Exelon Generation ~,
RS-16-177 November 28, 2016 U.S. Nuclear Regulatory Commission A TIN: Document Control Desk Washington, DC 20555-0001 Limerick Generating Station, Units 1 and 2 1 O CFR 50.54(f)
Renewed Facility Operating License Nos. NPF-39 and NPF-85 NRG Docket Nos. 50-352 and 50-353
Subject:
High Frequency Supplement to Seismic Hazard Screening Report, Response to NRG Request for Information Pursuant to 1 O CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident
References:
- 1. NRG Letter, Request for Information Pursuant to Title 1 O of the Code of Federal Regulations 50.54(f) Regarding Recommendations 2.1, 2.3, and 9.3, of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident, dated March 12, 2012(ML12053A340}
- 2. NRG Letter, Electric Power Research Institute Report 3002000704, "Seismic Evaluation Guidance: Augmented Approach for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic," As An Acceptable Alternative to the March 12, 2012, Information Request for Seismic Reevaluations, dated May 7, 2013 (ML13106A331)
- 3. NEI Letter, Final Draft of Industry Seismic Evaluation Guidance, Screening, Prioritization and Implementation Details (SPID) for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic (EPRI 1025287), dated November 27, 2012 (ML12333A168 and ML12333A170)
- 4. NRG Letter, Endorsement of Electric Power Research Institute Final Draft Report 1025287, "Seismic Evaluation Guidance, Screening, Prioritization and Implementation Details (SPID) for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic," dated February 15, 2013(ML12319A074)
- 5. Exelon Generation Company, LLC letter to NRG, Limerick Generating Station, Units 1 and 2 - Seismic Hazard and Screening Report (CEUS Sites}, Response to NRG Request for Information Pursuant to 1 OCFR50.54(f) Regarding Recommendation 2.1 of Near-Term Task Force Review of Insights from the Fukushima Dai-lchi Accident, dated March 31, 2014 (RS-14-069) (ML14090A236}
U.S. Nuclear Regulatory Commission Seismic Hazard 2.1 High Frequency Supplement November 28, 2016 Page 2
- 6. NRC Letter, Screening and Prioritization Results Regarding Information Pursuant to Title 1 O of the Code of Federal Regulations 50.54(f) Regarding Seismic Hazard Re-evaluations for Recommendation 2.1 of the Near Term Task Force Review of Insights from the Fukushima Dai-ichi Accident, dated May 9, 2014 (ML14111A147)
- 7. NRC Memorandum, Support Document for Screening and Prioritization Results Regarding Seismic Hazard Re-Evaluation for Operating Reactors in the Central and Eastern United States, dated May 21, 2014 (ML14136A126)
- 8. NEI Letter, Request for NRC Endorsement of High Frequency Program: Application Guidance for Functional Confirmation and Fragility Evaluation (EPRI 3002004396),
dated July 30, 2015 (ML15223A100/ML15223A102)
- 9. NRC Letter to NEI: Endorsement of Electric Power Research Institute Final Draft Report 3002004396: "High Frequency Program: Application Guidance for Functional Confirmation and Fragility," dated September 17, 2015 (ML15218A569) 1 O. NRC Letter, Final Determination of Licensee Seismic Probabilistic Risk Assessments Under the Request for Information Pursuant to Title 1 O of the Code of Federal Regulations 50.54(f) Regarding Recommendation 2.1 "Seismic" of the Near-Term Task Force Review of Insights from the Fukushima Dai-lchi Accident, dated October 27, 2015 (ML15194A015)
On March 12, 2012, the Nuclear Regulatory Commission (NRC) issued a Request for Information per 1 O CFR 50.54(f) (Reference 1) to all power reactor licensees. The required response section of Enclosure 1 of Reference 1 indicated that licensees should provide a Seismic Hazard Evaluation and Screening Report within 1.5 years from the date of the letter for Central and Eastern United States (CEUS) nuclear power plants. By NRC letter dated May 7, 2013 (Reference 2), the date to submit the report was extended to March 31, 2014.
By letter dated May 9, 2014 (Reference 6), the NRC transmitted the results of the screening and prioritization review of the seismic hazards reevaluation report for Limerick Generating Station, Units 1 and 2 submitted on March 31, 2014 (Reference 5). In accordance with the Screening, Prioritization, and Implementation Details report (SPID) (References 3 and 4), and Augmented Approach Guidance (Reference 2), the reevaluated seismic hazard is used to determine if additional seismic risk evaluations are warranted for a plant. Specifically, the reevaluated horizontal Ground Motion Response Spectrum (GMRS) at the control point elevation is compared to the existing Safe Shutdown Earthquake (SSE) or Individual Plant Examination for External Events (IPEEE) High Confidence of Low Probability of Failure (HCLPF) Spectrum (IHS) to determine if a plant is required to perform a high frequency confirmation evaluation. As noted in the May 9, 2014 letter from the NRC (Reference 6) on page 3 of Enclosure 2, Limerick Generating Station, Units 1 and 2 is to conduct a limited scope High Frequency Evaluation (Confirmation).
Within the May 9, 2014 letter (Reference 6), the NRC acknowledged that these limited scope evaluations will require additional development of the assessment process. By Reference 8, the Nuclear Energy Institute (NEI) submitted an Electric Power Research Institute (EPRI) report entitled, High Frequency Program: Application Guidance for Functional Confirmation and Fragility Evaluation (EPRI 3002004396) for NRC review and endorsement. NRC endorsement
U.S. Nuclear Regulatory Commission Seismic Hazard 2.1 High Frequency Supplement November 28, 2016 Page 3 was provided by Reference 9. Reference 10 provided the NRC final seismic hazard evaluation screening determination results and the associated schedules for submittal of the remaining seismic hazard evaluation activities.
The High Frequency Evaluation Confirmation Report for Limerick Generating Station, Units 1 and 2, provided in the enclosure to this letter, shows that all high frequency susceptible equipment evaluated within the scoping requirements and using evaluation criteria of Reference 8 for seismic demands and capacities, are acceptable. Therefore, no additional modifications or evaluations are necessary.
This transmittal completes the scope of work described in Section 4.2 of Reference 5 for Limerick Generating Station, Units 1 and 2.
This letter closes the associated regulatory commitment contained in Enclosure 2 of Reference 5 for Limerick Generating Station, Units 1 and 2.
This letter contains no new regulatory commitments.
If you have any questions regarding this report, please contact Ronald Gaston at 630-657-3359.
I declare under penalty of perjury that the foregoing is true and correct. Executed on the 281h day of November 2016.
Respectfully submitted,
~kf:-
James Barstow Director - Licensing & Regulatory Affairs Exelon Generation Company, LLC
Enclosure:
Limerick Generating Station, Units 1 and 2 - Seismic High Frequency Evaluation Confirmation Report cc:
NRC Regional Administrator - Region I NRC Project Manager, NRA - Limerick Station NRC Senior Resident Inspector - Limerick Station Mr. Brett A. Titus, NRR/JLD/JCBB, NRC Mr. Stephen M. Wyman, NRR/JLD/JHMB, NRC Mr. Frankie G. Vega, NRR/JLD/JHMB, NRC Director, Bureau of Radiation Protection - Pennsylvania Department of Environmental Resources R. R. Janati, Chief, Division of Nuclear Safety, Pennsylvania Department of Environmental Protection, Bureau of Radiation Protection
Enclosure Limerick Generating Station, Units 1 and 2 Seismic High Frequency Evaluation Confirmation Report (11 O pages)
HIGH FREQUENCY CONFIRMATION REPORT IN RESPONSE TO NEAR TERM TASK FORCE (NTIF) 2.1 RECOMMENDATION for the LIMERICK GENERATING STATION, UNITS 1 AND 2 3146 Sanatoga Rd, Pottstown, PA 19464 Facility Operating License Nos. NPF-39 and NPF-85 NRC Docket Nos. 50-352 and 50-353 Correspondence No.: RS-16-177 Preparer:
Reviewer:
Approver:
Exelon Exelon Generation Company, LLC (Exelon)
PO Box 805398 Chicago, IL 60680-5398 Prepared by:
Stevenson & Associates 1661 Feehanvllle Drive, Suite 150 Mount Prospect, IL 60056 Report Number: 15C4345-RPT-002, Rev. O Printed Name F. Ganatra M. Delaney M. Delaney Signature Lead Responsible Engineer. Lll!M ~=='='
BranchManaser: ~\\U.D~
Senior Manager ~
--1~~_,q._...;:::o. __
Design En1lneerln1: -S-,...., &r1111tt Corporate Acceptance: \\iSSru, S. C lAr \\c.
~
10/27/2016 10/27/2016 10/27/2016 11/t-,i!D/~
\\\\~~l \\Cc.
"I er/ 1 b 11/.,/20ue
Document ID: 15C4345-RPT-002
Title:
High Frequency Confirmation Report for Limerick Generating Station, Unit 1 and 2 in Response to Near Term Task Force (NTTF) 2.1 Recommendation Document Type:
Criteria D Interface D Report ~ Specification D Other D Drawing D Project Name:
Limerick, Unit 1 and 2 High Frequency Confirmation Job No.: 15C4345 Client: ~ Exelon ~
This document has been prepared under the guidance of the S&A Quality Assurance Program Manual, Revision 18 and project requirements:
For Owner's Acceptance Review (Rev. 0) fU-4~
Date: 10/27 /2016 Originated by: F. Ganatra
~/t(~
Date: 10/27 /2016 Checked by: M. Delaney
~ft(~
Date: 10/27 /2016 Approved by: M. Delaney Revision Record:
Revision Originated by/
Checked by/
Approved by/
Description of Revision No.
Date Date Stevenson & Associates Date DOCUMENT APPROVAL SHEET Figure 2.8 PROJECT NO.
15C4345
Executive Summary 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 The purpose of this report is to provide information as requested by the Nuclear Regulatory Commission (NRC) in its March 12, 2012 letter issued to all power reactor licensees and holders of construction permits in active or deferred status [l]. In particular, this report provides information requested to address the High Frequency Confirmation requirements of Item (4), Enclosure 1, Recommendation 2.1: Seismic, of the March 12, 2012 letter [1].
Following the accident at the Fukushima Dai-ichi nuclear power plant resulting from the March 11, 2011, Great Tohoku Earthquake and subsequent tsunami, the Nuclear Regulatory Commission (NRC}
established a Near Term Task Force (NTIF) to conduct a systematic review of NRC processes and regulations and to determine if the agency should make additional improvements to its regulatory system. The NTIF developed a set of recommendations [15] intended to clarify and strengthen the regulatory framework for protection against natural phenomena. Subsequently, the NRC issued a 50.54(f} letter on March 12, 2012 [1], requesting information to assure that these recommendations are addressed by all U.S. nuclear power plants. The 50.54(f} letter requests that licensees and holders of construction permits under 10 CFR Part 50 reevaluate the seismic hazards at their sites against present-day NRC requirements and guidance. Included in the 50.54(f} letter was a request that licensees' perform a "confirmation, if necessary, that SSCs, which may be affected by high-frequency ground motion, will maintain their functions important to safety."
EPRI 1025287, "Seismic Evaluation Guidance: Screening, Prioritization and Implementation Details (SPID} for the resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic" [6]
provided screening, prioritization, and implementation details to the U.S. nuclear utility industry for responding to the NRC 50.54(f} letter. This report was developed with NRC participation and was subsequently endorsed by the NRC. The SPID included guidance for determining which plants should perform a High Frequency Confirmation and identified the types of components that should be evaluated in the evaluation.
Subsequent guidance for performing a High Frequency Confirmation was provided in EPRI 3002004396, "High Frequency Program, Application Guidance for Functional Confirmation and Fragility Evaluation," [8] and was endorsed by the NRC in a letter dated September 17, 2015 [3]. Final screening identifying plants needing to perform a High Frequency Confirmation was provided by NRC in a letter dated October 27, 2015 [2].
This report describes the High Frequency Confirmation evaluation undertaken for Limerick Generating Station, Unit 1 and 2 (LIM). The objective of this report is to provide summary information describing the High Frequency Confirmation evaluations and results. The level of detail provided in the report is intended to enable NRC to understand the inputs used, the evaluations performed, and the decisions made as a result of the evaluations.
EPRI 3002004396 [8] is used for the LIM engineering evaluations described in this report. In accordance with Reference [8], the following topics are addressed in the subsequent sections of this report:
Process of selecting components and a list of specific components for high-frequency confirmation Estimation of a vertical ground motion response spectrum (GMRS}
Page 3of110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Estimation of in-cabinet seismic demand for subject components Estimation of in-cabinet seismic capacity for subject components Summary of subject components' high-frequency evaluations Page 4 of 110
1 Introduction 1.1 PURPOSE 15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 The purpose of this report is to provide information as requested by the NRC in its March 12, 2012 S0.54(f) letter issued to all power reactor licensees and holders of construction permits in active or deferred status [1]. In particular, this report provides requested information to address the High Frequency Confirmation requirements of Item (4), Enclosure 1, Recommendation 2.1:
Seismic, ofthe March 12, 2012 letter [1].
1.2 BACKGROUND
Following the accident at the Fukushima Dai-ichi nuclear power plant resulting from the March 11, 2011, Great Tohoku Earthquake and subsequent tsunami, the Nuclear Regulatory Commission (NRC) established a Near Term Task Force (NTIF) to conduct a systematic review of NRC processes and regulations and to determine if the agency should make additional improvements to its regulatory system. The NTIF developed a set of recommendations intended to clarify and strengthen the regulatory framework for protection against natural phenomena.
Subsequently, the NRC issued a 50.54(f) letter on March 12, 2012 [1], requesting information to assure that these recommendations are addressed by all U.S. nuclear power plants. The 50.54(f) letter requests that licensees and holders of construction permits under 10 CFR Part 50 reevaluate the seismic hazards at their sites against present-day NRC requirements and guidance.
Included in the 50.54(f) letter was a request that licensees' perform a "confirmation, if necessary, that SSCs, which may be affected by high-frequency ground motion, will maintain their functions important to safety."
EPRI 1025287, "Seismic Evaluation Guidance: Screening, Prioritization and Implementation Details (SPID) for the resolution of Fukushima Near-Term Task Force Recommendation 2.1:
Seismic" [6] provided screening, prioritization, and implementation details to the U.S. nuclear utility industry for responding to the NRC 50.54(f) letter. This report was developed with NRC participation and is endorsed by the NRC. The SPID included guidance for determining which plants should perform a High Frequency Confirmation and identified the types of components that should be evaluated in the evaluation.
Subsequent guidance for performing a High Frequency Confirmation was provided in EPRI 3002004396, "High Frequency Program, Application Guidance for Functional Confirmation and Fragility Evaluation," [8] and was endorsed by the NRC in a letter dated September 17, 2015 [3].
Final screening identifying plants needing to perform a High Frequency Confirmation was provided by NRC in a letter dated October 27, 2015 [2].
On March 31, 2014, LIM submitted a reevaluated seismic hazard to the NRC as a part of the Seismic Hazard and Screening Report [4]. By letter dated October 27, 2015 [2], the NRC transmitted the results of the screening and prioritization review of the seismic hazards reevaluation.
This report describes the High Frequency Confirmation evaluation undertaken for LIM using the methodologies in EPRI 3002004396, "High Frequency Program, Application Guidance for Page 5of110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Functional Confirmation and Fragility Evaluation," as endorsed by the NRC in a letter dated September 17, 2015 (3].
The objective of this report is to provide summary information describing the High Frequency Confirmation evaluations and results. The level of detail provided in the report is intended to enable NRC to understand the inputs used, the evaluations performed, and the conclusions made as a result of the evaluations.
1.3 APPROACH EPRI 3002004396 [8] is used for the LIM engineering evaluations described in this report. Section 4.1 of Reference [8] provided general steps to follow for the high frequency confirmation component evaluation. Accordingly, the following topics are addressed in the subsequent sections of this report:
LIM SSE and GMRS Information Selection of components and a list of specific components for high-frequency confirmation Estimation of seismic demand for subject components Estimation of seismic capacity for subject components Summary of subject components' high-frequency evaluations Summary of Results 1.4 PLANT SCREENING LIM submitted reevaluated seismic hazard information including GMRS and seismic hazard information to the NRC on March 31, 2014 (4]. In a letter dated November 6, 2015, the NRC staff concluded that the submitted GMRS adequately characterizes the reevaluated seismic hazard forthe LIM site for 2.1 Seismic (14].
The NRC final screening determination letter concluded [2] that the LIM GMRS to SSE comparison resulted in a need to perform a High Frequency Confirmation in accordance with the screening criteria in the SPID [6].
1.5 REPORT DOCUMENTATION Section 2 describes the selection of devices. The identified devices are evaluated in Reference (17] for the seismic demand specified in Section 3 using the evaluation criteria discussed in Section 4. The overall conclusion is discussed in Section 5.
Table B-1 lists the devices identified in Section 2 and provides the results of the evaluations performed in accordance with Section 3 and Section 4.
Page 6 of 110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 2
Selection of Components for High-Frequency Screening The fundamental objective of the high frequency confirmation review is to determine whether the occurrence of a seismic event could cause credited equipment to fail to perform as necessary. An optimized evaluation process is applied that focuses on achieving a safe and stable plant state following a seismic event. As described in Reference [8], this state is achieved by confirming that key plant safety functions critical to immediate plant safety are preserved (reactor trip, reactor vessel inventory and pressure control, and core cooling) and that the plant operators have the necessary power available to achieve and maintain this state immediately following the seismic event (AC/DC power support systems).
Within the applicable functions, the components that would need a high frequency confirmation are contact control devices subject to intermittent states in seal-in or lockout circuits. Accordingly, the objective of the review as stated in Section 4.2.1 of Reference (8] is to determine if seismic induced high frequency relay chatter would prevent the completion of the following key functions.
2.1 REACTOR TRIP/SCRAM The reactor trip/SCRAM function is identified as a key function in Reference [8] to be considered in the High Frequency Confirmation. The same report also states that "the design requirements preclude the application of seal-in or lockout circuits that prevent reactor trip/SCRAM functions" and that "No high-frequency review of the reactor trip/SCRAM systems is necessary."
2.2 REACTOR VESSEL INVENTORY CONTROL The reactor coolant system/reactor vessel inventory control systems were reviewed for contact control devices in seal-in and lockout (SILO) circuits that would create a Loss of Coolant Accident (LOCA). The focus of the review was contact control devices that could lead to a significant leak path. Check valves in series with active valves would prevent significant leaks due to misoperation of the active valve; therefore, SILO circuit reviews were not required for those active valves.
The process/criteria for assessing potential reactor coolant leak path valves is to review all P&ID's attached to the Reactor Coolant System (RCS) and include all active isolation valves and any active second valve upstream or downstream that is assumed to be required to be closed during normal operation or close upon an initiating event (Loss of Coolant Accident "LOCA" or Seismic).
A table with the valves and associated P&ID is included in Table B-2 of this report.
Manual valves that are normally closed are assumed to remain closed and a second simple check valve is assumed to function and not be a Multiple Spurious Failure.
Page 7 of 110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 On BWR's the instrument lines that are 1" or less, in general, are assumed to have restricting orifices that are designed to mitigate any leakage due to make up.
Table B-2 contains a list of valves analyzed and based on the analysis detailed below, there are no moving contact control devices which could create a LOCA due to chatter-induced sustained valve misalignment, and thus no devices were selected for this category. For valves in Table B-2 that were identified as not requiring evaluation, the justification is provided in the Notes section of the table and is in accordance with guidance criteria.
Nuclear Steam Supply Shutoff Valves Reactor Head Vent Valves HV-041-lFOOl, HV-041-1F002, HV-041-2F001, HV-041-2F002 These two Unit 1 valves [HV-041-lFOOl, HV-041-1F002] are normally closed and in series with one another [23]. Note 39 on the P&ID stipulates HV-041-1F002 is "disabled by locking open the circuit breaker and using administrative controls to assure that the valve is maintained in a closed positon when not in use" [24]. Because HV-041-1F002 is closed, depowered, and blocking flow through HV-041-lFOOl, contact chatter in the control circuits of either valve is irrelevant. Note 50 on the Unit 2 P&ID makes the same statement [25, 26], thus this reasoning applies to the Unit 2 valves HV-041-2F001, HV-041-2F002 as well.
Auto Depressurization Valves PSV-041-1F013E/H/K/M/S, PSV-041-2F013E/H/K/M/S Electrical control for the solenoid-operated pilot valves is via relays B21C-K6A/C/E/G and B21C-K9A/C/E/G [27, 28, 29, 30]. These relays are controlled by the High Drywell Pressure I Reactor Pressure Vessel (RPV) Low Level Logic and the Residual Heat Removal (RHR) Pump Pressure relays B21C-K10A/C/E/G [31, 32]. The RHR Pump Pressure relays do not seal-in [33, 34] and, based on initial conditions at the time of the event, would block any inadvertent seal-in of the High Drywell Pressure I RPV Low Level Logic. Thus there is no SILO relays in this logic which could cause the Auto Depressurization Valves to remain open following a seismic event.
Safety Relief Valves PSV-041-1 F013A/B/C/D/F/G/l/L/N, PSV-041-2F013A/B/C/D/F/G/l/L/N Electrical control for the solenoid-operated pilot valves is via a rugged hand control switch. There are no chatter sensitive contact devices involved in the control of these valves [35, 36, 37, 38].
Main Steam Isolation Valves HV-041-1F022A/B/C/D, HV-041-1F028A/B/C/O, HV-041-2F022A/B/C/D, HV-041-2F028A/B/C/D Electrical control for the solenoid-operated pilot valves is via relays B21H-Kl8A/B/C/D. These relays are slaves to B21H-Kl4A/B/C/D isolation logic relays [39, 40, 41, 42]. These relays are energized for at-power operation and de-energized to close the valves [43, 44, 45, 46]. In the energized state B21H-K14A/B/C/D are sealed in and any chatter in the control logic would break the seal-in and close the valves. This action is a desired response to the seismic event and for this reason chatter is acceptable and no contact devices in this circuit meet the selection criteria.
Page 8of110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Main Steam Line Equalizer Valves HV-C-041-1F020, HV-C-041-2F020 These normally-open motor-operated valves are controlled by hand switches only [47, 48, 49].
Open limit switches in the opening circuit prevent seal-in of the opening contactor auxiliary contact and no contacts prevent valve closure via the control switch. Thus these valves are not affected by SILO.
Main Steam Line Drain Valves HV-041-1F016, HV-041-1F019, HV-041-2F016, HV-041-2F019 The opening of normally-closed motor-operated valves HV-041-1F016/ HV-041-2F016 is commanded by a rugged hand switch with no seal-in contacts [SO, 51]. This valve opening control is insensitive to contact chatter and thus the valve will remain closed after the seismic event. As stated in Table B-2, HV-041-1F019/HV-041-2F019 do not need to be analyzed provided HV-041-1F016/HV-041-2F016 remain closed.
Reactor Water Clean-Up Valves Reactor Water Clean-Up Flow Control Valves HV-044-lFlOS, HV-044-2F105; Bottom Head Drain Flow Control Valves HV-044-lFlOO, HV-044-2F100 These normally-open motor-operated valves are controlled by hand switches only [52, 53]. Open limit switches in the opening circuit prevent seal-in of the opening contactor auxiliary contact and no contacts prevent valve closure via the control switch. Thus these valves are not affected by SILO.
Reactor Water Clean-Up Isolation Valves HV-044-lFOOl, HV-044-1F004, HV-044-2F001, HV-044-2F004; Bottom Head Drain Flow Control Valves These are normally-open motor-operated valves which close upon an isolation signal. Open limit switches in the opening circuit prevent seal-in of the opening contactor auxiliary contact and no contacts prevent valve closure via the control switch or isolation relay B21H-K24A/B [54, 55, 56, 57]. These relays are energized for at-power operation and de-energized to close the valves [58, 59, 60, 61]. In the energized state B21H-K24A/B are sealed in and any chatter in the control logic would break the seal-in and close the valves. This action is a desired response to the seismic event and for this reason chatter is acceptable and no contact devices in this circuit meet the selection criteria.
Reactor Core Isolation Cooling Valves Reactor Core Isolation Cooling Steam Supply Line Isolation Valves HV-049-lFOOl, HV-049-lFOOB, HV-049-2F007, HV-049-2FOOB These normally-open motor-operated valves are required to remain open to supply steam to the RCIC turbine. There is no seal-in in the opening circuit, and closure, if needed, is not blocked by SILO [62, 63, 64, 65]. Inadvertent closure of these valves is covered in the RCIC chatter analysis in Section 5.3.7 of Ref. [18].
Residual Heat Removal Valves Testable Check Valves HV-051-1F041A/B/C/D, HV-051-lFOSOA/B, HV-051-2F041A/8/C/D, HV-051-2F050A/B These solenoid-operated valves are controlled by a rugged, normally open push button [66, 67, 68, 69, 70, 71, 72, 73, 74, 75]. There are no SILO devices that would prevent the normal operation of these check valves.
Page 9 of 110
15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 RHR Injection Valves HV-051-1F017A/B/C/D, HV-051-2F017A/B/C/D; RHR Shutdown Cooling Injection Valves HV-051-1F015A/B, HV-051-2F015A/B Since the testable check valves are not chatter sensitive and can be credited to remain closed, these downstream motor operated valves do not need to be analyzed per the notes in Table B-2.
RHR Shutdown Cooling Isolation Valves HV-051-1F008, HV-051-2F008; RHR Shutdown Cooling Suction Valves HV-051-1F009, HV-051-2F009 These normally-closed motor-operated valves are opened via a normally-open control switch and relay permissive. The valves can be closed manually via the control switch and automatically via an isolation signal. Sympathetic chatter on B21H-K29A/B and 42/0 auxiliary contact could cause valve to open [76, 77, 78, 79], however the low reactor pressure permissive in control logic would prevent seal-in of B21H-K29A/B [58, 59, 60, 61]. After the period of strong shaking the normally-closed contact of B21H-K29A/B (isolation signal) would command these valves to reclose.
Because there is no seal-in and the valves reclose without operator intervention, chatter is acceptable and no contact devices in this circuit meet the selection criteria.
Core Spray Valves Testable Check Valves HV-052-1F006A/B, HV-052-2F006A/B These solenoid-operated valves are controlled by a rugged, normally open push button [80, 81, 82, 83]. There are no SILO devices that would prevent the normal operation of these check valves.
Core Spray Outboard Check Valves HV-052-108, HV-052-208; Core Spray Inboard Motor Operated Valve HV-052-1F005, HV-052-2F005 Since the testable check valves are not chatter sensitive and can be credited to remain closed, these downstream motor operated valves do not need to be analyzed per the notes in Table B-2.
High Pressure Core Injection Valves High Pressure Core Injection Steam Supply Line Isolation Valves HV-055-1F002, HV-055-1F003, HV-055-2F002, HV-055-2F003 These normally-open motor-operated valves supply steam to the HPCI turbine. The opening circuit is controlled by a rugged hand switch and permissive from E41A-K50B/D [84, 85, 86, 87].
There is no seal-in in the opening circuit. The closing circuit is controlled manually by a rugged hand switch or automatically via the isolation relay E41A-K50B/D [88, 89]. Any chatter in the isolation logic would seal-in E41A-K50B/D and close the valves. Since RCIC, not HPCI, is credited for core cooling this seal-in causing valve closure is not a selection criterion. There is no SILO which would prevent closure of these valves and thus no contact devices in this circuit meet the selection criteria.
Page10of110
2.3 REACTOR VESSEL PRESSURE CONTROL 15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 The reactor vessel pressure control function is identified as a key function in Reference [8) to be considered in the High Frequency Confirmation. The same report also states that "required post event pressure control is typically provided by passive devices" and that "no specific high frequency component chatter review is required for this function."
2.4 CORE COOLING The core cooling systems were reviewed for contact control devices in seal-in and lockout circuits that would prevent at least a single train of non-AC power driven decay heat removal from functioning. Limerick credits their steam turbine-driven Reactor Core Isolation Cooling (RCIC}
Pump to provide core decay-heat cooling.
The selection of contact devices for the Safety Relief Valves (SRVs) overlaps with the RCS/Reactor Vessel Inventory Control Category. Refer to Section 2.2 for more information on the analysis of contact devices for these valves.
The selection of contact devices for RCIC was based on the premise that RCIC operation is desired, thus any SILO which would lead to RCIC operation is beneficial and thus does not meet the criteria for selection. Only contact devices which could render the RCIC system inoperable were considered.
The largest vulnerability to RCIC operation following a seismic event is contact chatter leading to a false RCIC Isolation Signal or false Turbine Trip. A false steam line break trip has the potential to delay RCIC operation while confirmatory inspections are being made. Chatter in the contacts of RCIC Isolation Signal Relay E51A-K31A or Steam Line High Differential Pressure Time Delay Relay E51A-K15A; or coincident chatter in the Turbine Exhaust Diaphragm High Pressure Relays E51A-K11A and E51A-K12A, or Reactor Pressure Relays E51A-K16A and E51A-K17A; may lead to a RCIC Isolation Signal and seal-in of E51A-K31A [19). This would cause the RCIC Isolation Valves to close and the RCIC Trip and Throttle Valve to trip. Similar chatter in the contact devices that drive those relays could also lead to seal-in: PIS-050-1N655A, PIS-050-1N655E, PIS-049-1N658A, and PIS-049-1N658E (20]. (The three-second time delay associated with E51A-K15A will mask any chatter on PDIS-049-1N657A and PDS-049-1N660A, so they are excluded.) The same rationale applies to the identical Division 3 devices: ES1A-K31C, E51A-K1SC, ESlA-KllC, E51A-K12C, E51A-K16C, ES1A-K17C, PIS-050-1N65SC, PIS-050-1N6SSG, PIS-049-1N658C, and PIS-049-1N658G (21, 22).
Any chatter that may lead to the energization of the Trip and Throttle Valve Remote Trip Circuit is considered as SILO as it will close the valve and require a manual reset prior to restoration of the RCIC system. Chatter in Turbine Trip Auxiliary Relay E51A-K28, or in the devices which control this relay; the Turbine Exhaust High Pressure Relays E51A-K13 and E51A-K14, the Pump Suction Low Pressure Relay ESlA-KlO, and the Isolation Signal Relays E51A-K30A, and E51A-K67C (19).
Similar chatter in the contact devices that drive those relays (and not already covered in the RCIC Isolation Signal analysis) could also lead to a turbine trip: ES1A-K30C, PIS-OS0-1N653, PIS-050-1N656A, and PIS-050-1N656E [20, 21).
