Report for the Audit of Licensee Responses to Interim Staff Evaluations Open Items Related to NRC Order EA-13-109 to Modify Licenses with Regard to Hardened Containment Vents
ML17299A781
Person / Time
Site: Nine Mile Point 
Issue date: 10/30/2017
From: Rajender Auluck
Beyond-Design-Basis Engineering Branch
To: Bryan Hanson
Exelon Generation Co
Lee B
References
CAC MF4481, EPID L-2014-JLD-0043
Download: ML17299A781 (26)


Text

UNITED ST ATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 Mr. Bryan C. Hanson Senior Vice President Exelon Generation Company, LLC President and Chief Nuclear Officer Exelon Nuclear 4300 Winfield Road Warrenville, IL 60555 October 30, 2017

SUBJECT:

NINE MILE POINT NUCLEAR STATION, UNIT 1 - REPORT FOR THE AUDIT OF LICENSEE RESPONSES TO INTERIM STAFF EVALUATIONS OPEN ITEMS RELATED TO NRC ORDER EA-13-109 TO MODIFY LICENSES WITH REGARD TO RELIABLE HARDENED CONTAINMENT VENTS CAPABLE OF OPERATION UNDER SEVERE ACCIDENT CONDITIONS (CAC NO. MF4481; EPID L-2014-JLD-0043)

Dear Mr. *Hanson:

On June 6, 2013 (Agencywide Documents Access and Management System (ADAMS)

Accession No. ML13143A334), the U.S. Nuclear Regulatory Commission (NRC) issued Order EA-13-109, "Order to Modify Licenses with Regard to Reliable Hardened Containment Vents Capable of Operation Under Severe Accident Condition," to all Boiling Water Reactor licensees with Mark I and Mark II primary containments. The order requirements are provided in to the order and are divided into two parts to allow for a phased approach to implementation. The order required licensees to submit for review overall integrated plans (OIPs) that describe how compliance with the requirements for both phases of Order EA-13-109 will be achieved.

By letter dated June 27, 2014 (ADAMS Accession No. ML14184B340), Exelon Generation Company, LLC. (the licensee) submitted its Phase 1 OIP for Nine Mile Point Nuclear Station, Unit 1 (NMP1). By letters dated December 16, 2014, June 30, 2015, December 15, 2015 (which included the combined Phase 1 and Phase 2 OIP), June 30, 2016, December 14, 2016, and June 30, 2017 (ADAMS Accession Nos. ML14356A192, ML15181A017, ML15364A075, ML16182A013, ML16349A033, and ML17181A033, respectively), the licensee submitted its 6-month updates to the OIP. The NRC staff reviewed the information provided by the licensee and issued interim staff evaluations (ISEs) for Phase 1 and Phase 2 of Order EA-13-109 for NMP1 by letters dated March 26, 2015 (ADAMS Accession No. ML15069A671), and August 30, 2016 (ADAMS Accession No. ML16231A452), respectively. When developing the ISEs, the staff identified open items where the staff needed additional information to determine whether the licensee's plans would adequately meet the requirements of Order EA-13-109.

The NRC staff is using the audit process described in the letters dated May 27, 2014 {ADAMS Accession No. ML14126A545), and August 10, 2017 (ADAMS Accession No. ML17220A328),

to gain a better understanding of licensee activities as they come into compliance with the order.

As part of the audit process, the staff reviewed the licensee's closeout of the ISE open items.

The NRG staff conducted a teleconference with the licensee on October 12, 2017. The enclosed audit report provides a summary of that aspect of the audit.

If you have any questions, please contact me at 301-415-1025 or by e-mail at Rajender.Auluck@nrc.gov.

Docket No.: 50-220

Enclosure:

Audit report cc w/encl: Distribution via Listserv Sincerely, Rajender Auluck, Senior Project Manager Beyond-Design-Basis Engineering Branch Division of Licensing Projects Office of Nuclear Reactor Regulation

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 AUDIT REPORT BY THE OFFICE OF NUCLEAR REACTOR REGULATION AUDIT OF LICENSEE RESPONSES TO INTERIM STAFF EVALUATIONS OPEN ITEMS RELATED TO ORDER EA-13-109 MODIFYING LICENSES WITH REGARD TO RELIABLE HARDENED CONTAINMENT VENTS CAPABLE OF BACKGROUND OPERATION UNDER SEVERE ACCIDENT CONDITIONS EXELON GENERATION COMPANY. LLC.

NINE MILE POINT NUCLEAR STATION. UNIT 1 DOCKET NO. 50-220 On June 6, 2013 (Agencywide Documents Access and Management System (ADAMS)

Accession No. ML13143A334), the U.S. Nuclear Regulatory Commission (NAG) issued Order EA-13-109, "Order to Modify Licenses with Regard to Reliable Hardened Containment Vents Capable of Operation Under Severe Accident Condition," to all Boiling Water Reactor (BWR) licensees with Mark I and Mark II primary containments. The order requirements are divided into two parts to allow for a phased approach to implementation.

Phase 1 of Order EA-13-109 requires license holders of BW Rs with Mark I and Mark 11 primary containments to design and install a Hardened Containment Vent System (HCVS), using a vent path from the containment wetwell to remove decay heat, vent the containment atmosphere (including steam, hydrogen, carbon monoxide, non-condensable gases, aerosols, and fission products), and control containment pressure within acceptable limits. The HCVS shall be designed for those accident conditions {before and after core damage) for which containment venting is relied upon to reduce the probability of containment failure, including accident sequences that result in the loss of active containment heat removal capability or extended loss of alternating current power (ELAP). The order required all applicable licensees, by June 30, 2014, to submit to the Commission for review an overall integrated plan (OIP) that describes how compliance with the Phase 1 requirements described in Order EA-13-109 Attachment 2 will be achieved.

