supplement 1, Attachment
Page 14 of 27
1
2
design basis of certain SSCs. Further, some SSCs are subject to existing regulatory
4 3
requirements or other acceptance 5 criteria to which the licensee is committed, and include
6
diversity in the design. In these cases, the licensees have incorporated 7diversity into the 8design
basis. In all other cases, the licensees need not consider the use of diversity (i.e., as described
in the staff requirements memorandum
9 on SECY 93-087) in evaluating a proposed modification
under 10 CFR 50.59. However, diversity within the proposed design, and any affected SSCs is
a powerful means which may significantly reduce the likelihood of malfunctions affecting the
accomplishment of design functions.
4.3.1.2 Digital Communications
Digital communications can reduce SSC independence credited or assumed in the UFSAR.
Reduction in independence may create the possibility of a new failure that could result in
concurrent failures not considered in the UFSAR. Careful consideration is needed to preclude
adverse effects on safety and non-safety related SSC independence. DI&C-ISG-04, Revision 1,
Highly-Integrated Control RoomsCommunications Issues (ADAMS Accession Number
ML083310185) provides an acceptable means of addressing digital communication between
redundant SSCs, echelons of defense-in-depth, or SSCs with different safety classifications. 10
11
DI&C-ISG-04 was developed to address digital communication among safety-related and
between safety-related and non-safety related SSCs. The principles of this ISG or other
technically justifiable considerations, may be used to assess non-safety related SSCs.
4.3.1.3 Combining (Integration) of Functions
Combining design functions of different safety-related or non-safety related SSCs in a manner
not previously evaluated or described in the UFSAR could introduce new interdependencies and
interactions that make it more difficult to account for new potential failure modes (i.e., single
failures and CCF). Failure of combined design functions that: 1) can effect malfunctions of 12
SSCs or accidents evaluated in the UFSAR; or, 2) involve different defense-in-depth 13 echelons5;
are of significant concern.
Combining previously separate component functions can result in more dependable system
performance due to the tightly coupled nature of the components and a reduction in complexity.
If such a combination does not create a new failure mode, it is generally acceptable. In all
cases in which a licensee proposes to combine previously separate design functions in a 14
15
safety-related and/or non-safety related digital I&C, the qualitative assessment needs to weigh
the risks of possible new malfunctions against the benefits 16 of combining the previously
17
separately controlled functions. Where possible, failure modes and effects analyses and
non-safety related control system segmentation analyses can be performed for the proposed
modification.
4.3.2 Quality of the Design Process and the use of Quality Standards
5 As stated in NEI 01-01, Section 5.2, a fundamental concept in the regulatory requirements and expectations for
instrumentation and control systems in nuclear power plants is the use of four echelons of defense-in-depth: 1)
Control Systems; 2) Reactor Trip System (RTS) and Anticipated Transient without SCRAM (ATWS); 3) Engineered
Safety Features Actuation System (ESFAS); and 4) Monitoring and indications.
Page: 22
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:42:15 PM
This should be "licensing basis", because BTP 7-19 does not address the design basis, it addresses only "beyond design basis" events.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 2:41:18 PM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:46:12 PM
Again, this should be "licensing basis".
Number: 4 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:46:03 PM
Change "diversity" to "adequate defense against CCF"
Number: 5 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:45:13 PM
This should say "have included adequate defensive against CCF vulnerabilities", because diversity is not the only acceptable defense.
Number: 6 Author: KenSc Subject: Highlight Date: 01/24/2018 2:44:02 PM
Number: 7 Author: KenSc Subject: Highlight Date: 01/24/2018 2:45:38 PM
Number: 8 Author: KenSc Subject: Highlight Date: 01/24/2018 2:42:42 PM
Number: 9 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:48:43 PM
I agree that diversity is not a requirement under 50.59 because it is also not a requirement under 10CFR50 or Part 52. But adequate defense against a CCF is a
requirement under 50.59, otherwise you cannot favorably answer Questions 5 and 6.
Number: 10 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:52:02 PM
ISG-04 does much more than "address". Change to 'ensure digital communication among ... SSCs does not reduce independence.'
Number: 11 Author: KenSc Subject: Highlight Date: 01/24/2018 2:50:47 PM
Number: 12 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:01:50 PM
This should be deleted or clarified, because ISG-02 makes it clear that no independence is needed between the RTS and ESF echelons.
Number: 13 Author: KenSc Subject: Highlight Date: 01/24/2018 3:00:04 PM
Number: 14 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:56:02 PM
No, 50.59 is not an assessment of design alternatives. Change to "the qualitative assessment shall demonstrate that concurrent malfunctions of the combined
equipment do not create unbounded plant conditions."
Number: 15 Author: KenSc Subject: Highlight Date: 01/24/2018 2:53:23 PM
Number: 16 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:06:38 PM
This implies that FMEA and segmentation analysis are not needed. This is not correct; they are always needed when previously independent functions are
combined and the CCF likelihood is not "sufficiently low". In addition, they are always possible; what would make these analyses not possible.
Number: 17 Author: KenSc Subject: Highlight Date: 01/24/2018 3:03:37 PM
RIS 2002-22 Supplement 1, Attachment
Page 15 of 27
Quality of the design process is a key element that determines the dependability of proposed
modifications. Licensees employing design processes consistent with the requirements of their
NRC approved quality assurance program will result in a quality design process.
