UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555"()001 February 15, 2013 Mr. Joseph E. Pollock, Executive Director Nuclear Energy Institute 1776 I Street NW, Suite 400 Washington, DC 20006-3708
SUBJECT:
ENDORSEMENT OF ELECTRIC POWER RESEARCH INSTITUTE FINAL DRAFT REPORT 1025287, "SEISMIC EVALUATION GUIDANCE"
Dear Mr. Pollock:
On behalf of the Nuclear Regulatory Commission (NRC), I am responding to the Nuclear Energy Institute's (NEl's) letter1 of November 27,2012, with attached Electric Power Research Institute (EPRI) final draft Report No. 1025287 entitled, "Seismic Evaluation Guidance: Screening, Prioritization and Implementation Details (SPID) for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic" (hereafter referred to as the SPID report). NEI's letter was submitted to support licensee responses to Enclosure 1 of the March 12, 2012, information requese that was issued pursuant to Title 10 of the Code of Federal Regulations (10 CFR), Section 50.54(f) (hereafter referred to as the 50.54(f) letter). The 50.54(f) letter was issued as part of the lessons learned from the accident at the Fukushima Dai-ichi nuclear facility.
The NRC staff interacted with the stakeholders on the development of the SPID report with a focus on screening, prioritization, and implementation details as they relate to performing a seismic reevaluation. The SPID report is the product of significant interaction between the NRC, NEI, EPRI, and other stakeholders, at over fifteen public meetings,3 over a 9-month period. These interactions and the insights gained from the meetings allowed for the development of this document in a very short time frame. The meetings helped develop the expectations for how licensees would perform plant evaluations after updating their seismic hazard information. At each meeting, the NRC staff provided its comments on the current version of the SPID report and discussed with stakeholders proposed subsequent revisions to the document. This iterative process, over a 9-month period, resulted in the final version of the document. The NRC staff's endorsement of the SPID report, subject to the additional guidance noted below, is based upon this cumulative development process resulting from the extensive interactions between stakeholders and the NRC staff.
The NRC staff has reviewed the SPID report and confirmed that it would provide licensees with the guidance necessary to perform seismic reevaluations. and r6port the results to the NRC in a manner that will address the Requested Information items (1) through (9) in Enclosure 1 of the 50.54(f) letter. The SPID report is intended to provide sufficient guidance for all sites, however, each site is unique and requirements for analYSIS can vary. lri cases where the SPID report Agencywide Documents Access and Management System (ADAMS) Accession No. ML123330282 2 The 50 54(f) letter is available in ADAMS under Accession No. ML1205:'1A340.
3 Public meetings were held on March 1 - 2, April 2 - 3, May 15 16, June 14, July 24 25, August 16 and 30, September 11 and 21, October 9 and 18, November 5, 9, 14, 20, and 26, 2012.
1
J. Pollock
- 2 may not account for the unique characteristics of a site, prudent and sound engineering judgment should be employed to assure all issues bearing on the hazard and risk evaluations are adequately addressed. Instances when unique site characteristics require such engineering judgment, or require analysis that is not included in the SPID report, should be clearly identified, along with the measures taken to assure the unique site characteristics are appropriately addressed.
Although the NRC staff finds that the performance and reporting of the seismic reevaluation in accordance with the SPID report would be responsive to the 50. 54(f) letter, there are four further issues described below for which the NRC staff provides additional guidance. These issues are: (1) the use of the Individual Plant Examination of External Events (IPEEE) submittals for screening purposes; (2) development of foundation input response spectra (FIRS) consistent with the site response used in the development of the site-specific ground motion response spectrum (GMRS); (3) updating the seismic source models; and (4) development of the site response.
Use of IPEEE for Screening Section 3.3 of the SPID report provides the criteria used to determine if the licensee's previous IPEEE submittal is adequate to use for screening purposes. A seismic assessment performed as part of the IPEEE program that demonstrates a plant capacity that is higher than the new GMRS can be used to screen out plants, provided they meet certain adequacy criteria.
Each licensee has the option of demonstrating the adequacy of its previous IPEEE submittal for screening purposes as part of its response to the 50.54(f) letter. The NRC staff will review each submittal and determine whether the provided information demonstrates the adequacy of the IPEEE analysis and risk insights. The licensee's description of each of the adequacy criteria, described in Section 3.3 of the SPID report, will be reviewed by the NRC staff in its integrated totality, rather than using a pass/fail approach. As such, even if one or more of the criteria are not deemed to be adequate, the staff may still decide that the overalllPEEE analysis is adequate to support its use for screening purposes. The NRC staff may conduct site visits to view IPEEE documentation referenced in support of the IPEEE adequacy submittal.