Phase 2 of Order EA-13-109 requires license holders of BWRs with Mark I and Mark II primary containments to design and install a system that provides venting capability from the containment drywell under severe accident conditions, or, alternatively, to develop and implement a reliable containment venting strategy that makes it unlikely that a licensee would need to vent from the containment drywell during severe accident conditions. The order required all applicable licensees, by December 31, 2015, to submit to the Commission for Enclosure review an OIP that describes how compliance with the Phase 2 requirements described in Order EA-13-109 Attachment 2 will be achieved.

By letter dated June 27, 2014 (ADAMS Accession No. ML14184B340), Exelon Generation Company, LLC. (Exelon, the licensee) submitted its Phase 1 OIP for Nine Mile Point Nuclear Station, Unit 1 (NMP1). By letters dated December 16, 2014, June 30, 2015, December 15, 2015 (which included the combined Phase 1 and Phase 2 OIP), June 30, 2016, December 14, 2016, and June 30, 2017 (ADAMS Accession Nos. ML14356A192, ML15181A017, ML15364A075, ML16182A013, ML16349A033, and ML17181A033, respectively), the licensee submitted its 6-month updates to the OIP, as required by the order.

The staff reviewed the information provided by the licensee and issued interim staff evaluations (ISEs) for Phase 1 and Phase 2 for NMP2 by letters dated March 26, 2015 (ADAMS Accession No. ML15069A671), and August 30, 2016 (ADAMS Accession No. ML16231A452), respectively.

When developing the ISEs, the staff identified open items where the staff needed additional information to determine whether the licensee's plans would adequately meet the requirements of Order EA-13-109.

The NRC staff is using the audit process in accordance with the letters dated May 27, 2014 (ADAMS Accession No. ML14126A545), and August 10, 2017 (ADAMS Accession No. ML17220A328), to gain a better understanding of licensee activities as they come into compliance with the order. The staff reviews submitted information, licensee documents (via ePortals), and preliminary Overall Program Documents (OPDs)/OIPs, while identifying areas where additional information is needed. As part of this process, the staff reviewed the licensee closeout of the ISE open items.

AUDIT

SUMMARY

As part of the audit, the NRC staff conducted a teleconference with the licensee on October 12, 2017. The purpose of the audit teleconference was to continue the audit review and provide the NRC staff the opportunity to engage with the licensee regarding the closure of open items from the ISEs. As part of the preparation for these audit calls, the staff reviewed the information and/or references noted in the OIP updates to ensure that closure of ISE open items and the HCVS design are consistent with the guidance provided in Nuclear Energy Institute (NEI) 13-02, Rev. 1 and related documents (e.g. white papers (ADAMS Accession Nos. ML14126A374, ML14358A040, ML15040A038 and ML15240A072, respectively) and frequently asked questions (FAQs, ADAMS Accession No. ML15271A148)) that were developed and reviewed as part of overall guidance development. The NRC staff audit members are listed in Table 1.

Table 2 is a list of documents reviewed by the staff. Table 3 provides the status of the ISE open item closeout for NMP1. The open items are taken from the Phase 1 and Phase 2 IS Es issued on March 26, 2015, and August 30, 2016, respectively.

FOLLOW UP ACTIVITY The staff continues to audit the licensee's information as it becomes available. The staff will issue further audit reports for NMP1, as appropriate.

Following the licensee's declarations of order compliance, the licensee will provide a final integrated plan (FIP) that describes how the order requirements are met. The NRC staff will evaluate the FIPs, the resulting site-specific OPDs, as appropriate, and other licensee documents, prior to making a safety determination regarding order compliance.

CONCLUSION This audit report documents the staff's understanding of the licensee's closeout of the ISE open items, based on the documents discussed above. The staff notes that several of these documents are still preliminary, and all documents are subject to change in accordance with the licensee's design process. In summary, the staff has no further questions on how the licensee has addressed the ISE open items, based on the preliminary information. The status of the NRC staff's review of these open items may change if the licensee changes its plans as part of final implementation. Changes in the NRC staff review will be communicated in the ongoing audit process.

Attachments:

1. Table 1 - NRC Staff Audit and Teleconference Participants
2. Table 2 - Audit Documents Reviewed
3. Table 3-ISE Open Item Status Table

Table 1 - NRC Staff Audit and Teleconference Participants Title Team Member Oraanization Team Lead/Sr. Project Manager Rajender Auluck NRR/DLP Project Manager Support/Technical Suooort - Containment I Ventilation Brian Lee NRR/DLP Technical Support - Containment I Ventilation Bruce Heida NRR/DLP Technical Support - Electrical Kerby Scales NRR/DLP Technical Support-Balance of Plant Kevin Roche NRR/DLP Technical Support-l&C Steve Wyman NRR/DLP Technical Support - Dose John Parillo NRR/DRA