Page 11 of 110
2.5 AC/DC POWER SUPPORT SYSTEMS 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 The AC and DC power support systems were reviewed for contact control devices in seal-in and lockout circuits that prevent the availability of DC and AC power sources. The following AC and DC power support systems were reviewed:
Emergency Diesel Generators, Battery Chargers, Inverters, EDG Ancillary Systems, and Switchgear, Load Centers, and MCCs.
Electrical power, especially DC, is necessary to support achieving and maintaining a stable plant condition following a seismic event. DC power relies on the availability of AC power to recharge the batteries. The availability of AC power is dependent upon the Emergency Diesel Generators and their ancillary support systems. EPRI 3002004396 [8] requires confirmation that the supply of emergency power is not challenged by a SILO device. The tripping of lockout devices or circuit breakers is expected to require some level of diagnosis to determine if the trip was spurious due to contact chatter or in response to an actual system fault. The actions taken to diagnose the fault condition could substantially delay the restoration of emergency power.
In order to ensure contact chatter cannot compromise the emergency power system, control circuits were analyzed for the Emergency Diesel Generators (EDG), Battery Chargers, Vital AC Inverters, and Switchgear/Load Centers/MCCs as necessary to distribute power from the EDGs to the Battery Chargers and EDG Ancillary Systems. General information on the arrangement of safety-related AC and DC systems, as well as operation of the EDGs, was obtained from Limerick's UFSAR [90]. Limerick has eight (8) EDGs which provide emergency power for their two units.
Each unit has four (4) divisions of Class lE loads with one EDG for each division [90, pp. 8.1-2].
The Class lE AC distribution scheme is shown on one-line drawings E-15 [91] (Unit 1) and E-16
[92] (Unit 2). The Class lE DC distribution scheme is described in the UFSAR (90, pp. 8.3-38] and shown on one-line drawings E-33 (93, 94] (Unit 1) and E-34 (95, 96] (Unit 2).
The analysis necessary to identify contact devices in this category relies on conservative worse-case initial conditions and presumptions regarding event progression. The analysis considers the reactor is operating at power with no equipment failures or LOCA prior to the seismic event. The Emergency Diesel Generators are not operating but are available. The seismic event is presumed to cause a Loss of Offsite Power (LOOP) and a normal reactor SCRAM.
In response to bus undervoltage relaying detecting the LOOP, the Class lE control systems must automatically shed loads, start the EDGs, and sequentially load the diesel generators as designed.
Ancillary systems required for EDG operation as well as Class lE battery chargers and inverters must function as necessary. The goal of this analysis is to identify any vulnerable contact devices which could chatter during the seismic event, seal-in or lock-out, and prevent these systems from performing their intended safety-related function of supplying electrical power during the LOOP.
The following sections contain a description of the analysis for each element of the AC/DC Support Systems. Contact devices are identified by description and Unit 1 Division 1 device ID in this narrative, however the analysis applies to the identical components and devices in all divisions of both units. The selected contact devices for both units and all divisions appear in Page 12 of 11 O
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table 7-1 of Reference [18] where they are identified by device-specific ID, as indicated on the referenced control schematics.
Emergency Diesel Generators The analysis of the Emergency Diesel Generators, 011, 012, 013, 014, 021, 022, 023, 024, is broken down into the generator protective relaying and diesel engine control. General descriptions of these systems and controls appear in the UFSAR [90, pp. 8.3-13].
Generator Protective Relaying The control circuits for the 152-11507 EOG circuit breaker [97, 98, 99, 100] include 186-115A, 186-115B, 186-115C bus lockout, 186-AG501 differential lockout, 151-AG501 phase overcurrent, and 132-AG501 anti-motoring protective relays. As mentioned above, there is no presumption of LOCA and thus none of these trips would be bypassed by the LOCA auxiliary control circuit.
Chatter in any of these relays may prevent closure of the EOG circuit breaker. The generator differential lockout relay 186-AG501 may be tripped by chatter in the 187G-AG501 differential and 151N-AG501 ground fault protective relays [101]. In addition, chatter in the 187-115 safeguards bus differential protective relays, or the 151-11509, 151-11502 overcurrent and 151N-11509, 151N-11502 ground fault relays associated with primary and alternate power feeds, could lead to the tripping of the bus lockout relay. When tripped, this bus lockout relay prevents closure of the EDG, ESW pump, and load center transformer circuit breakers [102].
The exciter [103] and governor control circuitry [104, 105, 106, 107, 108, 109, 110, 111] was analyzed and no devices within these circuits would cause a sustained change in control state such that the diesel generator would not operate after the period of strong shaking ends. The drawing note associated with an auxiliary contact of exciter contactor Kl, "Trips Generator Circuit Breaker" [104, 105, 106, 107, 108, 109, 110, 111], is not accurate. The as-built condition of this auxiliary contact, connected to TBC terminals 6 and 10, was confirmed by walkdown to be not used. Refer to Attachment 9.4 of Reference [18] for more information regarding this walkdown.
Diesel Engine Control Chatter analysis for the diesel engine control was performed on the start and shutdown circuits of each EDG [112, 113, 114] (Dll), [115, 116, 117] {012), [118, 119, 120] (Dl3), [121, 122, 123]
{014), [124, 125, 126] (D21), [127, 128, 129] (022), [130, 131, 132] (023), [133, 134, 135] {D24).
The start circuit is blocked by seal-in of the SDR engine trouble shutdown or SFR start failure relays. Chatter of the seal-in contacts of these relays or of the contacts of relays within the coil circuits of these relays may prevent EDG start.
The SFR start failure relay is controlled by the two overcrank timing relays, T2A and T2B. Chatter in the contacts of either of these timing relays may energize the start failure relay and once energized it will seal in. The time delay function of these overcrank relays prevent momentary chatter in their coil circuits from energizing them.
The SDR engine trouble shutdown relay is controlled by the EOS engine overspeed switch and EOR engine overspeed relay, the SE emergency stop relay, and a set of three switches and relays for each of the following engine faults: lube oil low pressure (OPLl, OPL2, OPL3, OPl, OP2, OP3),
jacket coolant low pressure (CPLl, CPL2, CPL3, CPl, CP2, CP3), lube oil high temperature {OTHl, OTH2, OTH3, OTl, OT2, OT3), and jacket coolant high temperature (CTHl, CTH2, CTH3, CTl, CT2, CT3). Chatter of the contacts of the overspeed relay is blocked by the overspeed switch contacts.
Chatter of the overspeed switch could energize the overspeed relay and lead to seal-in of the Page 13of110
1SC4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 shutdown relay. Chatter in the contacts of the emergency stop relay could lead to seal-in ofthe shutdown relay. Chatter in the emergency stop relay coil circuit is blocked from energizing the emergency stop relay by non-vulnerable control switches. Coincident chatter (occurring in two out of three of each group) on the relays or switches of the lube oil and jacket coolant temperature faults could lead to seal-in of the shutdown relay. Coincident chatter in the lube oil and jacket coolant pressure relay contacts (OPl/2/3, CPl/2/3) may seal-in the shutdown relay.
Since the pressure switches (OPLl/2/3, CPLl/2/3) are closed when the engine is not running, chatter in the T3A engine high speed time delay relay may cause the lube oil low pressure and jacket coolant low pressure relays to energize, which could lead to seal-in of the shutdown relay.
This means that chatter in T3A could prevent engine start regardless of chatter in the pressure switches. For this reason, this time delay relay will be selected and seismically analyzed while the pressure switches will not. If T3A is seismically screened (does not chatter), then chatter in the pressure switches are blocked. If T3A is not seismically screened (could potentially chatter), then the necessary mitigation actions for T3A would also address the potential for chatter in the pressure switches by default.
All other contact devices involved in engine start and engine shutdown circuits were analyzed and, other than the devices noted above, none would cause a sustained change in control state such that the diesel generator would not start after the period of strong shaking ends.
Battery Chargers Chatter analysis on the battery chargers was performed using information from the UFSAR [90]
as well as vendor schematic diagrams [136, 137, 138]. Each battery charger has a high voltage shutdown circuit [90, pp. 8.3-43] which is intended to protect the batteries and DC loads from output overvoltage due to charger failure. The high voltage shutdown circuit has a latching output relay K which disconnects the auxiliary voltage transformer, shutting the charger down
[136, 137]. Chatter in the contacts of this output relay will only have a temporary effect on the charger during the period of strong shaking. The operate coil of this relay is controlled by a non-vulnerable solid-state circuit [138]. No other vulnerable contact device affects the availability of the battery chargers.
Inverters Analysis of schematics for the lA, lB, 2A, and 2B RPS & UPS Static Inverters [139, 140], and the lA, lB, 2A, and 2B APRM UPS Inverters [141, 142] revealed no vulnerable contact devices and thus chatter analysis is unnecessary.
EDG Ancillary Systems In order to start and operate the Emergency Diesel Generators, a number of components and systems are required. For the purpose of identifying electrical contact devices, only systems and components which are electrically controlled are analyzed. Information in the UFSAR [90] was used as appropriate for this analysis.
Starting Air Based on Diesel Generator availability as an initial condition, the passive air reservoirs are presumed pressurized and the only active components in this system required to operate are the air start solenoids [143, 144], which are covered under the EOG engine control analysis in Section above.
Page 14 of 110
Combustion Air Intake and Exhaust 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 The combustion air intake and exhaust for the Diesel Generators are passive systems (145, 146]
which do not rely on electrical control.
Lube Oil The Diesel Generators utilize engine-driven mechanical lubrication oil pumps (147, 148] which do not rely on electrical control.
Fuel Oil The Diesel Generator Fuel Oil System is described in the UFSAR (90, pp. 9.5-28]. The Diesel Generators utilize engine-driven mechanical pumps and DC-powered auxiliary pumps (149, 150]
to supply fuel oil to the engines from the day tanks. The day tanks are re-supplied using AC-powered Diesel Oil Transfer Pumps. Chatter analysis of the control circuits for the electrically-powered auxiliary and transfer pumps (151, 152, 153, 154, 155, 156, 157, 158] concluded they do not include SILO devices. The mechanical pumps do not rely on electrical control.
Cooling Water The Diesel Generator Cooling Water System is described in the UFSAR (90, pp. 9.5-37]. This system consists of two cooling loops, jacket water and air cooler, which are each cooled by Emergency Service Water (ESW) (159, 160, 161, 162]. Engine driven pumps operating in both cooling loops are credited when the engine is operating. These mechanical pumps do not rely on electrical control. The electric jacket water pump is only used during shutdown periods and is thus not included in this analysis.
Four ESW pumps, DA, OB, DC, and OD, provide cooling water to the heat exchangers associated with the eight EDGs (163]. In automatic mode these pumps are started via the EDG Start Signal.
Chatter analysis of the EDG start signal is included in Section above. A chatter analysis of the 152-11508 ESW pump circuit breaker control circuits (164, 165, 166] indicates the 186-115 bus lockout, 150/151-11508 phase overcurrent, and 150G-11508 ground fault relays all could prevent automatic (sequential) breaker closure following the seismic event.
Ventilation The Diesel Generator Enclosure Ventilation System is described in the UFSAR (90, pp. 9.4-46].
Ventilation for each Diesel Generator Enclosure is provided via two exhaust fans (167, 168]. In automatic mode these fans are started via the EDG Start Signal. Chatter analysis of the EDG start signal is included in Section above. Other than SILO devices identified for the EDG start signal, chatter analysis of the control circuits for these fans (169, 170] and their associated dampers concluded they do not include SILO devices.
Switchgear, Load Centers, and MCCs Power distribution from the EDGs to the necessary electrical loads (Battery Chargers, Inverters, Fuel Oil Pumps, and EDG Ventilation Fans) was traced to identify any SILO devices which could lead to a circuit breaker trip and interruption in power. This effort excluded the EDG circuit breakers, which are covered in Section above, and the ESW Pump breakers which are covered in Section above, as well as component-specific contactors and their control devices, which are covered in the analysis of each component above.
Page 15 of 110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 The medium-and low-voltage circuit breakers in 4160V Busses and 440V Load Centers which are supplying power to loads identified in this section have been identified for evaluation. For Unit 1 Division 1 these breakers are 152-11507, 152-11505, 152-11508, 52-20133, and 52-20132. The 440V AC MCCs use Molded-Case Circuit Breakers (90, pp. 8.3-12] which are seismically rugged [8, pp. 2-11]; and DC power distribution is via non-vulnerable disconnect switches.
The only circuit breakers affected by protective relaying (not already covered) were those that distribute power via stepdown transformers from the 4KV Safeguards Busses to their associated 440V load centers. A chatter analysis of the control circuits for these circuit breakers [171, 172, 173] indicates the 186-115 bus lockout, 150/151-11505 transformer primary phase overcurrent, and 150G-11505 ground fault relays all could prevent automatic (sequential) breaker closure following the seismic event.
2.6
SUMMARY
OF SELECTED COMPONENTS The investigation of high-frequency contact devices as described above was performed in Ref.
[18]. A list of the contact devices requiring a high frequency confirmation is provided in Appendix B, Table B-1. The identified devices are evaluated in Ref. [17] per the methodology/description of Section 3 and 4. Results are presented in Section 5 and Table B-1.
Page16of110
3 Seismic Evaluation 3.1 HORIZONTAL SEISMIC DEMAND 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Per Reference (8], Sect. 4.3, the basis for calculating high-frequency seismic demand on the subject components in the horizontal direction is the LIM horizontal ground motion response spectrum (GMRS), which was generated as part of the LIM Seismic Hazard and Screening Report
[4] submitted to the NRC on March 31, 2014, and accepted by the NRC on November 6, 2015 (14].
It is noted in Reference [8] that a Foundation Input Response Spectrum (FIRS) may be necessary to evaluate buildings whose foundations are supported at elevations different than the Control Point elevation. However, for sites founded on rock, per Ref. [8], "The Control Point GMRS developed for these rock sites are typically appropriate for all rock-founded structures and additional FIRS estimates are not deemed necessary for the high frequency confirmation effort."
The applicable buildings at LIM are founded on rock; therefore, the Control Point GMRS is representative of the input at the building foundation.
The horizontal GMRS values are provided in Table 3-2.
3.2 VERTICAL SEISMIC DEMAND As described in Section 3.2 of Reference. (8), the horizontal GMRS and site soil conditions are used to calculate the vertical GMRS (VGMRS), which is the basis for calculating high-frequency seismic demand on the subject components in the vertical direction.
The site's soil mean shear wave velocity vs. depth profile is provided in Reference. [4], Table 2.3.2-2 and reproduced below in Table 3-1.
Page 17 of 110
Layer 1
2 3
4 5
6 7
8 9
10 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table 3-1: Soil Mean Shear Wave Velocity Vs. Depth Profile Depth Depth Thickness, Vs1 Vs30 (m)
(ft}
d1 (ft)
(ft/sec) d1/Vs1 I [ d1 /Vsi]
(ft/s) 3.048 10.0 10.0 3,452 2.90E-03 2.90E-03 6.096 20.0 10.0 3,457 2.89E-03 5.79E-03 9.144 30.0 10.0 3,462 2.89E-03 8.68E-03 12.192 40.0 10.0 3,467 2.88E-03 1.16E-02 15.24 50.0 10.0 3,472 2.88E-03 1.44E-02 18.288 60.0 10.0 3,477 2.88E-03 1.73E-02 3,418 21.336 70.0 10.0 3,482 2.87E-03 2.02E-02 24.384 80.0 10.0 3,487 2.87E-03 2.31E-02 27.432 90.0 10.0 3,492 2.86E-03 2.59E-02 30.48 100.0 10.0 3,497 2.86E-03 2.88E-02 Using the shear wave velocity vs. depth profile, the velocity of a shear wave traveling from a depth of 30m (98.43ft) to the surface of the site (Vs30) is calculated per the methodology of Reference [8], Section 3.5.
The time for a shear wave to travel through each soil layer is calculated by dividing the layer depth (d;) by the shear wave velocity of the layer (Vs;).
The total time for a wave to travel from a depth of 30m to the surface is calculated by adding the travel time through each layer from depths of Om to 30m (r[d;/Vs;)).
The velocity of a shear wave traveling from a depth of 30m to the surface is therefore the total distance {30m} divided by the total time; i.e., Vs30 = (3Dm}/r[d;/Vs;).
Note: The shear wave velocity is calculated based on time it takes for the shear wave to travel 30.48m {lOOft} instead of 30m (98.43ft). This small change in travel distance will have no impact on identifying soil class type.
The site's soil class is determined by using the site's shear wave velocity (Vs30) and the peak ground acceleration (PGA) of the GMRS and comparing them to the values within Reference [8),
Table 3-1. Based on the PGA of 0.193g and the shear wave velocity of 3418ft/s, the site soil class is B-Hard.
Once a site soil class is determined, the mean vertical vs. horizontal GMRS ratios (V/H) at each frequency are determined by using the site soil class and its associated V/H values in Reference
[8], Table 3-2.
The vertical GMRS is then calculated by multiplying the mean V/H ratio at each frequency by the horizontal GMRS acceleration at the corresponding frequency. It is noted that Reference [8],
Table 3-2 values are constant between O.lHz and 15Hz.
The V /H ratios and VG MRS values are provided in Table 3-2 of this report.
Figure 3-1 below provides a plot of the horizontal GMRS, V/H ratios, and vertical GMRS for LIM.
Page 18of110
15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 Table 3-2: Horizontal and Vertical Ground Motions Response Spectra Frequency (Hz)
HGMRS (g)
V/H Ratio VGMRS (g) 100 0.193 0.8 0.154 90 0.195 0.82 0.160 80 0.198 0.87 0.172 70 0.202 0.91 0.184 60 0.210 0.92 0.193 so 0.228 0.9 0.205 45 0.243 0.89 0.216 40 0.258 0.86 0.222 35 0.279 0.81 0.226 30 0.306 0.75 0.230 25 0.339 0.7 0.237 20 0.363 0.68 0.247 15 0.381 0.68 0.259 12.5 0.386 0.68 0.262 10 0.385 0.68 0.262 9
0.381 0.68 0.259 8
0.374 0.68 0.254 7
0.361 0.68 0.245 6
0.340 0.68 0.231 5
0.315 0.68 0.214 4
0.264 0.68 0.180 3.5 0.235 0.68 0.160 3
0.203 0.68 0.138 2.5 0.169 0.68 0.115 2
0.149 0.68 0.101 1.5 0.125 0.68 0.085 1.25 0.106 0.68 0.072 1
0.090 0.68 0.061 0.9 0.082 0.68 0.056 0.8 0.073 0.68 0.049 0.7 0.065 0.68 0.044 0.6 0.056 0.68 0.038 0.5 0.046 0.68 0.031 0.4 0.036 0.68 0.025 0.35 0.032 0.68 0.022 0.3 0.027 0.68 0.019 0.25 0.023 0.68 0.016 0.2 0.018 0.68 0.012 0.15 0.014 0.68 0.009 0.125 0.011 0.68 0.008 0.1 0.009 0.68 0.006 Page19of110
0.50 0.40
- !9 0.30 c
0
':t:i t!
CV Qj ti 0.20 ct VG MRS HGMRS
-- V/H Ratio (B-Hard) h-L I_
I I
!-="==-----_._ -'-----
I 0.10 --
0.00 0.1 1
Frequency [Hz]
10 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177
---~-.- 1.00
.,. 0.90
\\
\\
I
\\
I
\\
--~1'
~'
-, 0.80 0
".jj RI ex:
100
- c
~
0.70 >
0.60 0.50 Figure 3-1 Plot of the Horizontal and Vertical Ground Motions Response Spectra and V /H Ratios Page 20 of 110
3.3 COMPONENT HORIZONTAL SEISMIC DEMAND 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Per Reference [8] the peak horizontal acceleration is amplified using the following two factors to determine the horizontal in-cabinet response spectrum:
Horizontal in-structure amplification factor AFsH to account for seismic amplification at floor elevations above the host building's foundation Horizontal in-cabinet amplification factor AFc to account for seismic amplification within the host equipment (cabinet, switchgear, motor control center, etc.)
The in-structure amplification factor AFsH is derived from Figure 4-3 in Reference [8]. The in-cabinet horizontal amplification factor, AFc is associated with a given type of cabinet construction. The three general cabinet types are identified in Reference [8] and Appendix I of EPRI NP-7148-SL [13] assuming 5% in-cabinet response spectrum damping. EPRI NP-7148-SL [13]
classified the cabinet types as high amplification structures such as switchgear panels and other similar large flexible panels, medium amplification structures such as control panels and control room bench board panels and low amplification structures such as motor control centers.
All of the electrical cabinets containing the components subject to high frequency confirmation (see Table B-1 in Appendix B) can be categorized into one of the in-cabinet amplification categories in Reference [8] as follows:
Motor Control Centers are typical motor control center cabinets consisting of a lineup of several interconnected sections. Each section is a relatively narrow cabinet structure with height-to-depth ratios of about 4.5 that allow the cabinet framing to be efficiently used in flexure for the dynamic response loading, primarily in the front-to-back direction. This results in higher frame stresses and hence more damping which lowers the cabinet response. In addition, the subject components are not located on large unstiffened panels that could exhibit high local amplifications. These cabinets qualify as low amplification cabinets.
Switchgear cabinets are large cabinets consisting of a lineup of several interconnected sections typical of the high amplification cabinet category. Each section is a wide box-type structure with height-to-depth ratios of about 1.5 and may include wide stiffened panels. This results in lower stresses and hence less damping which increases the enclosure response. Components can be mounted on the wide panels, which results in the higher in-cabinet amplification factors.
Control cabinets are in a lineup of several interconnected sections with moderate width.
Each section consists of structures with height-to-depth ratios of about 3 which results in moderate frame stresses and damping. The response levels are mid-range between MCCs and switchgear and therefore these cabinets can be considered in the medium amplification category.
3.4 COMPONENT VERTICAL SEISMIC DEMAND The component vertical demand is determined using the peak acceleration of the VG MRS between 15 Hz and 40 Hz and amplifying it using the following two factors:
Vertical in-structure amplification factor AFsv to account for seismic amplification at floor elevations above the host building's foundation Page 21of110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Vertical in-cabinet amplification factor AFc to account for seismic amplification within the host equipment (cabinet, switchgear, motor control center, etc.)
The in-structure amplification factor AFsv is derived from Figure 4-4 in Reference [8]. The in-cabinet vertical amplification factor, AFc is derived in Reference [8] and is 4.7 for all cabinet types.
Page 22of110
4 Contact Device Evaluations 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Per Reference [8], seismic capacities (the highest seismic test level reached by the contact device without chatter or other malfunction) for each subject contact device are determined by the following procedures:
(1) If a contact device was tested as part of the EPRI High Frequency Testing program [7],
then the component seismic capacity from this program is used.
(2) If a contact device was not tested as part of [7], then one or more of the following means to determine the component capacity were used:
(a) Device-specific seismic test reports (either from the station or from the SQURTS testing program.
(b) Generic Equipment Ruggedness Spectra (GERS) capacities per [9], [10], [11], and [12].
(c) Assembly (e.g. electrical cabinet) tests where the component functional performance was monitored.
The high-frequency capacity of each device was evaluated with the component mounting point demand from Section 3 using the criteria in Section 4.5 of Reference [8]
A summary of the high-frequency evaluation conclusions is provided in Table B-1 in Appendix B of this report.
Page 23 of 11 o
5 Conclusions 5.1 GENERAL CONCLUSIONS 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 LIM has performed a High Frequency Confirmation evaluation in response to the NRC's 50.54(f) letter [1] using the methods in EPRI report 3002004396 [8].
The evaluation identified a total of 528 components that required evaluation. As summarized in Table B-1 in Appendix B, all of the devices have adequate seismic capacity for the reevaluated seismic hazard [4].
5.2 IDENTIFICATION OF FOLLOW-UP ACTIONS No follow-up actions were identified.
Page 24of110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 6
References 1
NRC (E. Leeds and M. Johnson) Letter to All Power Reactor Licensees et al., "Request for Information Pursuant to Title 10 of the Code of Federal Regulations 50.54(f} Regarding Recommendations 2.1, 2.3 and 9.3 of the Near-Term Task Force Review of Insights from the Fukushima Dai-lchi Accident," March 12, 2012, ADAMS Accession Number ML12053A340 2
NRC (W. Dean) Letter to the Power Reactor Licensees on the Enclosed List. "Final Determination of Licensee Seismic Probabilistic Risk Assessments Under the Request for Information Pursuant to Title 10 of the Code of Federal Regulations 50.54{f} Regarding Recommendation 2.1 "Seismic" of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident." October 27, 2015, ADAMS Accession Number ML15194A015 3
NRC (J. Davis) Letter to Nuclear Energy Institute (A. Mauer). "Endorsement of Electric Power Research Institute Final Draft Report 3002004396, 'High Frequency Program:
Application Guidance for Functional Confirmation and Fragility."' September 17, 2015, ADAMS Accession Number ML15218A569 4
Seismic Hazard and Screening Report in Response to the 50.54{f) Information Request Regarding Fukushima Near-Term Task Force Recommendation 2.1: Seismic for Limerick Generating Station, Unit 1 and 2 dated March 31, 2014, ADAMS Accession Number ML14090A236 5
Not Used 6
EPRI 1025287, "Seismic Evaluation Guidance: Screening, Prioritization and Implementation Details (SPID} for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1:
Seismic." February 2013 7
EPRI 3002002997, "High Frequency Program: High Frequency Testing Summary."
