FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-2Revision 30Page 1 of 5STRUCTURES CLASSIFICATION RG 1.29INTREPRETATIONSEISMIC BUILDINGCLASSIFICATIONDESIGN CLASSDESIGN CODECONTAINMENT (SHELL AND BASE Category IClass 1 SLAB)1. ConcreteACI 318-63ACI 301-66

2. LinerASME B&PV Code,Sec III, VIII and IX, 19653. Personnel Air Lock,ACI 318-63Escape Air Lock, andASME, Sec III, 1965 Equipment Hatch4. Pipe, Electrical and HVACACI 318-63 Penetrations*ASME, Sec III, 1965CONTAINMENT INTERIOR Category IClass 1ACI 318-63STRUCTURESAISC 1963AUXILIARY BUILDING (Excluding Category IClass 1ACI 318-63Admin and Access Control Areas)AISC 1963*Steam Generator Blowdown and Recirc Penetration End Plates are ASME Section III, Subsection NC, 1986 Ed.

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-2Revision 30 Page 2 of 5STRUCTURES CLASSIFICATION RG 1.29INTREPRETATIONSEISMIC BUILDINGCLASSIFICATIONDESIGN CLASSDESIGN CODE(a) UBC-64 was utilized for seismic and wind loading design. In addition, International Building Code 2006 and ASCE 7-05were utilized for seismic and wind parameters for tower E-30A.(b) Usually this applies to the basin and not the tower framing above the basin, if the basin is a backup source of water forsafety functions.(c) The definition of Class 1E electrical equipment is provided in Subsection 8.1.1.(d) Information not located.(e) Year unknown.(f) Pultruded structure for tower E-30A was designed in accordance with Cooling Tower Institute Standard Specification 137.1972 AUXILIARY BUILDING Category IClass 1ACI 318-63RADWASTE ADDITIONAISC 19691983 AUXILIARY BUILDING (d)Class 1ACI 318-77TSC/EER/HVAC/ADDITIONAISC 1978COOLING TOWERSCategory I(b)Class 3(a)(d)(f)COOLING TOWER PUMP HOUSE Category IClass 3(a)ACI 318-71 AISC 1969 DISCHARGE STRUCTURE Category IClass 3(a)UBC(e)FEEDWATER PURITY BUILDINGNoncategory IClass 3(a)UBC(e)

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-2Revision 30 Page 3 of 5STRUCTURES CLASSIFICATION RG 1.29INTREPRETATIONSEISMIC BUILDINGCLASSIFICATIONDESIGN CLASSDESIGN CODE(a) UBC-64 was utilized for seismic and wind loading design. In addition, International Building Code 2006 and ASCE 7-05were utilized for seismic and wind parameters for tower E-30A.(b) Usually this applies to the basin and not the tower framing above the basin, if the basin is a backup source of water forsafety functions.(c) The definition of Class 1E electrical equipment is provided in Subsection 8.1.1.(d) Information not located.(e) Year unknown.(f) Pultruded structure for tower E-30A was designed in accordance with Cooling Tower Institute Standard Specification 137.INTAKE STRUCTURE (Except as Noted)Noncategory IClass 3UBC(e)1. Portion Above Elevation 590 Category IClass 1ACI 318-63 Housing Service Water Pumps,AISC 1963 Fire Pumps/Drivers and Electrical Support2. Triangular Portion Below Category IClass 1ACI 318-63 Elevation 590 Adjacent to theAISC 1963 Intersection of Column Rows Y and 5 SERVICE BUILDINGNoncategory IClass 3(a)UBC(e)SUPPORTS FOR CLASS 1 MECHANI-Category IClass 1AISC 1969CAL EQUIPMENT AND CLASS 1EELECTRICAL EQUIPMENT(c)

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-2Revision 30 Page 4 of 5STRUCTURES CLASSIFICATION RG 1.29INTREPRETATIONSEISMIC BUILDINGCLASSIFICATIONDESIGN CLASSDESIGN CODE(a) UBC-64 was utilized for seismic and wind loading design. In addition, International Building Code 2006 and ASCE 7-05were utilized for seismic and wind parameters for tower E-30A.(b) Usually this applies to the basin and not the tower framing above the basin, if the basin is a backup source of water forsafety functions.(c) The definition of Class 1E electrical equipment is provided in Subsection 8.1.1.(d) Information not located.(e) Year unknown.(f) Pultruded structure for tower E-30A was designed in accordance with Cooling Tower Institute Standard Specification 137.TURBINE BUILDING (Except as Noted)Noncategory IClass 3(a)ACI 318-63AISC 19631. Auxiliary Feedwater Pump Category IClass 1ACI 318-63 RoomAISC 19632. Electrical Penetration Category IClass 1ACI 318-63 EnclosureCONDENSATE STORAGE TANK Category IClass 1ACI 318-63 FOUNDATION PRIMARY SYSTEM MAKEUP TANK Category IClass 1ACI 318-63FOUNDATION (T-90)