Table 2 - Audit Documents Reviewed ECP 13-000086-103 - Missile Evaluation ECP 13-000086 - DCS Electrical Section, Battery and Charger S1 O-HVAC-HV11, "TB Building Maximum & Minimum Temperatures" HCVS-OGP HCVS Hose Radiological Evaluation S22.4-201.1 P002, "HCVS Piping Analysis for Non-Torus Attached Piping" S22.4-201.13F004, Revision 0, "Hardened Contaniment Vent Capacity" ECP 13-000086-1 03 - Suppresion Pool Thermal Capacity S22.4-201.13F001, Revision 0, "Hardened Containment Vent Purge System Design Calculation" Procedure N1-0P-51, Revision 01300 - Plant Communications H21C-115, "NMP1 Hardened Containment Vent System Dose Analysis" Calculation 125VDCSCES-FLEX-BDB, Revision 0, "Fukushima/NFPA-805 125VDC Portable Battery Charger Equipment Sizing" S22.4-201.13M002, Revision 0, "HCVS Valve Motive Gas Supply Sizing" VENRPT-15-000013-Seismic Qualifiaction Summary for Hardened Containment Vent Components ECP 13-000086-103 - Instrumentation & Controls Section 4.1.36 ECP 13-000086-103 - Environmental Conditions and Impacts Section 4.1.14 ECP 13-000086-103 - Assessment of Operator Access to HCVS Equipment Section 4.1.19 N2-MISC-004, Revision 0, "MAAP Analysis to Support SAWA Strategy" ECP-17-000279-CN-001 - H21C-115, "Hardened Containment Vent System (HCVS)

Radiological Dose Analysis" BWROG-TP-008, "Severe Accident Water Addition Timing" BWROG-TP-011, "Severe Accident Water Management Supporting Evaluations"

ISE Open Item Number Requested Action Phase 1 ISE 011 Make available for NRC staff audit the seismic and tornado missile final design criteria for the HGVS stack.

Nine Mile Point Nuclear Station, Unit 1 Vent Order Interim Staff Evaluation Open Items:

Table 3 - ISE Open Item Status Table Licensee Response - Information NRC Staff Close-out notes provided in 6 month updates and on the ePortal Seismic Design of HCVS stack The NRC staff reviewed the information provided in the 6*

The HCVS vent piping system has been month updates and on the evaluated to Seismic Category I ePortal.

requirements in pipe stress calculations S22.4-201.1 P002 and S22.4-201.13P003 Calculations S22.4-201.1 P002 consistent with the plants seismic design and S22.4-201.13P003 address basis to comply with NEI 13-02, Section the HCVS seismic qualification.

5.2 seismic design guidance. Per NRG The licensee evaluated the entire Letter, May 9, 2014, "

Subject:

Screening HCVS system to Seismic and Prioritization Results Regarding Category I, which is consistent Information Pursuant to Title 1 Oof the with the plant's seismic design-Code of Federal Regulations 50.54(f) basis.

Regarding Seismic Hazard Reevaluations for Recommendation 2.1 of the Near-The Engineering Change Term Task Force Review of Insights from Package ( EGP) 000086-103 the Fukushima Dai-ichi Accident", the addresses the HCVS Tornado NRG concluded that NMP1 "screened Missile Protection. The licensee out" of performing the seismic risk credits NEI 13-02, Section 5.1.1.6 evaluation as part of the HCVS seismic risk informed approach to wind-analysis. Therefore, use of current borne missiles. The licensee licensing basis and design basis seismic indicated they have contingency Information (i.e., response spectra) is actions available in the event a considered acceptable for the BOB wind-borne missile blocks vent

[beyond-design-basis] analysis of the gas flow. The licensee's design is HCVS piping system at NMP1. The consistent with the endorsed above referenced pipe stress calculations white paper and meets all of the are available for NRG review in the tornado missile assumptions ePortal.

identified in HCVS-WP-04.

Safety Evaluation (SE) status Closed; Pending; Open (need additional information from licensee)

Closed

[Staff evaluation to be included in SE Section 3.2.2]

Missile Protection of the outdoor HCVS No follow-up questions.

stack NEI 13-02, Section 5.1.1.6 requires that missile impacts are to be considered for portions of the HCVS. The Nuclear Energy Institute (NEI) issued a white paper, HCVS-WP-04, endorsed by the NRC, which provides a risk-informed approach to evaluate the threat posed to exposed portions of the HCVS by wind-borne missiles. The white paper concludes that the HCVS is unlikely to be damaged in a manner that prevents containment venting by wind-generated missiles coincident with an ELAP or LUHS [loss of ultimate heat sink], for plants that are enveloped by the assumptions in the white paper.

A NMP1 specific missile evaluation is documented in the Engineering Change Package (ECP) consistent with HCVS-WP-04. The conclusion of the evaluation is that NMP1 meets all of the tornado missile assumptions identified in HCVS-WP-04 and as such, supplementary protection is not required for the HCVS piping and components. The ECP missile evaluation is available on the eportal for NRC review.

Phase 1 ISE 01 2 The HCVS is sized to provide sufficient The NRC staff reviewed the Closed venting capacity to prevent a long-term information provided in the 6-Make available for NRC staff overpressure failure of the containment by month updates and on the

[Staff evaluation to be audit analyses demonstrating keeping the containment pressure below ePortal.

included in SE Section that HCVS has the capacity to the containment design pressure and the 3.1.2.1]

vent the steam/energy primary containment pressure limit. The ECP-13-000086-103, Attachment equiva1eni ul cne rercent of HCVS has been demonstrated by B determined the energy released licensed/rated thermal power calculation S22.4-201.13F004 to have the for 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> is 2.9E8 BTUs. The (unless a lower value is capacity to Vl='r*,t t~e steam/enerov justified), and that the equivalent of 1 percent of licensed/rated capacity of the suppression pool suppression pool and the thermal power. The calculation indicates is 6.299E8 BTUs.