1
2
When possible, the use of applicable industry consensus standards contributes to a quality
design process and provides a previously established acceptable approach (e.g IEEE Std. 1074-2006, IEEE Standard for Developing a Software Project Life Cycle Process, RG 1.173,
Developing Software Life Cycle Processes for Digital Computer Software Used in Safety
Systems of Nuclear Power Plant). In some cases, other nuclear or non-nuclear standards also
provide technically justifiable approaches that can be used if confirmed applicable for the
specific application.
Quality standards should not be confused with quality assurance programs or procedures.
Quality standards are those standards which describe the benchmarks that are specified to be
achieved in a design. Quality standards should be documents that are established by
consensus and approved by an accredited standards development organization. For example,
IEEE publishes consensus-based quality standards relevant to digital I&C modifications and is a
recognized standards development organization. Quality standards used to ensure the 3
4
proposed change has been developed using a quality design process do not need to be solely
those endorsed by the NRC staff. The qualitative assessment document should demonstrate
that the standard being applied is valid for the circumstances for which it is being used.
4.3.3 Evaluation of Relevant Operating Experience
5
6
Operating experience relevant to a proposed digital I&C change may be credited as part of an
adequate basis for a determination that the proposed change does not result in more than a
minimal increase in the frequency of occurrence of initiating events that can lead to accidents,
or in more than a minimal increase in the likelihood of occurrence of a malfunction of an SSC
important to safety previously evaluated in the UFSAR. Differences may exist in the specific
digital I&C application between the proposed digital I&C modification and that of the equipment
and software whose operating experience is being credited. In all cases, however, the
architecture of the referenced equipment and software should be substantially similar to that of
the system being proposed. Further, the design conditions and modes of operation of the
equipment whose operating experience is being referenced also needs to be substantially
similar to that being proposed as a digital I&C modification. For example, it is important to
recognize that when crediting operating experience from other facilities, one needs to
understand what design features were present in the design whose operating experience is
being credited, and what operating conditions (e.g., ambient environment, continuous duty, etc.)
were experienced by the referenced design. Design features, which serve to prevent or limit
possible common cause failures, and references into relevant operating experience, should be
noted, and considered in the proposed design. Doing so would provide additional support for a
determination that the dependability of the proposed design will be similar to the referenced
application.
7
5. Engineering Evaluations Supporting Qualitative Assessments
5.1 Introduction
This section describes approaches that could be used for conducting and documenting
engineering evaluations when they are used to support qualitative assessments. In some cases
Page: 23
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:08:05 PM
Delete or clarify. The use of industry standards always contributes to quality.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 3:07:02 PM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:11:01 PM
I agree for non-safety systems. But for safety systems, even under CGD, compliance to NRC guidance or compensating measures for non-compliance, is
required.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 3:09:50 PM
Number: 5 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:12:03 PM
It needs to be clear that OE cannot be the only justification.
Number: 6 Author: KenSc Subject: Highlight Date: 01/24/2018 3:11:33 PM
Number: 7 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:53:11 PM
How are these evaluations different than the evaluations described in the previous section. This document is far too long and far too repetitive. Most of this
section repeats the material in previous sections.
RIS 2002-22 Supplement 1, Attachment
Page 16 of 27
these approaches describe efforts beyond those discussed in NEI 01-01. This information is
provided for consideration only. They do not represent an NRC position of what is necessary or
required. Use of any of this information is at the discretion of licensees.
Prior to implementing new digital I&C designs, engineering evaluations of the proposed design
need to be performed as part of the design and verification processes. Although the plant is
designed to cope with single failures of SSCs, it is possible that new sources of common cause
failure could be introduced as part of the digital I&C design, such as through the introduction of
identical software into redundant channels; through the use of shared resources; or common
hardware and software among systems performing different design functions. Therefore it is 1
essential that such sources of common cause failure be identified, 2to the extent practicable, and
addressed during the design stage as one acceptable method to support the technical basis
concluding that a proposed new design has a low likelihood of failure that is evaluated in the
subsequent licensing evaluation.
Section 3.2.2 of NEI 01-01 states:
For digital systems, the likelihood of software-related failure is minimized using
the same basic approach of controlling the design, implementation, operation,
and maintenance processes. Compliance with industry standards and regulatory
requirements coupled with tests, evaluations, and reviews is used to assure a
very low likelihood of failure. The important activities that are performed
throughout the various phases of the digital modification process and that
contribute to minimizing risk are summarized in Section 3.3 [Phases of the Plant
Modification Process] and discussed in detail in Section 5 [Additional Guidance
on Addressing Digital Upgrade Issues.] Results of these activities are then used
in the 10 CFR 50.59 process as described in Section 4 [Licensing Process and
10 CFR 50.59.] With respect to failures due to software, including common
cause failures, the key to addressing 3these in licensing is having performed
appropriate design, analysis and evaluation activities to provide reasonable
assurance that 4such failures have a very low likelihood. [emphasis added]
Such key evaluation activities may include, but are not limited to: a) the deterministic analysis of
the conformance of the design with regulatory requirements, engineering standards, and
regulatory guidance, as well as the licensing basis of the plant; b) the performance of adequate 5
6
deterministic failure analyses, including analysis of the effects of digital I&C failures at the
component-level, system-level, and plant-level; c) the evaluation of the proposed modification
for its overall dependability; and d) the deterministic evaluation of the design for the adequacy
of its ability to provide adequate defense-in-depth. It should be noted that items b), 7 c), & d) may
8
be distinct analyses from a), but they are performed as a consequence of a). The qualitative
assessment framework discussed in the previous sections of this Attachment relies, in part, on
the technical bases and conclusions documented within these engineering evaluations.