Development of Foundation Input Response Spectra (FIRS)
The SPID report does not discuss the development of FIRS used for performing soil-structure interaction analyses. Consistent with guidance described in DC/COL-ISG-017, "Ensuring Hazard-Consistent Seismic Input for Site Response and Soil Structure Interaction Analyses,"
the FIRS should be derived in a manner consistent with the site response used in the development of the site-specific GMRS. As such, the FIRS should be derived as performance-based site-specific response spectra at the foundation level in the free field. The starting point for development of the FIRS should be the same hard rock elevation used as the starting point for developing the GMRS. As the engineering properties of soil are strain dependent and can be highly non-linear, the characterization of soil layers and their associated properties used in the GMRS analysis should also be used for the derivation of the site-specific FIRS at the foundation elevation. The performance-based FIRS can be developed using either a full-column outcrop motion that includes the effect of the soil above, or as a geologic outcrop motion for which the soil layers above the foundation elevation have been removed.
J. Pollock
- 3 Updating the Central and Eastern United States (CEUS)-Seismic Source Characterization (SSG) model Section 2.2 of the SPID report provides an overview of the CEUS-SSC model and explains why it is appropriate to use without update for the seismic reevaluations. Specifically, Section 2.2 states, "for site-specific licensing applications or site-specific safety decisions, these seismic sources would be reviewed on a site-specific basis to determine if they need to be updated.
Such evaluations would be appropriate in a licensing application, where focus could be made on site-specific applications. However, for a screening-level study of multiple plants for the purpose of setting priorities, the use of these seismic sources as published is appropriate."
The NRC staff agrees that the CEUS-SSC model does not need to be updated for the seismic reevaluations, but the staff's rationale is different than that presented in the SPID report.
Specifically, the staff has determined that the CEUS-SSC model does not need to be updated because the model is up-to-date and is sufficiently refined to allow a site-specific source model to be developed. To adequately respond to the 50.54(f) letter, a site-specific GMRS should be calculated for each plant so that an informed decision can be made regarding which plants will be required to complete a risk evaluation. Further, the site-specific GMRS will also be used in the risk evaluations, if needed.
Prior to issuing the CEUS-SSC model, the Technical Integration Team considered potentially significant events (such as the 2011 Mineral, VA earthquake) that had occurred after the model was developed, and determined that those events did not change their interpretations of seismic sources or earthquake recurrence rates. If a significant earthquake in the CEUS were to occur or new information were to emerge during the reevaluation period that could require an update of the CEUS-SSC model, the staff expects licensees to evaluate the significance of the new information to determine if the CEUS-SSC model needs to be updated in order to appropriately respond to the 50.54(f) request.
Site Response Section 2.4.1 and Appendix 8 of the SPID report provides guidance on how to develop the site response in cases where limited site response data exists. As stated in Appendix 8, the NRC staff expects licensees to use available geologic, geotechnical, and geophysical data collected during the initial licensing or subsequent activities at the site to the extent practicable. Where limited site response data exists, information from core borings and data collected from site and regional evaluations should be used to develop the site response amplification. Section 4 of the SPID report states that licensees should provide the basis for the site responses used in the reevaluations. The NRC staff expects site-specific geology, geotechnical, and geophysical information to be a significant part of the basis.
In accordance with the 50.54(f) letter, each licensee is to submit to the NRC its intention to follow the NRC-endorsed seismic reevaluation guidance, or an alternative approach, 60 days after the issuance of the NRC-endorsed guidance. For the purpose of meeting this deadline, the 60-day response period commences on the date this endorsement of the SPID report is published in the Federal Register.
J. Pollock
-4 Licensees may use the SPID report as one acceptable method for responding to the information requested in Enclosure 1 of the 50.54(f) letter. Accordingly, the NRC staff's issuance of this letter endorsing the SPI D report is not considered backfitting, as defined in 10 CFR 50.1 09(a)(1).
The NRC requests that EPRI publish a final version of the SPID report within 1 month of receipt of this letter. The final version of the SPID report should incorporate this letter between the title page and the first section, and remove the draft markings from the document. If you or your staff have additional questions, please contact my office or Mrs. Lisa Regner, of my staff at 301 415-1906, or by email at Lisa.Regner@nrc.gov.