HCVS together are able to that a vent capacity of approximately absorb and reject decay heat, 68,300 lbm/hour of saturated steam at the Analysis ECP-13-000086-MU-008 such that following a reactor primary containment design pressure is used the RELAP5 computer shutdown from full power required. The results of this calculation program. The 1% venting containment pressure is show that the capacity of the HCVS capacity required is 68,303 restored and then maintained exceeds this value.

lbm/hr. The vent capacity is below the primary containment 63,259 lbm/hr at 25 per square design pressure and the The suppression pool thermal capacity inch gauge (psig) and 71,658 primary containment pressure must be sufficient to absorb the decay lbm/hr at 30 psig. The vent limit.

heat generated during at least the first 3 capacity at 35 psig is 79,859 hours0.00994 days <br />0.239 hours <br />0.00142 weeks <br />3.268495e-4 months <br /> following reactor shutdown. The lbm/hr. Updated Final Safety total decay heat available to the Analysis Report Section Vl.B.2.1 suppression pool for the first 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> design limits the Drywell and 35 following reactor shutdown, when starting psig and 25°F for the Suppression at 102% reactor thermal power, is 2.91 Pool (Torus). This document OE8 BTU [British Thermal Unit]; and the confirmed that the size of the suppression pool thermal capacity, i.e., its wetwell portion of the HCVS capacity to absorb energy, is 6.299E8 provides adequate capacity to BTU. Therefore, there is sufficient meet or exceed the order criteria.

suppression pool capacity to absorb the decay heat during the first 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> No follow-up questions.

following reactor shutdown, and the EA-13-109, Attachment 2, Requirement 1.21 and NEI 13-02, Section 4.1.1 are satisfied.

The calculations supporting the above response are available for NRC review in the ePortal.

Phase 1 ISE 01 3 As discussed in the December 2015 OIP The NRC staff reviewed the Closed submittal, the NMP1 design will use an information provided in the 6-Provide a description of the Argon purge system to prevent the month updates and on the

[Staff evaluation to be final design of the HCVS to possibility of hydrogen detonation and ePortal.

included in SE Section address hydrogen detonation deflagration. The argon purge system 3.1.2.11]

and deflagration.

design is illustrated on Piping and The licensee's design is Instrumentation Drawing C-18014-C, Sht.

consistent with option 3 of the 7, and is available for NRC review in the endorsed white paper HCVS-WP-ePortal. The arqon purqe system was

03.

sized in calculation S22.4-201.13F001 which is on the ePortal.

Calculation S33.4-201.13F001, "HCVS Purge System Design,"

determined the quantity of Argon required to inert the hydrogen in the vent system to preclude the potential for a hydrogen deflagration. The calculation assumed 8 argon purges in the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> with a minimum of 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between purges.

No follow-up questions.

Phase 1 ISE 01 4 At NMP1, the primary operating station for The NRC staff reviewed the Closed HCVS operation is located in the Auxiliary information provided in the 6-Make available for N RC staff Control Room. A HCVS remote operating month updates and on the

[Staff evaluation to be audit documentation that station (ROS) is located in the turbine ePortal.

included in SE Section demonstrates adequate building. The location was evaluated for 3.1.1.1]

communication between the habitability and accessibility during a The communication methods are remote HCVS operation severe accident.

the same as accepted in Order locations and HCVS decision EA-12-049.

makers during ELAP and Onsite communications will be performed severe accident conditions.

using either the installed sound powered No follow-up questions.

headset system or the 450 MHz [mega hertz] radios in the talk around mode, or a combination thereof. A sound powered phone jack is available near the ROS to communicate with the rest of the plant.

Offsite communications will utilize fixed satellite phones in the Control Room and Technical Support Center (TSC). Both locations also have portable satellite phones staged.

Communications protocol for beyond design basis events are documented in CC-NM-118 and procedure N2-0P-76 which are available for NRC review on the ePortal.

These communication methods are consistent with FLEX communication practices at NMP1 and have been previously reviewed by the staff as documented in a communications safety assessment regarding NTTF Rec 9.3 Communications for NMP ([ADAMS Accession No.l ML13100A236).

Phase 1 ISE 01 5 P&IDs C18014C, Sheets 1 and 7 are The NRC staff reviewed the Closed available to the NRC for review on the information provided in the 6-Provide a description of the ePortal. The P&IDs combined with the month updates and on the

[Staff evaluation to be strategies for hydrogen control following system description provides a ePortal.

included in SE Section that minimizes the potential for summary of the system design intended 3.1.2.12]

hydrogen gas migration and to minimize the potential for hydrogen gas The licensee has installed a new ingress into the reactor migration and ingress into the reactor HCVS wetwell pipe which building or other buildings.

building or other buildings:

provides a dedicated HCVS flowpath from the wetwell The new HCVS wetwell pipe has a penetration PCIVs to the outside dedicated HCVS flowpath from the with no interconnected wetwell penetration PCIVs [primary downstream piping. The staff's containment isolation valve] to the outside review of the proposed system with no interconnected downstream indicates that the licensee's piping. The HCVS discharges the effluent design appears to maintain to a release point above main plant hydrogen below flammability structures. The new HCVS vent limits.

interfaces with lines 201.1-20-L T (upstream of PCIVs IV-201-16 and IV-No follow-up questions.

201-17) and 201.1-3-L T (upstream of PCIV IV-201.2-33 and IV-201.2-06) of the Containment System.