Design Process Considerations
Section 3.2 of NEI 01-01 includes a figure (Figure 3-2, Using Failure Analysis to Understand
and Manage Risk) that illustrates "how failure analysis is applied during the design process to
understand and manage risk. Risk is a function of both the likelihood and the consequences of
potential failures and hazards. Depending on the combination, risk 9 could be judged to be
10
negligible, non-negligible (but acceptable), or unacceptable. In practice, the design process
Page: 24
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:14:29 PM
Delete these words. This is absolutely necessary. If you have not identified the sources, how can you reach a conclusion of "sufficiently low".
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 3:13:13 PM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:15:47 PM
Again, you can't reach a "low likelihood" conclusion if you have not identified the failures.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 3:15:18 PM
Number: 5 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:17:03 PM
The effects of a failure, acceptable or not acceptable, have nothing to do with the likelihood of the failure.
Number: 6 Author: KenSc Subject: Highlight Date: 01/24/2018 3:16:16 PM
Number: 7 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:20:21 PM
This implies that the results of (a) could preclude the need for b, c and d. I disagree.
Number: 8 Author: KenSc Subject: Highlight Date: 01/24/2018 3:18:15 PM
Number: 9 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:23:00 PM
It is inconsistent that there are three tiers of risk, but only two tiers of likelihood. You need three tiers of likelihood to ensure appropriate analysis methods are
employed (design basis, or beyond design basis, or no analysis needed at all).
Number: 10 Author: KenSc Subject: Highlight Date: 01/24/2018 3:21:13 PM
RIS 2002-22 Supplement 1, Attachment
Page 17 of 27
identifies unacceptable risks and makes adjustments accordingly, so by the time a proposed
change is ready for implementation in the plant or for NRC review, it will always lie in the region
of negligible or acceptable risk. [emphasis added]
The design process, in part, answers the following questions: a) what can go wrong? b) how
likely is it to occur?; and c) what actions are needed to address it? In Section 5.2, key
engineering evaluations are described that provide insights to whether adequate design
attributes and features have been incorporated to minimize the occurrence of system failures,
and to demonstrate sufficient system/equipment redundancy, diversity, separation, or
independence.
Section 3.1 of NEI 01-01 states:
Engineering evaluations include the collection of activities that are performed to
demonstrate reasonable assurance that the system is safe and satisfies the
specified requirements (e.g., for quality, dependability, and performance). This
may include evaluating and interpreting the results of the failure analysis, design
verifications, software V&V, and review of vendor software design and
development processes. Where appropriate, analyses of overall
defense-in-depth and diversity of the plant may be warranted to demonstrate the
ability to cope with common cause failures.
Section 4.1.1 of NEI 01-01 states that two key elements of the engineering evaluations are
evaluating the dependability of the digital equipment 1 and its associated software, and analyzing
potential failures. One of the key considerations in licensing digital upgrades is determining
2
whether failures due to software are as likely as other potential failures addressed in the
UFSAR. This issue is addressed by establishing reasonable assurance that such failures are
unlikely, based on the engineering evaluations performed as part of the design process.
5.2 Key Engineering Evaluations
Section 4 Engineering Evaluations of Appendix B, Outline for Documenting 10 CFR 50.59
Screens and Evaluations, of NEI 01-01 provides guidance for documenting why the proposed
digital I&C modification as designed is considered appropriate for the application. This
Appendix section describes types of engineering evaluations that may be used to provide
justification as to why the proposed design is appropriate. These include an evaluation of the
design for conformance with applicable design criteria, regulatory requirements and industry
standards.
The analyses described below represent acceptable methods for performing engineering
evaluations supporting a qualitative assessment. One result of performing these evaluations is
to provide insights as to whether a proposed digital I&C design modification may need to be
enhanced with the inclusion of different or additional design attributes. Such different or
additional design attributes would serve to prevent the occurrence of a possible software CCF, 3
reduce the likelihood of occurrence of a possible software CCF, 4or mitigate the effects of a
software CCF that can occur.
5.2.1 Failure Analyses
Page: 25
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:05:22 PM
This contradicts your definition of "sufficiently low" which requires the failure likelihood to be "comparable to failures not considered in the FSAR", not 'as likely
as those that are considered'. These thresholds are quite different.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 11:26:09 AM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:06:15 PM
The ability to mitigate the malfunction is completely different than the determination of likelihood.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 11:27:52 AM
RIS 2002-22 Supplement 1, Attachment
Page 18 of 27
As stated in Section 5.1 of NEI 01-01, a digital I&C modification failure analysis is a part of the
design process that should be performed as part of plant design procedures and should be
documented as part of the design process. The performance of such a deterministic failure
analysis of a proposed digital I&C modification is one acceptable method for providing insights
regarding the possible failure modes of the modification that are needed to support such
licensing evaluations, which are typically performed later in the modification process. The
failure analysis provides, in part, the insights needed to determine if a proposed digital I&C 1
modification is vulnerable to possible software CCF 2such that the resulting design could reduce
redundancy, diversity, separation, or independence, which could result in more than a minimal
increase in the likelihood of occurrence of accidents or malfunctions. Such deterministic failure
analyses provide feedback to the designers regarding effects of possible failures of the
proposed digital I&C modification on plant systems so that the designers can make
determinations as to whether there is a need to further modify the design to address any design
issues that are uncovered. For example, a failure analysis may reveal that due to the adequacy
of design features already included within a proposed design, the possible occurrence3 of 4
failures due to a software CCF vulnerability is considered to have 5such a low risk that the
proposed design is considered to be adequate.