September 2014 8
EPRI 3002004396, "High Frequency Program: Application Guidance for Functional Confirmation and Fragility Evaluation." July 2015 9
EPRI NP-7147-SL, "Seismic Ruggedness of Relays." August 1991 10 EPRI NP-7147-SLV2, Addendum 1, "Seismic Ruggedness of Relays", September 1993 11 EPRI NP-7147-SLV2, Addendum 2, "Seismic Ruggedness of Relays", April 1995 12 EPRI NP-7147 SQUG Advisory 2004-02, "Relay GERS Corrections." September 10, 2004 13 EPRI NP-7148-SL, "Procedure for Evaluating Nuclear Power Plant Relay Seismic Functionality", 1990 14 NRC {F. Vega) Letter to Limerick Generating Station (B. Hanson), "Limerick Generating Station, Unit 1 and 2 - Staff Assessment of Information Provided Pursuant to Title 10 of the Code of Federal Regulations Part 50, Section 50.54{f), Seismic Hazard Reevaluations for Recommendation 2.1 ofthe Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident (TAC NOS. MF3864 and MF3865)." November 6, 2015, ADAMS Accession Number ML15296A492 15 Recommendations For Enhancing Reactor Safety in the 21'1 Century, "The Near-Term Task Force Review of Insights from the Fukushima Dai-I chi Accident" July 12, 2011, ADAMS Accession Number ML111861807 16 NEI 12-06, Rev. 2, "Diverse and Flexible Coping Strategies {FLEX) Implementation Guide" Page 25 of 11 O
1SC434S-RPT-002, Rev. 0 Correspondence No.: RS-16-177 17 1SC434S-CAL-001, Rev. 2, "High Frequency Functional Confirmation and Fragility Evaluation of Relays" 18 1SC434S-RPT-001, Rev. 3, "Selection of Relays and Switches for High Frequency Seismic Evaluation" 19 Limerick Drawing ESl-1040-E-003 Rev. 32, Elementary Diagram Reactor Core Isolation 20 Limerick Drawing ESl-1040-E-013 Rev. 16, Elementary Diagram RCIC System Sheet 3A 21 Limerick Drawing ESl-1040-E-004 Rev. 30, Elementary Diagram Reactor Core Isolation 22 Limerick Drawing ESl-1040-E-014 Rev. 16, Elementary Diagram RCIC System Sheet 4A 23 Limerick Drawing M-0041Sheet1Rev.47, Piping and Instrument Diagram Nuclear Boiler 24 Limerick Drawing M-0041 Sheet 3 Rev. SS, Piping and Instrument Diagram Nuclear Boiler 2S Limerick Drawing M-0041Sheet4 Rev. 43, Piping and Instrument Diagram Nuclear Boiler 26 Limerick Drawing M-0041 Sheet 6 Rev. SS, Piping and Instrument Diagram Nuclear Boiler 27 Limerick Drawing B21-1060-E-004 Rev. 14, Elementary Diagram Automatic De pressurization System Sheet 4 28 Limerick Drawing B21-1060-E-OOS Rev. 13, Elementary Diagram Automatic Depressurization System Sheet S 29 Limerick Drawing B21-1060-E-018 Rev. 7, Elementary Diagram Automatic Depressurization System 30 Limerick Drawing B21-1060-E-019 Rev. 6, Elementary Diagram Automatic Depressurization System 31 Limerick Drawing B21-1060-E-003 Rev. 16, Elementary Diagram Automatic Depressurization System 32 Limerick Drawing B21-1060-E-01S Rev. S, Elementary Diagram Auto Depressurization System 33 Limerick Drawing B21-1060-E-008 Rev. 14, Elementary Diagram Auto Depressurization System Sheet 3A 34 Limerick Drawing B21-1060-E-016 Rev. 4, Elementary Diagram Auto Depressurization System Sheet 3A 3S Limerick Drawing B21-1060-E-006 Rev. 19, Elementary Diagram Auto Depressurization System Sheet 6 36 Limerick Drawing B21-1060-E-011Rev.12, Elementary Diagram Auto Depressurization System Sheet 6A 37 Limerick Drawing B21-1060-E-020 Rev. 7, Elementary Diagram Auto Depressurization System 38 Limerick Drawing B21-1060-E-021 Rev. 6, Elementary Diagram Auto Depressurization System 39 Limerick Drawing B21-1090-E-010 Rev. 23, Elementary Diagram Nuclear Steam Supply Shutoff System 40 Limerick Drawing B21-1090-E-011 Rev. 23, Elementary Diagram Nuclear Steam Supply Shutoff System 41 Limerick Drawing B21-1090-E-027 Sheet 10 Rev. 8, Elementary Diagram Reactor Core Isolation 42 Limerick Drawing B21-1090-E-027 Sheet 11 Rev. 9, Elementary Diagram Nuclear Steam Supply Shutoff System Page 26 of 11 O
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 43 Limerick Drawing B21-1090-E-006 Rev. 27, Elementary Diagram Nuclear Steam Supply Shutoff System Sheet 6 44 Limerick Drawing B21-1090-E-007 Rev. 25, Elementary Diagram Nuclear Steam Supply Shutoff System Sheet 7 45 Limerick Drawing B21-1090-E-027 Sheet 6 Rev. 7, Elementary Diagram Nuclear Steam Supply Shutoff System 46 Limerick Drawing B21-1090-E-027 Sheet 7 Rev. 8, Elementary Diagram Nuclear Steam Supply Shutoff System 47 Limerick Drawing B21-1040-E-004 Rev. 23, Elementary Diagram Nuclear Boiler Process 48 Limerick Drawing B21-1040-E-008 Rev. 8, Elementary Diagram Nuclear Boiler Process 49 Limerick Drawing B21-1040-E-009 Rev. 9, Elementary Diagram Nuclear Boiler Process 50 Limerick Drawing B21-1090-E-032 Sheet 1 Rev. l, HV-041-1F016 Main Steam Drain Inboard PCIV Steam Drains Inboard 51 Limerick Drawing B21-1090-E-038 Sheet 1 Rev. 0, Elementary Diagram HV-051-2F016 52 Limerick Drawing G31-1040-E-001 Rev. 46, Elementary Diagram Reactor Water Cleanup System 53 Limerick Drawing G31-1040-E-005 Rev. 24, Elementary Diagram Reactor Water Cleanup System 54 Limerick Drawing B21-1090-E-012 Rev. 29, Elementary Diagram Nuclear Steam Supply Shutoff System 55 Limerick Drawing B21-1090-E-016 Sheet 2 Rev. 4, Elementary Diagram Nuclear Steam Supply Shutoff System 56 Limerick Drawing B21-1090-E-027 Sheet 12 Rev. 16, Elementary Diagram Nuclear Steam Supply Shutoff System 57 Limerick Drawing B21-1090-E-027 Sheet 2A Rev. 15, Elementary Diagram Nuclear Steam Supply Shutoff System 58 Limerick Drawing B21-1090-E-008 Rev. 32, Elementary Diagram Nuclear Steam Supply Sheet 8 59 Limerick Drawing B21-1090-E-017 Rev. 33, Elementary Diagram Nuclear Steam Supply Sheet 8A 60 Limerick Drawing B21-1090-E-027 Sheet 8 Rev. 16, Elementary Diagram Nuclear Steam Supply Shutoff System 61 Limerick Drawing B21-1090-E-027 Sheet 8A Rev. 14, Elementary Diagram Nuclear Steam Supply Shutoff System 62 Limerick Drawing ESl-1040-E-052 Sheet 1 Rev. l, Schematic HV-049-1F007 Main Steam Supply Inboard PCIV Inboard 63 Limerick Drawing ESl-1040-E-053 Sheet 1 Rev. 2, Schematic HV-049-1F008 RCIC Steam Line Outboard PCIV Outboard 64 Limerick Drawing ESl-1040-E-056 Sheet 1Rev.1, Elementary Diagram HV-049-2F007 65 Limerick Drawing ESl-1040-E-057 Sheet 1 Rev. 1, Elementary Diagram HV-049-2F008 66 Limerick Drawing Ell-1040-E-016 Rev. 35, Elementary Diagram Residual Heat Removal System 67 Limerick Drawing Ell-1040-E-018 Rev. 35, Elementary Diagram Residual Heat Removal System Page 27 of 110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 68 Limerick Drawing Ell-1040-E-019 Rev. 32, Elementary Diagram Residual Heat Removal System 69 Limerick Drawing Ell-1040-E-020 Rev. 23, Elementary Diagram Residual Heat Removal System 70 Limerick Drawing Ell-1040-E-021 Rev. 21, Elementary Diagram Residual Heat Removal System 71 Limerick Drawing Ell-1040-E-049 Rev. 17, Elementary Diagram Residual Heat Removal System 72 Limerick Drawing Ell-1040-E-051Rev.16, Elementary Diagram Residual Heat Removal System 73 Limerick Drawing Ell-1040-E-052 Rev. 15, Elementary Diagram Residual Heat Removal System 74 Limerick Drawing Ell-1040-E-053 Rev. 10, Elementary Diagram Residual Heat Removal System 75 Limerick Drawing Ell-1040-E-054 Rev. 11, Elementary Diagram Residual Heat Removal System 76 Limerick Drawing B21-1090-E-018 Sheet 2 Rev. 4, Elementary Diagram Nuclear Steam Supply Shutoff System 77 Limerick Drawing B21-1090-E-033 Sheet 1Rev.1, Schematic HV-051-1F009 RHR Shutdown Cooling Suction Inboard PCI Inboard 78 Limerick Drawing B21-1090-E-034 Sheet 1 Rev. 1, Elementary Diagram HV-051-2F008 79 Limerick Drawing B21-1090-E-035 Rev. 1, Elementary Diagram HV-051-2F009 80 Limerick Drawing E21-1040-E-009 Rev. 25, Elementary Diagram Core Spray System 81 Limerick Drawing E21-1040-E-010 Rev. 22, Elementary Diagram Core Spray System 82 Limerick Drawing E21-1040-E-030 Rev. 9, Elementary Diagram Core Spray System 83 Limerick Drawing E21-1040-E-031 Rev. 8, Elementary Diagram Core Spray System 84 Limerick Drawing E41-1040-E-014 Sheet 2 Rev. 1, Elementary Diagram HPCI System 85 Limerick Drawing E41-1040-E-013 Sheet 2 Rev. 0, Elementary Diagram HPCI System 86 Limerick Drawing E41-1040-E-027 Sheet 2 Rev. 0, Elementary Diagram HPCI System Sheet 11 87 Limerick Drawing E41-1040-E-027 Sheet 6 Rev. 0, Elementary Diagram HPCI System 88 Limerick Drawing E41-1040-E-006 Rev. 36, Elementary Diagram HPCI System 89 Limerick Drawing E41-1040-E-022 Rev. 8, Elementary Diagram HPCI System 90 Limerick Report, "Updated Final Safety Analysis Report (UFSAR)," Rev. 18, September 2016 91 Limerick Drawing E-0015 Sheet 1 Rev. 30, Single Line Meter and Relay Diagram 4KV Safeguard Power System Unit 1 92 Limerick Drawing E-0016 Sheet 1 Rev. 26, Single Line Meter and Relay Diagram 4KV Safeguard Power System Unit 2 93 Limerick Drawing E-0033 Sheet 1 Rev. 45, Single Line Meter and Relay Diagram 125, 250VDC System 94 Limerick Drawing E-0033 Sheet 2 Rev. 47, Single Line Meter and Relay Diagram 125, 250VDC System 95 Limerick Drawing E-0034 Sheet 1 Rev. 38, Single Line Meter and Relay Diagram 125, 250V DC System Page 28 of 11 O
15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 96 Limerick Drawing E-0034 Sheet 2 Rev. 40, Single Line Diagram Instrumentation AC System 97 Limerick Drawing E-0164 Sheet 1 Rev. 19, Safeguard Busses Dll thru D14, D21 thru D24 Generator Breakers 4KV 98 Limerick Drawing E-0164 Sheet 3 Rev. 10, Safeguard Busses Dll thru D14 and D21 thru D24 Generator Breakers 4KV 99 Limerick Drawing E-0164 Sheet 5 Rev. 9, Safeguard Busses Dll thru D14 Generator Breakers 4KV 100 Limerick Drawing E-0164 Sheet SA Rev. 1, Schematic Diagram Safeguard Busses D21, 22, 23, 24 Generator Breakers 4KV Unit 2 101 Limerick Drawing E-0169 Sheet 1 Rev. 11, Schematic Diagram - Diesel Generator Protective 102 Limerick Drawing E-0168 Sheet 1 Rev. 6, Schematic Diagram - Safeguard Buses, Protective Relaying 103 Limerick Drawing M-071-00147 Sheet 1 Rev. 21, Schematic Power Chassis Nuclear Exciter/Regulator 104 Limerick Drawing M-071-00065 Sheet lA Rev. 19, Control Schematic Dll Diesel Generator 105 Limerick Drawing M-071-00065 Sheet 6 Rev. 2, Control Schematic D12 Diesel Generator 106 Limerick Drawing M-071-00065 Sheet 12 Rev. 3, Control Schematic D13 Diesel Generator 107 Limerick Drawing M-071-00065 Sheet 18 Rev. 3, Control Schematic D14 Diesel Generator 108 Limerick Drawing M-071-00065 Sheet 24 Rev. 3, Control Schematic D21 Diesel Generator 109 Limerick Drawing M-071-00065 Sheet 30 Rev. 3, Control Schematic D22 Diesel Generator 110 Limerick Drawing M-071-00065 Sheet 36 Rev. 2, Control Schematic D23 Diesel Generator 111 Limerick Drawing M-071-00065 Sheet 42 Rev. 3, Control Schematic D24 Diesel Generator 112 Limerick Drawing M-071-00048 Sheet 1 Rev. 30, Schematic Engine Control Dll Diesel Generator 113 Limerick Drawing M-071-00048 Sheet 2 Rev. 32, Schematic Engine Control Dll Diesel Generator 114 Limerick Drawing M-071-00048 Sheet 3 Rev. 33, Schematic Engine Control Dll Diesel Generator 115 Limerick Drawing M-071-00048 Sheet 6 Rev. 14, Schematic Engine Control D12 Diesel Generator 116 Limerick Drawing M-071-00048 Sheet 7 Rev. 3, Schematic Engine Control D12 Diesel Generator 117 Limerick Drawing M-071-00048 Sheet 8 Rev. 1, Schematic Engine Control D12 Diesel Generator 118 Limerick Drawing M-071-00048 Sheet 11Rev.0, Schematic Engine Control D13 Diesel Generator 119 Limerick Drawing M-071-00048 Sheet 12 Rev. 3, Schematic Engine Control D13 Diesel Generator 120 Limerick Drawing M-071-00048 Sheet 13 Rev. 1, Schematic Engine Control D13 Diesel Generator 121 Limerick Drawing M-071-00048 Sheet 16 Rev. 0, Schematic Engine Control D14 Diesel Generator 122 Limerick Drawing M-071-00048 Sheet 17 Rev. 3, Schematic Engine Control D14 Diesel Generator Page 29of110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 123 Limerick Drawing M-071-00048 Sheet 18 Rev. 1, Schematic Engine Control D14 Diesel Generator 124 Limerick Drawing M-071-00048 Sheet 21 Rev. 0, Schematic Engine Control D21 Diesel Generator 125 Limerick Drawing M-071-00048 Sheet 22 Rev. 3, Schematic Engine Control D21 Diesel Generator 126 Limerick Drawing M-071-00048 Sheet 23 Rev. 1, Schematic Engine Control D21 Diesel Generator 127 Limerick Drawing M-071-00048 Sheet 26 Rev. 0, Schematic Engine Control D22 Diesel Generator 128 Limerick Drawing M-071-00048 Sheet 27 Rev. 3, Schematic Engine Control D22 Diesel Generator 129 Limerick Drawing M-071-00048 Sheet 28 Rev. 1, Schematic Engine Control D22 Diesel Generator 130 Limerick Drawing M-071-00048 Sheet 31 Rev. 0, Schematic Engine Control D23 Diesel Generator 131 Limerick Drawing M-071-00048 Sheet 32 Rev. 3, Schematic Engine Control D23 Diesel Generator 132 Limerick Drawing M-071-00048 Sheet 33 Rev. 1, Schematic Engine Control D23 Diesel Generator 133 Limerick Drawing M-071-00048 Sheet 36 Rev. 0, Schematic Engine Control D24 Diesel Generator 134 Limerick Drawing M-071-00048 Sheet 37 Rev. 3, Schematic Engine Control D24 Diesel Generator 135 Limerick Drawing M-071-00048 Sheet 38 Rev. 1, Schematic Engine Control D24 Diesel Generator 136 Limerick Drawing E-017-00012 Sheet 1Rev.11, Diagram - Schematic Arrangement 130 K300 and 400 Chargers 137 Limerick Drawing E-017-00014 Sheet 1 Rev. 9, Diagram - Schematic Arrangement 130 HK75/100F3 Chargers 138 Limerick Drawing E-017-00065 Sheet 1 Rev. 2, High Voltage Shutdown with Time Delay Universal PC Board 139 Limerick Drawing E-0032 Sheet 1 Rev. 64, Single Line Meter and Relay Diagram Uninterruptible AC, RPS, UPS, Computer 140 Limerick Drawing N-OOE-72-00010 Sheet 1Rev.1, Power Stage Wiring 30KVA Inverter Solid State Switch 1AD160 141 Limerick Drawing E-0032 Sheet 2 Rev. 39, Single Line Meter and Relay Diagram Un interruptible AC System 142 Limerick Drawing N-OOE-72-00015 Sheet 1 Rev. 1, Power Stage Wiring 30KVA Inverter Solid State Switch 1BD160 143 Limerick Drawing M-0020 Sheet 6 Rev. 52, Piping and Instrument Diagram Fuel and Diesel Oil Storage and Transfer (Starting Air System Unit 1) 144 Limerick Drawing M-0020 Sheet 12 Rev. 16, Piping and Instrument Diagram Fuel and Diesel Oil Storage and Transfer (Starting Air System Unit 2)
Page 30of110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 145 Limerick Drawing M-0020 Sheet 8 Rev. 23, Piping and Instrument Diagram Fuel and Diesel Oil Storange and Transfer (Combustion Air Intake and Exhaust System Unit 1) 146 Limerick Drawing M-0020 Sheet 14 Rev. 15, Piping and Instrument Diagram Fuel and Diesel Oil Storage and Transfer (Combustion Air Intake and Exhaust System Unit 2) 147 Limerick Drawing M-0020 Sheet 7 Rev. 53, Piping and Instrument Diagram Fuel and Diesel Oil Storage and Transfer (Lube Oil System Unit 1) 148 Limerick Drawing M-0020 Sheet 13 Rev. 18, Piping and Instrument Diagram Fuel and Diesel Oil Storage and Transfer (Lube Oil System Unit 2) 149 Limerick Drawing M-0020 Sheet 3 Rev. 39, Piping and Instrument Diagram Fuel and Diesel Oil Storage and Transfer (Fuel Oil and Transfer System Unit 1) 150 Limerick Drawing M-0020 Sheet 9 Rev. 17, Piping and Instrument Diagram Fuel and Diesel Oil Storage and Transfer (Fuel Oil and Transfer System Unit 2) 151 Limerick Drawing M-071-00048 Sheet 5 Rev. 21, Schematic Engine Control Dll Diesel Generator 152 Limerick Drawing M-071-00048 Sheet 10 Rev. 1, Schematic Engine Control D12 Diesel Generator 153 Limerick Drawing M-071-00048 Sheet 15 Rev. 1, Schematic Engine Control D13 Diesel Generator 154 Limerick Drawing M-071-00048 Sheet 20 Rev. 1, Schematic Engine Control D14 Diesel Generator 155 Limerick Drawing M-071-00048 Sheet 25 Rev. 1, Schematic Engine Control D21 Diesel Generator 156 Limerick Drawing M-071-00048 Sheet 30 Rev. 1, Schematic Engine Control D22 Diesel Generator 157 Limerick Drawing M-071-00048 Sheet 35 Rev. 1, Schematic Engine Control 023 Diesel Generator 158 Limerick Drawing M-071-00048 Sheet 40 Rev. 1, Schematic Engine Control 024 Diesel Generator 159 Limerick Drawing M-0020 Sheet 4 Rev. 46, Piping and Instrument Diagram Fuel and Diesel Oil Storage and Transfer (Cooling Water System Unit 1) 160 Limerick Drawing M-0020 Sheet 5 Rev. 44, Piping and Instrument Diagram Fuel and Diesel Oil Storage and Transfer (Cooling Water System Unit 1) 161 Limerick Drawing M-0020 Sheet 10 Rev. 51, Piping and Instrument Diagram Fuel and Diesel Oil Storage and Transfer (Coling Water System Unit 2) 162 Limerick Drawing M-0020 Sheet 11 Rev. 8, Piping and Instrument Diagram Fuel and Diesel Oil Storage and Transfer (Cooling Water System Unit 2) 163 Limerick Drawing M-0011Sheet1 Rev. 86, Piping and Instrument Diagram Emergency Service Water (Unit 1, Unit 2, and Common) 164 Limerick Drawing E-0321 Sheet 2 Rev. 19, Schematic Diagram Emergency Service Water Pumps 165 Limerick Drawing E-0321Sheet3 Rev. 19, Schematic Diagram Emergency Service Water Pumps 166 Limerick Drawing E-0321Sheet5 Rev. 17, Schematic Diagram Emergency Service Water Pumps Page 31of110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 167 Limerick Drawing M-0081Sheet1 Rev. 31, Piping and Instrument Diagram Miscellaneous Structures HVAC 168 Limerick Drawing M-0081 Sheet 3 Rev. 15, Piping and Instrument Diagram Miscellaneous Structures HVAC (Unit 2 and Common) 169 Limerick Drawing E-0490 Sheet 1 Rev. 16, Schematic Diagram Diesel Generator Ventilation Air Exhaust Fans and Auxiliary Control Units 1 and 2 170 Limerick Drawing E-0490 Sheet 2 Rev. 10, Schematic Diagram Diesel Generator Ventilation Air Exhaust Fans and Auxiliary Control Units 1 and 2 171 Limerick Drawing E-0163 Sheet 1 Rev. 18, Schematic Diagram - Safeguard Buses - Safeguard Load Center 172 Limerick Drawing E-0163 Sheet 2 Rev. 3, Schematic Diagram - Safeguard Buses - Safeguard Load Center 173 Limerick Drawing E-0162 Sheet 1Rev.13, Schematic Diagram-Safeguard Buses - Dl44 and D244 Page 32of110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 A Representative Sample Component Evaluations The following sample calculation is extracted from Reference [17).
Notes:
- 1.
Reference citations within the sample calculation are per the Ref. [17) reference section shown on the following page.
- 2.
This sample calculation contains evaluations of sample high-frequency-sensitive components per the methodologies of both the EPRI high-frequency guidance [8) and the flexible coping strategies guidance document NEI 12-06 [16).
Page 33 of 11 O
St""""""1&Aisociates S&A Cale. No.: 15C4345-CAL-001, Rev. 2
Title:
High Frequency Functional Confirmation and Fragility Evaluation of Components 6
REFERENCES
- 1.
Codes. Guidance. and Standards 15(4345-RPT-002, Rev.a Correspondence No.: RS-16-177 Sheet 9 of 20 Prepared: FG Date: 10/27 /16 Reviewed: MD Date: 10/27/16 1.1.
EPRI 3002004396. "High Frequency Program: Application Guidance for Functional Confirmation and Fragility Evaluation." July 2015.
1.2.
EPRI 3002002997. "High Frequency Program: High Frequency Testing Summary." September 2014.
1.3. Not Used 1.4.
NEI 12-06, Appendix H, Rev. 2, "Diverse and Flexible Coping Strategies (FLEX) Implementation Guide."
1.5.
IEEE 344-1975 "IEEE Recommended Practices for Seismic Qualification of Class lE Equipment for Nuclear Power Generating Stations" 1.6.
SQUG GIP 3A, "Generic Implementation Procedure (GIP) for Seismic Verification of Nuclear Plant Equipment", December 2001 1.7.
EPRI NP-7147-SL, "Seismic Ruggedness of Relays", August 1991 1.8.
EPRI NP-7147-SL, SQUG Advisory 2004-02. "Relay GERS Corrections", September 10, 2004 1.9.
EPRI NP-7147-SLV2, Addendum 1, "Seismic Ruggedness of Relays", September 1993 1.10. ANSI/IEEE C37.98-1987, "An American National Standard IEEE Standard Seismic Testing of Relays."
January 15, 1988 1.11. EPRI NP-6041-SL, Rev. 1, "A Methodology for Assessment of Nuclear Power Plant Seismic Margin",
August 1991 1.12. EPRI NP-7147-SLV2, Addendum 2, "Seismic Ruggedness of Relays", April 1995
- 2.
Nuclear Regulatory Commission Documents 2.1.
Limerick Generating Station Units 1 & 2 Seismic Hazard and Screening Report, Rev. 0, NRC Docket No.
STN 50-352 & STN 50-353, Correspondence No. RS-14-069
- 3.
Station Documents 3.1.
Limerick Drawing C-0409, Rev. 33, "Control Room Area, Foundations, Wall Elevations Area 8" 3.2. General Electric Report GE-101, Rev. 2, "GE Dynamic Qualification Report for Class lE Control Room Panels" 3.3.
General Electric Report GE-201, Rev. 2, "GE Dynamic Qualification Report for Class lE Control Room Panels" 3.4.
Limerick Drawing C-0682, Rev. 11, "Diesel Generator Building Unit 2 Wall Elevation & Sections" 3.5.
Limerick Report D-0014, Rev. 7, "Dynamic Qualification Book", Volumes 1-3.
3.6.
Limerick Report D-0007, Rev. 10, "Dynamic Qualification Book", Volumes 1-2.
3.7. Not Used 3.8. Limerick Report D-0015, Rev. 12, "Dynamic Qualification Book", Volumes 1-4.
- 4.
S&A Documents 4.1.
15C4345-RPT-001, Rev. 3, "Selection of Relays and Switches for High Frequency Seismic Evaluation."
- 5.
Other Documents 5.1.
TE Connectivity, Qualification Test Report 501-529, "Nuclear Environmental Qualification Test Report on Agastat EGP, EML and ETR Control Relays by Control Products Division, Amerace Corporation" 5.2.
GE Multilin IAC Time-Overcurrent Brochure, "Time-overcurrent protection of AC circuits and apparatus." (See Attachment E) 5.3. Agastat Nuclear Qualified Control Relays, dated 4/24/2002 "Series EGP/EML/ETR" (See Attachment F)
Page 34 of 110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 SA S&A Cale. No.: 1SC4345-CAL-001, Rev. 2
Title:
High Frequency Functional Confirmation and Fragility Evaluation of Components Prepared: FG Reviewed: MD Sheet 12 of 20 Date: 10/27 /16 Date: 10/27 /16 Stevenson & As.scxiates 8
ANALYSIS (cont'd) 8.2 High-Frequency Seismic Demand Calculate the high-frequency seismic demand on the components per the methodology from Ref. 1.1.
Sample calculations for the high-frequency seismic demand of components PIS-050-1 N653 located in Unit 1 and E51A-K10 located in Unit 1 are presented below. A table that calculates the high-frequency seismic demand for all of the subject components listed in Attachment A, Table A-1 of this calculation is provided in Attachment A, Table A-2 of this calculation.
8.2.1 Horizontal Seismic Demand The horizontal site-specific GMRS for Limerick is per Ref. 2.1. GMRS data can be found in Attachment B of this calculation.
Determine the peak acceleration of the horizontal GMRS between 15 Hz and 40 Hz.
Peak acceleration of horizontal GMRS between 15 Hz and 40 Hz (Ref. 2.1; see Attachment B of this calculation):
S~MRS := 0.381 g (at 15 Hz)
Calculate the horizontal in-structure amplification factor based on the distance between the bottom of the foundation elevation and the subject floor elevation.
Bottom of Deepest Foundation Elevation:
(Ref. 2.1, Table 2.3.1-1, Note C)
Component Floor Elevation (See Table A-1 ):
Elfound := 174*ft Elcomp :- 289 *ft Components PIS-050-1 N653 and E51A-K10 are both located in the Control Enclosure building at elevation 289'.
Distance Between Component Floor and Foundation Elevation:
hcomp := ELcomp - Elfound - 115.00 *ft Page 35 of 110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 SA S&A Cale. No.: 1SC4345-CAL-001, Rev. 2
Title:
High Frequency Functional Confirmation and Fragility Evaluation of Components Prepared: FG Reviewed: MD Sheet 13 of 20 Date: 10/27 /16 Date: 10/27/16 Stevenson & A5scc:iates 8
ANALYSIS (cont'd) 8.2 High-Frequency Seismic Demand (cont'd)
B.2.1 Horizontal Seismic Demand (cont'd)
Work the distance between the component floor and foundation with Ref. 1.1, Fig. 4-3 to calculate the horizontal in-structure amplification factor.
Slope of Amplification Factor Line, Oft < hcomp < 4Dft Intercept of Amplification Factor Line, Oft < hcomp < 40ft 2.1 - 1.2 1
mh :=
= 0.0225 *-
40ft - Oft ft Horizontal In-Structure Amplification Factor:
AF SH(hcomp) := I (
mh
- hcomp + bh) if hcomp s 40ft 2.1 otherwise Calculate the horizontal in-cabinet amplification factor based on the type of cabinet that contains the subject component.
Type of Cabinet (per Ref. 3.2 and 3.3)
(enter "MCC", "Switchgear", "Control Cabinet", or "Rigid"):
Horizontal In-Cabinet Amplification Factor (Ref. 1.1, p. 4-13):
cab := "Control Cabinet" AFc.h(cab) :=
3.6 if 7.2 if 4.5 if 1.0 if AFc.h(cab) = 4.5 cab= "MCC" cab = "Switchgear" cab = "Control Cabinet" cab = "Rigid" Multiply the peak horizontal GMRS acceleration between by the horizontal in-structure and in-cabinet amplification factors to determine the in-cabinet response spectrum demand on the components.
Horizontal In-Cabinet Response Spectrum (Ref. 1.1, p. 4-12, Eq. 4-1a):
Note that the horizontal seismic demand is the same for both components PIS-050-1 N653 and E51A-K10.
Page 36 of 110
S&A Cale. No.: 1SC4345-CAL-001, Rev. 2 1SC4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 SA
Title:
High Frequency Functional Confirmation and Fragility Evaluation of Components Prepared: FG Reviewed: MD Sheet 14 of 20 Date: 10/27 /16 Date: 10/27/16 Stevenson & As.scciiltes 8
ANALYSIS (cont'd) 8.2 High-Frequency Seismic Demand (cont'd)
B.2.2 Vertical Seismic Demand Determine the peak acceleration of the horizontal GMRS between 15 Hz and 40 Hz.
Peak Acceleration of Horizontal GMRS Between 15 Hz and 40 Hz (See Sect. 8. 2.1 of this Calculation)
S~MRS - 0.381.g (at 15 Hz)
Obtain the peak ground acceleration (PGA) of the horizontal GMRS from Ref. 2.1 (See Attachment B of this calculation).
Peak Ground Acceleration (GMRS):
PGAGMRS :"" 0.193g Calculate the shear wave velocity traveling from a depth of 30m to the surface of the site 01530) from Ref. 1.1 and Attachment C.
Shear Wave Velocity:
- where, di: Thickness of the layer (ft)
V si: Shear wave velocity of the layer (ft/s)
(30m)
Vs30 = 1:( di.)
VSI Per Attachment C, the sum of thickness of the layer over shear wave velocity of the layer is 0.0288 sec.
Shear Wave Velocity:
30m ft v
- =
= 3418 *-
s3o 0.028Bsec sec Page 37 of 110
S&A Cale. No.: 15C4345-CAL-001, Rev. 2 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 SA
Title:
High Frequency Functional Confirmation and Fragility Evaluation of Components Prepared: FG Reviewed: MD Sheet 15 of 20 Date: 10/27/16 Date: 10/27 /16 Stevenson & Associates 8
ANALYSIS (cont'd) 8.2 High-Frequency Seismic Demand (cont'd) 8.2.2 Vertical Seismic Demand (cont'd)
Work the PGA and shear wave velocity with Ref. 1.1, Table 3-1 to determine the soil class of the site. Based on the PGA of 0.1939 and shear wave velocity of 3418ft/sec at Limerick, the site soil class is B-Hard.
Work the site soil class with Ref. 1.1, Table 3-2 to determine the mean vertical vs. horizontal GMRS ratios (V/H) at each spectral frequency. Multiply the V/H ratio at each frequency between 15Hz and 40Hz by the corresponding horizontal GMRS acceleration at each frequency between 15Hz and 40Hz to calculate the vertical GMRS.
See Attachment B for a table that calculates the vertical GMRS (equal to (V/H) x horizontal GMRS) between 15Hz and 40Hz.
Determine the peak acceleration of the vertical GMRS (SAvGMRs) between frequencies of 15Hz and 40Hz. (By inspection of Attachment B, the SAvGMRs occurs at 15Hz.)
V/H Ratio at 15Hz (See Attachment B of this calculation):
Horizontal GMRS at Frequency of Peak Vertical GMRS (at 15Hz)
(See Attachment B of this calculation):
Peak Acceleration of Vertical GMRS Between 15 Hz and 40 Hz:
VH := 0.68 HGMRS :- 0.3819 SAvGMRS := VH *HGMRS -= 0.259*9 (at 15 Hz)
A plot of horizontal and vertical GMRS is provided in Attachment B of this calculation.
Page 38 of 110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 SA Stevenson & As.soc:iates S&A Cale. No.: 15C4345-CAL-001, Rev. 2
Title:
High Frequency Functional Confirmation and Fragility Evaluation of Components 8
ANALYSIS (cont'd) 8.2 High-Frequency Seismic Demand (cont'd) 8.2.2 Vertical Seismic Demand (cont'd)
Prepared: FG Reviewed : MD Sheet 16 of 20 Date: 10/27 /16 Date: 10/27 /16 Calculate the vertical in-structure amplification factor based on the distance between the plant foundation elevation and the subject floor elevation.
Distance Between Component Floor and Foundation (See Sect. 8.2.1 of this Calculation):
hcomp = 115.QQ.ft Work the distance between the component floor and foundation with Ref. 1.1, Fig. 4-4 to calculate the vertical in-structure amplification factor.
Slope of Amplification Factor Line:
2.7 1.0 1
mv
- ~
- 0.017 *-
1 OD ft - Oft ft Intercept of Amplification Factor Line:
Vertical In-Structure Amplification Factor:
AF SV :- mv* hcomp + bv = 2. 96 Per Ref. 1.1, the vertical in-cabinet amplification factor is 4. 7 regardless of cabinet type.
Vertical In-Cabinet Amplification Factor:
Multiply the peak vertical GMRS acceleration between by the vertical in-structure and in-cabinet amplification factors to determine the in-cabinet response spectrum demand on the component.
Vertical In-Cabinet Response Spectrum (Ref. 1.1, p. 4-12, Eq. 4-1b):
ICRSc.v :: AFsv*AFc.v *SAvGMRS = 3.60*g Note that the vertical seismic demand is the same for both components PIS-050-1 N653 and E51A-K1 DA.
Page 39 of 110
S&A Cale. No.: 15C4345-CAL-001, Rev. 2 15(4345-RPT-002, Rev. a Correspondence No.: RS-16-177 SA
Title:
High Frequency Functional Confirmation and Fragility Evaluation of Components Prepared: FG Reviewed: MD Sheet 17 of 20 Date: 10/27 /16 Date: 10/27 /16 Steven.son & Associates 8
ANALYSIS (cont'd) 8.3 High-Frequency Seismic Capacity A sample calculation for the high-frequency seismic capacity of components PIS-050-1 N653 and E51A-K10 located in Unit 1 is presented here. A table that calculates the high-frequency seismic capacities for all of the subject components listed in Attachment A, Table A-1 of this calculation is provided in Attachment A, Table A-2 of this calculation.