Line 201.1-20-L T is utilized for supplying nitrogen to the torus through isolation valves IV-201-16 and IV-201-17 during primary containment inerting. Similarly, the containment purge fan takes suction through this flow path when de-inserting containment. IV-201-16 and IV-201-17 are normally closed and automatically close upon receipt of a containment isolation signal from the Reactor Protection System or a high radiation signal from the Off-Gas System monitors.

Line 201.1-3-L T provides nitrogen makeup to the torus through isolation valves IV-201.2-33 and IV-201.2-06 during normal operation. IV-201.2-33 and IV-201.2-06 are normally closed and automatically close upon receipt of a containment isolation signal from the Reactor Protection System or a loss of nitrogen to the valve actuator.

The new HCVS vent will be normally isolated from the Containment System by two new normally closed PCIVs (IV-201.13-7 4 and IV-201.13-71) and will not impact the operation of these interfacing systems. The new HCVS piping is designed as an independent, isolable branch off of Line 201.1-20-L T. There are no branch lines downstream of the HCVS vent piping PCIVs (IV-201.13-71 and IV-201.13-7 4), which interface with existing plant systems and there is no potential for cross flow from the HCVS, thereby meeting the requirements of NEI 13-02, Section 1.2.3. Therefore, valves IV-201.2-33, IV-201.2-06, IV-201-16 and IV-201-17 are not considered boundary valves. These valves are exposed to the containment atmosphere, as a result of the original plant design, independent of the addition of HCVS.

Phase 1 ISE 01 6 An assessment of Operator access to The NRG staff reviewed the Closed HCVS equipment was performed and information provided in the 6-Make available for NRG staff documented in the Design Consideration month updates and on the audit an evaluation of Section (DCS) of Engineering Change ePortal.

temperature and radiological Package ECP-13-000086 which has been

[Staff evaluation to be conditions to ensure that loaded on the ePortal.

ECP-13-000086-103 documents included in SE Sections operating personnel can safely that temperature and radiological 3.1.1.2 and 3.1.1.3]

access and operate controls The assessment evaluated the conditions should not inhibit and support equipment.

temperature and radiological conditions of operator actions needed to initiate all areas that will be needed to be and operate the HCVS during an accessed by plant Operators in order to ELAP with severe accident initiate and operate the HCVS during a conditions.

beyond design basis event. The assessment provides the expected Temperatures do not exceed 110 temperature and radiological conditions in degrees Fahrenheit (F°), which is each area documented in tabular form in acceptable for long-term the DCS. The assessment concludes that personnel habitability.

during the 7 days of sustained operation Radiological conditions result in during a beyond design basis event the low operator dose.

predicted environmental and radiological conditions will be acceptable for the No follow-up questions.

operators to gain access to areas required for HCVS operation in the primary and remote operatinQ stations.

Phase 1 ISE 01 7 Batteries/Battery Charger Sizing:

The NRG staff reviewed the Closed information provided in the 6-Make available for NRG staff The new battery selected is a sixty (60) month updates and on the

[Staff evaluation to be audit the final sizing evaluation cell GNB battery with the battery cells ePortal.

included in SE Section for HCVS batteries/battery connected in series to create 125VDC 3.1.2.6]

charger including incorporation nominal voltage. The battery is a Valve The licensee stated that all into FLEX DG loading Regulated Lead Acid (VALA) type rated electrical power required for calculation.

for 104 ampere-hours. The battery is operation of HCVS components is selected in accordance to IEEE [Institute provided by a dedicated HCVS of Electrical and Electronics Engineers]

battery charger and batteries.

485. The Battery Sizing Requirements indicates that based on 1.5 ampere The battery sizing requirements loading requirements for 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> duty confirmed that the HCVS period, a minimum of a sixty (60) cell, 55 batteries have a minimum ampere hours battery is required to bound capacity capable of providing the required battery duty cycle and end-of power for 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> without cycle battery terminal voltage recharging, and therefore is requirements. The selected battery adequate.

capacity of 104 ampere-hours is more than the minimum required 55 ampere-hours battery capacity. Therefore, the The licensee revised the FLEX selected battery is adequate.

portable battery charger equipment sizing calculation The battery charger is rated for 130 volts 125VDCSCES-FLEX-BDB to add nominal DC [direct current] output the loads for the HCVS. The voltage, 10 amperes nominal DC output NRC staff reviewed the revised current, 120 volts AC [alternating current]

calculation and confirmed that input voltage and a current limit with the additional load added, it's adjustment range of 50% - 120%.

still within the capacity and capability of the portable battery The HCVS loads may also be powered charger BC-BOB.

via 125 voe [volts direct current] battery board 12 which is downstream of the No follow-up questions.

station battery charger 12 (DC side). The FLEX DG sizing calc. 600VACDGES-FLEX-BOB was already sized to accommodate the station battery charger 12 full load rating (AC side). Additionally, the HCVS loads will be powered by FLEX portable power sources at T =24 hours when the station battery would have been fully charged and load shedding would have been completed during ELAP.

Therefore, there will be no impact on the FLEX DG loading calculation 600VACDGES-FLEX-BDB. A minor revision to the FLEX portable battery charger equipment sizing calculation 125VDCSCES-FLEX-BDB was completed to address the addition of the HCVS loads. The calculation concluded that the HCVS panel load addition ot i.5 amperes DC is negligible and still within the 400 ampere rating of the portable battery charger BC-BOB.

The battery/battery charger sizing requirements evaluation and the minor revision to calculation 125VDCSCES-FLEX-BOB are in the ePortal for NRC review.