NEI 01-01 Section 5.1 states, in part, that the failure analysis should include the following
elements..:
- Identification of potential system-level failure and undesirable behavior (which
may not be technically failures) and their consequences. This includes
consideration of potential single failures as well as plausible common cause
failures.
- Identification of potential vulnerabilities, which could lead to system failures or
undesirable conditions.
- Assessment of the significance and risk of identified vulnerabilities.
- Identification of appropriate resolutions for identified vulnerabilities, including
provide [sic] means for annunciating system failures to the operator.
NEI 01-01 Section 5.1 also states:
A variety of methodologies and analysis techniques can be used in these
evaluations, and the scope of the evaluations performed and documentation
produced depends on the scope and complexity of the upgrade. The analysis
maintains a focus at the level of the design functions performed by the system,
because it is the effects of the failure on the system and the resulting impact on
the plant that are important. Failures that impact plant safety are those that
could: prevent performance of a safety function of the system, affect the ability of
6
other systems to perform their safety functions, or lead to plant trips or transients
that could challenge safety systems.
NEI 01-01 Section 5.1.1 states, in part,
Page: 26
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:43:31 PM
Preventing a software design defect or mitigating the effects of a software design defect are not requirements to satisfy NRC criteria for redundancy, separation
or independence. Therefore, these words should be deleted.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 3:42:45 PM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:45:20 PM
For consistency with the rest of this document, replace risk with likelihood. Alternately, clarify that this means risk comparable to other failures that are not
considered in the FSAR and distinguish this from risks that do not reach this level and therefore require further analysis of the plant level effects.
Number: 4 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:48:15 PM
I really think there is no place for any risk discussion in this document. Because for compliance to 50.59, even a malfunction that has very low consequences can
be a malfunction with a different result. Likelihood is the correct discussion, not risk.
Number: 5 Author: KenSc Subject: Highlight Date: 01/24/2018 11:30:54 AM
Number: 6 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:50:39 PM
You are missing failures that have not been analyzed. These are equally important threats to plant safety because the plant level effect is unknown.
RIS 2002-22 Supplement 1, Attachment
Page 19 of 27
It is useful at this stage to review the UFSAR to determine how failures of the
affected system are described and analyzed. An understanding of the UFSAR-
described failures and their results is needed to support the 10 CFR 50.59
evaluation discussed in Section 4 [Licensing Process and 10 CFR 50.59.] If the
plant design change introduces any failures that cause results different from
those analyzed in the UFSAR, then a license amendment may be required.
The introduction of new digital designs having sources of CCF in common with other plant
non-safety related designs that have been assumed in the safety analyses to remain functional,
may result in the plant being put into a condition for which it has not been analyzed. This is 1
particularly the case when such common sources of CCF also 2are subject to common triggers.
An adequate failure analysis is one that includes a sufficient level of detail to enable licensees to
make a determination as to the possibility for and likelihood of potential new failures that could
be introduced by a proposed modification. This includes an understanding of the operations of
any external connections of the modified SSC(s) to and from other SSCs, as well as an
understanding of how identical hardware and software, power supplies, human-machine
interfaces, etc. may have been employed elsewhere in the plant, such that after the modification
has been implemented, there remains a possible commonality in vulnerabilities to the same
common cause sources and their triggers. NEI 01-01, Section 4.1.2 states that additional
factors that can contribute to the determination that the likelihood of software CCF is acceptably
low include:
Simple software architecture, few inputs/outputs, well-defined failure states, built-
in fault tolerance (see Section 5.3.2). Systems that are sufficiently simple can
have well defined failure modes and tend to allow for more thorough testing of all
input and output combinations than complex systems. The simplicity of the
digital equipment itself and of the application should be considered.
Modifications that employ effective design attributes and features such as internal or external
systematic diversity help to ensure that possible vulnerabilities do not result in CCFs. The
design of such systems are deemed to be adequate.
5.2.2 Dependability Evaluation
The dependability of a design is described in NEI 01-01 (Page 2-3) as a broad concept
incorporating various characteristics of digital equipment, including reliability, safety, availability,
maintainability, and others. Section 4.1.2 of NEI 01-01 states:
To determine whether a digital system poses a significant risk of software failure,
the factors that contribute to its dependability (or likelihood of failure) and quality
need to be evaluated.
NEI 01-01, Section 4.1.2 further states that additional factors that can contribute to the
determination that the likelihood of software CCF is acceptably low include:
The maturity of the product and substantial relevant history of satisfactory
operation in similar application (including operating experience at other plants
and in other industries). Additional confidence is gained if the same equipment
Page: 27
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:51:57 PM
Or the triggers are not self-announcing.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 3:51:42 PM
RIS 2002-22 Supplement 1, Attachment
Page 20 of 27
and application program have been used successfully in other nuclear plants or
other similar applications.