8.3.1 Seismic Test Capacity The high frequency seismic capacity of a component can be determined from the EPRI High Frequency Testing Program (Ref. 1.2) or other broad banded low frequency capacity data such as the Generic Equipment Ruggedness Spectra (GERS) or other qualification reports.
The model for component PIS-050-1 N653, a Rosemount 510DU2 trip unit per Table A-1, was not tested as part of the Ref. 1.2 high-frequency testing program. Attachment A (Group 1) provides a seismic capacity calculation for Rosemount 510DU2 trip unit based on Limerick Seismic Report GE-101 (Ref. 3.20). The seismic capacity was calculated in Attachment A to be 11. 62g for component Pl S-050-1 N653.
The model for component E51A-K10 is an Agastat EGPB002 relay per Table A-1. Per Ref. 5.1, Page 2, Agastat EGP and GP series relays are the same relays and the "E" (nuclear safety related) designator was added to the front. Per Ref. 1.12, Page 2-4, the lowest capacity of Agastat Model GP relay 5.0g. Note that the capacity of Agastat GP relay provided in Ref. 1.12, Page 2-4 and 2-6 is based on additional verification test level only (this capacity is not the GERS capacity, but a qualification test capacity).
Seismic Test Capacity (SA*):
8.3.2 Effective Spectral Test Capacity
(
11.62)
SA':=
g 5.00
(
PIS-050-1 N653 )
E51A-K10 Since a qualification report was used as the capacity source for both components, there are no spectral acceleration increases and the effective spectral test capacity is equal to the seismic test capacity.
Effective Spectral Test Capacity (Ref. 1.1, p. 4-16):
- -(SA'1 J-(11.62)
SAT.-
- g SA'2 5.00
(
PIS-050-1 N653)
E51A-K10 Page 40 of 110
SA Stevenson & Associates S&A Cale. No.: 1SC4345-CAL-001, Rev. 2
Title:
High Frequency Functional Confirmation and Fragility Evaluation of Components 8
ANALYSIS (cont'd) 8.3 High-Frequency Seismic Capacity (cont'd) 8.3.3 Seismic Capacity Knockdown Factor 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Prepared: FG Reviewed: MD Sheet 18 of 20 Date: 10/27 /16 Date: 10/27 /16 Determine the seismic capacity knockdown factor for the subject component based on the type of testing used to determine the seismic capacity of the component.
Using Table 4-2 of Ref. 1.1 and the capacity sources from Section 8.3.1 above, the knockdown factors are chosen as:
Seismic Capacity Knockdown Factor:
8.3.4 Seismic Testing Single-Axis Correction Factor F := (1.20 )
k 1.20
(
PIS-050-1 N653)
E51A-K10 Determine the seismic testing single-axis correction factor of the subject component, which is based on whether the equipment housing to which the component is mounted has well-separated horizontal and vertical motion or not.
Per Ref. 1.1, pp. 4-18, conservatively take the FMs value as 1.0.
Single-Axis Correction Factor (Ref. 1.1, pp. 4-17 to 4-18):
FMS := 1.0 Page 41 of 110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Steven.son & As.scciates S&A Cale. No.: 15C4345-CAL-001, Rev. 2
Title:
High Frequency Functional Confirmation and Fragility Evaluation of Components 8
ANALYSIS (cont'd)
Prepared: FG Reviewed: MD 8.3 High-Frequency Seismic Capacity for Ref. 1.1 Components (cont'd) 8.3.5 Effective Wide-Band Component Capacity Acceleration Calculate the effective wide-band component capacity acceleration per Ref. 1.1, Eq. 4-5.
Effective Wide-Band Component Capacity Acceleration (Ref. 1. 1, Eq. 4-5):
[
SAT)
(9.683)
TRS :=-
- FMS =
- g Fk 4.167 8.4 High-Frequency Seismic Capacity for Ref. 1.4, Appendix H Components 8.4.1 Effective Wide-Band Component Capacity Acceleration Sheet 19 of 20 Date: 10/27/16 Date: 10/27 /16
(
PIS-050-1N653 )
E51A-K10 Per a review of the capacity generation methodologies of Ref. 1.1 and Ref. 1.4, App. H, Section H.5, the capacity of a Ref. 1.4 component is equal to the Ref. 1.1 effective wide-band component capacity multiplied by a factor accounting for the difference between a 1 % probability of failure (C1 %* Ref. 1.1) and a 10%
probability of failure (C10'A,. Ref. 1.4).
Per Ref. 1.4, App. H, Table H.1, use the C10% vs. C1% ratio from the Realistic Lower Bound Case for components.
c10',, vs. c,% ratio Effective wide-band component capacity acceleration (Ref. 1.4, App. H, Sect. H.5) c10 :=- 1.36
(
13.169)
TRS1 4 := TRS*C10 -'
- g 5.667
(
PIS-050-1N653 )
E51A-K10 Page 42 of 110
SA Stevenson & Associates S&A Cale. No.: 15C4345-CAL-001, Rev. 2
Title:
High Frequency Functional Confirmation and Fragility Evaluation of Components 8
ANALYSIS (cont'd) 8.5 Component (Ref. 1.1) High-Frequency Margin 1SC4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Prepared: FG Reviewed: MD Sheet 20 of 20 Date: 10/27/16 Date: 10/27/16 Calculate the high-frequency seismic margin for components per Ref. 1.1, Eq. 4-6.
A sample calculation for the high-frequency seismic demand of components PIS-050-1 N653 and E51A-K10 is presented here. A table that calculates the high-frequency seismic margin for all of the subject components listed in Attachment A, Table A-1 of this calculation is provided in Attachment A, Table A-2 of this calculation.
TRS (2.689)
> 1.0, O.K.
(PIS-050-1N653)
Horizontal seismic margin (Ref. 1.1, Eq. 4-6):
ICRSc.h "' 1.157
> 1.0, O.K.
> 1.0, O.K.
( PIS-050-1 N653)
Vertical seismic margin (Ref. 1.1, Eq. 4-6):
ICRSc.v =
1.158
> 1.0, O.K.
E51A-K10 Both the horizontal and vertical seismic margins for PIS-050-1 N653 and E51A-K10 are greater than 1.00; indicating that these components are adequate for high frequency seismic spectral ground motion for its Ref.
1.1 functions.
8.6 Component (Ref. 1.4) High-Frequency Margin Calculate the high-frequency seismic margin for Ref. 1.4 components per Ref. 1.1, Eq. 4-6.
A sample calculation for the high-frequency seismic demand of component components PIS-050-1 N653 and E51A-K10 is presented here. A table that calculates the high-frequency seismic margin for all of the subject components listed in Attachment A, Table A-1 of this calculation is provided in Attachment A, Table A-2 of this calculation.
Horizontal seismic margin (Ref. 1.1, Eq. 4-6):
=
TRS1 4 (3.658)
ICRSc.h 1.574 Vertical seismic margin (Ref. 1.1, Eq. 4-6):
TRS1.4 (3.660)
ICRSc.v =
1.575
> 1.0, O.K.
> 1.0, O.K.
> 1.0, O.K.
> 1.0, O.K.
(
PIS-050-1 N653 )
(
PIS-050-1 N653)
E51A-K10 Both the horizontal and vertical seismic margins for PIS-050-1 N653 and E51A-K10 are greater than 1.00; therefore, these components are adequate for high-frequency seismic spectral ground motion for its Ref. 1.4 functions.
Page 43 of 110
1SC4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 B Components Identified for High Frequency Confirmation Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Component Evaluation Floor No.
Unit Manufacturer Model No.
Building Elev. {ft)
Basis for Evaluation ID Type System Function ID Type Capacity Result PIS-049-Control Core RCIC Steam Pressure Rosemount 510DU1 10-C617 Control Control 289 Qualification Cap> Dem 1
1 1N658A Relay Cooling Indicating Switch Cab.
Enclosure Test 2
1 PIS-049-Control Core RCIC Steam Pressure Rosemount 710DUOIT 10-C640 Control Control 289 Qualification Cap> Dem 1N658C Relay Cooling Indicating Switch Cab.
Enclosure Test PIS-049-Control Core RCIC Steam Pressure 510DU1 10-C617 Control Control 289 Qualification 3
1 1N658E Relay Cooling Indicating Switch Rosemount Cab.
Enclosure Test Cap> Dem PIS-049-Control Core RCIC Steam Pressure 510DU1 10-C640 Control Control 289 Qualification 4
1 1N658G Relay Cooling Indicating Switch Rosemount Cab.
Enclosure Test Cap> Dem 5
1 PIS-050-Control Core RCIC Pump Suction Rosemount 510DU2 10-C617 Control Control 289 Qualification Cap> Dem 1N653 Relay Cooling Header Cab.
Enclosure Test 6
1 PIS-050-Control Core RCIC Turbine Exhaust Rosemount 510DU1 10-C617 Control Control 289 Qualification 1N655A Relay Cooling Line Vent Cab.
Enclosure Test Cap> Dem PIS-050-Control Core RCIC Turbine Exhaust 510DU1 10-C640 Control Control Qualification 7
1 1N655C Relay Cooling Line Vent Rosemount Cab.
Enclosure 289 Test Cap> Dem 8
1 PIS-050-Control Core RCIC Turbine Exhaust Rosemount 510DU1 10-C617 Control Control 289 Qualification Cap> Dem 1N655E Relay Cooling Line Vent Cab.
Enclosure Test PIS-050-Control Core RCIC Turbine Exhaust 510DU1 10-C640 Control Control 289 Qualification 9
1 1N655G Relay Cooling Line Vent Rosemount Cab.
Enclosure Test Cap>Dem 10 1
PIS-050-Control Core RCIC Pump Turbine 510DU2 10-C617 Control Control 289 Qualification 1N656A Relay Cooling Exhaust Rosemount Cab.
Enclosure Test Cap> Dem 11 1
PIS-050-Control Core RCIC Pump Turbine Rosemount 510DU2 10-C617 Control Control 289 Qualification 1N656E Relay Cooling Exhaust Cab.
Enclosure Test Cap> Dem 12 2
PIS-049-Control Core RCIC Steam Pressure 510DU1 20-C617 Control Control 289 Qualification 2N658A Relay Cooling Indicating Switch Rosemount Cab.
Enclosure Test Cap> Dem 13 2
PIS-049-Control Core RCIC Steam Pressure Rosemount 710DUOIT 20-C640 Control Control 289 Qualification 2N658C Relay Cooling Indicating Switch Cab.
Enclosure Test Cap> Dem 14 2
PIS-049-Control Core RCIC Steam Pressure Rosemount 510DU1 20-C617 Control Control 289 Qualification Cap> Dem 2N658E Relay Cooling Indicating Switch Cab.
Enclosure Test Page 44 of 110
I 1 ~~.t ~
No.
I ' Type_]
110 2
PIS-049-Control 15 2N658G Relay PIS-050-Control 16 2
2N653 Relay PIS-OSO-Control 17 2
2N655A Relay PIS-050-Control 18 2
2N655C Relay PIS-050-Control 19 2
2N655E Relay 2
PIS-050-Control 20 2N655G Relay 2
PIS-050-Control 21 2N656A Relay PIS-050-Control 22 2
2N656E Relay Control 23 1
E51A-K10 Relay Control 24 1
E51A-K11A Relay Control 25 1
E51A-K11C Relay Control 26 1
E51A-K12A Relay 15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component
~S~ f B~ll~~--,
Floor Component Evaluation I ~yste~ J ~ctlon
~
[Manufactu~
Model No.
Elev. (ft)
'Basis for Evaluation Type CaDacltv Result Core RCIC Steam Pressure Rosemount 710DUOTI 20-C640 Control Control 289 Qualification Cap> Dem Cooling Indicating Switch Cab.
Enclosure Test Core RCIC Pump Suction 710DUOTI 20-C617 Control Control 289 Qualification Cap> Dem Rosemount Cooling Header Cab.
Enclosure Test Core RCIC Turbine Exhaust Rosemount 510DU1 20-C617 Control Control 289 Qualification Cap> Dem Cooling Line Vent Cab.
Enclosure Test Core RCIC Turbine Exhaust 710DUOTI 20-C640 Control Control 289 Qualification Cap> Dem Cooling Line Vent Rosemount Cab.
Enclosure Test Core RCIC Turbine Exhaust 710DUOTI 20-C617 Control Control 289 Qualification Cap> Dem Cooling Line Vent Rosemount Cab.
Enclosure Test Core RCIC Turbine Exhaust Rosemount 510DU2 20-C640 Control Control 289 Qualification Cap> Dem Cooling Line Vent Cab_
Enclosure Test Core RCIC Pump Turbine Rosemount 710DUOTI 20-C617 Control Control 289 Qualification Cap> Dem Cooling Exhaust Cab.
Enclosure Test Core RCIC Pump Turbine 710DUOTI 20-C617 Control Control 289 Qualification Cap> Dem Cooling Exhaust Rosemount Cab.
Enclosure Test RCIC Pump Suction Core Pressure Relay Control Control Qualification Cooling Energize on Pressure Agastat EGPB002 10-C621 Cab.
Enclosure 289 Test Cap> Dem On Vacuum Less than Set-point RCIC Relay-Energize Core on Turbine Control Control Qualification Cooling Diaphragm Exhaust Agastat EGPB002 10-C621 Cab.
Enclosure 289 Test Cap> Dem Pressure Above Set-point RCIC Relay - Energize Core On Turbine Control Control Qualification Cooling Diaphragm Exhaust Agastat EGPB002 10-C640 Cab.
Enclosure 289 Test Cap> Dem Pressure Above Set-Point RCIC RELAY-Core Energize on Turbine Control Control Qualification Cooling Diaphragm Exhaust Agastat EGPB002 10-C621 Cab.
Enclosure 289 Test Cap> Dem Pressure Above Set-point Page 45 of 110
No. ' Unit "El [
ID II Type 27 1
E51A-K12C Control Relay 28 1
E51A-K13 Control Relay 29 1
E51A-K14 Control Relay 30 1
E51A-K16A Control Relay E51A-K16C Control 31 1
Relay Control 32 1
E51A-K17A Relay 33 1
E51A-K17C Control Relay 34 1
E51A-K28 Control Relay 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation
'Enclosure Building]
Component Floor J Component Evaluation
!! Sys;~ ] ! ~unction lr Man:itact~ i ModelNo. 1
~
Elev. {ft)
Basis for Evaluation ID Capacity Result RCIC Relay - Energize Core on Turbine Control Control Qualification Cooling Diaphragm Exhaust Agastat EGPB002 10-C640 Cab.
Enclosure 289 Test Cap> Dem Pressure Above Set-Point RCIC Relay -
Core Energizes On Turbine Agastat EGPB002 10-C621 Control Control 289 Qualification Cap> Dem Cooling Exhaust Pressure Cab.
Enclosure Test Above Set-point RCIC Relay -
Core Energizes On Turbine Agastat EGPB002 10-C621 Control Control 289 Qualification Cap> Dem Cooling Exhaust Pressure Cab.
Enclosure Test Above Set-Point RCIC Relay -
Core Energizes On Steam Agastat EGPB002 10-C621 Control Control 289 Qualification Cap> Dem Cooling Line Pressure Below Cab.
Enclosure Test Set-point RCIC Relay -
Core Energizes On Steam Agastat EGPB002 10-C640 Control Control 289 Qualification Cap> Dem Cooling Line Pressure Below Cab.
Enclosure Test Set-Point RCIC Relay -
Core Energizes On Steam Agastat EGPB002 10-C621 Control Control 289 Qualification Cooling Line Pressure Below Cab.
Enclosure Test Cap> Dem Set-point RCIC Relay -
Core Energizes On Steam Agastat EGPB002 10-C640 Control Control 289 Qualification Cap>Dem Cooling Line Pressure Below Cab.
Enclosure Test Set-Point Core RCIC Turbine Trip Agastat EGPD002 10-C621 Control Control 289 Qualification Cap> Dem Cooling Auxiliary Relay Cab.
Enclosure Test Page 46 of 110
[~n:J I
No.,
[= ro l [_rvpe :!
35 1
E51A-K30A Control Relay 36 1
ES1A-K30C Control Relay 37 1
E51A-K31A Control Relay 38 1
ES1A-K31C Control Relay 39 1
E51A-K67C Control Relay Control 40 2
ESlA-KlO Relay Control 41 2
ESlA-KllA Relay Control 42 2
ESlA-KllC Relay 15C4345-RPT-002, Rev. a Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation
<lomponent Enclosure
~ullding !
F.loor Component Evaluation
~te~J I Function x J ~nufact~~r l Model No.
ID
~
l;lev. (ft)
Basis for Evaluation capacity Result Steam Leak Detection Relay Core (RCIC Isolation Signal Agastat EGPD002 10-C621 Control Control 289 Qualification Cap > Dem Cooling Manual Isolation Cab.
Enclosure Test Relay - Valve ESl-F008)
RCIC DIV 3 Isolation Core Signal and Steam Agastat EGPD002 10-C640 Control Control 289 Qualification Cooling line Detection Relay Cab.
Enclosure Test Cap > Dem (ES1-F007)
RCIC Isolation Signal Core Manual Isolation Agastat EGPD002 10-C621 Control Control Qualification Cooling Relay - Valve ESl-Cab.
Enclosure 289 Test Cap> Dem F008 RCIC Isolation Signal Core Manual Isolation Agastat EGPD002 Control Control Qualification Cooling Relay-Valve ESl-10-C640 Cab.
Enclosure 289 Test Cap> Dem F008 Core RCIC DIV 3 Isolation Agastat EGPD002 10-C640 Control Control Qualification Cooling Signal Relay Enclosure 289 Cap> Dem Cab.
Test RCIC Pump Suction Core Pressure Relay -
Control Control Qualification Energize on Pressure Agastat EGPB003 20-C621 289 Cap > Dem Cooling on Vacuum Less than Cab.
Enclosure Test Set-point RCIC Relay - Energize Core on Turbine Control Control Qualification Diaphragm Exhaust Agastat EGPB003 20-C621 Cooling Cab.
Enclosure 289 Test Cap > Dem Pressure Above Set-Point RCIC Relay - Energize Core on Turbine Control Control Qualification Diaphragm Exhaust Agast at EGPB003 20-C640 289 Cap > Dem Cooling Pressure Above Set-Cab.
Enclosure Test Point Page 47of110
I No. I Unit ID Type Control 43 2
E51A-K12A Relay 44 2
E51A-K12C Control Relay E51A-K13 Control 45 2
Relay 46 E51A-K14 Control 2
Relay E51A-K16A Control 47 2
Relay Control 48 2
E51A-K16C Relay 2
E51A-K17A Control 49 Relay 50 2
E51A-K17C Control Relay 51 2
E51A-K28 Control Relay Table B-1: Components Identified for High Frequency Confirmation Enclosure Component I
Building System Function Manufacturer Model No.
ID Type RCIC Relay - Energize Core on turbine Control Control Diaphragm Exhaust Agastat EGPB003 20-C621 Cooling Cab.
Enclosure Pressure Above Set-Point RCIC Relay - Energize Core on Turbine Control Control Cooling Diaphragm Exhaust Agastat EGPB003 20-C640 Cab.
Enclosure Pressure Above Set-Point RCIC Relay-Core Energizes on Turbine Agastat EGPB003 20-C621 Control Control Cooling Exhaust Pressure Cab.
Enclosure Above Set-Point RCIC Relay-Core Energizes on Turbine Agastat EGPB003 20-C621 Control Control Cooling Exhaust Pressure Cab.
Enclosure Above Set-Point RCIC RELAY-Core Energizes On Steam Agastat EGPB003 20-C621 Control Control Cooling Line Pressure Below Cab.
Enclosure Set-Point RCIC Relay-Core Energizes on Steam EGPB003 20-C640 Control Control Cooling Line Pressure Below Agastat Cab.
Enclosure Set-Point RCIC RELAY-Core Energizes On Steam Agastat EGPB003 20-C621 Control Control Cooling Line Pressure Below Cab.
Enclosure Set-Point RCIC Relay-Core Energizes on Steam Agastat EGPB002 20-C640 Control Control Cooling Line Pressure Below Cab.
Enclosure Set-Point Core RCIC Turbine Trip Agastat EGPD003 20-C621 Control Control Cooling Auxiliary Relay Cab.
Enclosure 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Component Evaluation' I
Floor
- 1 Elev. (ft)
Basis for Evaluation capacltv Result Qualification 289 Cap> Dem Test Qualification 289 Test Cap> Dem 289 Qualification Cap> Dem Test 289 Qualification Cap >Dem Test 289 Qualification Cap> Dem Test 289 Qualification Cap> Dem Test 289 Qualification Cap> Dem Test 289 Qualification Cap> Dem Test 289 Qualification Cap> Dem Test Page 48 of 11 O
1No.
Unit ID f,ype S2 2
ES1A-K30A Control Relay ES1A-K30C Control S3 2
Relay ES1A-K31A Control S4 2
Relay SS 2
ES1A-K31C Control Relay S6 ES1A-K67C Control 2
Relay S7 1
ESlA-KlSA Control Relay Control SS 1
ESlA-KlSC Relay S9 2
ESlA-KlSA Control Relay Control 60 2
ESlA-KlSC Relay lSO/lSl-Protective 61 1
11508A Relay Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Bullc!lng System1 Function Manufacturer Model No.
ID Type I
Steam Leak Detection Relay Core
{RCIC Isolation Signal EGPD003 20-C621 Control Control Cooling Manual Isolation Agastat Cab.
Enclosure Relay-Valve ESl-FOOS)
RCIC DIV 3 Isolation Core Signal and Steam Agastat EGPD003 20-C640 Control Control Cooling Line Detection Relay Cab.
- Enclosure (ES1-F007)
RCIC Isolation Signal Core Manual Isolation Agastat EGPD003 20-C621 Control Control Cooling Relay - Valve ESl-Cab.
Enclosure FOOS RCIC Isolation Signal Core Manual Isolation EGPD003 20-C640 Control Control Cooling Relay-Valve ESl-Agastat Cab.
Enclosure FOOS Core RCIC DIV 3 Isolation Agastat EGPD003 20-C640 Control Control Cooling Signal Relay Cab.
Enclosure Core RCIC System Steam ETR14B3B Control Control Cooling Flow Above Set-point Agastat C2004002 10-C621 Cab.
Enclosure Time Delay Relay Core RCIC System Steam ETR14B3B Control Control Cooling Flow Above Set-Point Agastat C2004002 10-C640 Cab.
Enclosure Time Delay Relay Core RCIC System Steam ETR14B3C Control Control Cooling Flow Above Set-point Agastat 003 20-C621 Cab.
Enclosure Time Delay Relay Core RCIC System Steam ETR14B3C Control Control Cooling Flow Above Set-Point Agastat 003 20-C640 Cab.
Enclosure Time Delay Relay AC/DC Power ESW Pump OAPS48 GE 121AC66KS Dll-Bus-OS Switch Control Support Overcurrent Phase A A-S gear Enclosure Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177
- 1 Floor Component Evaluation Basis for
!;valuation Elev. (ft)
I Capacity Result 2S9 Qualification Cap> Dem Test 2S9 Qualification Cap> Dem Test 2S9 Qualification Cap> Dem Test 2S9 Qualification Cap> Dem Test 2S9 Qualification Cap> Dem Test Qualification 2S9 Test Cap> Dem Qualification 289 Test Cap> Dem Qua lificat1on 289 Test Cap> Dem Qualification 289 Test Cap> Dem 239 Qualification Cap> Dem Test Page 49 of 110
No.
Unit ID f
Type
~
62 lS0/151-Protective 1
115088 Relay lS0/151-Protective 63 1
11508C Relay 64 150/151-Protective 1
11608A Relay 65 1
150/151-Protective 116088 Relay 66 1
150/151-Protective 11608C Relay 67 2
lS0/151-Protective 11605A Relay 68 2
150/151-Protective 116058 Relay 69 2
150/151-Protective 11605C Relay 70 2
150/151-Protective 11708A Relay 71 2
150/151-Protective 117088 Relay Table B-1: Components Identified for High Frequency Confirmation C::omponent Enclosure System1 Function Manufacturer M oilelNo.
ID Type Bulldlng AC/DC Power ESW Pump OAP548 GE 121AC66K8 D11-8us-08 Switch Control Support Overcurrent Phase 8 A-S gear Enclosure Systems AC/DC Power ESW Pump OAP548 GE 121AC66K8 D11-8us-08 Switch Control Support Overcurrent Phase C A-S gear Enclosure Systems AC/DC Power ESW Pump 08PS48 GE 121AC66K8 D12-8us-08 Switch Control Support Overcurrent Phase A A-S gear Enclosure Systems AC/DC Power ESW Pump 08P548 GE 121AC66K8 D12-8us-08 Switch Control Support Overcurrent Phase 8 A-S gear Enclosure Systems AC/DC Power ESW Pump 08P548 GE 121AC66K8 D12-8us-08 Switch Control Support Overcurrent Phase C A-S gear Enclosure Systems AC/DC Power D224 Load Center GE 121AC778 D22-8us-05 Switch Control Support Overcurrent Phase A 812A-S gear Enclosure Systems AC/DC Power D224 Load Center GE 121AC778 D22-8us-05 Switch Control Support Overcurrent Phase 8 812A-S gear Enclosure Systems AC/DC Power D224 Load Center GE 121AC778 D22-8us-05 Switch Control Support Overcurrent Phase C 812A-S gear Enclosure Systems AC/DC Power ESW Pump OCP548 GE 121AC66K8 D23-8us-08 Switch Control Support Overcurrent Phase A A-S gear Enclosure Systems AC/DC Power ESW Pump OCP548 GE 121AC66K8 D23-8us-08 Switch Control Support Overcurrent Phase B A-S gear Enclosure Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Floor Component Evaluation Elev. (ft)
Basis for Evaluation Capacity Result 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem Page 50of110
1 No. I Unit ID
~ype 150/151-Protective 72 2
11708C Relay 73 1
132-AG501 Protective Relay Protective 74 1
132-BGSOl Relay Protective 75 1
132-CGSOl Relay 132-DGSOl Protective 76 1
Relay 187G-Protective 77 1
Relay AGSOlA 187G-Protective 78 1
Relay AG501B 187G-Protective 79 1
AG501C Relay 80 187G-Protective 1
Relay BGSOlA 187G-Protective 81 1
BG501B Relay Table B-1: Components Identified for High Frequency Confirmation Component Enclosure r
Building System Function Manufacturer Model No.
ID Type AC/DC Power ESW Pump OCP548 GE 121AC66KB D23-Bus-08 Switch Control Support Overcurrent Phase C A-S gear Enclosure Systems AC/DC Power Anti-Motoring Relay 121CW51A Dll-Bus-07 Switch Control GE 2A-S Enclosure Support gear Systems AC/DC Power Anti-Motoring Relay GE 121CW51A D12-Bus-07 Switch Control 2A-S Enclosure Support gear Systems AC/DC Power Anti-Motoring Relay GE 121CW51A Dl3-Bus-07 Switch Control 2A-S Enclosure Support gear Systems AC/DC Power Anti-Motoring Relay GE 121CW51A D14-Bus-07 Switch Control 2A-S Enclosure Support gear Systems AC/DC Power Dll A Phase GE 121JD52Al Dll-Bus-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power Dll B Phase GE 121JD52A1 Dll-Bus-07 Switch Control Support Differential Relay 1A-S Enclosure gear Systems AC/DC Power Dll C Phase GE 121JD52A1 Dll-Bus-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power D12 A Phase GE 121JD52Al D12-Bus-07 Switch Control Differential Relay lA-S Enclosure Support gear Systems AC/DC Power 012 B Phase GE 121JD52Al D12-Bus-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems 15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 I Fk>or Component Evaluation I Elev. (ft) 1 Basis for Evaluation Capacity Result 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Test Cap> Dem 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test Page51 of110
I No. I Unit I 110 T,ype I
I 187G-Protective 82 1
Relay BGSOlC 187G-Protective 83 1
Relay CGSOlA 187G-Protective 84 1
Relay CGSOlB 187G-Protective 85 1
Relay CGSOlC 86 187G-Protective 1
Relay DGSOlA 187G-Protective 87 1
DGSOlB Relay 88 187G-Protective 1
DGSOlC Relay 132-AGSOl Protective 89 2
Relay 90 2
132-BGSOl Protective Relay 91 2
132-CGSOl Protective Relay Table B-1: Components Identified for High Frequency Confirmation Component Enclosure System I I Function Manufacturer Model No.
ID Type Building AC/DC Power D12 C Phase GE 121JD52Al D12-Bus-07 Switch Control Differential Relay lA-S Enclosure Support gear Systems AC/DC Power D13 A Phase 121JD52A1 D13-Bus-07 Switch Control Differential Relay GE lA-S Enclosure Support gear Systems AC/DC Power D13 B Phase GE 121JD52A1 D13-Bus-07 Switch Control Differential Relay Enclosure Support lA-S gear Systems AC/DC Power D13 C Phase GE 121JD52Al D13-Bus-07 Switch Control Differential Relay lA-S Enclosure Support gear Systems AC/DC Power D14 A Phase GE 121JD52Al D14-Bus-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power D14 B Phase GE 121JD52Al D14-Bus-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power D14 C Phase GE 121JD52Al D14-Bus-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power Anti-Motoring Relay GE 121CWS1A D21-Bus-07 Switch Control Support 2A-S Enclosure gear Systems AC/DC Power Anti-Motoring Relay GE 121CWS1A D22-Bus-07 Switch Control Support 2A-S gear Enclosure Systems AC/DC Power Anti-Motoring Relay GE 121CW51A D23-Bus-07 Switch Control Support 2A-S gear Enclosure Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Floor Component Evaluation Elev. (ft)
Basis for Evaluation Capacltv Result 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Test Cap> Dem 239 Qualification Cap> Dem Test Page 52 of 110
No.
Unit ID Type 92 2
132-DGSOl Protective Relay 187G-Protective 93 2
AGSOlA Relay 187G-Protective 94 2
AGSOlB Relay 95 2
187G-Protective AGSOlC Relay 96 187G-Protective 2
BGSOlA Relay 97 187G-Protective 2
BGSOlB Relay 98 2
187G-Protective BGSOlC Relay 187G-Protective 99 2
CGSOlA Relay 100 2
187G-Protective CGSOlB Relay 101 2
187G-Protective CGSOlC Relay Table B-1: Components Identified for High Frequency Confirmation Component Enclosure System Function
' Manufacturer Model No.