David L. Skeen, Director Japan Lessons-Learned Project Directorate Office of Nuclear Reactor Regulation cc: See enclosed list Additional distribution via Listserv
POWER REACTOR LICENSEES AND HOLDERS OF CONSTRUCTION PERMITS IN ACTIVE OR DEFERRED STATUS Arkansas Nuclear One Entergy Operations, Inc.
Docket Nos. 50-313 and 50-368 License Nos. DPR-51 and NPF-6 Vice President, Operations Entergy Operations, Inc.
Arkansas Nuclear One 1448 S.R. 333 Russellville, AR 72802 Beaver Valley Power Station First Energy Nuclear Operating Co.
Docket Nos. 50-334 and 50-412 License Nos. DPR-66 and NPF-73 Mr. Paul A Harden Site Vice President FirstEnergy Nuclear Operating Company Mail Stop A-BV-SEB1 P.O. Box 4, Route 168 Shippingport, PA 15077 Bellefonte Nuclear Power Station Tennessee Valley Authority Docket Nos. 50-438 and 50-439 Construction Permit Nos. CPPR-122 and CPPR-123 Mr. Michael D. Skaggs Senior Vice President, Nuclear Construction Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, TN 37402-2801 Braidwood Station Exelon Generation Co., LLC Docket Nos. STN 50-456 and STN 50-457 License Nos. NPF-72 and NPF-77 Mr. Michael J. Pacilio President and Chief Nuclear Officer Exelon Nuclear 4300 Winfield Road Warrenville, IL 60555 Browns Ferry Nuclear Plant Tennessee Valley Authority Docket Nos. 50-259, 50-260 and 50-296 License Nos. DPR-33, DPR-52 and DPR-68 Mr. Joseph W. Shea Vice President, Nuclear Licensing Tennessee Valley Authority 3R Lookout Place 1101 Market Street, LP 3D-C Chattanooga, TN 37402-2801 Brunswick Steam Electric Plant Carolina Power & Light Co.
Docket Nos. 50-325 and 50-324 License Nos. DPR-71 and DPR-62 Mr. Michael J. Annacone Vice President Carolina Power & Light Company Brunswick Steam Electric Plant P. O. Box 10429 Southport, NC 28461 Enclosure
- 2 Byron Station Exelon Generation Co., LLC Docket Nos. STN 50-454 and STN 50-455 License Nos. NPF-37 and NPF-66 Mr. Michael J. Pacilio President and Chief Nuclear Officer Exelon Nuclear 4300 Winfield Road Warrenville, IL 60555 Callaway Plant Union Electric Company Docket No. 50-483 License No. NPF-30 Mr. Adam C. Heflin Senior Vice President and Chief Nuclear Officer Union Electric Company Ameren Missouri P. O. Box 620 Fulton, MO 65251 Calvert Cliffs Nuclear Power Plant Calvert Cliffs Nuclear Power Plant, LLC Docket Nos. 50-317 and 50-318 License Nos. DPR-53 and DPR-69 Mr. George H. Gellrich Vice President Calvert Cliffs Nuclear Power Plant, LLC Calvert Cliffs Nuclear Power Plant 1650 Calvert Cliffs Parkway Lusby, MD 20657-4702 Catawba Nuclear Station Duke Energy Carolinas, LLC Docket Nos. 50-413 and 50-414 License Nos. NPF-35 and NPF-52 Mr. Kelvin Henderson Site Vice President Duke Energy Carolinas, LLC Catawba Nuclear Station 4800 Concord Road York, SC 29745 Clinton Power Station Exelon Generation Co., LLC Docket No. 50-461 License No. NPF-62 Mr. Michael J. Pacilio President and Chief Nuclear Officer Exelon Nuclear 4300 Winfield Road Warrenville, IL 60555 Columbia Generating Station Energy Northwest Docket No. 50-397 License No. NPF-21 Mr. Mark E. Reddemann Chief Executive Officer Energy Northwest MD 1023 North Power Plant Loop P.O. Box 968 Richland, WA 99352
- 3 Comanche Peak Nuclear Power Plant Luminant Generation Co., LLC Docket Nos. 50-445 and 50-446 License Nos. NPF-87 and NPF-89 Mr. Rafael Flores Senior Vice President and Chief Nuclear Officer Luminant Generation Company, LLC Attn: Regulatory Affairs P. O. Box 1002 Glen Rose, TX 76043 Cooper Nuclear Station Nebraska Public Power District Docket No. 50-298 License No. DPR-46 Mr. Oscar A. Limpias Vice President Nuclear and Chief Nuclear Officer Nebraska Public Power District 72676 648A Avenue P.O. Box 98 Brownville, NE 68321 Crystal River Nuclear Generating Plant Florida Power Corp.