Technical evaluation in combination with deterministic design measures can be used to make a
determination as to whether1 a proposed I&C modification is sufficiently dependable. However,
2
there might not be clearly applicable consensus methods for accurately quantifying the reliability
of software. Therefore, it may be necessary to use engineering judgment as to whether the
proposed design is still sufficiently dependable in its ability to perform its required functions
while significantly limiting, or avoiding the introduction of possible new sources of software CCF.
The dependability evaluation relies on some degree of engineering judgment to support a
conclusion that the digital modification is considered to be sufficiently dependable. When
performing a dependability evaluation, one acceptable method is to consider: (1) inclusion of
any deterministically-applied defensive design features and attributes, (2) conformance with
applicable standards regarding quality of the design process for software and hardware, and 3 (3)
4
relevant operating experience. Although not stated in NEI 01-01, staff believes that judgements
regarding the quality of the design process and operating experience may supplement, but not
replace the inclusion of design features and attributes.
For proposed designs that are more complex or more risk significant, the inclusion of design
features and attributes that: serve to prevent vulnerabilities to software CCF, significantly reduce
the possible occurrence of software CCF, or significantly limit the consequences of such
software CCF, should be key considerations for supporting a sufficiently dependable
determination. Design features maximizing reliable system performance, to the extent
practicable, can be critical in establishing a basis for the dependability of complex or risk
significant designs.
Section 5.1.3 of NEI 01-01 states that Judgments regarding dependability, likelihood of failures,
and significance of identified potential failures should be documented. It may be challenging
to demonstrate sufficient dependability using solely the quality of the design process.
5.2.3 Defense-in-Depth Analyses
5
6
If there are specific licensing basis discussions for diversity or defense-in-depth applicable to
the affected design function they must be explicitly addressed. For example, as discussed in
Section 5.2 of NEI 01-01, a defense-in-depth and diversity (D3) analysis is required when the 7
trip logic and actuation portions of the RTS and/or ESFAS are modified with digital equipment.
8
9
Although a formal D3 analysis is not required for non-protection systems, a defense-in-depth
analysis should also be considered for complex digital modifications of non-protection systems to
determine the impact of any new potential vulnerabilities to common cause failures due to the
introduction of shared resources, common hardware and software, or the combination of design
functions of systems that were previously considered to be independent of one another. If a new
potential common cause vulnerability has been introduced, the defense in depth analysis can
identify whether there may be diverse manual or automatic means that can perform the same or
different functions or whether additional design features (e.g., internal diversity) are appropriate
for incorporation.
Possible software CCFs that have been identified in the failure analysis (and not eliminated from
consideration based on the dependability evaluation) can be assessed to determine whether
Page: 28
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:55:04 PM
Change to "are not".
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 3:54:46 PM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:56:04 PM
delete these words. This RIS defines he Staff's position, not opinions.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 3:55:35 PM
Number: 5 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:57:05 PM
Where?
Number: 6 Author: KenSc Subject: Highlight Date: 01/24/2018 3:56:55 PM
Number: 7 Author: KenSc Subject: Sticky Note Date: 01/24/2018 3:58:18 PM
A D3 is needed even when there is not a discussion of this previously.
Number: 8 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:09:37 PM
A RIS cannot change current Staff policy. BTP 7-19 says a D3 analysis is required for "safety systems" not just protection systems. That analysis first determines if
there is adequate protection against a CCF. If so, no further analysis is needed; so the D3 analysis stops there. But there is no safety system for which a D3
analysis (i.e., at least the CCF susceptibilty part) is not required. This RIS should not change Staff policy.
Number: 9 Author: KenSc Subject: Highlight Date: 01/24/2018 11:36:08 AM
RIS 2002-22 Supplement 1, Attachment
Page 21 of 27
adequate diversity and defense-in-depth will remain after the digital I&C modification is
implemented. Possible means, for ensuring adequate diversity and defense-in-depth will
1
remain at the system or plant level, can include: (a) the use of design attributes to achieve
2
adequate diversity, (b) the crediting of available high-quality, non-safety related, but 3
4
independent systems, or (c) manual actions that are already analyzed and credited in the
UFSAR safety analysis.
Page: 29
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 4:01:23 PM
If you do not allow "best estimate" methods then non-safety systems cannot be credited. Non-safety systems cannot be credited in design basis analyses.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 3:59:44 PM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 4:03:29 PM
What is the basis for excluding new manual actions. New manual actions using equipment that is already described in the FSAR should be allowed. If "best
estimate" methods are allowed these actions can employ non-safety systems. If "best estimate" methods are not allowed, then manual actions must employ
safety systems, only.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 4:01:40 PM
RIS 2002-22 Supplement 1, Attachment
Page 22 of 27
Section 5.2.1 of NEI 01-01 states:
The cumulative effects of a series of upgrades or modifications should also be
considered in the determination of whether a defense-in-depth and diversity
analysis is performed. For any change to the plant, consideration should be
given to the effects the change 1 may have on diversity and defense-in-depth for
2
RTS/ESFAS functions. If the change would affect the diversity and defense-in-
depth of the RTS/ESFAS functions, then the analysis should be performed.
Also, if other I&C systems, including ATWS and other non-safety systems, are
being upgraded to digital in plants where digital upgrades to RTS and/or ESFAS
have already been done, prior defense-in-depth and diversity analyses should be
reviewed. If the I&C system under consideration was credited in the prior
analysis as providing backup, then the replacement digital equipment should be
diverse from that used in the protection systems. NUREG-6303 provides
guidance on methods that can be used to assess the diversity of digital systems.