ID Type Building AC/DC Power Anti-Motoring Relay GE 121CWS1A D24-Bus-07 Switch Control Support 2A-S gear Enclosure Systems AC/DC Power D21 A Phase GE 121JD52Al D21-Bus-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power 021 B Phase GE 121JD52Al D21-Bus-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power D21 C Phase GE 121JD52Al D21-Bus-07 Switch Control Support Differential Relay lA-S gear Enclosure Systems AC/DC Power D22 A Phase GE 121JD52Al D22-Bus-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power D22 B Phase GE 121JD52Al D22-Bus-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power D22 C Phase GE 121JD52Al D22-Bus-07 Switch Control Support Differential Relay lA-S gear Enclosure Systems AC/DC Power D23 A Phase GE 121JD52Al D23-Bus-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power D23 B Phase GE 121JD52Al D23-Bus-07 Switch Control Support Differential Relay lA-S gear Enclosure Systems AC/DC Power D23 C Phase GE 121JDS2Al 023-Bus-07 Switch Control Support Differential Relay lA-S gear Enclosure Systems 15C4345-RPT-002, Rev.O Correspondence No.: RS-16-177 1
Floor Component Evaluation Elev. (ft)
Basis for-Evaluation Capacity Result 239 Qualification Cap> Dem Test 239 Qualification Test Cap>Dem 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test Page 53 of 110
No.
Unit ID Type 2
187G-Protective 102 DG501A Relay 187G-Protective 103 2
Relay DG501B 187G-Protective 104 2
DG501C Relay 150/151-Protective 105 1
11505A Relay 150/151-Protective 106 1
115058 Relay 107 1
150/151-Protective 11505C Relay 108 1
150/151-Protective 11605A Relay 109 1
150/151-Protective 116058 Relay 110 1
150/151-Protective 11605C Relay 1
150/151-Protective 111 11705A Relay Table B-1: Components Identified for High Frequency Confirmation Compon_ent Enclosure System Function Manufacturer Model No.
ID I
Type Bulldlng AC/DC Power D24 A Phase GE 121JD52Al D24-8us-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power D24 8 Phase 121JD52Al D24-8us-07 Switch Control Support Differential Relay GE lA-S Enclosure gear Systems AC/DC Power D24 C Phase GE 121JD52Al D24-8us-07 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power D114 Load Center GE 121AC778 Dll-8us-05 Switch Control Support Overcurrent Phase A 812A-S Enclosure gear Systems AC/DC Power D114 Load Center GE 121AC77B Dll-8us-05 Switch Control Support Overcurrent Phase 8 812A-S Enclosure gear Systems AC/DC Power D114 Load Center GE 121AC778 Dll-8us-05 Switch Control Support Overcurrent Phase C 812A-S gear Enclosure Systems AC/DC Power D124 Load Center GE 121AC778 D12-8us-05 Switch Control Support Overcurrent Phase A 812A-S gear Enclosure Systems AC/DC Power D124 Load Center GE 121AC778 D12-8us-05 Switch Control Support Overcurrent Phase 8 812A-S gear Enclosure Systems AC/DC Power D124 Load Center GE 121AC778 D12-8us-05 Switch Control Support Overcurrent Phase C 812A-S gear Enclosure Systems AC/DC Power Dl34 Load Center GE 121AC778 D13-8us-05 Switch Control Support Overcurrent Phase A 812A-S Enclosure gear Systems 15C4345-RPT-002,Rev.O Correspondence No.: RS-16-177 Floor Component Evaluatlon Basis for Evaluatlon Elev. (ft) canadtv Result 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap>Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Test Cap> Dem Page 54of110
No. I ~ Un it
~
ID Type 112 150/151-Protective 1
117058 Relay 150/151-Protective 113 1
11705C Relay 114 1
150/151-Protective 11805A Relay 115 150/151-Protective 1
118050 Relay 116 1
150/151-Protective 11805C Relay 117 2
150/151-Protective 11505A Relay 118 2
150/151-Protective 115050 Relay 119 150/151-Protective 2
11505C Relay 120 2
150/151-Protective 11705A Relay 121 2
150/151-Protective 117058 Relay Table B-1: Components Identified for High Frequency Confirmation Component Enclosure System I Function Manufacturer Model No.
ID Type Building AC/DC Power D134 Load Center GE 121AC77B D13-Bus-05 Switch Control Support Overcurrent Phase B 812A-S Enclosure gear Systems AC/DC Power D134 Load Center GE 121AC77B D13-Bus-05 Switch Control Support Overcurrent Phase C 812A-S Enclosure gear Systems AC/DC Power D144 Load Center GE 121AC77B D14-Bus-05 Switch Control Support Overcurrent Phase A 812A-S gear Enclosure Systems AC/DC Power D144 Load Center GE 121AC77B D14-0us-05 Switch Control Support Overcurrent Phase 0 812A-S Enclosure gear Systems AC/DC Power D144 Load Center GE 121AC770 D14-0us-05 Switch Control Support Overcurrent Phase C 812A-S gear Enclosure Systems AC/DC Power D214 Load Center GE 121AC770 D21-0us-05 Switch Control Support Overcurrent Phase A 812A-S gear Enclosure Systems AC/DC Power D214 Load Center GE 121AC77B D21-Bus-05 Switch Control Support Overcurrent Phase 0 812A-S gear Enclosure Systems AC/DC Power D214 Load Center GE 121AC77B D21-Bus-05 Switch Control Support Overcurrent Phase C 812A-S Enclosure gear Systems AC/DC Power D234 Load Center GE 121AC77B D23-Bus-05 Switch Control Support Overcurrent Phase A 812A-S gear Enclosure Systems AC/DC Power D234 Load Center GE 121AC770 D23-0us-05 Switch Control Support Overcurrent Phase B 812A-S gear Enclosure Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 11 Floor i Co!!Jponent Evaluation J;lev. (ft)
Basis for Evaluation Capacity Result 239 Qualification Cap> Dem Test 239 Qualification Cap>Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem Page 55 of 110
No. ! r: n-lt l
~ *~_ 10 H
T,ype ' J 150/151-Protective 122 2
11705C Relay 150/151-Protective 123 2
Relay 11805A 150/151-Protective 124 2
118058 Relay 150/151-Protective 125 2
11805C Relay 150/151-Protective 126 2
Relay 11808A 150/151-Protective 127 2
118088 Relay 150/151-Protective 128 2
11808C Relay 129 151-11702A Protective 1
Relay 130 1
151-11702B Protective Relay 151-11702C Protective 131 1
Relay 15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component Enclosure l B~dlng I Floor Component Evaluation L ~tem I
~ F~nctio'!..
! I Manufa~u~~
- Model No. [~ I? ~ilrv~
Elev. (ft)
Basis for Evaluation capacity Result AC/DC Power D234 Load Center GE 121AC77B D23-Bus-05 Switch Control 239 Qualification Cap> Dem Support Overcurrent Phase C 812A-S Enclosure Test gear Systems AC/DC Power 0244 Load Center GE 121AC77B D24-Bus-05 Switch Control 239 Qualification Cap>Dem Support Overcurrent Phase A 812A-S Enclosure Test gear Systems AC/DC Power D244 Load Center GE 121AC77B D24-Bus-05 Switch Control 239 Qualification Cap> Dem Support Overcurrent Phase B 812A-S Enclosure Test gear Systems AC/DC Power D244 Load Center GE 121AC77B D24-Bus-05 Switch Control 239 Qualification Cap> Dem Support Overcurrent Phase C 812A-5 Enclosure Test gear Systems AC/DC Power ESW Pump ODP548 GE 12JAC66K8 D24-Bus-08 Switch Control 239 Qualification Cap> Dem Overcurrent Phase A A-S Enclosure Test Support gear Systems AC/DC Power ESW Pump ODP548 GE 121AC66K8 024-Bus-08 Switch Control 239 Qualification Cap> Dem Support Overcurrent Phase 8 A-S Enclosure Test gear Systems AC/DC Power ESW Pump ODP548 GE 121AC66K8 D24-8us-08 Switch Control 239 Qualification Cap> Dem Support Overcurrent Phase C A-S Enclosure Test gear Systems AC/DC A117 Breaker 702 Power Bus A Phase GE 121AC53A D13-Bus-02 Switch Control 239 Qualification Cap> Dem Support 802A-S Enclosure Test Overcurrent Relay gear Systems AC/DC All 7 Breaker 702 Power Bus B Phase GE 121AC53A 013-Bus-02 Switch Control 239 Qualification Cap> Dem Support Overcurrent Relay 802A-S gear Enclosure Test Systems AC/DC All 7 Breaker 702 Power Bus C Phase GE 121AC53A D13-Bus-02 Switch Control 239 Qualification Support 802A-S Enclosure Test Cap > Dem Overcurrent Relay gear Systems Page 56of110
No.
Unit ID Type
.J Protectrve 132 1
151-11709A Relay 133 1
151-11709B Protective Relay 134 1
151-11709C Protective Relay 151-Protective 135 1
AG501A Relay 136 151-Protective 1
AG501B Relay 151-Protective 137 1
AG501C Relay 138 151-Protective 1
Relay BG501A 139 151-Protective 1
BG501B Relay 140 151-Protective 1
BG501C Relay 151-Protective 141 1
CG501A Relay Table B-1: Components Identified for High Frequency Confirmation Enclosure Component f System Function Manufacturer ModellNo.
ID Type BuUdlng AC/DC A117 Breaker 709 Power 12JAC53A Switch Control Bus A Phase GE 802A-S D13-Bus-09 Enclosure Support Overcurrent Relay gear Systems AC/DC A117 Breaker 709 Power 121AC53A Switch Control Bus B Phase GE 802A-S D13-Bus-09 Enclosure Support Overcurrent Relay gear Systems AC/DC All 7 Breaker 709 Power 121AC53A Switch Control Bus C Phase GE 802A-S D13-Bus-09 Enclosure Support Overcurrent Relay gear Systems AC/DC Power Phase Overcurrent GE 121AC53A Dll-Bus-07 Switch Control Support Relay Phase A 802A-5 Enclosure gear Systems AC/DC Power Phase Overcurrent GE 12JAC53A Dll-Bus-07 Switch Control Support Relay Phase B 802A-S Enclosure gear Systems AC/DC Power Phase Overcurrent GE 121AC53A Dll-Bus-07 Swrtch Control Support Relay Phase C 802A-S Enclosure gear Systems AC/DC Power Phase Overcurrent GE 12JAC53A D12-Bus-07 Switch Control Support Relay Phase A 802A-S Enclosure gear Systems AC/DC Power Phase Overcurrent GE 121AC53A D12-Bus-07 Switch Control Support Relay Phase B 802A-S Enclosure gear Systems AC/DC Power Phase Overcurrent GE 121AC53A D12-Bus-07 Switch Control Support Relay Phase C 802A-S Enclosure gear Systems AC/DC Power Phase Overcurrent GE 121AC53A D13-Bus-07 Switch Control Support Relay Phase A 802A-S Enclosure gear Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Floor Component Evaluation Elev. (ft)
Basis for Evaluation Caoadtv Result Qualrfication 239 Test Cap> Dem Qualification 239 Test Cap>Dem Qualification 239 Test Cap> Dem 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test Page 57 of 110
l ~lt ll No.
~f=- Type ID 142 1
151-Protective CG501B Relay 151-Protective 143 1
CG501C Relay 144 1
151-Protective DG501A Relay 145 1
151-Protective DG501B Relay 146 1
lSl-Protective DG501C Relay Protective 147 1
151-11502A Relay 148 1
151-11502B Protective Relay Protective 149 1
151-11502C Relay 150 1
151-11509A Protective Relay 151 1
151-11509B Protective Relay 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component r
Enclosure
- . ' I
[ Building I Floor Component Evaluation 1 1iis~~ ~nctio~ =
l ~nufacturer I [ M~~~., r-I~
[
Type_ I Basis for Evaluation Elev. (ft}
Ca pacify Result AC/DC Power Phase Overcurrent GE 121AC53A D13-Bus-07 Switch Control 239 Qualification Cap> Dem Support Relay Phase B 802A-S gear Enclosure Test Systems AC/DC Power Phase Overcurrent GE 121AC53A D13-Bus-07 Switch Control 239 Qualification Support Relay Phase C 802A-S Enclosure Cap> Dem gear Test Systems AC/DC Power Phase Overcurrent GE 121AC53A D14-Bus-07 Switch Control 239 Qualification Cap> Dem Support Relay Phase A 802A-S gear Enclosure Test Systems AC/DC Power Phase Overcurrent GE 121AC53A D14-Bus-07 Switch Control 239 Qualification Cap> Dem Support Relay Phase B 802A-S gear Enclosure Test Systems AC/DC Power Phase Overcurrent GE 121AC53A D14-Bus-07 Switch Control 239 Qualification Cap> Dem Support Relay Phase C 802A-S gear Enclosure Test Systems AC/DC A115 Breaker 502 Power 121ACS3A Switch Control Qualification Bus A Phase GE Dll-Bus-02 239 Cap > Dem Support Overcurrent Relay 802A-S gear Enclosure Test Systems AC/DC A115 Breaker 502 Power Bus B Phase GE 121AC53A Dll-Bus-02 Switch Control 239 Qualification Support 802A-S gear Enclosure Test Cap > Dem Systems Overcurrent Relay AC/DC A115 Breaker 502 Power 121AC53A Switch Control Qualification Support Bus C Phase GE 802A-S Dll-Bus-02 Enclosure 239 Cap> Dem Overcurrent Relay gear Test Systems AC/DC A115 Breaker 509 Power Bus A Phase GE 121AC53A Dll-Bus-09 Switch Control 239 Qualification Support 802A-S gear Enclosure Test Cap> Dem Systems Overcurrent Relay AC/DC A115 Breaker 509 Power Bus B Phase GE 121AC53A Dll-Bus-09 Switch Control 239 Qualification Support 802A-S gear Enclosure Test Cap> Dem Systems Overcurrent Relay Page 58of110
a, No.
![
ID T,ype 152 1
151-11509C Protective Relay 153 1
151-11602A Protective Relay 1
151-11602B Protective 154 Relay 155 1
151-11602C Protective Relay 156 1
151-11609A Protective Relay 157 1
151-11609B Protective Relay Protective 158 1
151-11609C Relay Protective 159 1
151-11802A Relay 160 1
151-11802B Protective Relay Protective 161 1
151-11802C Relay 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component
~
Enclosure
- i B~;din~]
Floor Comp()nent Evaluation
'~temj
[ ~a~ufacturer I Mod.ei~~~o. ]~
ID I T~~.J Basis for Evaluation Function l;lev. (ft)
Capacity Result AC/DC A115 Breaker 509 Power Bus C Phase GE 121AC53A Dll-Bus-09 Switch Control
. 239 Qualification Cap> Dem Support Overcurrent Relay 802A-S gear Enclosure Test Systems AC/DC A116 Breaker 602 Power 121AC53A Switch Control Qualification Support Bus A Phase GE 802A-S D12-Bus-02 Enclosure 239 Test Cap > Dem Overcurrent Relay gear Systems AC/DC A116 Breaker 602 Power Bus B Phase GE 121AC53A D12-Bus-02 Switch Control 239 Qualification Cap> Dem Support 802A-S Enclosure Test Overcurrent Relay gear Systems AC/DC A116 Breaker 602 Power Bus C Phase GE 121AC53A D12-Bus-D2 Switch Control 239 Qualification Cap> Dem Support Overcurrent Relay 802A-S gear Enclosure Test Systems AC/DC A116 Breaker 609 Power Bus A Phase GE 121AC53A D12-Bus-09 Switch Control 239 Qualification Cap> Dem Support Overcurrent Relay 802A-S gear Enclosure Test Systems AC/DC A116 Breaker 609 Power Bus B Phase GE UIAC53A D12-Bus-09 Switch Control 239 Qualification Support B02A-S Enclosure Test Cap> Dem Overcurrent Relay gear Systems AC/DC A116 Breaker 609 Power 121AC53A Switch Control Qualification Bus c Phase GE D12-Bus-09 239 Cap> Dem Support Overcurrent Relay 802A-S gear Enclosure Test Systems AC/DC A118 Breaker 802 Power 121AC53A Switch Control Qualification Support Bus A Phase GE 802A-S D14-Bus-02 Enclosure 239 Test Cap> Dem Overcurrent Relay gear Systems AC/DC AllB Breaker 802 Power Bus B Phase GE 121AC53A D14-Bus-02 Switch Control 239 Qualification Cap> Dem Support 802A-S gear Enclosure Test Systems Overcurrent Relay AC/DC All8 Breaker 802 Power 121AC53A Switch Control Qualification Support Bus C Phase GE 802A-S D14-Bus-02 Enclosure 239 Test Cap> Dem Overcurrent Relay gear Systems Page 59 of 110
I Unit No. I ID T,ype l
162 151-11809A Protective 1
Relay 163 1
151-11809B Protective Relay 164 1
151-11809C Protective Relay 16S 2
151-11702A Protective Relay 166 2
1Sl-11702B Protective Relay 167 2
151-11702C Protective Relay 168 2
151-11709A Protective Relay 169 2
151-11709B Protective Relay 170 2
151-11709C Protective Relay 171 2
151-Protective AG501A Relay Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Building System ' Function Manufacturer Model No.
ID Type AC/DC A118 Breaker 809 Power Bus A Phase GE 121AC53A D14-Bus-09 Switch Control Support 802A-S Enclosure Overcurrent Relay gear Systems AC/DC A118 Breaker 809 Power 121AC53A Switch Control Support Bus B Phase GE 802A-S D14-Bus-09 Enclosure Overcurrent Relay gear Systems AC/DC A118 Breaker 809 Power Bus C Phase GE 121AC53A D14-Bus-09 Switch Control Support 802A-S Enclosure Overcurrent Relay gear Systems AC/DC A117 Breaker 702 Power Bus A Phase GE 121AC53A D23-Bus-02 Switch Control Support Overcurrent Relay 802A gear Enclosure Systems AC/DC A117 Breaker 702 Power Bus B Phase GE 121AC53A D23-Bus-02 Switch Control Support Overcurrent Relay 802A gear Enclosure Systems AC/DC A117 Breaker 702 Power Bus C Phase GE 121AC53A D23-Bus-02 Switch Control Support Overcurrent Relay 802A gear Enclosure Systems AC/DC All 7 Breaker 709 Power Bus A Phase GE 121AC53A D23-Bus-09 Switch Control Support 802A-S Enclosure Overcu rrent Relay gear Systems AC/DC A117 Breaker 709 Power Bus B Phase GE 121AC53A D23-Bus-09 Switch Control Support 802A-S Enclosure Overcurrent Relay gear Systems AC/DC A117 Breaker 709 Power Bus C Phase GE 121AC53A D23-Bus-09 Switch Control Support Overcurrent Relay 802A-S gear Enclosure Systems AC/DC Power Phase Overcurrent GE 121AC53A D21-Bus-07 Switch Control Support Relay Phase A 802A-S gear Enclosure Systems 15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 Floor Component Evaluatio_11 I
Basis for Evaluation Elev. (ft)
Capacity Result 239 Qualification Cap> Dem Test Qualification 239 Test Cap >Dem 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Cap> Dem Test 239 Qualification Test Cap> Dem Page 60of110
No.
Unit I
ID Type 172 151-Protective 2
AG501B Relay 151-Protective 173 2
AG501C Relay 174 2
151-Protective BG501A Relay 175 151-Protective 2
BG501B Relay 176 2
151-Protective BG501C Relay 177 2
151-Protective CG501A Relay 178 2
151-Protective CG501B Relay 179 2
151-Protective CG501C Relay 180 2
151-Protective DG501A Relay 181 2
151-Protective DGS01B Relay Table B-1: Components Identified for High Frequency Confirmation Component I
Enclosure System Function Manufacturer Model No.
ID Type Building AC/DC Power Phase Overcurrent GE 121ACS3A D21-Bus-07 Switch Control Support Relay Phase B 802A-S Enclosure gear Systems AC/DC Power Phase Overcurrent GE 121ACS3A D21-Bus-07 Switch Control Support Relay Phase C 802A-S Enclosure gear Systems AC/DC Power Phase Overcurrent GE 121ACS3A D22-Bus-07 Switch Control Support Relay Phase A 802A-S gear Enclosure Systems AC/DC Power Phase Overcurrent GE 12JACS3A D22-Bus-07 Switch Control Support Relay Phase B 802A-S Enclosure gear Systems AC/DC Power Phase Overcurrent GE 12JACS3A D22-Bus-07 Switch Control Support Relay Phase C 802A-S gear Enclosure Systems AC/DC Power Phase Overcurrent GE 12JACS3A D23-Bus-07 Switch Control Support Relay Phase A 802A-S gear Enclosure Systems AC/DC Power Phase Overcurrent GE 121ACS3A D23-Bus-07 Switch Control Support Relay Phase B 802A-S gear Enclosure Systems AC/DC Power Phase Overcurrent GE 121ACS3A D23-Bus-07 Switch Control Support Relay Phase C 802A-S gear Enclosure Systems AC/DC Power Phase Overcurrent GE 121ACS3A D24-Bus-07 Switch Control Support Relay Phase A 802A-S gear Enclosure Systems AC/DC Power Phase Overcurrent GE 121AC53A D24-Bus-07 Switch Control Support Relay Phase B 802A-S gear Enclosure Systems 1SC4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Floor Compo!ll!nt Evaluation I Elev. (ft) j Basis for Evaluation Capacity Result 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap>Dem Test 239 Qualification Test Cap> Dem 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test Page 61 of 110
1 No.
Unit ID Type 182 2
151-Protective DG501C Relay Protective 183 2
151-11502A Relay 184 2
151-11502B Protective Relay 185 2
151-11502C Protective Relay 186 2
151-11509A Protective Relay Protective 187 2
1Sl-11509B Relay Protective 188 2
151-11509C Relay Protective 189 2
151-11602A Relay Protective 190 2
151-11602B Relay Protective 191 2
151-11602C Relay Table B-1: Components Identified for High Frequency Confirmation Component Enclosure System Function Manufacturer Model No.
ID Type Building AC/DC Power Phase Overcurrent GE 121AC53A D24-Bus-07 Switch Control Support Relay Phase C 802A-S gear Enclosure Systems AC/DC A115 Breaker 502 Power 121AC53A Switch Control Support Bus A Phase GE 802A-S D21-Bus-02 Enclosure Overcurrent Relay gear Systems AC/DC A115 Breaker 502 Power Bus B Phase GE 121AC53A D21-Bus-02 Switch Control Support 802A-S Enclosure Overcurrent Relay gear Systems AC/DC A115 Breaker 502 Power Bus C Phase GE 121AC53A D21-Bus-02 Switch Control Support 802A-S Enclosure Overcurrent Relay gear Systems AC/DC A115 Breaker 509 Power Bus A Phase GE 121AC53A D21-Bus-09 Switch Control Support 802A-S gear Enclosure Systems Overcurrent Relay AC/DC A115 Breaker 509 Power 121AC53A Switch Control Bus B Phase GE D21-Bus-09 Support Overcurrent Relay 802A-S gear Enclosure Systems AC/DC A115 Breaker 509 Power 121AC53A Switch Control Support Bus C Phase GE 802A-S D21-Bus-09 Enclosure Overcurrent Relay gear Systems AC/DC A116 Breaker 602 Power 121AC53A Switch Control Support Bus A Phase GE 803A D22-Bus-02 Enclosure Overcurrent Relay gear Systems AC/DC A116 Breaker 602 Power 121AC53A Switch Control Support Bus B Phase GE 802A-S D22-Bus-02 Enclosure Overcurrent Relay gear Systems AC/DC A116 Breaker 602 Power 121AC53A Switch Control Support Bus C Phase GE 802A-S D22-Bus-02 Enclosure Overcurrent Relay gear Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Component Evaluation Floor I
Basis for I Evaluation Elev. (ft)
Capacltv Result 239 Qualification Test Cap> Dem Qualification 239 Test Cap>Dem 239 Qualification Cap> Dem Test 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem Qualification 239 Cap>Dem Test Qualification 239 Cap> Dem Test Qualification 239 Cap >Dem Test Qualification 239 Cap> Dem Test Qualification 239 Cap> Dem Test Page 62 of 110
I No.
Unit I
ID Type
_j Protective 192 2
151-11609A Relay Protective 193 2
151-11609B Relay Protective 194 2
151-11609C Relay Protective 195 2
151-11802A Relay Protective 196 2
151-11802B Relay Protective 197 2
151-11802C Relay Protective 198 2
151-11809A Relay Protective 199 2
1Sl-11809B Relay 151-11809C Protective 200 2
Relay 151N-Protective 201 1
11502 Relay Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Building System Function Manufacturer Model No.
ID Type AC/DC A116 Breaker 609 Power 121AC53A Switch Control Support Bus A Phase GE 802A-S D22-Bus-09 Enclosure Overcurrent Relay gear Systems AC/DC A116 Breaker 609 Power 121AC53A Switch Control Bus B Phase GE 802A-S D22-Bus-09 Enclosure Support Overcurrent Relay gear Systems AC/DC A116 Breaker 609 Power 121AC53A Switch Control Bus C Phase GE 802A-S D22-Bus-09 Enclosure Support Overcurrent Relay gear Systems AC/DC A118 Breaker 802 Power 121AC53A Switch Control Bus A Phase GE 802A-S D24-Bus-02 Enclosure Support Overcurrent Relay gear Systems AC/DC A118 Breaker 802 Power 121AC53A Switch Control Bus B Phase GE 802A-S D24-Bus-02 Enclosure Support Overcurrent Relay gear Systems AC/DC A118 Breaker 802 Power Bus C Phase GE 121AC53A D24-Bus-02 Switch Control Support 802A-S Enclosure Overcurrent Relay gear Systems AC/DC All8 Breaker 809 Power 121AC53A Switch Control Bus A Phase GE 802A-S D24-Bus-09 Enclosure Support Overcurrent Relay gear Systems AC/DC A118 Breaker 809 Power 121AC53A Switch Control Bus B Phase GE 802A-S D24-Bus-09 Enclosure Support Overcurrent Relay gear Systems AC/DC All8 Breaker 809 Power Bus C Phase GE 121AC53A D24-Bus-09 Switch Control 802A-S Enclosure Support Overcurrent Relay gear Systems AC/DC All5 Breaker 502 Power Neutral Overcurrent GE 121AC51A Dll-Bus-02 Switch Control 801A-S Enclosure Support Relay gear Systems 15C4345-RPT-002,Rev.O Correspondence No.: RS-16-177 11 Floor Component Evaluation Elev. (ft)
Basis for Evaluation
(;apacltv Result Qualification 239 Test Cap> Dem Qualification 239 Test Cap> Dem Qualification 239 Test Cap> Dem Qualification 239 Test Cap> Dem Qualification 239 Test Cap> Dem 239 Qualification Cap> Dem Test Qualification 239 Test Cap>Dem Qualification 239 Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qualification Cap> Dem Test Page 63 of 110
No. [ Unit
- Type 11 ID I
~
lSlN-Protective 202 1
11S09 Relay 203 1
lSlN-11602 Protective Relay 1S1N-Protective 204 1
Relay 11609 1S1N-Protective 20S 1
11702 Relay 1S1N-Protective 206 1
11709 Relay 1S1N-Protective 207 1
11802 Relay 1S1N-Protective 208 1
11809 Relay lSlN-Protective 209 2
11S02 Relay 2
lSlN-Protective 210 11S09 Relay 1S1N-Protective 211 2
11602 Relay 15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Component Evaluation Floor j Building Elev. {ft),
Basis1for Evaluation System I Function Manufacturer Model No.
ID Type
___j Capacity Result AC/DC AllS Breaker S09 Power Neutral Overcurrent GE 121ACS1A Dll-Bus-09 Switch Control 239 Qualification Cap> Dem Support 801A-S Enclosure Test Relay gear Systems AC/DC A116 Breaker 602 Power 121AC51A Switch Control Qualification Neutral Overcurrent GE 801A-S D12-Bus-02 Enclosure 239 Test Cap>Dem Support gear Systems Relay AC/DC A116 Breaker 609 Power Neutral Overcurrent GE 121ACS1A D12-Bus-09 Switch Control 239 Qualification Cap> Dem 801A-S Enclosure Test Support gear Systems Relay AC/DC All 7 Breaker 702 Power Neutral Overcurrent GE 121AC51A D13-Bus-02 Switch Control 239 Qualification Cap> Dem Support 801A-S Enclosure Test Relay gear Systems AC/DC All 7 Breaker 709 Power 121AC51A Switch Control Qualification Support Neutral Overcurrent GE 801A-S D13-Bus-09 Enclosure 239 Test Cap >Dem Relay gear Systems AC/DC A118 Breaker 802 Power Neutral Overcurrent GE 121AC51A D14-Bus-02 Switch Control 239 Qualification Cap> Dem Support 801A-S Enclosure Test Relay gear Systems AC/DC A118 Breaker 809 Power Neutral Overcurrent GE 121AC51A D14-Bus-09 Switch Control 239 Qualification Cap > Dem Support 801A-S Enclosure Test Relay gear Systems AC/DC AllS Breaker S02 Power Neutral Overcurrent GE 121AC51A D21-Bus-02 Switch Control 239 Qualification Cap> Dem Support 801A-S Enclosure Test Relay gear Systems AC/DC AllS Breaker S09 Power Neutral Overcurrent GE 121ACS1A D21-Bus-09 Switch Control 239 Qualification Cap> Dem Support 801A-S Enclosure Test Relay gear Systems AC/DC A116 Breaker 602 Power Neutral Overcurrent 121ACS1A D22-Bus-02 Switch Control 239 Qualification Cap> Dem Support GE 801A-S Enclosure Test Relay gear Systems Page 64 of 110
No.
Unit I
I ID Type 212 2
151N-Protective 11609 Relay 151N-Protective 213 2
11702 Relay 214 2
151N-Protective 11709 Relay 215 2
151N-Protective 11802 Relay 216 2
151N-Protective 11809 Relay 217 186-115A Control 1
Relay 218 1
186-115B Control Relay 219 1
186-llSC Control Relay 220 1
186-116A Control Relay 221 186-116B Control 1
Relay Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Building System Function Manufacturer Model1No.