Docket No. 50-302 License No. DPR-72 Mr. Jon A. Franke Site Vice President Attn: Supervisor, Licensing & Regulatory Programs Progress Energy, Inc.
Crystal River Nuclear Plant (NA2C) 15760 West Power Line Street Crystal River, FL 34428-6708 Davis-Besse Nuclear Power Station First Energy Nuclear Operating Co.
Docket No. 50-346 License No. NPF-3 Mr. Ray Lieb Site Vice President FirstEnergy Nuclear Operating Company clo Davis-Besse NPS 5501 N. State Route 2 Oak Harbor, OH 43449-9760 Diablo Canyon Power Plant Pacific Gas & Electric Co.
Docket Nos. 50-275 and 50-323 License Nos. DPR-80 and DPR-82 Mr. Edward D. Halpin Senior Vice President and Chief Nuclear Officer Pacific Gas and Electric Company P.O. Box 56, Mail Code 104/6 Avila Beach, CA 93424 Donald C. Cook Nuclear Plant Indiana Michigan Power Company Docket Nos. 50-315 and 50-316 License Nos. DPR-58 and DPR-74 Mr. Lawrence J. Weber Senior Vice President and Chief Nuclear Officer Indiana Michigan Power Company Nuclear Generation Group One Cook Place Bridgman, MI 49106
- 4 Dresden Nuclear Power Station Exelon Generation Co., LLC Docket Nos. 50-237 and 50-249 License Nos. DPR-19 and DPR-25 Mr. Michael J. Pacilio President and Chief Nuclear Officer Exelon Nuclear 4300 Winfield Road Warrenville, IL 60555 Duane Arnold Energy Center NextEra Energy Duane Arnold, LLC Docket No. 50-331 License No. DPR-49 Mr. Rich Anderson Site Vice President NextEra Energy Duane Arnold Energy Center 3277 DAEC Road Palo, IA 52324-9785 Edwin I. Hatch Nuclear Plant Southern Nuclear Operating Co.
Docket Nos. 50-321 and 50-366 License Nos. DPR-57 and NPF-5 Mr. C.R. Pierce Regulatory Affairs Director Southern Nuclear Operating Co., Inc.
P.O. Box 1295/BIN B038 Birmingham, AL 35201-1295 Fermi Detroit Edison Co.
Docket No. 50-341 License No. NPF-43 Mr. Joseph H. Plona Senior Vice President and Chief Nuclear Officer Detroit Edison Company Fermi 2 - 210 NOC 6400 North Dixie Highway Newport, MI 48166 Fort Calhoun Station Omaha Public Power District Docket No. 50-285 License No. DPR-40 Mr. Louis Cortopassi Vice President and Chief Nuclear Officer Omaha Public Power District Fort Calhoun Station Mail Stop FC-2-4 9610 Power Lane Blair, NE 68008 Grand Gulf Nuclear Station Entergy Operations, Inc.
Docket No. 50-416 License No. NPF-29 Vice President, Operations Entergy Operations, Inc.
Grand Gulf Nuclear Station P.O. Box 756 Port Gibson, MS 39150 H. B. Robinson Steam Electric Plant Carolina Power & Light Co.
Docket No. 50-261 License No. DPR-23 Mr. William R. Gideon Vice President Carolina Power & Light Company 3581 West Entrance Road Hartsville, SC 29550
- 5 Hope Creek Generating Station PSEG Nuclear, LLC Docket No. 50-354 License No. NPF-57 Mr. Thomas Joyce President and Chief Nuclear Officer PSEG Nuclear LLC - N09 P. O. Box 236, Hancocks Bridge, NJ 08038 Indian Point Energy Center Entergy Nuclear Operations, Inc.
Docket Nos. 50-247 and 50-286 License Nos. DPR-26 and DPR-64 Vice President, Operations Entergy Nuclear Operations, Inc.