For RPS and ESFAS, BTP 7-19, Revision 7, Section 1.9 states that many system design
attributes, testing, procedures, and practices can contribute to significantly reducing the
3
probability of CCF occurrence. However, there are two design attributes, either of which is
sufficient to eliminate consideration of software based or software 5logic based CCF. 4For other
6
systems, different design attributes and testing can be used if: (1) technically acceptable, (2)
suitable for the application, and (3) defensible. Properly implemented, these different attributes
could serve to significantly reduce uncertainty and establish that the risk is determined
negligible or acceptable.
To simplify and to facilitate the D3 analysis, a CCF may be assessed using best-estimate 7
8
methods and realistic assumptions. However, such methods are not appropriate for use in
evaluating the effects of failures when performing 50.59 evaluations. Unless already
incorporated into the design and licensing basis, best-estimate methods cannot be used for
evaluating different results than those previously evaluated in the UFSAR.
A defense-in-depth evaluation may reveal any direct or indirect impacts on interfaces with
existing plant SSCs. This type of evaluation may reveal there are existing backup capabilities
that could serve to mitigate any negative effects of possible low likelihood failures that could be
introduced through the proposed design of the modification.
5.3 Appropriate Resolution to Identified Failures
If a postulated common cause failure of a digital modification has been provisionally determined
to be not sufficiently low, in general, the following options can be considered:
- seek NRC approval first, pursuant 10 CFR 50.90 for the modification;
- satisfy 10 CFR 50.59 criteria using an alternative approach6; or
- redesign the proposed modification so that a sufficiently low likelihood of failure conclusion
could be made.
9
6 10 example of an alternative approach is a deterministic conclusion that failure likelihood is less than comparable
An
failures in the UFSAR.
Page: 30
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 4:06:47 PM
This contradicts previous statements that say other systems may be as important as RTS/ESFAS. Therefore, a D3 analysis is needed for any of these important
systems. However, only the CCF susceptibility analysis is required. If there is no CCF vulnerability (i.e., susceptibility) then no further analysis is required (i.e. no
further CCF mafunction results analysis).
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 4:04:36 PM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 4:09:15 PM
Clarify that this does not apply to other systems that are as important as RTS/ESF, including load sequencers and HSI for credited manual actions.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 4:08:13 PM
Number: 5 Author: KenSc Subject: Sticky Note Date: 01/24/2018 4:09:10 PM
BTP 7-19 is guidance for Staff review. Therefore, these other attributes can be used when accompanied by Staff review. Now you are changing the Staff policy
to allow these other attributes to be used without Staff review and without additional endorsed Staff guidance. We need Staff endorsement of NEI 16-16 before
additional attributes can be used without additional Staff review.
Number: 6 Author: KenSc Subject: Highlight Date: 01/24/2018 11:39:34 AM
Number: 7 Author: KenSc Subject: Sticky Note Date: 01/24/2018 4:09:58 PM
You are making a statement with inadequate justification. "Best estimate" methods are used in most, maybe all, FSARs for all beyond design basis events. SECY
93-087 and BTP 7-19 define CCF with concurrent accidents as a beyond design basis event. Now, you are using this RIS to say "best estimate" methods cannot
be used for beyond design basis events, which is a change to current NRC policy.
Number: 8 Author: KenSc Subject: Highlight Date: 01/24/2018 11:40:21 AM
Number: 9 Author: KenSc Subject: Sticky Note Date: 01/24/2018 2:13:25 PM
This is not an alternate approach. It is your definition of "sufficiently low". Therefore, this is a prerequisite, not an alternate.
Number: 10 Author: KenSc Subject: Highlight Date: 01/24/2018 11:43:50 AM
RIS 2002-22 Supplement 1, Attachment
Page 23 of 27
NEI 01-01 Section 5.1.4, states, in part, with regard to appropriate resolution for identified
potential failures, the following:
Modify the design or apply greater emphasis to appropriate parts of the design
process to address the potential failure. If the failure is considered significant
because of a lack of confidence (or difficulty in achieving reasonable assurance)
in a portion of the design or in a particular software element in the design, then
one option may be to apply additional design verification or testing activities.
This additional design verification or testing could develop the needed confidence
and achieve reasonable assurance that the likelihood of the failure is such that it
is no longer considered a significant risk [sufficiently low]. Alternatively, the
design itself may be modified to either preclude the failure (e.g., make it fail safe
for this particular failure) or add internal backups in the design, such as
redundancy or diversity.
Redesigning a proposed modification to include additional design attributes, design features (e.g.,
internal or external systematic diversity) and/or additional design verification and testing activities
is a recommended option for licensees to consider if the licensee wants to implement the
modification without prior NRC approval. Redesigning could also help ensure potential new
failure modes and misbehaviors are adequately addressed in the design. Providing additional
design verification and/or testing activities on software or software-based elements of a proposed
design that demonstrates high reliability can be a key consideration in demonstrating the overall
dependability of the proposed modification and that the modification will exhibit a low likelihood of
failure.
NEI 01-01 Section 5.1.4, also states, in part, with regard to appropriate resolution for identified
potential failures, the following:
1
2
Rely on existing backup capability offered by existing systems to address the
failure - other equipment or systems that provide alternate ways of
accomplishing the function or otherwise provide backup for this failure. This may
include operator action if there is adequate information and time available for the
operator to act, and with appropriate procedures and/or training.