Phase 1 ISE 01 8 As discussed in the December 2015 OIP The NRC staff reviewed the Closed submittal, the NMP1 design will use a information provided in the 6-Make available for NRC staff nitrogen bottle station to supply motive month updates and on the

[Staff evaluation to be audit documentation of the force to the HCVS isolation valves. The ePortal.

included in SE Section HCVS nitrogen pneumatic bottle station will be located in a readily 3.1.2.6]

system design including sizing accessible protected area in the turbine Calculation S22.4-201.13M002, and location.

building. The nitrogen supply system Revision 0 "HCVS Valve Motive design is illustrated on Piping and Gas Supply Sizing" determined instrumentation Drawing C18014-C, Sht.

that if the N2 bottles are 7, and is available for NRC review in the maintained above 1993 psig, they ePortal.

will have sufficient capacity to operate the HCVS for 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

A calculation was completed to determine the required pneumatic supply storage No follow-up questions.

volume and supply pressure required to operate the HCVS isolation valves (IV-201.13-71 and IV-201.13-74)for24hours following a loss of normal pneumatic supplies during an ELAP. Calculation S22.4-201.13M002 is available for NRC review in the ePortal.

Phase 1 ISE 01 9 New components related to HCVS The NRC staff reviewed the Closed operation are required to be designed to information provided in the 6-Make available for NRC staff operate following a seismic event. Most month updates and on the

[Staff evaluation to be audit documentation of a equipment came qualified or evaluated by ePortal.

included in SE Section seismic qualification evaluation the vendor. Some equipment was 3.2.2]

of HCVS components.

purchased as commercial grade (non-The licensee provided several safety related) and was shake tested in reports which demonstrate the order to prove the components' ability to seismic adequacy of the HCVS withstand a bounding seismic event.

components. The staff reviewed these reports and confirmed that Qualification/evaluation documentation the components required for provided by the vendor, or test results HCVS venting remain functional from shake tests were compiled into a following a design-basis single report for HCVS dedicated earthquake.

equipment (Ref. VENRPT-15-000013) with the exception of separate seismic No follow-up questions.

desiqn reports for the PCIVs and rupture disc. These reports are available on the ePortal for NRC review.

Phase 1 ISE 01 10 Description of Existing Instrumentation:

The NRC staff reviewed the Closed information provided in the 6-Make available for NRC staff In the Phases 1 and 2 combined HCVS month updates and on the

[Staff evaluation to be audit descriptions of all OIP, Part 2: Key Venting Parameters ePortal.

included in SE Section instrumentation and controls section, both drywell pressure, torus 3.1.2.8]

(existing and planned) pressure and torus level are listed as key ECP-13-000086-103 Revision 3, necessary to implement this parameters. Other Part 2 OIP sections Section 4.1.36 discusses the order including qualification only list drywell pressure and torus pool environmental conditions during methods.

level as key parameters. In Part 3 of the an accident at the locations OIP, drywall pressure and suppression containing l&C components. The pool level are stated as the key staff's review indicated that the parameters for SAWM [severe accident environmental qualification met water management] operations. The the order requirements.

following discussion has been revised since the June 2016 six-month update to No follow-up questions.

clarify what key parameters are used for HCVS initiation and cycling for Phases 1 and 2.

Existing control room indications for wetwell (suppression chamber) pressure and suppression pool (primary containment) water level are used for HCVS venting operation. Operation of the HCVS will be based on guidance in the EOPs [emergency operating procedures] and SAPs [severea accident procedures] and will follow the primary containment pressure limit (PCPL) curves contained in these procedures. The PCPL curves use suppression chamber pressure vs. primary containment water level parameters to determine when to vent containment. Therefore, containment wetwell pressure indication is preferred to determine the need, timing and effectiveness of the venting operation followinq a BDBEE, in order to ensure

that containment pressure does not exceed the PCPL Existing control room indication for wetwell pressure, shown on Pl-201.2-595A (Channel 12) and Pl-201.2-594A Channel 11 ), will be used for this purpose.

These indicators receive pressure signals from pressure transmitters PT-201.2-595 and PT-201.2-594, respectively. These pressure transmitters sense the torus pressure from a penetration at the top of the torus and therefore will not be impacted by high water levels.

Drywell pressure instrumentation may also be referenced during the event.

Containment pressure is displayed on indicator Pl-201.2-483A (Channel 12) and Pl-201.2-484A (Channet 11 ). These indicators receive pressure signals from pressure transmitters PT-201.2-483 and PT-201.2-484, respectively. Wetwell level indication is needed to determine that the wetwell vent path is preserved. Wetwell level is displayed on indicator Ll-201.2-5950 (Channel 12) and Ll-201.2-594C (Channel 11 ). Ll-201.2-5950 receives signals from PT-201.2-595 and PT-201.2-596 while Ll-201.2-594C receives signals from PT-201.2-594 and PT-201.2-680.

As indicated in the OIP, LI 58-05A (LT58-

05) can also be used to monitor torus level and Pl 201.2-106A (PT 201.2-106) can also be used to monitor drywell pressure.

The pressure and level indicators and related transmitters are all Safety Related, Reoulatory Guide 1.97 compliant components. Channel 12 is the FLEX diesel power backed loop, and Channel 11 can be powered as an alternate strategy.

Description of New Instrumentation:

The l&C scope for the HCVS is to display the following and to control the SOVs

[solenoid-operated valves] associated with the new primary containment isolation valves.