Indian Point Energy Center 450 Broadway, GSB P.O. Box 249 Buchanan, NY 10511-0249 James A. FitzPatrick Nuclear Power Plant Entergy Nuclear Operations, Inc.
Docket No. 50-333 License No. DPR-59 Vice President Entergy Nuclear Operations, Inc.
James A. FitzPatrick Nuclear Power Plant P.O. Box 110 Lycoming, NY 13093 Joseph M. Farley Nuclear Plant Southern Nuclear Operating Co.
Docket Nos. 50-348 and 50-364 License Nos. NPF-2 and NPF-8 Mr. C.R. Pierce Regulatory Affairs Director Southern Nuclear Operating Co., Inc.
P.O. Box 1295/Bin 038 Birmingham, AL 35242 Kewaunee Power Station Dominion Energy Kewaunee, Inc.
Docket No. 50-305 License No. DPR-43 Mr. David A. Heacock President and Chief Nuclear Officer Dominion Energy Kewaunee, Inc.
Innsbrook Technical Center 5000 Dominion Boulevard Glen Allen, VA 23060-6711 LaSalle County Station Exelon Generation Co., LLC Docket Nos. 50-373 and 50-374 License Nos. NPF-11 and NPF-18 Mr. Michael J. Pacilio President and Chief Nuclear Officer Exelon Nuclear 4300 Win'field Road Warrenville, IL 60555 Limerick Generating Station Exelon Generation Co., LLC Docket Nos. 50-352 and 50-353 License Nos. NPF-39 and NPF-85 Mr. Michael J. Pacilio President and Chief Nuclear Officer Exelon Nuclear 4300 Winfield Road Warrenville,IL 60555
- 6 Millstone Nuclear Power Station Dominion Nuclear Connecticut, Inc.
Docket Nos. 50-336 and 50-423 License Nos. DPR-65 and NPF-49 Mr. David A. Heacock President and Chief Nuclear Officer Dominion Nuclear Connecticut, Inc.
Innsbrook Technical Center 5000 Dominion Boulevard Glen Allen, VA 23060-6711 Monticello Nuclear Generating Plant Northern States Power Company Docket No. 50-263 License No. DPR-22 Mr. Mark A. Schimmel Site Vice President Northern States Power Company - Minnesota Monticello Nuclear Generating Plant 2807 West County Road 75 Monticello, MN 55362-9637 Nine Mile Point Nuclear Station Nine Mile Point Nuclear Station, LLC Docket Nos. 50-220 and 50-410 License Nos. DPR-63 and NPF-69 Mr. Christopher Costanzo Vice President Nine Mile Point Nine Mile Point Nuclear Station, LLC P. O. Box 63 Lycoming, NY 13093 North Anna Power Station Virginia Electric & Power Co.
Docket Nos. 50-338 and 50-339 License Nos. NPF-4 and NPF-7 Mr. David A. Heacock President and Chief Nuclear Officer Dominion Nuclear Innsbrook Technical Center 5000 Dominion Boulevard Glen Allen, VA 23060-6711 Oconee Nuclear Station Duke Energy Carolinas, LLC Docket Nos. 50-269, 50-270 and 50-287 License Nos. DPR-38, DPR-47 and DPR-55 Mr. Preston Gillespie Site Vice President, Oconee Nuclear Station Duke Energy Carolinas, LLC 7800 Rochester Highway Seneca, SC 29672 Oyster Creek Nuclear Generating Station Exelon Generation Co., LLC Docket No. 50-219 License No. DPR-16 Mr. Michael J. Pacilio President and Chief Nuclear Officer Exelon Nuclear 4300 Winfield Road Warrenville, IL 60555 Palisades Nuclear Plant Entergy Nuclear Operations, Inc.
Docket No. 50-255 License No. DPR-20 Vice President, Operations Entergy Nuclear Operations, Inc.
Palisades Nuclear Plant 27780 Blue Star Memorial Highway Covert, M I 49043
- 7 Palo Verde Nuclear Generating Station Arizona Public Service Company Docket Nos. STN 50-528, STN 50-529 and STN 50-530 License Nos. NPF-41, NPF-51 and NPF-74 Mr. Randall K. Edington Executive Vice President Nuclear and Chief Nuclear Officer Arizona Public Service Co.