Supplement the existing backup capability such that the failure is adequately
addressed. This could include improving the ability to detect the failure
automatically so the repair response will be timely, improving procedures and
training for the operators to mitigate the effects of the failure, or providing
additional backup capability (e.g., manually operated switches for critical
functions and procedural guidance for their use), so that the resulting risk is
insignificant.
3
Reliance on existing backup capability that has been evaluated and documented as part of a
4
plants licensing bases is one acceptable means to address postulated failure modes and
undesirable behaviors of a proposed digital I&C modification. Similarly, re-design of existing
backup capabilities is also considered acceptable, as a means to address failures that can be
introduced by the modification. In cases where reliance on back-up capability or operator actions
is not part of the plants licensing basis, prior NRC approval would likely be required.
Page: 31
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 12:01:52 PM
"Best estimate" methods facilitate crediting backups. Without "best estimate" methods backups cannot be credited because they will never achieve the same
performance (e.g. response time, design basis margin to critical safety function limits) as the original system.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 11:59:40 AM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 12:03:16 PM
This is not an economical means nor is it likely to show equivalent design basis results. This is why "best estimate" methods are needed.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 12:02:23 PM
RIS 2002-22 Supplement 1, Attachment
Page 24 of 27
5.4 Documentation of Engineering Evaluations
The documentation of adequate engineering evaluation outlines the identification of potential
new failure modes or undesirable behaviors on the design function of the modified SSC(s) or
other SSC(s), the possible effects of these vulnerabilities on plant safety, and the design
features or operating provisions that are being put into place to prevent and/or mitigate their
occurrence as well as descriptions of the types of engineering evaluations performed.
Documenting an adequate engineering evaluation of appropriate resolutions to the identified
vulnerabilities permits a clear understanding by designers and future evaluators of the potential
effects of the vulnerabilities to plant safety and operations.
Table 2 below provides a suggested outline for documentation to support NEI 01-01 Appendix B
guidance for engineering evaluations that supports and forms the basis for qualitative
assessments for safety-related and non-safety related SSCs, as applicable. Although not
required, licensees may use Table 2 as an example basis for the level of detail, types of
evaluations, and documentation such that technical conclusions reached through the
engineering evaluations can be verified independently. Implementation details are at the
discretion of the licensee, consistent with the licensees procedures.
Engineering Evaluations and Documentation for Non-Safety Related SSCs
With regard to engineering evaluations of non-safety related SSCs, there may be differences in
the level of detail, types of analyses and documentation based upon the non-safety related
SSC(s) being modified and the characteristics of the design within the proposed modification.
Adequate engineering evaluation for non-safety related SSCs helps ensure:
- Postulated new failure modes do not result in concurrent failures in shared resources,
common hardware and software, or communications among two or more different
non-safety related SSCs such as the combining of different design functions that were
previously separate (e.g. Feedwater and Turbine Bypass controls).
- Postulated new failure modes do not exist that could propagate to two or more different
non-safety related SSCs such that the effect could place the plant into an unanalyzed
condition based upon the plants existing safety analysis.
- Identified vulnerabilities have been adequately addressed (e.g. specific design features,
quality of the design processes or demonstration of relevant operating experience).
Documentation for non-safety related modifications should be consistent with the licensees
procedures. Licensees need not prepare formal qualitative assessments for every proposed
digital modification to non-safety related SSCs where the nature of the proposed modification
does not have the characteristics described above (i.e., with the potential to impact assumptions
in the safety analysis), consistent with requirements of licensee procedures.
This page contains no comments
RIS 2002-22 Supplement 1, Attachment
Page 25 of 27
Table 2Example - Engineering Evaluation Documentation Outline
to support a Qualitative Assessment
Topical Area Description
Step 1 Describe the full extent of the SSCs to be modifiedboundaries of the
Identification design change, interconnections with other SSCs, and potential
commonality to vulnerabilities with existing equipment.
- What are all of the UFSAR-described design functions of the
upgraded/modified components within the context of the plant
system, subsystem, etc.?
- Describe what design function(s) that were provided by the
previously installed equipment are affected and how those same
design functions will be accomplished by the modified design. Also
describe any new design functions to be performed by the modified
design that were not part of the original design.
- What assumptions and conditions are expected for each associated
design function for either safety-related or power generation
purposes? For example, the evaluation should consider both active
and inactive states, as well as transitions from one mode of
operation to another.
Step 2Identify Consider the possibility that the proposed modification may have
potential introduced potential single failures and plausible common cause failures.
vulnerabilities: failure * What are potential new undesirable behaviors of the modified
modes and system? A key consideration is that undesirable behaviors may
undesirable behavior not necessarily constitute a SSC failure, but a mis-operation. (e.g.,
spurious actuation)
- Consider errors or failures as a result of hardware, software
including operating systems, application software, combining of
functions onto the same controller(s), introduction of shared
resources, or common hardware and software, etc.
- Are there interconnections or interdependencies among the
modified SSC and other SSCs? This could be facilitated by use of
digital communications, modification of control logic, common
usage of hardware/software, etc.
- Are there potential new sources of common cause failure being
introduced that are also subject to common triggering
mechanisms with those of other SSCs not being modified?