SIRW TANK FOUNDATION Category IClass 1ACI 318-63 FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-2Revision 30 Page 5 of 5STRUCTURES CLASSIFICATION RG 1.29INTREPRETATIONSEISMIC BUILDINGCLASSIFICATIONDESIGN CLASSDESIGN CODE(a) UBC-64 was utilized for seismic and wind loading design. In addition, International Building Code 2006 and ASCE 7-05were utilized for seismic and wind parameters for tower E-30A.(b) Usually this applies to the basin and not the tower framing above the basin, if the basin is a backup source of water forsafety functions.(c) The definition of Class 1E electrical equipment is provided in Subsection 8.1.1.(d) Information not located.(e) Year unknown.(f) Pultruded structure for tower E-30A was designed in accordance with Cooling Tower Institute Standard Specification 137.UTILITY WATER TANK FOUNDATION Category IClass 1ACI 318-63(T-91)

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 1 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.1. Reactor Protective System Channels InputsNuclear Instrumentation Power Range Safety YesPrimary Coolant Flow YesPressurizer Pressure YesPrimary Coolant Temperatures YesSteam Generator Level YesSteam Generator Pressure Yes2. Reactor Protective System Control Devices (Including CRDM Clutches and ManualActivation) (Does Not Include Clutch Power Supplies)

Yes3. Engineered Safeguards Controls Channels InputsPressurizer Pressure YesContainment Pressure YesContainment Radiation YesRefueling Radiation NoSIRW Tank Level Yes FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 2 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.4. Engineered Safeguards Control Devices (for Activation of)HPSI Pumps YesLPSI Pumps YesContainment Spray Pumps YesCharging Pumps NoLetdown Control Valves YesValve Between Auxiliary Spray Line and Charging YesValve Between the Charging Pumps and the HPSI System YesMotor Operated Valves in the SI System YesValves for Safety Injection Recirculation YesContainment Isolation Valves YesComponent Cooling Water Pumps YesComponent Cooling Water Valves YesService Water Pumps YesService Water Valves YesContainment Recirculation Air Cooler FansMix (e)Emergency Generators Yes FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 3 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.5. Engineered Safeguards Controls InstrumentationHPSI Flow to Primary Coolant System YesSafety Injection Tank Level (Passive Injection)

NoSafety Injection Tank Pressure (Passive Injection)

NoService Water Break Detectors (in Containment)

No6. Safe Shutdown and Auxiliary Feedwater Instruments Yes7. Safe Shutdown and Auxiliary Feedwater Control Devices (Activating Circuits)Power Operated Relief Valves YesShutdown Cooling Isolation Valves YesTurbine-Driven Auxiliary Feedwater Pump YesMotor-Driven Auxiliary Feedwater Pumps YesPressurizer Heaters NoAtmospheric Dump Valves NoAFW Control Valves Yes8. AFW Automatic Initiation, Isolation and FOGG Control Devices (Including AFWPumps Suction Pressure)

Yes FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 4 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.9. Primary Coolant Overpressurization Control DevicesPressurizer Pressure Channels YesPCS Overpressurization Protection Devices YesShutdown Cooling Isolation Valves Controls Yes10. Reactor Vessel Gas Vent Isolation Valves Controls Yes11. Engineered Safeguards Pump Rooms and Radwaste Area Radiation Monitors No12. Control Room Ventilation, Instrumentation and Controls (See Table 9-14)

Yes(c)

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 5 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.13. Other Safety-Related Display SystemsSubcooled Margin Monitor YesContainment Pressure YesContainment Water Level YesContainment Temperature NoWide-Range Steam Generator Level YesContainment Hydrogen Monitor NoHigh-Range Containment Gamma Radiation Monitor YesReactor Vessel Level Monitoring System YesCore Exit Thermocouples (16 of 43)