P. O. Box 52034, MS 7602 Phoenix, AZ 85072-2034 Peach Bottom Atomic Power Station Exelon Generation Co., LLC Docket Nos. 50-277 and 50-278 License Nos. DPR-44 and DPR-56 Mr. Michael J. Pacilio President and Chief Nuclear Officer Exelon Nuclear 4300 Winfield Road Warrenville, IL 60555 Perry Nuclear Power Plant FirstEnergy Nuclear Operating Co.
Docket No. 50-440 License No. NPF-58 Mr. Vito A Kaminskas Site Vice President - Nuclear - Perry FirstEnergy Nuclear Operating Company Perry Nuclear Power Plant 10 Center Road, A290 Perry,OH 44081 Pilgrim Nuclear Power Station Unit No.1 Entergy Nuclear Operations, Inc.
Docket No. 50-293 License No. DPR-35 Mr. Robert Smith Vice President and Site Vice President Entergy Nuclear Operations, Inc.
Pilgrim Nuclear Power Station 600 Rocky Hill Road Plymouth, MA 02360-5508 Point Beach Nuclear Plant NextEra Energy Point Beach, LLC Docket Nos. 50-266 and 50-301 License Nos. DPR-24 and DPR-27 Mr. Larry Meyer Site Vice President NextEra Energy Point Beach, LLC Point Beach Nuclear Plant, Units 1 & 2 6610 Nuclear Road Two Rivers, WI 54241-9516 Prairie Island Nuclear Generating Plant Northern States Power Co. Minnesota Docket Nos. 50-282 and 50-306 License Nos. DPR-42 and DPR-60 Mr. James E. Lynch Site Vice President Northern States Power Company - Minnesota Prairie Island Nuclear Generating Plant 1717 Wakonade Drive East Welch, MN 55089-9642
- 8 Quad Cities Nuclear Power Station Exelon Generation Co., LLC Docket Nos. 50-254 and 50-265 License Nos. DPR-29 and DPR-30 Mr. Michael J. Pacilio President and Chief Nuclear Officer Exelon Nuclear 4300 Winfield Road Warrenville, IL 60555 R E. Ginna Nuclear Power Plant R E. Ginna Nuclear Power Plant, LLC Docket No. 50-244 License No. DPR-18 Mr. Joseph E. Pacher Vice President R.E. Ginna Nuclear Power Plant, LLC RE. Ginna Nuclear Power Plant 1503 Lake Road Ontario, NY 14519 River Bend Station Entergy Operations, Inc.
Docket No. 50-458 License No. NPF-47 Vice President, Operations Entergy Operations, Inc.
River Bend Station 5485 U.S. Highway 61 N St. Francisville, LA 70775 Salem Nuclear Generating Station PSEG Nuclear, LLC.
Docket Nos. 50-272 & 50-311 License Nos. DPR-70 and DPR-75 Mr. Thomas Joyce President and Chief Nuclear Officer PSEG Nuclear LLC - N09 P. O. Box 236, Hancocks Bridge, NJ 08038 San Onofre Nuclear Generating Station Southern California Edison Company Docket Nos. 50-361 and 50-362 License Nos. NFP-10 and NFP-15 Mr. Peter T. Dietrich Senior Vice President and Chief Nuclear Officer Southern California Edison Company San Onofre Nuclear Generating Station P.O. Box 128 San Clemente, CA 92674-0128 Seabrook Nuclear Plant NextEra Energy Seabrook, LLC Docket No 50-443 License No. NFP-86 Mr. Kevin Walsh Vice President, Seabrook Nuclear Plant c/o Mr. Michael O'Keefe NextEra Energy Seabrook, LLC P.O. Box 300 Seabrook, NH 03874 Sequoyah Nuclear Plant Tennessee Valley Authority Docket Nos. 50-327 and 50-328 License Nos. DPR-77 and DPR-79 Mr. Joseph W. Shea Vice President, Nuclear Licensing Tennessee Valley Authority 3R Lookout Place 1101 Market Street Chattanooga, TN 37402-2801
- 9 Shearon Harris Nuclear Power Plant Carolina Power & Light Co.
Docket No. 50-400 License No. NPF-63 Mr. George T. Hamrick Vice President Carolina Power and Light Company Shearon Harris Nuclear Power Plant P. O. Box 165, Mail Zone 1 New Hill, NC 27562-0165 South Texas Project STP Nuclear Operating Co.