  • HCVS Isolation Valve Position Indication (POS)
  • Temperature and Radiation of the HCVS Pipe (POS)
  • Radiation of the HCVS Pipe (ROS)
  • HCVS Purge System Supply Pressure (POS and ROS)
  • HCVS Battery Voltage (ROS)

The ROS panel serves as the main power distribution for all l&C components and will contain local indicators to display HCVS battery voltage, radiation, and purge gas supply pressure. The POS panel provides all other indication except HCVS battery voltage and allows for the control of the HCVS SOVs via key lock switches.

A detailed description of new I &C components including qualification methods is included in the Engineering Change Package and is available on the ePortal for NRC review.

Phase 1 ISE 01 11 The HCVS is located in the Reactor The NRC staff re_yiewed the Closed Building, Turbine Building, Auxiliary information provided in the 6-Control Room, and outside the Reactor Make available for NRG staff Building. Environmental conditions and month updates and on the

[Staff evaluation to be audit the descriptions of local impacts are evaluated in detail in the ePortal.

included in SE Section conditions (temperature, Engineering Change Package (ECP).

3.1.1.4]

radiation and humidity)

The ECP includes a listing of the ECP-13-000086-103 Revision 3, anticipated during ELAP and components in each area along with the Section 4.1.36 discusses the severe accident for the corresponding environmental conditions environmental conditions during components (valves, including temperature, radiation and an accident at the locations instrumentation, sensors, humidity. The ECP also includes a containing l&C components. The transmitters, indicators, detailed listing of environmental staff's review indicated that the electronics, control devices, qualification requirements. The complete environmental qualification met and etc.) required for HCVS listing and information from the ECP is the order requirements.

venting including confirmation available on the ePortal for NRG review.

that the components are No follow-up questions.

capable of performing their On November 17, 2016 a teleconference functions during ELAP and between Exelon and the NRG was held to severe accident conditions.

review NMP2 Phase 1 closure of open items. In this call NMP clarified that consistent with NEI 13-02 Appendix C Section C.8.1, no further environmental qualification of existing containment parameter monitoring instrumentation is required if the instrumentation is already RG 1.97 qualified.

Phase 2 ISE 01 1 Refer to the closure summary for ISE The NRG staff reviewed the Closed Phase 2 Open Item No. 2.

information provided in the 6-Licensee to confirm through month updates and on the

[Staff evaluation to be analysis the temperature and ePortal.

included in SE Sections radiological conditions to 4.1.1.4 and 4.2.1.4]

ensure that operating Calculation $1 O-HVAC-HV11, personnel can safely access Revision 1, "TB Bldg. Max & Min and operate controls and Temperatures" along with ECP-support equipment.

13-000086-103, shows that temperature and radiological conditions should not inhibit operator actions needed to initiate and operate the HCVS during an ELAP with severe accident conditions.

No follow-up questions.

Phase 2 ISE 01 2 Equipment and Controls:

The NRC staff reviewed the Closed information provided in the 6-Licensee to evaluate the Plant instrumentation for SAWM that is month updates and on the

[Staff evaluation to be SAWA [severe accident water qualified to RG 1.97 or equivalent is ePortal.

included in SE Sections addition] equipment and considered qualified for the sustained 4.1.1.4 and 4.2.1.4]

controls, as well as ingress operating period without further Calculation S 1 O-HVAC-HV11, and egress paths for the evaluation. The following plant Revision 1, "TB Bldg. Max & Min expected severe accident instruments are qualified to RG 1.97:

Temperatures," along with ECP-Conditions (temperature, 13-000086-103, shows that humidity, radiation) for the PT-201.2-594, PT-201.2-680, PT-201.2-temperature and radiological sustained operating period.

594C -Wetwell Water Level conditions should not inhibit operator actions or SAWA PT-201.2-595, PT-201.2-596, PT-201.2-equipment and controls needed to 5950 - Wetwell Water Level initiate and operate the HCVS during an ELAP with severe PT-201.2-595, PT-201.2-595A - Wetwell accident conditions.

Pressure No follow-up questions.

PT-201.2-594 PT-201.2-594A-Wetwell Pressure Passive componems that de nnt need to change state after initially establishing SAWA flow do not require evaluation beyond the first 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, at which time they are expected to be installed and ready for use to support SAWA/SAWM.

Also the fire hoses used are the "Big 1 O" model from Key hose. This hose is a heavy duty double jacketed hose using both polyurethane and EPDM rubber. Per HCVS-OGP-009 these materials will withstand the maximum doses that can be experienced during a sever accident and are therefore acceptable.

The following additional equipment performing an active SAWA/SAWM function is considered:

SAW A/SAWM flow instrument SAW A/SAWM pump SAW A/SAWM generator Active valves in SAWA flow path (Not applicable as there are no active valves in the SAWA flow path)

The above listed additional SAWA/SAWM equipment performing an active function evaluated for radiation and temperature/humidity as described below:

SAWA/SAWM flow instrument:

The SAWA flow instrumentation will be mounted on a cart with a throttling valve and stored in the FLEX Storage Building.

During FLEX/SAW A flow injection to the RPV, the cart will be moved into the turbine building near the HCVS Remote Operating Station (ROS). A quantitative evaluation of expected dose rates has been performed per HCVS-WP-02 and found the dose rates at the flow instrument are acceptable. Refer to calculation H21 C115 loaded in the ePortal. The dose rate at the operating location of the flow meter cart (just west of the ROS, between column rows G and H) is 2.25E-05 rem/hr. The area just east of the ROS may be acceptable as well as long as an operator does not stay at the flow meter for an extended period of time as the dose rate east of the ROS increases to 7.335E-01 rem/hr per H21 C115 page C3. Using the higher dose rate, the total dose over the 7-day period is 123 rem. This dose is well below the generally accepted maximum for digital equipment, 1000 rem. The flow meter is commercial equipment and does not have a published radiation dose limit.