ID Type AC/DC A116 Breaker 609 Power Neutral Overcurrent GE 121AC51A D22-Bus-09 Switch Control Support Relay 801A-S gear Enclosure Systems AC/DC All 7 Breaker 702 Power Neutral Overcurrent GE 121AC51A D23-Bus-02 Switch Control Support 801A-S Enclosure Relay gear Systems AC/DC All 7 Breaker 709 Power Neutral Overcurrent GE 121AC51A D23-Bus-09 Switch Control Support Relay 801A-S gear Enclosure Systems AC/DC A118 Breaker 802 Power Neutral Overcurrent GE 121AC51A D24-Bus-02 Switch Control Support Relay 801A-S gear Enclosure Systems AC/DC A118 Breaker 809 Power Neutral Overcurrent GE 121AC51A D24-Bus-09 Switch Control Support Relay 801A-S gear Enclosure Systems AC/DC Power A115 Bus Lockout Electroswitch Series 24 Dll-Bus-06 Switch Control Support Relay Enclosure gear Systems AC/DC Power A115 Bus Lockout Electroswitch Series 24 Dll-Bus-09 Switch Control Support Relay gear Enclosure Systems AC/DC Power Al15 Bus Lockout Electroswitch Series 24 Dll-Bus-09 Switch Control Support Relay gear Enclosure Systems AC/DC Power Al16 Bus Lockout Electroswitch Series 24 D12-Bus-06 Switch Control Support Relay gear Enclosure Systems AC/DC Power A116 Bus Lockout Electroswitch Series 24 D12-Bus-09 Switch Control Support Relay Enclosure gear Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Floor Component Evaluation Basis for Evaluation Elev. (ft) capacity __
Result 239 Quahficat1on Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Test Cap> Dem Page 65 of 11 O
j B No.
I ~ ~.~ ~! T~
222 1
186-116C Control Relay 223 1
186-117A Control Relay 224 1
186-117B Control Relay 225 1
186-117C Control Relay 226 1
186-118A Control Relay 227 1
186-118B Control Relay 228 1
186-118C Control Relay 229 1
186-AGSOl Control Relay 230 1
186-BGSOl Control Relay 231 1
186-CGSOl Control Relay 15C4345-RPT-002,Rev.O Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component Enclosure t
uildlng]
Floor Component Evaluation J ~vste-"'.J c
- f1Manufacture~ 'I B~sis for Evaluation Function Model No.
ID Type Elev. (ft)
- caoacJty, Result AC/DC Power All6 Bus Lockout Electroswitch Series 24 D12-Bus-09 Switch Control 239 Qualification Support Relay gear Enclosure Test Cap> Dem Systems AC/DC Power All 7 Bus Lockout Electroswitch Series 24 D13-Bus-06 Switch Control 239 Qualification Support Relay Enclosure Test Cap>Dem gear Systems AC/DC Power All 7 Bus Lockout Electroswitch Series 24 D13-Bus-09 Switch Control 239 Qualification Cap> Dem Support Relay gear Enclosure Test Systems AC/DC Power All 7 Bus Lockout Electroswitch Series 24 D13-Bus-09 Switch Control 239 Qualification Support Relay gear Enclosure Test Cap> Dem Systems AC/DC Power All8 Bus Lockout Electroswitch Series 24 D14-Bus-06 Switch Control 239 Qualification Support Relay gear Enclosure Test Cap> Dem Systems AC/DC Power All8 Bus Lockout Electroswitch Series 24 D14-Bus-09 Switch Control 239 Qualification Support Relay gear Enclosure Test Cap> Dem Systems AC/DC Power A118 Bus Lockout Electroswitch Series 24 D14-Bus-09 Switch Control Qualification Support Relay Enclosure 239 Cap> Dem gear Test Systems AC/DC Power Dll Lockout Relay Electroswitch Series 24 Dll-Bus-07 Switch Control 239 Qualification Support gear Enclosure Test Cap> Dem Systems AC/DC Power D12 Lockout Relay Electroswitch Series 24 D12-Bus-07 Switch Control 239 Qualification Support gear Enclosure Test Cap > Dem Systems AC/DC Power D13 Lockout Relay Electroswitch Series 24 Dl3-Bus-07 Switch Control 239 Qualification Support gear Enclosure Test Cap> Dem Systems Page 66 of 110
No. I <Unit r ID T.'(111!
232 1
186-DGSOl Control Relay 233 2
186-llSA Control Relay 186-llSB Control 234 2
Relay 235 2
186-115C Control Relay 236 2
186-116A Control Relay 237 2
186-116B Control Relay 238 2
186-116C Control Relay 239 2
186-117A Control Relay 240 2
186-117B Control Relay 241 2
186-117C Control Relay Table B-1: Components Identified for High Frequency Confirmation Component Enclosure System Function I ' Manufacturer Model No.
ID Type Building AC/DC Power D14 Lockout Relay Electroswitch Series 24 D14-Bus-07 Switch Control Support gear Enclosure Systems AC/DC Power A115 Bus Lockout Electroswitch Series 24 D21-Bus-06 Switch Control Support Relay Enclosure gear Systems AC/DC Power A115 Bus Lockout Electroswitch Series 24 D21-Bus-09 Switch Control Support Relay Enclosure gear Systems AC/DC Power A115 Bus Lockout Electroswitch Series 24 D21-Bus-09 Switch Control Support Relay gear Enclosure Systems AC/DC Power A116 Bus Lockout Electroswitch Series 24 D22-Bus-06 Switch Control Support Relay gear Enclosure Systems AC/DC Power A116 Bus Lockout Electroswitch Series 24 D22-Bus-09 Switch Control Support Relay gear Enclosure Systems AC/DC Power A116 Bus Lockout Electroswitch Series 24 D22-Bus-09 Switch Control Support Relay gear Enclosure Systems AC/DC Power All 7 Bus Lockout Electroswitch Series 24 D23-Bus-06 Switch Control Support Relay gear Enclosure Systems AC/DC Power A117 Bus Lockout Electroswitch Series 24 D23-Bus-09 Switch Control Support Relay gear Enclosure Systems AC/DC Power All 7 Bus Lockout Electroswitch Series 24 Switch Control Support Relay D23-Bus-09 Enclosure gear Systems 1SC4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Floor
~Component Evaluation Elev. (ft) [
Basis1for Evaluation I
Capadtv Result 239 Qualification Cap> Dem Test 239 Qualification Cap>Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem 239 Qua Jification Test Cap> Dem 239 Qualification Test Cap> Dem Qualification 239 Test Cap> Dem Page 67of110
El No.
[~
JI ID Type 242 2
186-118A Control Relay 186-llBB Control 243 2
Relay 244 2
186-118C Control Relay 245 2
186-AGSOl Control Relay 246 2
186-BGSOl Control Relay 247 2
186-CGSOl Control Relay 248 2
186-DGSOl Control Relay 249 150G-Protective 1
11505 Relay 250 1
150G-Protective 11508 Relay 251 1
150G-Protective 11605 Relay 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component c
Enclosure
'* J
~ Bul~dln8]
Floor Col!lponent Evaluation ff svste;J ~ction K
11 Manufacturer !
ID
~
Basis for Evaluation Model1No.
Elev. {ft)
Cai>acltv Result AC/DC Power A118 Bus Lockout Electroswitch Series 24 D24-Bus-06 Switch Control 239 Qualification Cap> Dem Support Relay gear Enclosure Test Systems AC/DC Power A118 Bus Lockout Electroswitch Series 24 D24-Bus-09 Switch Control 239 Qualification Support Relay Enclosure Test Cap> Dem gear Systems AC/DC Power A118 Bus Lockout Electroswitch Series 24 D24-Bus-09 Switch Control 239 Qualification Cap> Dem Support Relay gear Enclosure Test Systems AC/DC Power D21 Lockout Relay Electroswitch Series 24 D21-Bus-07 Switch Control 239 Qualification Support gear Enclosure Test Cap> Dem Systems AC/DC Power D22 Lockout Relay Electroswitch Series 24 D22-Bus-07 Switch Control 239 Qualification Support gear Enclosure Test Cap> Dem Systems AC/DC Power D23 Lockout Relay Electroswitch Series 24 D23-Bus-07 Switch Control 239 Qualification Support gear Enclosure Test Cap>Dem Systems AC/DC Power D24 Lockout Relay Electroswitch Series 24 D24-Bus-07 Switch Control 239 Qualification Support gear Enclosure Test Cap> Dem Systems AC/DC Power Dl14 Load Center 12HFC11B Dll-Bus-05 Switch Control 239 Qualification Support Ground Fault GE lA-S Enclosure Test Cap> Dem gear Systems AC/DC Power ESW Pump OAP548 GE 12HFC11B Dll-Bus-08 Switch Control 239 Qualification Support Ground Fault lA-S gear Enclosure Test Cap> Dem Systems AC/DC Power D124 Load Center 12HFC11B Switch Control Qualification Support Ground Fault GE lA-S D12-Bus-05 Enclosure 239 Cap> Dem gear Test Systems Page 68 of 110
EJ No. ; Unit : l 1~ L:ry~ ~I 150G-Protective 252 1
11608 Relay 150G-Protective 253 1
Relay 11705 150G-Protective 254 1
Relay 11805 151N-Protective 255 1
AG501 Relay 151N-Protective 256 1
Relay BGSOl lSlN-Protective 257 1
CGSOl Relay 151N-Protective 258 1
DG501 Relay Protective 259 1
187-llSA Relay 187-1158 Protective 260 1
Relay Protective 261 1
187-llSC Relay 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component Enclosure r
~ullding]
Floor Component Evaluation
-I Function~* -:J l Man~~cturer j Basis for, Evaluation System Model No.
ID Type Elev. {ft)
Capacltv Result AC/DC Power ESW Pump OBP548 GE 12HFC11B D12-Bus-08 Switch Control 239 Qualification Cap> Dem Support Ground Fault lA-S gear Enclosure Test Systems AC/DC Power Dl34 Load Center GE 12HFC11B D13-Bus-05 Switch Control 239 Qualification Cap> Dem Ground Fault lA Enclosure Test Support gear Systems AC/DC Power D144 Load Center GE 12HFC11B D14-Bus-05 Switch Control 239 Qualification Cap> Dem Ground Fault lA-S Enclosure Test Support gear Systems AC/DC Power Dll Neutral Westinghous 264C899A Dll-Bus-07 Switch Control 239 Qualification Cap> Dem Support Overcurrent Relay 01 Enclosure Test e
gear Systems AC/DC Power D12 Neutral westinghous 264C899A D12-Bus-07 Switch Control 239 Qualification Cap> Dem Overcurrent Relay 01 Enclosure Test Support e
gear Systems AC/DC Power D13 Neutral Westinghous 264C899A D13-Bus-07 Switch Control 239 Qualification Cap> Dem Support Overcurrent Relay 01 Enclosure Test e
gear Systems AC/f?C Power D14 Neutral Westinghous 264C899A D14-Bus-07 Switch Control 239 Qualification Cap>Dem Support Overcurrent Relay 01 Enclosure Test e
gear Systems AC/DC Power AllS Bus A Phase GE 12PVD21B Dll-Bus-06 Switch Control 239 Qualification Cap> Dem Support Differentia I Relay lA-S Enclosure Test gear Systems AC/DC Power Al15 Bus B Phase GE 12PVD21B Dll-Bus-06 Switch Control 239 Qualification Cap> Dem Differential Relay Enclosure Test Support lA-S gear Systems AC/DC Power AllS Bus C Phase GE 12PVD21B Switch Control 239 Qualification Cap> Dem Differential Relay lA-S Dll-Bus-06 Enclosure Test Support gear Systems Page 69 of 110
,No. j t Un~ I [
110 _J[
Type J 262 1
187-116A Protective Relay 263 1
187-116B Protective Relay 264 1
187-116C Protective Relay 265 1
187-117A Protective Relay 266 1
187-117B Protective Relay 267 187-117C Protective 1
Relay 268 1
187-118A Protective Relay 269 187-llSB Protective 1
Relay 270 1
187-llSC Protective Relay 271 2
150G-Protective 11505 Relay 15(4345-RPT-002, Rev. a Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component I
- EnclOsure ----=i Bulldl~
Floor f omponent Evaluation I
I System] ~ction-J ;
Manufacturer Model No.
ID
[~J Elev. (ft) 1 Basis for Evaluation Caoacltv Result AC/DC Power A116 Bus A Phase GE 12PVD21B D12-Bus-06 Switch Control 239 Qualification Cap> Dem Support Differential Relay lA-S gear Enclosure Test Systems AC/DC Power A116 Bus B Phase GE 12PVD21B D12-Bus-06 Switch Control 239 Qualification Cap> Dem Support Differential Relay lA-S Enclosure Test gear Systems AC/DC Power A116 Bus C Phase GE 12PVD21B D12-Bus-06 Switch Control 239 Qualification Cap> Dem Support Differential Relay lA-S gear Enclosure Test Systems AC/DC Power All 7 Bus A Phase GE 12PVD21B Dl3-Bus-06 Switch Control 239 Qualification Cap> Dem Support Differential Relay lA-S gear Enclosure Test Systems AC/DC Power All 7 Bus B Phase GE 12PVD21B D13-Bus-06 Switch Control 239 Qualification Support Differential Relay lA-S gear Enclosure Test Cap> Dem Systems AC/DC Power All 7 Bus C Phase GE 12PVD21B Dl3-Bus-06 Switch Control 239 Qualification Support Differential Relay lA-S Enclosure Test Cap > Dem gear Systems AC/DC Power Al18 Bus A Phase GE 12PVD21B D14-Bus-06 Switch Control 239 Qualification Cap>Dem Support Differential Relay lA-S gear Enclosure Test Systems AC/DC Power A118 Bus B Phase GE 12PVD21B D14-Bus-06 Switch Control Qualification Support Differential Relay lA-S Enclosure 239 Test Cap> Dem gear Systems AC/DC Power A118 Bus C Phase GE 12PVD21B D14-Bus-06 Switch Control 239 Qualification Support Differential Relay lA-5 gear Enclosure Test Cap > Dem Systems AC/DC Power D214 Load Center GE 12HFC11B D21-Bus-OS Switch Control 239 Qualification Support Ground Fault lA-S gear Enclosure Test Cap> Dem Systems Page 70of110
Eli No.
]~-- ;vpeJ ID 272 2
150G-Protective 11605 Relay 150G-Protective 273 2
11705 Relay 274 2
150G-Protective 11708 Relay 275 2
150G-Protective 11805 Relay 276 2
150G-Protective 11808 Relay 277 2
151N-Protective AG501 Relay 278 2
151N-Protective BG501 Relay 279 2
151N-Protective CGSOl Relay 280 2
151N-Protective DGS01 Relay 281 2
187-llSA Protective Relay Table B-1: Components Identified for High Frequency Confirmation Component
~ Enclosyre I
Sys~~] l!unctlo: ~
"] [Manufa~~er ] Model No.
ID M
Building AC/DC Power D224 Load Center GE 12HFC11B D22-Bus-05 Switch Control Support Ground Fault lA-S gear Enclosure Systems AC/DC Power D234 Load Center GE 12HFC11B D23-Bus-DS Switch Control Support Ground Fault lA-S Enclosure gear Systems AC/DC Power ESW Pump OCPS48 GE 12HFC11B D23-Bus-08 Switch Control Support Ground Fault lA-S gear Enclosure Systems AC/DC Power D244 Load Center GE 12HFC11B D24-Bus-DS Switch Control Support Ground Fault 1A-S gear Enclosure Systems AC/DC Power ESW Pump DDPS48 GE 12HFC11B D24-Bus-08 Switch Control Support Ground Fault 1A-S gear Enclosure Systems AC/DC Power D21 Neutral Westinghous 264C899A D21-Bus-07 Switch Control Support Overcurrent Relay e
01 gear Enclosure Systems AC/DC Power D22 Neutral Westinghous 264C899A D22-Bus-07 Switch Control Support Overcurrent Relay e
01 gear Enclosure Systems AC/DC Power D23 Neutral westinghous 264C899A Switch Control Support Overcurrent Relay 01 D23-Bus-07 Enclosure e
gear Systems AC/DC Power D24 Neutral Westinghous 264C899A D24-Bus-07 Switch Control Support Overcurrent Relay e
01 gear Enclosure Systems AC/DC Power AUS Bus A Phase GE 12PVD21B D21-Bus-06 Switch Control Support Differential Relay lA-S gear Enclosure Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Component Evalu;itlon Floor Elev. (ft)
Basis for Evaluation Capacity Result 239 Qualification Cap> Dem Test 239 Qualification Cap > Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Test Cap> Dem 239 Qualification Cap> Dem Test 239 Qualification Test Cap>Dem Qualification 239 Cap> Dem Test 239 Qualification Test Cap> Dem 239 Qualification Test Cap> Dem Page 71 of 110
I I
No.
Unit II ID Type
~
282 2
187-llSB Protective Relay 283 2
187-USC Protective Relay 187-U6A Protective 284 2
Relay 2
187-116B Protective 285 Relay 2
187-116C Protective 286 Relay 2
187-117A Protective 287 Relay 2
187-117B Protective 288 Relay 289 2
187-117C Protective Relay 290 2
187-118A Protective Relay 2
187-118B Protective 291 Relay Table B-1: Components Identified for High Frequency Confirmation Component Enclosure System Function Manufacturer Model No.
ID Type Building AC/DC Power AUS Bus B Phase GE 12PVD21B D21-Bus-06 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power AUS Bus C Phase GE 12PVD21B D21-Bus-06 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power AU6 Bus A Phase GE 12PVD21B D22-Bus-06 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power A116 Bus B Phase GE 12PVD21B D22-Bus-06 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power Al16 Bus C Phase GE 12PVD21B D22-Bus-06 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power All 7 Bus A Phase GE 12PVD21B D23-Bus-06 Switch Control Support Differential Relay lA-S Enclosure gear Systems AC/DC Power A117 Bus B Phase GE 12PVD21B D23-Bus-06 Switch Control Support Differential Relay 1A-S Enclosure gear Systems AC/DC Power AU 7 Bus C Phase GE 12PVD21B D23-Bus-06 Switch Control Support Differential Relay 1A-S gear Enclosure Systems AC/DC Power A118 Bus A Phase GE 12PVD21B D24-Bus-06 Switch Control Support Differential Relay 1A-S gear Enclosure Systems AC/DC Power A118 Bus B Phase GE 12PVD21B D24-Bus-06 Switch Control Support Differential Relay 1A-S Enclosure gear Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 I Floor Component Evaluation Elev. (ft)
!Iasis for Evaluation Capacltv Result 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test Page 72 of 110
No. :'8 1
,(~~'] [_ f ype 292 2
187-118C Protective Relay Medium Dll-Bus-07 Voltage 293 1
(152-11507)
Circuit Breaker Medium 294 1
Dll-Bus-05 Voltage
{152-11505)
Circuit Breaker Medium 295 1
D11-Bus-08 Voltage
{152-11508)
Circuit Breaker Medium 296 1
D12-Bus-07 Voltage
{152-11607)
Circuit Breaker Medium 297 1
D12-Bus-05 Voltage (152-11605)
Circuit Breaker Medium D12-Bus-08 Voltage 298 1
(152-11608)
Circuit Breaker Medium 299 1
D13-Bus-07 Voltage (152-11707)
Circuit Breaker 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table 8-1: Components Identified for High Frequency Confirmation Component I Enclosure I Building J Floor Component Evaluation
] rs;~
[ ~unction _=1 [ ~anufa~~rer 1 I M~eiNo. 1 ID
~
Basis,for Evaluation Elev. (ft)
Capacitv Result AC/DC Power A118 Bus C Phase GE 12PVD21B D24-Bus-06 Switch Control 239 Qualification Cap> Dem Support Differential Relay l A-S gear Enclosure Test Systems AC/DC Power Dll Diesel Generator ABB/ITE 5HK 350 D11-Bus-07 Switch Control 239 Qualification Cap> Dem Support Circuit Breaker gear Enclosure Test Systems AC/DC Power D114 LC Transformer ABB/ITE 5HK 350 D11-Bus-05 Switch Control 239 Qualification Cap> Dem Support Circuit Breaker gear Enclosure Test Systems AC/DC QA Essential Service Power Water Pump Circuit ABB/ITE 5HK 350 Dll-Bus-08 Switch Control 239 Qualification Cap> Dem Support Breaker gear Enclosure Test Systems AC/DC Power D12 Diesel Generator ABB/ITE 5HK 350 D12-Bus-07 Switch Control 239 Qualification Cap > Dem Support Circuit Breaker gear Enclosure Test Systems AC/DC Power D124 LC Transformer ABB/ITE 5HK 350 012-Bus-05 Switch Control Qualification Support Circuit Breaker Enclosure 239 Cap> Dem gear Test Systems AC/DC OB Essential Service Power Switch Control Qualification Support Water Pump Circuit ABB/ITE 5HK 350 D12-Bus-08 Enclosure 239 Cap> Dem Breaker gear Test Systems AC/DC Power Dl3 Diesel Generator ABB/ITE 5HK 350 013-Bus-07 Switch Control Qualification Support Circuit Breaker Enclosure 239 Cap > Dem gear Test Systems Page 73 of 110
No.
Unit ID Type i
Medium DB-Bus-OS Voltage 300 1
(152-11705)
Circuit Breaker Medium D14-Bus-07 Voltage 301 1
(152-11807)
Circuit Breaker Medium D14-Bus-05 Voltage 302 1
(152-11805)
Circuit Breaker Medium D21-Bus-07 Voltage 303 2
(152-11507)
Circuit Breaker Medium D21-Bus-OS Voltage 304 2
(152-11505)
Circuit Breaker Medium D22-Bus-07 Voltage 305 2
(152-11607)
Circuit Breaker Medium 2
D22-Bus-OS Voltage 306 (152-11605)
Circuit Breaker Medium 2
D23-Bus-07 Voltage 307
{152-11707)
Circuit Breaker Table B-1: Components Identified for High Frequency Confirmation Component Enclosure System Function
'Manufacturer Model1No.
ID Type Building AC/DC Power OB4 LC Transformer ABB/ITE 5HK 350 DB-Bus-OS Switch Control Support Circuit Breaker gear Enclosure Systems AC/DC Power D14 Diesel Generator ABB/ITE SHK 350 D14-Bus-07 Switch Control Circuit Breaker Enclosure Support gear Systems AC/DC Power D144 LC Transformer ABB/ITE SHK 350 D14-Bus-OS Switch Control Support Circuit Breaker gear Enclosure Systems AC/DC Power D21 Diesel Generator ABB/ITE SHK 350 D21 Bus-07 Switch Control Circuit Breaker Enclosure Support gear Systems AC/DC Power D214 LC Transformer ABB/ITE SHK 350 D21-Bus-OS Switch Control Support Circuit Breaker Enclosure gear Systems AC/DC Power D22 Diesel Generator ABB/ITE SHK 350 D22-Bus-07 Switch Control Circuit Breaker Enclosure Support gear Systems AC/DC Power D224 LC Transformer ABB/ITE SHK 350 D22-Bus-OS Switch Control Support Circuit Breaker Enclosure gear Systems AC/DC Power D23 Diesel Generator ABB/ITE SHK 350 D23-Bus-07 Switch Control Support Circuit Breaker gear Enclosure Systems 15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 Floor Component Evaluation Elev. (ft)
Basis for Evaluation caoacltv Result 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test Page 74of110
I
'~
Unit* j" I
No. 1 ID il'ype
~
~
Medium D23-Bus-05 Voltage 308 2
(152-11705)
Circuit Breaker Medium D23-Bus-08 Voltage 309 2
(152-11708)
Circuit Breaker Medium D24-Bus-07 Voltage 310 2
Circuit Breaker Medium D24-Bus-05 Voltage 311 2
(152-11805)
Circuit Breaker Medium 2
D24-Bus-08 Voltage 312 (152-11808)
Circuit Breaker T2A (1ETB-Control 313 1
AG501)
Relays T2B (1ETB-Control 314 1
AG501)
Relays 315 1
T2A (1ETB-Control BG501)
Relays T2B (lETB-Control 316 1
BG501)
Relays Table B-1: Components Identified for High Frequency Confirmation
~mponent Enclosure I
Building
~ Function System Manufacturer Model No.
ID Type AC/DC Power D234 LC Transformer ABB/ITE 5HK 350 D23-Bus-05 Switch Control Support Circuit Breaker gear Enclosure Systems AC/DC OC Essential Service Power Switch Control Water Pump Circuit ABB/ITE 5HK 350 D23-Bus-08 Support Breaker gear Enclosure Systems AC/DC Power D24 Diesel Generator ABB/ITE 5HK 350 D24-Bus-07 Switch Control Support Circuit Breaker Enclosure gear Systems AC/DC Power D244 LC Transformer ABB/ITE 5HK 350 D24-Bus-05 Switch Control Support Circuit Breaker Enclosure gear Systems AC/DC OD Essential Service Power Water Pump Circuit ABB/ITE 5HK 350 D24-Bus-08 Switch Control Support Enclosure Breaker gear Systems AC/DC Power Overcrank Relay Tyco ETR14D3B 1ETB-Control Diesel Support 004 AG501 Cab.
Generator Systems AC/DC Power Overcrank Relay Tyco ETR14D3B 1ETB-Control Diesel Support 004 AG501 Cab.
Generator Systems AC/DC Power Overcrank Relay Tyco ETR14D3B 1ETB-Control Diesel Support 004 BG501 Cab.
Generator Systems AC/DC Power Overcrank Relay Tyco ETR14D3B lETB-Control Diesel Support 004 BG501 Cab.
Generator Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Component Evaluation Floor I
' Elev. (ft) j Basis for Evaluation Capacity Result L
239 Qualification Cap> Dem Test Qualification 239 Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 239 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test Page 75 of 110
No. I
~
~I Unit I ID i:vpe T2A (lETB-Control 317 1
CGSOl)
Relays T2B (lETB-Control 318 1
CGSOl)
Relays T2A (lETB-Control 319 1
DGSOl)
Relays 320 1
T2B (lETB-Control DGSOl)
Relays 2
T2A (2ETB-Control 321 AGSOl)
Relays 2
T2B (2ETB-Control 322 AGSOl)
Relays 323 2
T2A (2ETB-Control BGSOl)
Relays 2
T2B (2ETB-Control 324 BGSOl)
Relays 325 2
T2A (2ETB-Control CGSOl)
Relays T2B (2ETB-Control 326 2
CGSOl)
Relays Table B-1: Components Identified for High Frequency Confirmation Component Enclosure System I I Function Manufacturer Model No.
ID Type Building AC/DC Power Overcrank Relay Tyco ETR14D3B lETB-Control Diesel Support 004 CGSOl Cab.
Generator Systems AC/DC Power Overcrank Relay Tyco ETR14D3B lETB-Control Diesel Support 004 CGSOl Cab.
Generator Systems AC/DC Power Overcrank Relay Amerace ETR14D3B lETB-Control Diesel Support 002 DGSOl Cab.
Generator Systems AC/DC Power Overcrank Relay Amerace ETR14D3B lETB-Control Diesel Support 002 DGSOl Cab.
Generator Systems AC/DC Power Overcrank Relay Tyco ETR14D3B 2ETB-Control Diesel Support 004 AGSOl Cab.
Generator Systems AC/DC Power Overcrank Relay Tyco ETR14D3B 2ETB Control Diesel Support 004 AGSOl Cab.
Generator Systems AC/DC Power Overcrank Relay Tyco ETR14D3B 2ETB-Control Diesel Support 004 BGSOl Cab.
Generator Systems AC/DC Power Overcrank Relay Tyco ETR14D3B 2ETB-Control Diesel Support 004 BGSOl Cab.
Generator Systems AC/DC Power Overcrank Relay Tyco ETR14D3B 2ETB-Control Diesel Support 004 CGSOl Cab.
Generator Systems AC/DC Power Overcrank Relay Tyco ETR14D3B 2ETB-Control Diesel Support 004 CGSOl Cab.
Generator Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Floor I
Component Evaluation Elev. (ft) I Basis for Evaluation Capacltv Result 217 Qualification Cap > Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap>Dem Test 217 Qualification Test Cap> Dem 217 Qualification Test Cap> Dem 217 Qualification Cap > Dem Test Page 76 of 110
r No. I' IUnlt j ID Type
~
T2A (2ETB-Control 327 2
DG501)
Relays T2B (2ETB-Control 328 2
DG501)
Relays T3A (1ETB-Control 329 1
AGSOl)
Relays 330 T3A (1ETB-Control 1
BGSOl)
Relays 331 T3A (lETB-Control 1
CGSOl)
Relays T3A (lETB-Control 332 1
DGSOl)
Relays 333 2
T3A (2ETB-Control AG501)
Relays 334 2
T3A (2ETB-Control BG501)
Relays 335 2
T3A (2ETB-Control CGSOl)
Relays 336 2
T3A (2ETB-Control DGSOl)
Relays Table B-1: Components Identified for High Frequency Confirmation Component Enclosure System
- l Function 1 Manufacturer Model No.
ID Type BulldJng AC/DC Power Overcrank Relay Amerace ETR14D3B 2ETB-Control Diesel Support 002 DGS01 Cab.
Generator Systems AC/DC Power Overcrank Relay Amerace ETR14D3B 2ETB-Control Diesel Support 002 DG501 Cab.
Generator Systems AC/DC Power High Speed Relay Tyco ETR14D3B lETB-Control Diesel Support 004 AGSOl Cab.
Generator Systems AC/DC Power High Speed Relay Tyco ETR14D3B lETB-Control Diesel Support 004 BGSOl Cab.
Generator Systems AC/DC Power High Speed Relay Tyco ETR14D3B 1ETB-Control Diesel Support 004 CGSOl Cab.
Generator Systems AC/DC Power High Speed Relay Amerace ETR14D3B lETB-Control Diesel Support 002 DGSOl Cab.
Generator Systems AC/DC Power High Speed Relay Tyco ETR14D3B 2ETB-Control Diesel Support 004 AGSOl Cab.
Generator Systems AC/DC Power High Speed Relay Tyco ETR14D3B 2ETB-Control Diesel Support 004 BGSOl Cab.
Generator Systems AC/DC Power High Speed Relay Tyco ETR14D3B 2ETB-Control Diesel Support 004 CGSOl Cab.
Generator Systems AC/DC Power High Speed Relay Amerace ETR14D3B 2ETB-Control Diesel Support 002 DGSOl Cab.
Generator Systems 1SC4345-RPT-002,Rev.O Correspondence No.: RS-16-177 Floor.-
Component Evaluation Elev. {ft)
Basls*for Evaluation capacity Result 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Test Cap> Dem 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap >Dem Test Page 77of110
J I
~
No.
Unit I
ID Type 337 1
Dll-SE Control Relays 338 1
D12-SE Control Relays 339 D13-SE Control 1
Relays 340 1
D14-SE Control Relays Control 341 2
D21-SE Relays 342 D22-SE Control 2
Relays D23-SE Control 343 2
Relays D24-SE Control 344 2
Relays 345 Dll-CPl Control 1
Relays 346 1
Dll-CP2 Control Relays 15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Component Evaluation Floor I Building I Basls*for Evaluation System Function Manufacturer Model No.