Docket Nos. 50-498 and 50-499 License Nos. NPF-76 and NPF-80 Mr. Dennis L. Koehl President and CEO/CNO STP Nuclear Operating Company South Texas Project Electric Generating Station P.O. Box 289 Wadsworth, TX 77483 St. Lucie Plant Florida Power & Light Co.
Docket Nos. 50-335 and 50-389 License Nos. DPR-67 and NPF-16 Mr. Mano Nazar Executive Vice President and Chief Nuclear Officer NextEra Energy 700 Universe Boulevard P. O. Box 14000 Juno Beach, FL 33408-0420 Surry Power Station Virginia Electric & Power Co.
Docket Nos. 50-280 and 50-281 License Nos. DPR-32 and DPR-37 Mr. David A. Heacock President and Chief Nuclear Officer Dominion Nuclear Innsbrook Technical Center 5000 Dominion Boulevard Glen Allen, VA 23060-6711 Susquehanna Steam Electric Station PPL Susquehanna, LLC Docket Nos. 50-387 and 50-388 License Nos. NPF-14 and NPF-22 Mr. Timothy S. Rausch Senior Vice President and Chief Nuclear Officer PPL Susquehanna, LLC 769 Salem Boulevard NUCSB3 Berwick, PA 18603-0467 Three Mile Island, Unit 1 Exelon Nuclear Docket No. 50-289 License No. DPR-50 Mr. Michael J. Pacilio President and Chief Nuclear Officer Exelon Nuclear 4300 Winfield Road Warrenville, IL 60555
Turkey Point Florida Power & Light Co.
Docket Nos. 50-250 and 50-251 License Nos. DPR-31 and DPR-41 Mr. Mano Nazar Executive Vice President and Chief Nuclear Officer NextEra Energy 700 Universe Boulevard P. O. Box 14000 Juno Beach, FL 33408-0420 Vermont Yankee Nuclear Power Station Entergy Nuclear Operations, Inc.
Docket No. 50-271 License No. DPR-28 Vice President, Operations Entergy Nuclear Operations, Inc.
Vermont Yankee Nuclear Power Station P.O. Box 250, Governor Hunt Road Vernon, VT 05354 Virgil C. Summer Nuclear Station South Carolina Electric & Gas Co.
Docket No. 50-395 License No. NPF-12 Mr. Thomas D. Gatlin Vice President Nuclear Operations South Carolina Electric & Gas Company Virgil C. Summer Nuclear Station Post Office Box 88, Mail Code 800 Jenkinsville, SC 29065
- 10 Vogtle Electric Generating Plant Southern Nuclear Operating Co.
Docket Nos. 50-424 and 50-425 License Nos. NPF-68 and NPF-81 Mr. C.R Pierce Regulatory Affairs Director Southern Nuclear Operating Co., Inc.
P.O. Box 1295/Bin 038 Birmingham, AL 35201 Waterford Steam Electric Station Entergy Operations, Inc.
Docket No. 50-382 License No. NPF-38 Vice President, Operations Entergy Operations, Inc.
Waterford Steam Electric Station, Unit 3 17265 River Road Killona, LA 70057-0751 Watts Bar Nuclear Plant. Units 1 and 2 Watts Bar Nuclear Plant, Unit 1 Tennessee Valley Authority Docket No. 50-390 License No. NPF-90 Watts Bar Nuclear Plant, Unit 2 Tennessee Valley Authority Docket No. 50-391 Construction Permit No. CPPR No. 092 Mr. Joseph W. Shea Chief Nuclear Officer and Executive Vice President Tennessee Valley Authority 3R Lookout Place 1101 Market Street Chattanooga, TN 37402-2801
- 11 William B. McGuire Nuclear Station Duke Energy Carolinas, LLC Docket Nos. 50-369 and 50-370 License Nos. NPF-9 and NPF-17 Mr. Regis T. Repko Vice President Duke Energy Carolinas, LLC McGuire Nuclear Site 12700 Hagers Ferry Road Huntersville, NC 28078 Wolf Creek Generating Station Wolf Creek Nuclear Operating Corp.