The selected instrument is designed for the expected flow rate, temperature and pressure for SAWA over the period of sustained operation.

Phase 2 ISE 01 3 Refer to the closure summary for ISE The NRC staff reviewed the Closed Phase 2 Open Item No. 2.

information provided in the 6*

Licensee to demonstrate how month updates and on the

[Staff evaluation to be instrumentation and equipment ePortal.

included in SE Sections being used for SAW A and 4.1.1.4 and 4.2.1.4]

supporting equipment is Calculation S10-HVAC-HV11, capable to perform for the Revision 1, "TB Bldg. Max & Min sustained operating period Temperatures," along with ECP-under the expected 13-000086-103, shows that temperature and radiological temperature and radiological conditions conditions should not inhibit operability for instrumentation and equipment being used for BAWA supporting equipment during an ELAP with severe accident conditions.

No follow-up questions.

Phase 2 ISE OI 4 The wetwell vent has been designed and The NRC staff reviewed the Closed installed to meet NEI 13-02 Rev 1 information provided in the 6-Licensee to demonstrate that guidance, which will ensure that it is month updates and on the

[Staff evaluation to be containment failure as a result adequately sized to prevent containment ePortal.

included in SE Sections of overpressure can be overpressure under severe accident 4.1 and 4.2]

prevented without a drywell conditions.

Calculation N2-MISC-004, vent during severe accident Revision 0 demonstrates the conditions.

The SAWM strategy will ensure that the suppression pool will be provided wetwell vent remains functional for the with sufficient makeup to maintain period of sustained operation. Nine Mile a heat sink for reactor decay heat, Point Unit 1 will follow the guidance (flow which will maintain containment rate and timing) for SAW A/SAWM within design limits. The SAWM described in BWROG-TP-15-008 and strategy will ensure that the BWROG-TP-15-011. The wetwell vent wetwell vent remains functional will be opened prior to exceeding the for the period of sustained PCPL value of 43 PSIG. Therefore, operation.

containment over pressurization is prevented without the need for a drywell No follow-up questions.

vent.

Phase 2 ISE 01 5 Reference Plant The NRC staff reviewed the Closed Torus freeboard volume is 525,000 information provided in the 6-Licensee to demonstrate how gallons month updates and on the

[Staff evaluation to be the plant is bounded by the ePortal.

included in SE Section reference plant analysis that NMP1 4.2.1.1]

shows the SAWM strategy is Total freeboard volume is 862,288 Calculation N2-MISC-004, successful in making it unlikely gallons Revision 0 addresses that a drywell vent is needed.

SAWA/SAWM and the ability to Reference Plant maintain containment integrity.

SAWA flow is 500 GPM [gallons per The calculation shows that minute] at 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> followed by 100 GPM sufficient water is added to from 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> to 168 hours0.00194 days <br />0.0467 hours <br />2.777778e-4 weeks <br />6.3924e-5 months <br /> maintain or increase water level in the suppression pool and NMP1 demonstrates a successful SAWA flow is 263 GPM at 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> SAWA/SAWM strategy.

followed by 54 GPM* from 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> to 168 hours0.00194 days <br />0.0467 hours <br />2.777778e-4 weeks <br />6.3924e-5 months <br /> No follow-up questions.

NMP1 has performed a plant specific MAAP [modular accident analysis program] analysis to establish an initial SAWA flow rate using the above parameters of 263 GPM at 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> followed by 54 GPM* from 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> to 168 hours0.00194 days <br />0.0467 hours <br />2.777778e-4 weeks <br />6.3924e-5 months <br />. The MAAP analysis demonstrates that the plant is bounded by the reference plant analysis and that the SAWM strategy is successful in making it unlikely that a drywell vent is needed to prevent containment failure (N1-MISC-004).

(*Note that 53 GPM was quoted in the OIP but NMP1 will use 54 GPM in its procedures consistent with the flowrate used in MAAP)

Phase 2 ISE 01 6 NMP1 utilizes the installed sound The NRG staff reviewed the Closed powered headset system and/or the 450 information provided in the 6-Licensee to demonstrate that MHz radios in the talk around mode to month updates and on the

[Staff evaluation to be there is adequate communicate between the MGR and the ePortal.

included in SE Section communication between the SAWA flow control location.

4.1]

main control room (MGR) and The communication methods are the operator at the FLEX This communication method is the same the same as accepted in Order manual valve during severe as accepted in Order EA-12-049. These EA-12-049.

accident conditions.

items will be powered and remain powered using the same methods as No follow-up questions.

valuated under EA-12-049 for the period of sustained operation, which may be longer than identified for EA-12-049.

Phase 2 ISE 01 7 Refer to the closure summary for ISE The NRG staff reviewed the Closed Phase 2 Open Item No. 2.

information provided in the 6-Licensee to demonstrate the month updates and on the

[Staff evaluation to be SAWM flow instrumentation ePortal.

included in SE Sections qualification for the expected 4.1.1.3 and 4.2.1.3]

environmental conditions.

ECP-17-000279-CN-001-H21 C115, Rev 0 discusses the

. SAWM flow instrumentation qualification. The NRG staff found through engineering judgement that the accuracy of the flow meter and the environmental qualifications related to the performance of the flow meter meet the intent of Order EA-13-109.

No follow-up questions.