- What potential failure modes or undesired behaviors may be
introduced as a result of the modification (e.g. new operator
interfaces, introduction of digital communications)
Step 3Assess the * Could the possible new failure mode or undesired behavior lead to
effects of the a plant trip or transient?
identified * Could the possible new failure mode or undesired behavior
vulnerabilities prevent performance of a safety function of the SSC(s) being
modified?
- Can the possible new failure mode or undesired behavior affect
the ability of other SSCs to perform their safety function?
- Could the possible new failure mode of the SSC, concurrent with
a similar failure of another SSC not being modified but sharing a
This page contains no comments
RIS 2002-22 Supplement 1, Attachment
Page 26 of 27
Table 2Example - Engineering Evaluation Documentation Outline
to support a Qualitative Assessment
Topical Area Description
common vulnerability and triggering mechanism, place the plant
into an unanalyzed condition, or into a condition for which the
other SSC was assumed to function as expected for a particular
event analyzed in the existing1 safety analysis?
2
- What are the results of the postulated new failure(s) of the
modified SSC(s) compared to previous evaluation results
described in the UFSAR?
- Does the possible new failure mode or undesired behavior affect
the ability of the modified SSC or other SSCs to provide its design
function (as defined in NEI 96-07)?
Step 4Identify What actions are being taken (or were taken) to address significant
appropriate identified vulnerabilities?
resolutions for each * Are further actions required?
identified vulnerability * Re-design in order to add additional design features or attributes?
- Credit existing backup capability? 3
- Is there 4means to annunciate the postulated failure or misbehavior
to the operator?
Step 5Rationale Provide a brief description of why the identified resolutions described in
Step 4 of this table adequately address the identified vulnerabilities in
Step 3 of this table.
Step 6 * An acceptable documentation describes each of the resolutions
Documentation of needed to address the potential low likelihood failure modes
Available Evidence identified in Step 2 of this table
- Conformance to regulatory requirements (e.g. General Design
Criteria and Regulatory Guides) and Industry consensus
standards, etc. that are met or credited. (e.g., seismic, EMI/RFI,
ambient temperature, heat contribution, etc.), as applicable.
- Quality of the Design Processes employed in such as within the
software life cycle development (e.g., verification and validation
processes used as evident in a traceability matrix, quality
assurance (QA) documentation, unit test and system test results,
etc.,),
- Description of relevant Operating History (e.g., platform used in
numerous applications worldwide, etc. with minimal failure history,
etc.)
- Description of how the design features/attributes are credited
towards resolution of the vulnerabilities identified (e.g., internal
design features within the digital I&C architectures such as self-
diagnostic and self-testing features or physical restrictions
external to the digital I&C portions of the modified SSC(s)),
defense-in-depth (e.g., internal systematic diversity, internal back-
up capability, etc.)
- Engineering evaluations performed such as failure analysis,
dependability analysis, defense-in-depth analysis, etc.
Page: 34
Number: 1 Author: KenSc Subject: Sticky Note Date: 01/24/2018 4:18:58 PM
Rewrite to clarify that this refers to "bounded" "plant-level" end-results.
Number: 2 Author: KenSc Subject: Highlight Date: 01/24/2018 4:17:55 PM
Number: 3 Author: KenSc Subject: Sticky Note Date: 01/24/2018 4:16:43 PM
Self-announcing does not always require alarms. A CCF that repositions a plant component and causes a plant transient is immediately identifiable.
Number: 4 Author: KenSc Subject: Highlight Date: 01/24/2018 4:15:38 PM
RIS 2002-22 Supplement 1, Attachment
Page 27 of 27
Table 2Example - Engineering Evaluation Documentation Outline
to support a Qualitative Assessment
Topical Area Description
Step 7Conclusion Apply the results of the engineering evaluation to the qualitative
assessment to respond to the 50.59 evaluation questions as appropriate.
6. Qualitative Assessment Documentation
NRC endorsed guidance for documenting 10 CFR 50,59 evaluations to meet the requirements
of 10 CFR 50.59 (d) is provided in both NEI 96-07, Revision 1 in Section 5.0, Documentation
and Reporting and NEI 01-01, Appendix B. Both of these documents reiterate the principals
that documentation should include an explanation providing adequate basis for the
conclusion so that a knowledgeable reviewer could draw the same conclusion.
Considerations and conclusions reached while performing qualitative assessments supporting
the evaluation criteria of 10 CFR 50.59, are subject to the aforementioned principles. In order
for a knowledgeable reviewer to draw the same conclusion regarding qualitative assessments,
details of the considerations made, and their separate and aggregate effect on any qualitative
assessments need to be included or clearly referenced in the 10 CFR 50.59 evaluation
documentation. Documentation of referenced documents includes the document name and
location of the information within any referenced document.
If the qualitative assessment categories discussed in Section 4.3 are used, each category would
be discussed in the documentation including positive and negative aspects considered,
consistent with the examples provided in Table 1. In addition, a discussion of the degree to
which each of the categories was relied on to reach the qualitative assessment conclusion
would be documented.
This page contains no comments
RIS 2002-22 Supplement 1, Attachment
Page 28 of 27
SUBJECT: NRC REGULATORY ISSUE SUMMARY, CLARIFICATION ON ENDORSEMENT
OF NUCLEAR ENERGY INSTITUTE GUIDANCE IN DESIGNING DIGITAL UPGRADES IN
INSTRUMENTATION AND CONTROL SYSTEMS, SUPPLEMENT 1 TO RIS 2002-22,
DATE: January XX, 2018
This page contains no comments