Docket No. 50-482 License No. NPF-42 Mr. Matthew W. Sunseri President and Chief Executive Officer Wolf Creek Nuclear Operating Corporation P.O. Box411 Burlington, KS 66839
M L 12319A07 4
- Concurrence via e-mail
- Non-concurrence via e-mail FICE LA: NRR/DORL
- PM: NRR/~ILD/PMB NROIDSEA*
DO: NRO/DSEA
- LRegner CMunson NChokshi NAME ABaxter 02/13/2013 DATE 02/13/2013 02/14/2013 0211312013 0: NRR/DE*
0: NRRIDRA*
BC:NRRlJLD/PMB* OGC*
r-cwFICE JBiggins DHarrison for JGiitter MMitcheli AME PHiland*
02/12/2013 02/12/2013 02/12/2013 ATE 02/12/2013 0: NRR/JLD FFICE NRO/DSEAJRGS 1 **
DSkeen NAME DSeber I
02/15/2013 02/12/2013 DATE
Letter to Joseph E. Pollock from David L. Skeen dated February 15, 2013
SUBJECT:
ENDORSEMENT OF ELECTRIC POWER RESEARCH INSTITUTE FINAL DRAFT REPORT 1025287, "SEISMIC EVALUATION GUIDANCE" Distribution:
PUBLIC N. Choski LPL1-1 RlF LPL 1-2 RtF LPLl2-1 R/F LPL2-2 RlF LPL3-1 R/F LPL3-2 RlF LPL4 RtF RidsNroOd RidsNrrDorl RidsNrrDorlLpl1-1 RidsNrrDorlLpl1-2 RidsNrrDorlLpl2-1 RidsNrrDorlLpl2-2 RidsNrrDorlLpl3-1 RidsNrrDorlLpl3-2 RidsNrrDorlLpl4 RidsNrrOd RidsNsirOd RidsOeMailCenter RidsOgcMailCenter JShea, NRO
~IKratchman, NRR RLaura, NRR RPascarelli, NRR BPurnell, NRR DSkeen, NRR RTaylor, NRR MKhanna, NRR RPascarelli, f\\lRR JQuichocho, NRR RCarlson, NRR MMarkley, NRR DBroaddus, NRR RidsNrrLAABaxter RidsNrrLAJBurkhardt RidsNrrLABClayton RidsNrrLASFigueroa RidsNrrLAKGoldstein RidsNrrLASRohrer RidsNrrPMANO RidsNrrPMBeaverValley RidsNrrPM Bellefonte RidsNrrPMBraidwood RidsNrrPMBrownsFerry RidsNrrPMBrunswick RidsNrrPMByron RidsNrrPMCallaway RidsNrrPMCalvertCliffs RidsNrrPMCatawba RidsNrrPMClinton RidsNrrPMColumbia RidsNrrPMComanchePeak RidsNrrPMCooper RidsNrrPMCrystalRiver RidsNrrPM DCCook RidsNrrPM DavisBesse RidsNrrPM DiabloCanyon RidsNrrPMDresden RidsNrrPMDuaneArnold RidsNrrPMFarley RidsNrrPMFermi2 RidsNrrPMFitzPatrick RidsNrrPMFortCalhoun RidsNrrPMGrandGulf RidsNrrPMHatch RidsNrrPMHopeCreek RidsNrrPMlndianPoint RidsNrrPMKewaunee RidsNrrPMLaSalie RidsNrrPMLimerick RidsNrrPMMcGuire RidsNrrPMMiIIstone RidsNrrPMMonticello RidsNrrPM NineM ilePoint RidsNrrPMNorthAnna RidsNrrPMOconee RidsNrrPMOysterCreek RidsNrrPMPalisades RidsNrrPIVIPaloVerde RidsNrrPMPeachBottom RidsNrrPM Perry RidsNrrPMPilgrim RidsNrrPM Point Beach RidsNrrPMPrairielsland RidsNrrPMQuadCities RidsNrrPMREGinna RidsNrrPMRiverBend RidsNrrPMRobinson RidsNrrPMSalem RidsNrrPMSanOnofre RidsNrrPMSeabrook RidsNrrPMSequoyah RidsNrrPMShearonHarris RidsNrrPMSouthTexas RidsNrrPMStLucie RidsNrrPMSummer RidsNrrPMSurry RidsNrrPMSusquehanna RidsNrrPMThreeMilelsland RidsNrrPMTurkeyPoint RidsNrrPMVermontYankee RidsNrrPMVogtle RidsNrrPMWaterford Rids NrrPMWattsBar1 RidsNrrPMWattsBar2 RidsNrrPMWolfCreek RidsOgcRp Resource RidsRgn1 MailCenter Resource RidsRgn2MailCenter Resource RidsRgn3MailCenter Resource RidsRgn4MailCenter Resource