Yes14. Local Instrumentation (Refer to Plant Safety Classification (Q-List) for Details)Transmitters (Inputs to Reactor Protective System)Mix(d)Level, Pressure, etc, Switches (Inputs to Reactor Protective System)Mix(d)Transmitters (Inputs to Engineered Safeguards and Containment Isolation)Mix(d)Level, Pressure, etc, Switches (Inputs to Engineered Safeguards and CI)Mix(d)Transmitters (Inputs to Reactor Shutdown and Decay Heat Removal)Mix(d)Level, Pressure, etc, Switches (Inputs to Reactor Shutdown and DHR)Mix(d)

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 6 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.15. Valve ActuatorsPrimary Coolant Power Operated Relief Valves Actuators YesPrimary Coolant PORV Block Valves Actuators YesInterconnecting Valve (Actuators) Required To Perform Safety Injection Function YesInterconnecting Valve (Actuators) Required To Perform Recirculating Function YesInterconnecting Valve (Actuators) Required To Perform Spray and Spray Test Function YesInterconnecting Valve (Actuators) Required To Perform Letdown, Charging and Supply of SIRW Tank Functions NoInterconnecting Valve (Actuators) Required To Perform Boric Acid Storage and Supply Function NoInterconnecting Valves (Actuators) Required To Perform Demineralizer Function NoAuxiliary Pressurizer Spray Valve Actuators NoInterconnecting Valve (Actuators) Required To Perform Residual Heat Removal Function (Shutdown Cooling)

YesInterconnecting Valve (Actuators) Required To Perform Quality Groups B and C Components CoolingYes Interconnecting Valve (Actuators) Required To Perform Quality Group C Service Cooling YesInterconnecting Valve (Actuators) Within Main Steam Lines From Secondary Side of the Steam Generators up to and Including the Outermost Containment Isolation Valve YesAtmospheric Dump Valve Actuator NoInterconnecting Valve (Actuators) Within Feedwater Lines Extending From the Secondary Side of the Steam Generators up to and Including the Outermost Containment Isolation Valve Yes FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 7 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.Interconnecting Valve (Actuators) Required To Supply AFW From Condensate Storage Tank to Steam Generators YesInterconnecting Valve (Actuators) Required To Supply Steam From Main Steam System to AFW Turbine-Driven Pump YesInterconnecting Valve (Actuators) That Form an Extension of the Containment Boundary up to and Including the Outermost Containment Isolation Valve for the Containment Purge SystemYesContainment Cooling Dampers Actuators YesInterconnecting Valves (Actuators) of the Reactor Coolant Pressure Boundary That Penetrate the Containment up to and Including the Outermost Containment Isolation Valve YesInterconnecting Valves (Actuators) of Quality Group B, C or D System That Penetrate the Containment From the First Isolation Valve Inside Con- tainment up to and Including the Outermost Containment Isolation Valve Yes FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 8 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.16. Instrument and Control PanelsControl Room Panel (C02) - Primary Process and Reactor YesControl Room Panel (C03) - Containment Isolation and Miscellaneous YesControl Room Panel (C06) - Reactor Protective System YesControl Room Panel (C08) - Service Water and Comp CoolingPartial(c)Control Room Panel (C09) - Turbine Interface Panel NoControl Room Panel (C11) - Radiation and Turbine MonPartial(c)Control Room Panel (C12) - Feedwater, Primary Process, NIPartial(c)Control Room Panel (C13) - DBA, Shutdown and Miscellaneous YesLocal Control Panel (C15) - Rod Drive Controls NoLocal Control Panel (C17) - Charging Pump A Speed Control NoControl Room Panel (C27) -T Power and RPS CalibrationPartial (c)Local Control Panel (C33) - Engineered Safeguards Auxiliary YesLocal Control Panel (C35) - Air Compressor Controls NoLocal Control Panel (C36) - Motor-Driven Fire Pump Control NoLocal Control Panel (C37) - Diesel-Driven Fire Pump Control NoLocal Control Panel (C40) - Radwaste Controls NoLocal Control Panel (C41) - Refueling Disconnect NoLocal Control Panel (C101) - Radwaste System Sample NoLocal Control Panel (C103) - Auxiliary Building Gas Analyzer NoControl Room Panel (C106) - Cooling Tower Controls No FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 9 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.Control Room Panel (C115) - Radwaste Addition Rad Mon NoControl Room Panel (C125) - H&V Controls NoControl Room Panel (C126) - Circulating Water and Iodine RemovalPartialLocal Control Panel (C150) - Auxiliary Shutdown Controls YesLocal Control Panel (C207) - Rad Monitoring Controls (FW Purity)