ID Type Elev. (ft)
- Capacity Result AC/DC Power Emergency Stop Amerace 7024PE lETB-Control Diesel 217 GERS Cap> Dem Support Relay AGSOl Cab.
Generator Systems AC/DC Power Emergency Stop 7024PE lETB-Control Diesel 217 GERS Cap>Dem Support Relay Amerace BGSOl Cab.
Generator Systems AC/DC Power Emergency Stop Amerace 7024PE lETB-Control Diesel 217 GERS Cap> Dem Support Relay CGSOl Cab.
Generator Systems AC/DC Power Emergency Stop Amerace 7024PE lETB-Control Diesel 217 GERS Cap> Dem Support Relay DGSOl Cab.
Generator Systems AC/DC Power Emergency Stop Amerace 7024PE 2ETB-Control Diesel 217 GERS Cap> Dem Support Relay AGSOl Cab.
Generator Systems AC/DC Power Emergency Stop Amerace 7024PE 2ETB-Control Diesel 217 GERS Cap> Dem Support Relay BGSOl Cab.
Generator Systems AC/DC Power Emergency Stop Amerace 7024PE 2ETB-Control Diesel 217 GERS Cap> Dem Support Relay CGSOl Cab.
Generator Systems AC/DC Power Emergency Stop Amerace 7024PE 2ETB-Control Diesel 217 GERS Cap> Dem Support Relay DGSOl Cab.
Generator Systems AC/DC Power Jacket Cooling ITE Jl3P3012 lETB-Control Diesel 217 GERS Cap> Dem Support Pressure Low Relay AGSOl Cab.
Generator Systems AC/DC Power Jacket Cooling ITE J13P3012 lETB-Control Diesel 217 GERS Cap> Dem Support Pressure Low Relay AGSOl Cab.
Generator Systems Page 78of110
EJ[
No *.
J[
ID Type 347 1
D11-CP3 Control Relays 348 1
Dll-CTl Control Relays 349 1
Dll-CT2 Control Relays 350 1
D11-CT3 Control Relays 351 1
Dll-OPl Control Relays 352 1
Dll-OP2 Control Relays 353 1
Dll-OP3 Control Relays 354 1
Dll-OTl Control Relays 355 1
Dl1-0T2 Control Relays 356 1
Dl1-0T3 Control Relays 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component Enclosure
- I Buil~~ni]
Component Evaluation Floo;J
]'i System
- ~nction
--=i I llll~~ufacturer
~
Elev.~)
Basis for Evaluation Model No.
ID Capacity Result AC/DC Power Jacket Cooling ITE J13P3012 lETB-Control Diesel 217 Support Pressure Low Relay AGSOl Cab.
Generator GERS Cap> Dem Systems AC/DC Power Jacket Coolant ITE J13P3012 lETB-Control Diesel 217 Support Temperature Relay AGSOl Cab.
Generator GERS Cap> Dem Systems AC/DC Power Jacket Coolant ITE J13P3012 lETB-Control Diesel 217 GERS Support Temperature Relay AG501 Cab.
Generator Cap> Dem Systems AC/DC Power Jacket Coolant ITE J13P3012 lETB-Control Diesel 217 GERS Support Temperature Relay AG501 Cab.
Generator Cap> Dem Systems AC/DC Power Lube Oil Pressure ITE J13P3012 lETB-Control Diesel Support Low Relay AG501 Cab.
Generator 217 GERS Cap> Dem Systems AC/DC Power Lube Oil Pressure ITE Jl3P3012 lETB-Control Diesel 217 Support Low Relay AG501 Cab.
Generator GERS Cap> Dem Systems AC/DC Power Lube Oil Pressure ITE J13P3012 lETB-Control Diesel 217 Support Low Relay AG501 Cab.
Generator GERS Cap>Dem Systems AC/DC Power Lube Oil High ITE J13P3012 lETB-Control Diesel 217 Support Temperature Relay AG501 Cab.
Generator GERS Cap> Dem Systems AC/DC Power Lube Oil High ITE J13P3012 lETB-Control Diesel Support Temperature Relay AGSOl Cab.
Generator 217 GERS Cap> Dem Systems AC/DC Power Lube Oil High ITE J13P3012 lETB-Control Diesel 217 GERS Support Temperature Relay AGSOl Cab.
Generator Cap> Dem Systems Page 79 of 110
No. 'i EJ 1* ~~.J [ ~
357 1
Dll-SDR Control Relays 358 1
Dll-SFR Control Relays 359 1
D12-CP1 Control Relays 360 1
D12-CP2 Control Relays 361 1
D12-CP3 Control Relays 362 1
D12-CT1 Control Relays 363 1
D12-CT2 Control Relays 364 1
D12-CT3 Control Relays 365 1
D12-0P1 Control Relays 366 1
D12-0P2 Control Relays 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Compone!lt rw. '_
Enclosure ~.. I Building j i Floor J Component Evaluation J[~tem] ~ction
,_]
rM~ufact~rer I I
~od;!No.]
r T~]
Basis for
~ Evaluation ID Elev. (ft) caoacltv Result AC/DC Power Shutdown Relay ITE J13P3012 lETB-Control Diesel 217 Support AG501 Cab.
Generator GERS Cap> Dem Systems AC/DC Power Start Failure Relay ITE J13P3012 lETB-Control Diesel 217 GERS Cap>Dem Support AGSOl Cab.
Generator Systems AC/DC Power Jacket Cooling ITE J13P3012 lETB-Control Diesel 217 Support Pressure Low Relay BG501 Cab.
Generator GERS Cap> Dem Systems AC/DC Power Jacket Cooling ITE J13P3012 lETB-Control Diesel 217 Support Pressure Low Relay BG501 Cab.
Generator GERS Cap> Dem Systems AC/DC Power Jacket Cooling ITE J13P3012 lETB-Control Diesel 217 Support Pressure Low Relay BG501 Cab.
Generator GERS Cap> Dem Systems AC/DC Power Jacket Coolant lETB-Control Diesel Support Temperature Relay ITE J13P3012 BGSOl Cab.
Generator 217 GERS Cap> Dem Systems AC/DC Power Jacket Coolant ITE Jl3P3012 lETB-Control Diesel Support Temperature Relay BG501 Cab.
Generator 217 GERS Cap> Dem Systems AC/DC Power Jacket Coolant lETB-Control Diesel Support Temperature Relay ITE J13P3012 BG501 Cab.
Generator 217 GERS Cap> Dem Systems AC/DC Power Lube Oil Pressure lETB-Control Diesel Support Low Relay ITE J13P3012 BG501 Cab.
Generator 217 GERS Cap> Dem Systems AC/DC Power Lube Oil Pressure lETB-Control Diesel Support Low Relay ITE J13P3012 BG501 Cab.
217 GERS Cap> Dem Generator Systems Page 80of110
B[
~
No.
- *~]
Type D12-0P3 Control 367 1
Relays Control 368 1
D12-0Tl Relays 369 1
D12-0T2 Control Relays 370 1
D12-0T3 Control Relays 371 1
D12-SDR Control Relays 372 1
D12-SFR Control Relays 373 1
D13-CP1 Control Relays 374 1
D13-CP2 Control Relays 375 1
D13-CP3 Control Relays 376 1
D13-CT1 Control Relays Table B-1: Components Identified for High Frequency Confirmation Component Enclosure
~~
~ction I
[ Manufacturer l
[ M:ciel No. j 1 ID 1-1 Building AC/DC Power Lube Oil Pressure ITE J13P3012 lETB-Control Diesel Support Low Relay BGSOl Cab.
Generator Systems AC/DC Power Lube Oil High ITE J13P3012 lETB-Control Diesel Support Temperature Relay BGSOl Cab.
Generator Systems AC/DC Power Lube Oil High ITE J13P3012 lETB-Control Diesel Support Temperature Relay BGSOl Cab.
Generator Systems AC/DC Power Lube Oil High ITE J13P3012 lETB-Control Diesel Support Temperature Relay BGSOl Cab.
Generator Systems AC/DC Power Shutdown Relay ITE J13P3012 lETB-Control Diesel Support BGSOl Cab.
Generator Systems AC/DC Power Start Failure Relay ITE J13P3012 lETB-Control Diesel Support BGSOl Cab.
Generator Systems AC/DC Power Jacket Cooling ITE J13P3012 lETB-Control Diesel Support Pressure Low Relay CGSOl Cab.
Generator Systems AC/DC Power Jacket Cooling ITE J13P3012 lETB-Control Diesel Support Pressure Low Relay CGSOl Cab.
Generator Systems AC/DC Power Jacket Cooling ITE J13P3012 lETB-Control Diesel Support Pressure Low Relay CGSOl Cab.
Generator Systems AC/DC Power Jacket Coolant ITE J13P3012 lETB-Control Diesel Support Temperature Relay CGSOl Cab.
Generator Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177
~ Floo~ '
Component Evaluation Elev. (ft)
Basis for Evaluation CapacltV Result 217 GERS Cap > Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap > Dem 217 GERS Cap> Dem Page 81 of 110
No. I 81
,ID II Ty~ ]
377 D13-CT2 Control 1
Relays 378 1
D13-CT3 Control Relays 379 D13-0P1 Control 1
Relays 380 1
D13-0P2 Control Relays 381 1
D13-0P3 Control Relays 382 1
Dl3-0T1 Control Relays 383 1
Dl3-0T2 Control Relays 384 1
Dl3-0T3 Control Relays 385 1
Dl3-SDR Control Relays 386 1
013-SFR Control Relays 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component
~
Floor Component Evaluation
[Sv~i;m ~ ~ction -* J r Manufacturer 1 ~No. !*
~
Building 1Elev. (ft)
Basis for Evaluation ID Capacity Result AC/DC Power Jacket Coolant ITE J13P3012 lETB-Control Diesel 217 GERS Support Temperature Relay CGSOl Cab.
Generator Cap > Dern Systems AC/DC Power Jacket Coolant ITE J13P3012 lETB-Control Diesel 217 GERS Support Temperature Relay CGSOl Cab.
Generator Cap> Dern Systems AC/DC Power Lube Oil Pressure ITE J13P3012 lETB-Control Diesel 217 GERS Support Low Relay CGSOl Cab.
Generator Cap> Dern Systems AC/DC Power Lube Oil Pressure ITE J13P3012 lETB-Control Diesel 217 GERS Support Low Relay CGSOl Cab.
Generator Cap > Dern Systems AC/DC Power Lube Oil Pressure ITE J13P3012 lETB-Control Diesel 217 GERS Support Low Relay CGSDl Cab.
Generator Cap> Dem Systems AC/DC Power Lube Oil High ITE J13P3012 lETB-Control Diesel 217 GERS Support Temperature Relay CGSOl Cab.
Generator Cap > Dern Systems AC/DC Power Lube Oil High ITE J13P3012 lETB-Control Diesel Support Temperature Relay CGSOl Cab.
Generator 217 GERS Cap > Dem Systems AC/DC Power Lube Oil High ITE J13P3012 lETB-Control Diesel 217 Support Temperature Relay CGSOl Cab.
Generator GERS Cap > Dern Systems AC/DC Power Shutdown Relay ITE J13P3012 lETB-Control Diesel 217 Support CGSOl Cab.
Generator GERS Cap> Dem Systems AC/DC Power Start Failure Relay ITE J13P3012 lETB-Control Diesel Support CGSOl Cab.
Generator 217 GERS Cap> Dem Systems Page 82of110
No. EJ 387 1
388 1
389 1
390 1
391 1
392 1
393 1
394 1
395 1
396 1
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component r.
Enclosure I
r B~~--1 Floor Component _;valuation
[
10 _ J l _:rv~ J
~ Syste~ ~ction==:JI Manufacturer 10
[ Typ~
Elev. (ft)
Basls*for Evaluation Mo<!el1No.
Capacltv1 Result AC/DC D14-CP1 Control Power Jacket Cooling ITE J13P3012 l ETB-Control Diesel 217 GERS Cap> Dem Relays Support Pressure Low Relay DGSOl Cab.
Generator Systems AC/DC Control Power Jacket Cooling ITE Jl3P3012 lETB-Control Diesel 217 GERS Cap> Dem D14-CP2 Relays Support Pressure Low Relay DGSOl Cab.
Generator Systems AC/DC D14-CP3 Cont rol Power Jacket Cooling ITE J13P3012 lETB-Control Diesel 217 GERS Cap> Dem Relays Support Pressure Low Relay DGSOl Cab.
Generator Systems AC/ DC D14-CT1 Control Power Jacket Coolant ITE J13P3012 lETB-Control Diesel 217 GERS Cap> Dem Relays Support Temperature Relay DGSOl Cab.
Generator Systems AC/DC D14*CT2 Control Power Jacket Coolant ITE J13P3012 lETB-Control Diesel 217 GERS Cap> Dem Relays Support Temperature Relay DGSOl Cab.
Generator Systems AC/DC D14-CT3 Control Power Jacket Coolant ITE J13P3012 lETB-Control Diesel 217 GERS Cap> Dem Relays Support Temperature Relay DGSOl Cab.
Generator Systems AC/DC D14-0P1 Control Power Lube Oil Pressure ITE J13P3012.
lETB-Control Diesel 217 GERS Cap>Dem Relays Support Low Relay DGSOl Cab.
Generator Systems AC/DC D14-0P2 Control Power Lube Oil Pressure ITE J13P3012 lETB-Control Diesel Relays Support Low Relay DGSOl Cab.
Generator 217 GERS Cap> Dem Systems AC/DC D14-0P3 Control Power Lube Oil Pressure ITE J13P3012 lETB-Control Diesel 217 Relays Support Low Relay DGSOl Cab.
Generator GERS Cap> Dem Systems AC/DC D14-0T1 Control Power Lube Oil High ITE lETB-Control Diesel Relays Support Temperature Relay J13P3012 DGSOl Cab.
Generator 217 GERS Cap> Dem Systems Page 83 of 110
No.
Unit j
ID T.ype D14-0T2 Control 397 1
Relays 398 1
D14-0T3 Control Relays D14-SDR Control 399 1
Relays 400 1
D14-SFR Control Relays 2
D21-CP1 Control 401 Relays 2
D21-CP2 Control 402 Relays 403 2
D21-CP3 Control Relays 2
D21-CT1 Control 404 Relays 405 2
D21-CT2 Control Relays 406 2
D21-CT3 Control Relays Table B-1: Components Identified for High Frequency Confirmation Component Enclosure System Function Manufacturer Model'No.
ID Type Building AC/DC Power Lube Oil High ITE J13P3012 lETB-Control Diesel Support Temperature Relay DGSOl Cab.
Generator Systems AC/DC Power Lube Oil High ITE J13P3012 lETB-Control Diesel Support Temperature Relay DGSOl Cab.
Generator Systems AC/DC Power Shutdown Relay ITE J13P3012 lETB-Control Diesel Support DGSOl Cab.
Generator Systems AC/DC Power Start Failure Relay ITE J13P3012 lETB-Control Diesel Support DGSOl Cab.
Generator Systems AC/DC Power Jacket Cooling ITE J13P3012 2ETB-Control Diesel Support Pressure Low Relay AGSOl Cab.
Generator Systems AC/DC Power Jacket Cooling ITE Jl3P3012 2ETB-Control Diesel Support Pressure Low Relay AGSOl Cab.
Generator Systems AC/DC Power Jacket Cooling ITE J13P3012 2ETB-Control Diesel Support Pressure Low Relay AGSOl Cab.
Generator Systems AC/DC Power Jacket Coolant ITE J13P3012 2ETB-Control Diesel Support Temperature Relay AGSOl Cab.
Generator Systems AC/DC Power Jacket Coolant ITE J13P3012 2ETB-Control Diesel Support Temperature Relay AGSOl Cab.
Generator Systems AC/DC Power Jacket Coolant ITE J13P3012 2ETB-Control Diesel Support Temperature Relay AGSOl Cab.
Generator Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Component Evaluation Floor Elev. (ft)
Basis for Evaluation Capacity Result 217 GERS Cap > Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap>Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem Page 84of110
Table B-1: Components Identified for High Frequency Confirmation 81 I Enclosure Component No. :
ID_ J[ rvi.] I Sys~
~ction
~
r M~ufacturer 11 ~odel N;i
[ Typ~
Building ID AC/DC Control Power Lube Oil Pressure ITE J13P3012 2ETB-Control Diesel 407 2
D21-0P1 Relays Support Low Relay AGSOl Cab.
Generator Systems AC/DC Cont rol Pow er Lube Oil Pressure ITE J13P3012 2ETB-Control Diesel 408 2
D21-0P2 Relays Support Low Relay AGSOl Cab.
Generator Systems AC/DC 409 D21-0P3 Control Power Lube Oil Pressure ITE J13P3012 2ETB-Control Diesel 2
Relays Support Low Relay AGSOl Cab.
Generator Systems AC/DC D21-0Tl Control Power Lube Oil High ITE J13P3012 2ETB-Control Diesel 410 2
Relays Support Temperature Relay AGSOl Cab.
Generator Systems AC/DC D21-0T2 Control Power Lube Oil High ITE J13P3012 2ETB-Control Diesel 411 2
Relays Support Temperatu re Relay AGSOl Cab.
Generator Systems AC/DC 412 2
D21-0T3 Control Power Lube Oil High ITE J13P3012 2ETB-Control Diesel Relays Support Temperature Relay AGSOl Cab.
Generator Systems AC/DC 413 2
D21-SDR Control Power Shutdown Relay ITE J13P3012 2ETB-Control Diesel Relays Support AGSOl Cab.
Generator Systems AC/DC D21-SFR Cont rol Power Start Failure Relay ITE J13P3012 2ETB-Control Diesel 414 2
Relays Support AGSOl Cab.
Generator Systems AC/DC 2
D22-CP1 Control Power Jacket Cooling ITE J13P3012 2ETB-Control Diesel 415 Relays Support Pressure Low Relay BGSOl Cab.
Generator Systems AC/DC D22-CP2 Cont rol Pow er Jacket Cooling ITE J13P3012 2ETB-Control Diesel 416 2
Relays Support Pressure Low Relay BGSOl Cab.
Generator Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Floor Component Evaluation I Elev. (ft)
Basis for Evaluation Capacity Result 217 GERS Cap > Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem Page 85of110
81 No. '
Jl.~- !Y~
,10 417 2
D22-CP3 Control Relays 418 2
D22-CT1 Control Relays 419 2
D22-CT2 Control Relays 420 2
D22-CT3 Control Relays 421 2
D22-0P1 Control Relays 422 2
D22-0P2 Control Relays 423 2
D22-0P3 Control Relays 424 2
D22-0T1 Control Relays 425 2
D22-0T2 Control Relays 426 2
D22-0T3 Control Relays 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Enclosure Component Floor 1'
Component Evaluation
! (ivs~iij ~ction OM
]
[ Manufa~rer ~ M;!' !'l~J
~]
Building J Elev. (ft)
Basis for Evaluation ID Capacity Result AC/DC Power Jacket Cooling ITE J13P3012 2ETB-Control Diesel 217 GERS Cap> Dem Support Pressure Low Relay BGSOl Cab.
Generator Systems AC/DC Power Jacket Coolant ITE J13P3012 2ETB-Control Diesel 217 GERS Support Temperature Relay BGSOl Cab.
Generator Cap> Dem Systems AC/DC Power Jacket Coolant ITE J13P3012 2ETB-Control Diesel 217 Support Temperature Relay BGSOl Cab.
Generator GERS Cap > Dem Systems AC/DC Power Jacket Coolant ITE J13P3012 2ETB-Control Diesel 217 Support Temperature Relay BGSOl Cab.
Generator GERS Cap> Dem Systems AC/DC Power Lube Oil Pressure ITE J13P3012 2ETB-Control Diesel 217 Support Low Relay BGSOl Cab.
Generator GERS Cap> Dem Systems AC/DC Power Lube Oil Pressure ITE J13P3012 2ETB-Control Diesel Support Low Relay BGSOl Cab.
Generator 217 GERS Cap> Dem Systems AC/DC Power Lube Oil Pressure ITE J13P3012 2ETB-Control Diesel Support Low Relay BGSOl Cab.
Generator 217 GERS Cap> Dem Systems AC/DC Power Lube Oil High 2ETB-Control Diesel Support Temperature Relay ITE J13P3012 BGSOl Cab.
Generator 217 GERS Cap> Dem Systems AC/DC Power Lube Oil High ITE J13P3012 2ETB-Control Diesel Support Temperature Relay BGSOl Cab.
Generator 217 GERS Cap> Dem Systems AC/DC Power Lube Oil High 2ETB-Control Diesel Support Temperature Relay ITE J13P3012 BGSOl Cab.
Generator 217 GERS Cap> Dem Systems Page 86 of 110
No.
Unit ID Type 2
D22-SDR Control 427 Relays 428 2
D22-SFR Control Relays 2
D23-CP1 Control 429 Relays 2
D23-CP2 Control 430 Relays 431 2
D23-CP3 Control Relays 432 2
D23-CT1 Control Relays 433 2
D23-CT2 Control Relays 434 2
D23-CT3 Control Relays 435 2
D23-0Pl Control Relays 436 2
D23-0P2 Control Relays Table B-1: Components Identified for High Frequency Confirmation component Enclosure I Building System Function Manufacturer Model No.
ID Type AC/DC Power Shutdown Relay ITE J13P3012 2ETB-Control Diesel Support BGSOl Cab.
Generator Systems AC/DC Power Start Failure Relay ITE J13P3012 2ETB-Control Diesel Support BGSOl Cab.
Generator Systems AC/DC Power Jacket Cooling ITE J13P3012 2ETB-Control Diesel Support Pressure Low Relay CGSOl Cab.
Generator Systems AC/DC Power Jacket Cooling ITE J13P3012 2ETB-Control Diesel Support Pressure Low Relay CGSOl Cab.
Generator Systems AC/DC Power Jacket Cooling ITE J13P3012 2ETB-Control Diesel Support Pressure Low Relay CGSOl Cab.
Generator Systems AC/DC Power Jacket Coolant ITE J13P3012 2ETB-Control Diesel Support Temperature Relay CGSOl Cab.
Generator Systems AC/DC Power Jacket Coolant ITE J13P3012 2ETB-Control Diesel Support Temperature Relay CGSOl Cab.
Generator Systems AC/DC Power Jacket Coolant ITE Jl3P3012 2ETB-Control Diesel Support Temperature Relay CGSOl Cab.
Generator Systems AC/DC Power Lube Oil Pressure ITE J13P3012 2ETB-Control Diesel Support Low Relay CGSOl Cab.
Generator Systems AC/DC Power Lube Oil Pressure ITE J13P3012 2ETB-Control Diesel Support Low Relay CGSOl Cab.
Generator Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Floor Component Evaluation Basis for Evaluation Elev. (ft)
Capacity Result 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem Page 87 of 110
I No.
Unit I
ID Type 437 2
D23-0P3 Control Relays 438 2
D23-0Tl Control Relays 439 2
D23-0T2 Control Relays 440 2
D23-0T3 Control Relays 441 2
D23-SDR Control Relays 442 2
D23-SFR Control Relays 443 2
D24-CP1 Control Relays 2
D24-CP2 Control 444 Relays 445 2
D24-CP3 Control Relays 446 2
D24-CT1 Control Relays 15C4345-RPT-002,Rev.O Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component Enclosure BuHding j Component Evaluation Floor
'Basis for Evaluation System Function Manufacturer ModeiNo.
ID Type I
Elev. {ft)
Capacltv Result AC/DC Power Lube Oil Pressure ITE J13P3012 2ETB-Control Diesel 217 GERS Cap> Dem Support Low Relay CGSOl Cab.
Generator Systems AC/DC Power Lube Oil High ITE J13P3012 2ETB-Control Diesel 217 GERS Cap> Dem Support Temperature Relay CGSOl Cab.
Generator Systems AC/DC Power Lube Oil High ITE J13P3012 2ETB-Control Diesel 217 GERS Cap> Dem Support Temperature Relay CGSOl Cab.
Generator Systems AC/DC Power Lube Oil High ITE J13P3012 2ETB-Control Diesel 217 GERS Cap> Dem Support Temperature Relay CGSOl Cab.
Generator Systems AC/DC Power Shutdown Relay ITE Jl3P3012 2ETB-Control Diesel 217 GERS Support CGSOl Cab.
Generator Cap> Dem Systems AC/DC Power Start Failure Relay ITE J13P3012 2ETB-Control Diesel 217 Support CGSOl Cab.
Generator GERS Cap> Dem Systems AC/DC Power Jacket Cooling ITE J13P3012 2ETB-Control Diesel 217 Support Pressure Low Relay DGSOl Cab.
Generator GERS Cap>Dem Systems AC/DC Power Jacket Cooling ITE Jl3P3012 2ETB-Control Diesel Support Pressure Low Relay DGSOl Cab.
Generator 217 GERS Cap> Dem Systems AC/DC Power Jacket Cooling ITE J13P3012 2ETB-Control Diesel 217 Support Pressure Low Relay DGSOl Cab.
Generator GERS Cap> Dem Systems AC/DC Power Jacket Coolant ITE 2ETB-Control Diesel Support Temperature Relay J13P3012 DGSOl Cab.
Generator 217 GERS Cap> Dem Systems Page 88 of 110
I Unit r*
No. I
~ '
110 TvPe 2
D24-CT2 Control 447 Relays 448 2
D24-CT3 Control Relays 2
D24-0P1 Control 449 Relays 450 2
D24-0P2 Control Relays 2
D24-0P3 Control 451 Relays 2
D24-0T1 Control 452 Relays 453 2
D24-0T2 Control Relays 2
D24-0T3 Control 454 Relays 455 2
D24-SDR Control Relays 456 2
D24-SFR Control Relays Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Building System Function Manufacturer
- Model No.
ID Type I
I AC/DC Power Jacket Coolant ITE J13P3012 2ETB-Control Diesel Support Temperature Relay DG501 Cab.
Generator Systems AC/DC Power Jacket Coolant ITE J13P3012 2ETB-Control Diesel Support Temperature Relay DG501 Cab.
Generator Systems AC/DC Power Lube Oil Pressure ITE J13P3012 2ETB-Control Diesel Support Low Relay DG501 Cab.
Generator Systems AC/DC Power Lube Oil Pressure ITE J13P3012 2ETB-Control Diesel Support Low Relay DG501 Cab.
Generator Systems AC/DC Power Lube Oil Pressure ITE J13P3012 2ETB-Control Diesel Support Low Relay DG501 Cab.
Generator Systems AC/DC Power Lube Oil High ITE J13P3012 2ETB-Control Diesel Support Temperature Relay DG501 Cab.
Generator Systems AC/DC Power Lube Oil High ITE J13P3012 2ETB-Control Diesel Support Temperature Relay DG501 Cab.
Generator Systems AC/DC Power Lube Oil High ITE Jl3P3012 2ETB-Control Diesel Support Temperature Relay DG501 Cab.
Generator Systems AC/DC Power Shutdown Relay ITE Jl3P3012 2ETB-Control Diesel Support DG501 Cab.
Generator Systems AC/DC Power Start Failure Relay ITE J13P3012 2ETB-Control Diesel Support DG501 Cab.
Generator Systems 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Component Evaluation Floor I
!Jaslsfor Evaluation I Elev. (ft)
Capacity Result 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap>Dem 217 GERS Cap> Dem 217 GERS Cap> Dem 217 GERS Cap> Dem Page 89of110
!Jnit
~
No.
ID Type 457 1
Dll-EOS Process Switch 458 1
DlZ-EOS Process Switch Process 459 1
D13-EOS Switch Process 460 1
D14-EOS Switch Process 461 2
D21-EOS Switch 2
D22-EOS Process 462 Switch 463 2
D23-EOS Process Switch D24-EOS Process 464 2
Switch 465 1
TSH-GA-Process llOA-1 Switch TSH-GA-Process 466 1
110A-2 Switch Table B-1: Components Identified for High Frequency Confirmation Component Enclosure System Function Manufacturer Model No.
ID I
Type Building AC/DC Power Engine Overspeed Honeywell BZE6-1A-G501 Diesel Diesel Support Switch 2RN7 Engine Generator Systems AC/DC Power Engine Overspeed Honeywell BZE6-1B-G501 Diesel Diesel Support Switch 2RN7 Engine Generator Systems AC/DC Power Engine Overspeed Honeywell BZE6-1C-G501 Diesel Diesel Support Switch 2RN7 Engine Generator Systems AC/DC Power Engine Overspeed Honeywell BZE6-1D-G501 Diesel Diesel Support Switch 2RN7 Engine Generator Systems AC/DC Power Engine Overspeed Honeywell BZE6-2A-G501 Diesel Diesel Support Switch 2RN7 Engine Generator Systems AC/DC Power Engine Overspeed Honeywell BZE6-2B-GS01 Diesel Diesel Support Switch 2RN7 Engine Generator Systems AC/DC Power Engine Overspeed Honeywell BZE6-2C-G501 Diesel Diesel Support Switch 2RN7 Engine Generator Systems AC/DC Power Engine Overspeed Honeywell BZE6-2D-G501 Diesel Diesel Support Switch 2RN7 Engine Generator Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J 1A-G501 Diesel Diesel Support Temperature Switch Engine Generator Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J 1A-G501 Diesel Diesel Support Temperature Switch Engine Generator Systems 1SC4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Floor Component Evaluation Elev. (ft)
Basis for Evaluation capacltv Result 217 EPRI HF Test Cap> Dem 217 EPRI HF Test Cap> Dem 217 EPRI HF Test Cap> Dem 217 EPRI HF Test Cap> Dem 217 EPRI HF Test Cap> Dem 217 EPRI HF Test Cap> Dem 217 EPRI HF Test Cap> Dem 217 EPRI HF Test Cap> Dem 217 Qualification Test Cap> Dem 217 Qualification Cap> Dem Test Page 90of110
l_~nl~ 1 No.
C l [. fype l ID 467 1
TSH-GA-Process llOA-3 Switch TSH-GA-Process 468 1
101A Switch 469 1
TSH-GA-Process 102A Switch 470 1
TSH-GA-Process 103A Switch 471 1
TSH-GA-Process llOB-1 Switch 472 1
TSH-GA-Process llOB-2 Switch 473 1
TSH-GA-Process llOB-3 Switch 474 1
TSH-GA-Process 101B Switch 475 1
TSH-GA-Process 102B Switch 476 1
TSH-GA-Process 103B Switch 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component r
Enclosure
_J I Build!~
Component Evaluation Floor
~Ste~
I Manufacturer II: Mooel No.
ID
~
Elev. (ft)
Basis for Evaluation Function Capacity Result AC/DC Power Jacket Coolant Allen Bradley 837-V3J lA-GSOl Diesel Diesel 217 Qualification Cap> Dem Support Temperature Switch Engine Generator Test Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J lA-GSOl Diesel Diesel 217 Qualification Support Temperature Switch Engine Generator Test Cap> Dem Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J lA-GSOl Diesel Diesel 217 Qualification Support Temperature Switch Engine Generator Test Cap> Dem Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J lA-GSOl Diesel Diesel 217 Qualification Support Temperature Switch Engine Generator Test Cap> Dem Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J lB-GSOl Diesel Diesel Qualification Support Temperature Switch Engine Generator 217 Test Cap> Dem Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J Diesel Diesel Qualification Support Temperature Switch lB-GSOl Engine Generator 217 Test Cap > Dem Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J 10-GSOl Diesel Diesel 217 Qualification Support Temperature Switch Engine Generator Test Cap>Dem Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J Diesel Diesel Qualification Support Temperature Switch lB-GSOl Engine Generator 217 Test Cap> Dem Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J Diesel Diesel Qualification lB-GSOl 217 Cap> Dem Support Temperature Switch Engine Generator Test Systems AC/DC Power Lube Oil High Allen Bradley Diesel Diesel Qualification Support Temperature Switch 837-V3J lB-GSOl Engine Generator 217 Test Cap> Dem Systems Page 91 of 110
l
~. Unit j No. 1 110
~ype 477 1
TSH-GA-Process llOC-1 Switch TSH-GA-Process 478 1
llOC-2 Switch 479 1
TSH-GA-Process llOC-3 Switch 480 1
TSH-GA-Process lOlC Switch 481 1
TSH-GA-Process 102C Switch 482 1
TSH-GA-Process 103C Switch 483 1
TSH-GA-Process llOD-1 Switch 484 1
TSH-GA-Process llOD-2 Switch 485 1
TSH-GA-Process llOD-3 Switch 486 1
TSH-GA-Process 101D Switch Table B-1: Components Identified for High Frequency Confirmation
~omponent Enclosure Building System Function Manufacturer Model No.
ID Type AC/DC Power Jacket Coolant Allen Bradley 837-V3J lC-GSOl Diesel Diesel Support Temperature Switch Engine Generator Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J lC-GSOl Diesel Diesel Support Temperature Switch Engine Generator Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J lC-GSOl Diesel Diesel Support Temperature Switch Engine Generator Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J lC-GSOl Diesel Diesel Support Temperature Switch Engine Generator Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J lC-GSOl Diesel Diesel Support Temperature Switch Engine Generator Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J lC-GSOl Diesel Diesel Support Temperature Switch Engine Generator Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J lD-GSOl Diesel Diesel Support Temperature Switch Engine Generator Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J Diesel Diesel Support Temperature Switch lD-GSOl Engine Generator Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J Diesel Diesel Support Temperature Switch lD-GSOl Engine Generator Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J Diesel Diesel Support Temperature Switch lD-GSOl Engine Generator Systems 1SC4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Floor Component Evaluation Basis for Evaluation Elev. (ft)
Capacity Result 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Cap> Dem Test 217 Qualification Test Cap> Dem 217 Qualification Test Cap> Dem 217 Qualification Test Cap> Dem 217 Qualification Test Cap >Dem Qualification 217 Test Cap> Dem Qualification 217 Test Cap> Dem Qualification 217 Test Cap> Dem Page 92 of 110
No. EJ 487 1
488 1
489 2
490 2
491 2
492 2
493 2
494 2
495 2
496 2
15(4345-RPT-002, Rev.a Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component I
Enclosure
=i Building al Component Evaluation Floor
! =
ID *-] I
~ T,ype s-, ~~
Fnct~ 11 Manufacture~ G~el No.1
[;~
Elev. (ft)
I Basis for Evaluation ID Capacity Result AC/DC TSH-GA-Process Power Lube Oil High Allen Bradley 837-V3J lD-GSOl Diesel Diesel 217 Qualification Cap> Dem 102D Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Lube Oil High Allen Bradley 837-V3J lD-GSOl Diesel Diesel 217 Qualification Cap> Dem 103D Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Jacket Coolant Allen Bradley 837-V3J 2A-G501 Diesel Diesel 217 Qualification Cap> Dem 210A-1 Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Jacket Coolant Allen Bradley 837-V3J 2A-G501 Diesel Diesel 217 Qualification Cap> Dem 210A-2 Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Jacket Coolant Allen Bradley 837-V3J 2A-GS01 Diesel Diesel 217 Qualification Cap> Dem 210A-3 Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Lube Oil High Allen Bradley 837-V3J 2A-G501 Diesel Diesel 217 Qualification Cap> Dem 201A Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Lube Oil High Allen Bradley 837-V3J 2A-G501 Diesel Diesel 217 Qualification Cap>Dem 202A Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Lube Oil High Allen Bradley 837-V3J 2A-G501 Diesel Diesel 217 Qualification Cap> Dem 203A Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Jacket Coolant Allen Bradley 837-V3J 2B-G501 Diesel Diesel 217 Qualification Cap> Dem 2106-1 Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Jacket Coolant Allen Bradley 837-V3J 2B-G501 Diesel Diesel 217 Qualification Cap> Dem 2108-2 Switch Support Temperature Switch Engine Generator Test Systems Page 93 of 110
j 81 No.
H Type~
ltl 497 2
TSH-GA-Process 210B-3 Switch TSH-GA-Process 498 2
2018 Switch 499 TSH-GA-Process 2
202B Switch soo 2
TSH-GA-Process 203B Switch 501 2
TSH-GA-Process 210C-1 Switch S02 2
TSH-GA-Process 210C-2 Switch 503 2
TSH-GA-Process 210C-3 Switch 504 2
TSH-GA-Process 201C Switch 50S 2
TSH-GA-Process 202C Switch 506 TSH-GA-Process 2
203C Switch 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component Enclosure
,je:i:1ng]
Component Evaluation Floor
(~;te~
Enction I r
Man~cturer I
~ ModeiN~
Basis for Evaluation ID Type Elev. (ftJ Capatity Result AC/DC Power Jacket Coolant Allen Bradley 837-V3J 2B-GS01 Diesel Diesel 217 Qualification Cap> Dem Support Temperature Switch Engine Generator Test Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J 2B-GS01 Diesel Diesel 217 Qualification Cap> Dem Support Temperature Switch Engine Generator Test Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J 2B-GS01 Diesel Diesel 217 Qualification Cap> Dem Support Temperature Switch Engine Generator Test Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J 2B-GS01 Diesel Diesel 217 Qualification Cap>Dem Support Temperature Switch Engine Generator Test Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J 2C-G501 Diesel Diesel 217 Qualification Cap> Dem Support Temperature Switch Engine Generator Test Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J 2C-GS01 Diesel Diesel 217 Qualification Cap> Dem Support Temperature Switch Engine Generator Test Systems AC/DC Power Jacket Coolant Allen Bradley 837-V3J 2C-G501 Diesel Diesel 217 Qualification Support Temperature Switch Engine Generator Test Cap> Dem Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J 2C-G501 Diesel Diesel 217 Qualification Support Temperature Switch Engine Generator Test Cap> Dem Systems AC/DC Power Lube Oil High Allen Bradley 837-V3J 2C-GS01 Diesel Diesel 217 Qualification Support Temperature Switch Engine Generator Test Cap> Dem Systems AC/DC Power Lube Oil High Allen Bradley 2C-G501 Diesel Diesel Qualification 837-V3J 217 Cap> Dem Support Temperature Switch Engine Generator Test Systems Page 94of110
No.
~ ~nl~
507 2
508 2
509 2
510 2
511 2
512 2
513 1
514 1
515 1
15C4345-RPT-002,Rev.O Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component Enclosure I I B~dl:J Floor
-Component Evaluation t= ~~o =J L Tv~~] j System] ~ction
_J ; Manufacture~
ID
~
Elev. (ft)
Basis for Evaluation Model No.
Capacltv Result AC/DC TSH-GA-Process Power Jacket Coolant Allen Bradley 837-V3J 2D-G501 Diesel Diesel 217 Qualification Cap > Dem 210D-1 Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Jacket Coolant Allen Bradley 837-V3J 2D-G501 Diesel Diesel 217 Qualification Cap > Dem 210D-2 Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Jacket Coolant Allen Bradley 837-V3J 2D-G501 Diesel Diesel 217 Qualification Cap> Dem 210D-3 Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Lube Oil High Allen Bradley 837-V3J 2D-G501 Diesel Diesel 217 Qualification Cap> Dem 2010 Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Lube Oil High Allen Bradley 837-V3J 2D-G501 Diesel Diesel 217 Qualification Cap> Dem 202D Switch Support Temperature Switch Engine Generator Test Systems AC/DC TSH-GA-Process Power Lube Oil High Allen Bradley 837-V3J 2D-G501 Diesel Diesel 217 Qualification Cap> Dem 203D Switch Support Temperature Switch Engine Generator Test Systems AC/DC Load D114-33 Low Voltage Power D114-D-G Motor K-600 Center Reactor Qualification (52-20133)
Circuit Support Control Center ABB/ITE Breaker D114-33 I
Enclosure 313 Test Cap> Dem Breaker Switch Systems gear AC/DC Load D114-32 Low Voltage Power D114-R-G Motor K-600 Center Reactor Qualification (52-20132)
Circuit Support Control Center ABB/ITE Breaker D114-32 I
Enclosure 313 Test Cap> Dem Breaker Systems Circuit Breaker Switch gear AC/DC Load D124-33 Low Voltage Power D124-D-G Motor K-600 Center Reactor Qualification (52-20233)
Circuit Support Control Center ABB/ITE Breaker D124-33 I
Enclosure 313 Test Cap> Dem Breaker Systems Switch gear Page 95 of 110
~
I No. *. Unit
- 10 Type
..J Low Voltage D124-32 516 1
(52-20232)
Circuit Breaker Low Voltage D134-33 517 1
Circuit (52-20333)
Breaker Low Voltage D134-24 518 1
(52-20324)
Circuit Breaker Low Voltage 519 D144-33 Circuit 1
(52-20433)
Breaker Low Voltage D144-24 520 1
(S2-20424)
Circuit Breaker D214-33 Low Voltage 521 2
Circuit (52-20133)
Breaker Low Voltage 0214-32 522 2
{52-20132)
Circuit Breaker D224-33 Low Voltage 523 2
{52-20233)
Circuit Breaker 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-1: Components Identified for High Frequency Confirmation Component Enclosure r F.loor Component Evaluation Building j Basis for Evaluation System Function Manufacturer Model No.
ID Type Elev. (ft)
Capacltv Result Load AC/DC D124-R-G Motor Center Power Control Center ABB/ITE K-600 D124-32 I
Reactor 313 Qualification Cap> Dem Support Breaker Enclosure Test Circuit Breaker Switch Systems gear Load AC/DC Center Power D134-D-G Motor K-600 Reactor Qualification Control Center ABB/ITE Breaker D134-33 I
Enclosure 253 Test Cap> Dem Support Switch Systems gear AC/DC Load D134-R-E Motor Center Power K-600 Reactor Qualification Control Center ABB/ITE Breaker D134-24 I
Enclosure 253 Test Cap> Dem Support Circuit Breaker Switch Systems gear AC/DC Load Center Power D144-D-G Motor ABB/ITE K-600 D144-33 I
Reactor 283 Qualification Cap> Dem Support Control Center Breaker Enclosure Test Switch Systems gear AC/DC Load D144-R-E Motor Center Power K-600 Reactor Qualification Support Control Center ABB/ITE Breaker D144-24 I
Enclosure 283 Test Cap> Dem Circuit Breaker Switch Systems gear AC/DC Load Power D214-D-G Motor K-600 Center Reactor Qualification ABB/ITE D214-33 I
313 Cap> Dem Support Control Center Breaker Switch Enclosure Test Systems gear AC/DC Load D214-R-G Motor Center Power K-600 Reactor Qualification Support Control Center ABB/ITE Breaker D214-32 I
Enclosure 313 Test Cap> Dem Circuit Breaker Switch Systems gear AC/DC Load Power 0224-D-G Motor K-600 Center Reactor Qualification Support Control Center ABB/ITE Breaker D224-33 I
Enclosure 313 Test Cap> Dem Switch Systems gear Page 96 of 11 O
INo. 1 I -
Unit [
110.~J LTv~ -=_]
D224-32 Low Voltage 524 2
Circuit
{52-20232)
Breaker Low Voltage 525 2
D234-33 Circuit (52-20333)
Breaker D234-24 Low Voltage 526 2
{52-20324)
Circuit Breaker D244-33 Low Voltage 527 2
(52-20433)
Circuit Breaker D244-24 Low Voltage 528 2
Circuit
{52-20424)
Breaker Table B-1: Components Identified for High Frequency Confirmation Component Enclosure
~ Building I
Sys~e~J
[_FUnction..
~
~anufacturer I ~ N~
[iype ]
ID AC/DC Load Power D224-R-G Motor K-600 Center Reactor Control Center ABB/ITE D224-32 I
Support Breaker Enclosure Systems Circuit Breaker Switch gear AC/DC Load Center Power D234-D-G Motor ABB/ITE K-600 D234-33 I
Reactor Support Control Center Breaker Enclosure Systems Switch gear AC/DC Load Power D234-R-E Motor K-600 Center Reactor Support Control Center ABB/ITE Breaker D234-24 I
Enclosure Systems Circuit Breaker Switch gear AC/DC Load Power D244-D-G Motor K-600 Center Reactor Support Control Center ABB/ITE Breaker D244-33 I
Enclosure Systems Switch gear AC/DC Load Power D244-R-E Motor K-600 Center Reactor Control Center ABB/ITE D244-24 I
Support Breaker Enclosure Systems Circuit Breaker Switch gear 1SC4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Floor Component Evaluation Elev. {ft)
Basis for Evaluation caoacitV Result Qualification 313 Cap> Dem Test 253 Qualification Cap> Dem Test Qualification 253 Test Cap> Dem Qualification 283 Test Cap> Dem Qualification 283 Cap> Dem Test Page 97 of 110
VAi.VE Ill> (Qn P&ID HV-lFOOl HV-1F002 HV-lFOOS HV-lFOllA lFOlOA HV-1F074A HV-lFOllB lFOlOB HV-1F074B PSV-1F013A 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation I
PIMSID.
- 'I P&ID f.SHEET Notes Evaluated in Ref. [1:8]
I I
HV-041-lFOOl M-0041 1
Yes*
HV-041-1F002 M-0041 1
Yes*
NORMALLY OPEN TO MAIN HV-041-lFOOS M-0041 1
STEAM LINE C. NOT A LEAK PATH No (No Need to be included-Line C is isolated)
DOWN STREAM CHECK VALVE HV-HV-041-lFOllA M-0041 1
lFOlOA will provide Boundary (No No Need to be included) 041-lFOlOA M-0041 1
SIMPLE CHECK VALVE (No Need to No be included)
HV-041-1F074A M-0041 1
DOWN STREAM OF CHECK VALVE (No Need to be included)
No DOWN STREAM CHECK VALVE HV-HV-041-lFOllB M-0041 1
lFOlOB will provide Boundary (No No Need to be included) 041-lFOlOB M-0041 1
SIMPLE CHECK VALVE (No Need to No be included)
HV-041-1F074B M-0041 1
DOWN STREAM OF CHECK VAL VE (No Need to be included)
No PSV-041-1F013A M-0041 2
SRV Yes*
Page 98of110
VALVE Ill> on i' P&ID PSV-1F013B PSV-1F013C PSV-1F013D PSV-1F013E PSV-1F013F PSV-1F013G PSV-1F013H PSV-1F013J PSV-1F013K PSV-1F013L PSV-1F013M PSV-1F013S PSV-1F013N HV-F022A HV-F028A HV-F022B 15C4345-RPT-002, Rev. a Correspondence No.: RS-16-177 Table B-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation PIMSID I
P&ID SHEET Notes Evaluated in Ref., [18)
PSV-041-1F013B M-0041 2
SRV Yes*
PSV-041-1F013C M-0041 2
SRV Yes*
PSV-041-1F013D M-0041 2
SRV Yes*
PSV-041-1F013E M-0041 2
SRV Yes*
PSV-041-1F013F M-0041 2
SRV Yes*
PSV-041-1F013G M-0041 2
SRV Yes*
PSV-041-1F013H M-0041 2
SRV Yes*
PSV-041-1F013J M-0041 2
SRV Yes*
PSV-041-1F013K M-0041 2
SRV Yes*
PSV-041-1F013L M-0041 2
SRV Yes*
PSV-041-1F013M M-0041 2
SRV Yes*
PSV-041-1F013S M-0041 2
SRV Yes*
PSV-041-1F013N M-0041 2
SRV Yes*
HV-041-1F022A M-0041 2
Yes*
HV-041-1F028A M-0041 2
Yes*
HV-041-1F022B M-0041 2
Yes*
Page 99of110
V~LVE ID on IP&ID HV-F028B HV-F022C HV-F028C HV-F022D HV-F028D HV-C-F020 HV-1F016 HV-1F019 HV-lFlOS HV-lFOOl HV-1F004 HV-lFlOO 15C4345-RPT-002,Rev.O Correspondence No.: RS-16-177 Table B-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation
[
PIMS llD J P&ID rH~~T I l Notes l
Evaluated in Ref. [18]
HV-041-1F028B M-0041 2
Yes*
HV-041-1F022C M-0041 2
Yes*
HV-041-1F028C M-0041 2
Yes*
HV-041-1F022D M-0041 2
Yes*
HV-041-1F028D M-0041 2
Yes*
HV-C-041-1F020 M-0041 2
Yes*
HV-041-lFOlG M-0041 2
Normally Closed Drain Line Yes*
Normally Closed Drain Line would No - See notes and discussion in HV-041-1F019 M-0041 2
only be a Leak Path if HV-1F016 Section 2.2 of this report.
Opens HV-044-lFlDS M-0044 1
Normally Open-Need to check if Yes*
there is a signal to close Would only be a Leak Path if HV-No - See notes and discussion in HV-044-lFOOl M-0044 1
lFlOS fails to be closed Section 2.2 of this report.
Would only be a Leak Path if HV-No - See notes and discussion in HV-044-1F004 M-0044 1
lFlOS fails to be closed Section 2.2 of this report.
HV-044-lFlOO M-0044 1
Normally Open-Need to check if Yes*
there is a signal to close Page 100of110
VAl!.VE ID on P&ID I
HV-1F007 HV-1F008 HV-1F021A HV-1F016A HV-1F041C HV-1F017C HV-1F041A HV-1F017A HV-1F050A HV-1F015A 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation PIMS ID ~~
l ;HE~
[~
Notes l '
Evaluated in Ref. (18]
___J HV-049-1F007 M-0049 1
Normally Open-Need to check if Yes*
there is a signal to close Would only be a Leak Path if HV-No - See notes and discussion in HV-049-lFOOS M-0049 1
1F107 fails to be closed Section 2.2 of this report.
Per the Plant this is the HV-051-1F021A M-0051 1
Containment Spray Valves and No - See Note does not communicate with the Reactor Per the Plant this is the HV-051-1F016A M-0051 1
Containment Spray Valves and No - See Note does not communicate with the Reactor HV-051-1F041C M-0051 1
CHECK VALVE Yes*
HV-051-1F017C M-0051 1
DOWN STREAM OF CHECK VALVE No - See notes and discussion in Section 2.2 of this report.
HV-051-1F041A M-0051 1
CHECK VALVE Yes*
HV-051-1F017A M-0051 1
DOWN STREAM OF CHECK VALVE No - See notes and discussion in Section 2.2 of this report.
HV-051-1F050A M-0051 1
CHECK VALVE Yes*
HV-051-1F015A M-0051 1
DOWN STREAM OF CHECK VALVE No - See notes and discussion in Section 2.2 of this report.
Page 101 of 110
VALVE ID on P&ID HV-1F008 HV-1F021B HV-1F016B HV-1F041D HV-1F017D HV-1F041B HV-1F017B HV-1F050B HV-1F015B HV-1F009 HV-1F006B 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation PIMSID P&ID I SHEET Notes I
Evaluated in 1Ref. [18)
HV-051-lFOOB M-0051 1
Yes*
Per the Plant this is the HV-M51-1F021B M-0051 3
Containment Spray Valves and No - See Note does not communicate with the Reactor Per the Plant this is the HV-051-1F016B M-0051 3
Containment Spray Valves and No - See Note does not communicate with the Reactor HV-051-1F041D M-0051 3
CHECK VALVE Yes*
HV-051-1F017D M-0051 3
DOWN STREAM OF CHECK VALVE No - See notes and discussion in Section 2.2 of this report.
HV-051-1F041B M-0051 3
CHECK VALVE Yes HV-051-1F017B M-0051 3
DOWN STREAM OF CHECK VALVE No - See notes and discussion in Section 2.2 of this report.
HV-051-1F050B M-0051 3
CHECK VALVE Yes*
HV-051-1F015B M-0051 3
DOWN STREAM OF CHECK VALVE No - See notes and discussion in Section 2.2 of this report.
HV-051-1F009 M-0051 3
Yes*
HV-052-lFOOGB M-0052 1
CHECK VALVE Yes*
Page 102 of 110
VAl.\\VE ID on ! [
P&ID HV-108 HV-1F006A HV-1F005 HV-1F002 HV-1F003 HV-2F001 HV-2F002 HV-2F005 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation PIMSID~ 1 P&ID
~:1 l-~-
Note; Evaluated in1 Ref. ~18)
DOWN STREAM OF CHECK VALVE No - See notes and discussion in HV-052-108 M-0052 1
Only needed if HV-1F006B fails to Section 2.2 of this report.
be closed HV-052-lFOOGA M-0052 1
CHECK VALVE Yes*
DOWN STREAM OF CHECK VALVE No - See notes and discussion in HV-052-1F005 M-0052 1
Only needed if HV-1F006A fails to be closed Section 2.2 of this report.
HV-055-1F002 M-0055 1
Normally Open-Need to check if Yes*
there is a signal to close HV-055-1F003 M-0055 1
Would only be a potential Leak No - See notes and discussion in Path if HV-1F002 fails to be closed Section 2.2 of this report.
HV-041-2F001 M-0041 4
Yes*
HV-041-2F002 M-0041 4
Yes*
NORMALLY OPEN TO MAIN HV-041-2F005 M-0041 4
STEAM LINE C. NOT A LEAK PATH (No Need to be included-Line C is No isolated)
Page 103 of 11 O
VALVE 10.,on, P&ID I I HV-2F011A 2F010A HV-2F074A HV-2F011B 2F010B HV-2F074B PSV-2F013A PSV-2F013B PSV-2F013C 1SC4345-RPT-002, Rev.a Correspondence No.: RS-16-177 Table B-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation PIMS ID P&ID SHEET Notes I
Evaluated in Ref. [18)
DOWN STREAM CHECK VALVE HV-HV-041-2F011A M-0041 4
2F010A will provide Boundary (No No Need to be included) 041-2F010A M-0041 4
SIMPLE CHECK VALVE {No Need to No be included)
HV-041-2F074A M-0041 4
DOWN STREAM OF CHECK VALVE No (No Need to be included)
DOWN STREAM CHECK VALVE HV-HV-041-2F011B M-0041 4
2F010B will provide Boundary (No No Need to be included) 041-2F010B M-0041 4
SIMPLE CHECK VALVE (No Need to No be included)
HV-041-2F074B M-0041 4
DOWN STREAM OF CHECK VALVE (No Need to be included)
No PSV-041-2F013A M-0041 5
SRV Yes*
PSV-041-2F013 B M-0041 5
SRV Yes*
PSV-041-2F013C M-0041 5
SRV Yes*
Page 104of110
VAL\\lE IDmi! *
- P&ID I
PSV-2F013D PSV-2F013E PSV-2F013F PSV-2F013G PSV-2F013H PSV-2F013J PSV-2F013K PSV-2F013L PSV-2F013M PSV-2F0135 PSV-2F013N HV-F022A 15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 Table B-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation PIMS[
P&ID I s.;~~ J [
-~= Notes l
Evaluated in Ref. r[l8]
-~
PSV-041-2F013D M-0041 5
SRV Yes*
PSV-041-2F013E M-0041 5
SRV Yes*
PSV-041-2F013F M-0041 5
SRV Yes*
PSV-041-2F013G M-0041 5
SRV Yes*
PSV-041-2F013H M-0041 5
SRV Yes*
PSV-041-2F013J M-0041 5
SRV Yes*
PSV-041-2F013K M-0041 5
SRV Yes*
PSV-041-2F013L M-0041 5
SRV Yes*
PSV-041-M-0041 5
SRV Yes*
2F013M PSV-041-2F0135 M-0041 5
SRV Yes*
PSV-041-2F013N M-0041 5
SRV Yes*
HV-041-2F022A M-0041 5
Yes*
Page 105of110
15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation VA~VE Iii> on r PIMS 0
- D~ ]
I SHEET I [
-,=---~-:~** 1 P&ID Evaluated in Ref. 1[l8]
P&ID HV-F028A HV-041-2F028A M-0041 5
Yes*
HV-F022B HV-041-2F022B M-0041 5
Yes*
HV-F028B HV-041-2F028B M-0041 5
Yes*
HV-F022C HV-041-2F022C M-0041 5
Yes*
HV-F028C HV-041-2F028C M-0041 5
Yes*
HV-F022D HV-041-2F022D M-0041 5
Yes*
HV-F028D HV-041-2F028D M-0041 5
Yes*
HV-C-F020 HV-C-041-2F020 M-0041 5
Yes*
HV-2F016 HV-041-2F016 M-0041 5
Normally Closed Drain Line Yes*
Normally Closed Drain Line would No - See notes and discussion in HV-2F019 HV-041-2F019 M-0041 5
only be a Leak Path if HV-2F016 Section 2.2 of this report.
Opens HV-2F105 HV-044-2F105 M-0044 3
Normally Open-Need to check if Yes*
there is a signal to close Page 106 of 110
VALVJ ID on I 1
P&ID HV-2F001 HV-2F004 HV-2F100 HV-2F007 HV-2F008 HV-2F021A HV-2F016A HV-2F041C 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table 8-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation PIMSID I
P&ID SHEET Notes Evaluated in Ref. 1[1.8]
I HV-044-2F001 M-0044 3
Would only be a Leak Path if HV-No - See notes and discussion in 2F105 fails to be closed Section 2.2 of this report.
HV-044-2F004 Would only be a Leak Path if HV-No - See notes and discussion in M-0044 3
2F105 fails to be closed Section 2.2 of this report.
HV-044-2F100 M-0044 3
Normally Open-Need to check if Yes*
there is a signal to close HV-049-2F007 M-0049 2
Normally Open-Need to check if Yes*
there is a signal to close HV-049-2F008 M-0049 2
Would only be a Leak Path if HV-No - See notes and discussion in 2F107 fails to be closed Section 2.2 of this report.
Per the Plant this is the HV-051-2F021A M-0051 5
Containment Spray Valves and No - See Note does not communicate with the Reactor Per the Plant this is the HV-051-2F016A M-0051 5
Containment Spray Valves and No - See Note does not communicate with the Reactor HV-051-2F041C M-0051 5
CHECK VALVE Yes*
Page 107of110
VALVE ID on 1
P&ID HV-2F017C HV-2F041A HV-2F017A HV-2F050A HV-2F015A HV-2F008 HV-2F021B HV-2F016B HV-2F041D 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation PIMSW)
P&ID SHEET Notes Evaluated in Ref. [18]
I HV-051-2F017C M-0051 5
DOWN STREAM OF CHECK VALVE No - See notes and discussion in Section 2.2 of this report.
HV-051-2F041A M-0051 5
CHECK VALVE Yes*
HV-051-2F017A M-0051 5
DOWN STREAM OF CHECK VALVE No - See notes and discussion in Section 2.2 of this report.
HV-051-2F050A M-0051 5
CHECK VALVE Yes*
HV-051-2F015A M-0051 5
DOWN STREAM OF CHECK VALVE No - See notes and discussion in Section 2.2 of this report.
HV-051-2F008 M-0051 5
Yes*
Per the Plant this is the HV-M51-2F021B M-0051 7
Containment Spray Valves and No - See Note does not communicate with the Reactor Per the Plant this is the HV-051-2F016B M-0051 7
Containment Spray Valves and No - See Note does not communicate with the Reactor HV-051-2F041D M-0051 7
CHECK VALVE Yes*
Page 108 of 110
VALVE ID on P&ID JI HV-2F017D HV-2F041B HV-2F017B HV-2F050B HV-2F015B HV-2F009 HV-2F006B HV-208 HV-2F006A HV-2F005 15C4345-RPT-002, Rev. 0 Correspondence No.: RS-16-177 Table B-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation I
I 1PIMSID P&ID SHEET Notes Evaluated in Ref. [18]
I
~
HV-051-2F017D M-0051 7
DOWN STREAM OF CHECK VALVE No - See notes and discussion in Section 2.2 of this report.
HV-051-2F041B M-0051 7
CHECK VALVE Yes*
HV-051-2F017B M-0051 7
DOWN STREAM OF CHECK VALVE No - See notes and discussion in Section 2.2 of this report.
HV-051-2F050B M-0051 7
CHECK VALVE Yes*
HV-051-2F015B M-0051 7
DOWN STREAM OF CHECK VALVE No - See notes and discussion in Section 2.2 of this report.
HV-051-2F009 M-0051 7
Yes*
HV-052-2F006B M-0052 3
CHECK VALVE Yes*
DOWN STREAM OF CHECK VALVE No - See notes and discussion in HV-052-208 M-0052 3
Only needed if HV-2F006B fails to Section 2.2 of this report.
be closed HV-052-2F006A M-0052 3
CHECK VALVE Yes*
DOWN STREAM OF CHECK VALVE No - See notes and discussion in HV-052-2F005 M-0052 3
Only needed if HV-2F006A fails to Section 2.2 of this report.
be closed Page 109of110
VALVE ID on P&ID HV-2F002 HV-2F003 15C4345-RPT-002, Rev.a Correspondence No.: RS-16-177 Table B-2: Reactor Coolant Leak Path Valve Identified for High Frequency Confirmation PIMSID P&ID I, SHEET Notes Evaluated in Ref. [18)
HV-055-2F002 M-0055 2
Normally Open-Need to check if Yes*
there is a signal to close Would only be a potential Leak No - See notes and discussion in HV-055-2F003 M-0055 2
Path if HV-2F002 fails to be closed Section 2.2 of this report.
- Note: the evaluation of this valve is discussed in Section 2.2 of this report as well as in report 15C4344-RPT-001 (Ref. 18).
Page 11 O of 11 O