NoControl Room Panel (C11A ) - Control Room HVAC Yes(c)Local Control Panel (C253) - Plant Process Computer - SOE Node NoLocal Control Panel (C269) - Plant Process Computer - Communication Hub No17. Post-Accident Monitoring Equipment per Regulatory Guide 1.97 (See Appendix 7C)(c)

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTS TABLE 5.4-1Revision 30Page 1 of 1SAFETY-RELATED EQUIPMENT THAT REQUIRES PROTECTION FROMFLOODING DUE TO FAILURES OF NONCLASS 1 SYSTEMSElevation of Description LocationSupporting FloorAuxiliary Feedwater PumpsTurbine Bldg 571'-0"BatteriesAuxiliary Bldg 607'-6"Containment Spray PumpsAuxiliary Bldg 570'-0"Emergency Diesel GeneratorsAuxiliary Bldg 590'-0"480 V Load CentersAuxiliary Bldg 607'-6"480 V Motor Control CentersAuxiliary Bldg 607'-6"Safety Injection PumpsAuxiliary Bldg 570'-0"Service Water PumpsIntake Structure 590'-0"2,400 V SwitchgearAuxiliary Bldg 607'-6"

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-2Revision 30Page 1 of 5STRUCTURES CLASSIFICATION RG 1.29INTREPRETATIONSEISMIC BUILDINGCLASSIFICATIONDESIGN CLASSDESIGN CODECONTAINMENT (SHELL AND BASE Category IClass 1 SLAB)1. ConcreteACI 318-63ACI 301-66

2. LinerASME B&PV Code,Sec III, VIII and IX, 19653. Personnel Air Lock,ACI 318-63Escape Air Lock, andASME, Sec III, 1965 Equipment Hatch4. Pipe, Electrical and HVACACI 318-63 Penetrations*ASME, Sec III, 1965CONTAINMENT INTERIOR Category IClass 1ACI 318-63STRUCTURESAISC 1963AUXILIARY BUILDING (Excluding Category IClass 1ACI 318-63Admin and Access Control Areas)AISC 1963*Steam Generator Blowdown and Recirc Penetration End Plates are ASME Section III, Subsection NC, 1986 Ed.

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-2Revision 30 Page 2 of 5STRUCTURES CLASSIFICATION RG 1.29INTREPRETATIONSEISMIC BUILDINGCLASSIFICATIONDESIGN CLASSDESIGN CODE(a) UBC-64 was utilized for seismic and wind loading design. In addition, International Building Code 2006 and ASCE 7-05were utilized for seismic and wind parameters for tower E-30A.(b) Usually this applies to the basin and not the tower framing above the basin, if the basin is a backup source of water forsafety functions.(c) The definition of Class 1E electrical equipment is provided in Subsection 8.1.1.(d) Information not located.(e) Year unknown.(f) Pultruded structure for tower E-30A was designed in accordance with Cooling Tower Institute Standard Specification 137.1972 AUXILIARY BUILDING Category IClass 1ACI 318-63RADWASTE ADDITIONAISC 19691983 AUXILIARY BUILDING (d)Class 1ACI 318-77TSC/EER/HVAC/ADDITIONAISC 1978COOLING TOWERSCategory I(b)Class 3(a)(d)(f)COOLING TOWER PUMP HOUSE Category IClass 3(a)ACI 318-71 AISC 1969 DISCHARGE STRUCTURE Category IClass 3(a)UBC(e)FEEDWATER PURITY BUILDINGNoncategory IClass 3(a)UBC(e)

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-2Revision 30 Page 3 of 5STRUCTURES CLASSIFICATION RG 1.29INTREPRETATIONSEISMIC BUILDINGCLASSIFICATIONDESIGN CLASSDESIGN CODE(a) UBC-64 was utilized for seismic and wind loading design. In addition, International Building Code 2006 and ASCE 7-05were utilized for seismic and wind parameters for tower E-30A.(b) Usually this applies to the basin and not the tower framing above the basin, if the basin is a backup source of water forsafety functions.(c) The definition of Class 1E electrical equipment is provided in Subsection 8.1.1.(d) Information not located.(e) Year unknown.(f) Pultruded structure for tower E-30A was designed in accordance with Cooling Tower Institute Standard Specification 137.INTAKE STRUCTURE (Except as Noted)Noncategory IClass 3UBC(e)1. Portion Above Elevation 590 Category IClass 1ACI 318-63 Housing Service Water Pumps,AISC 1963 Fire Pumps/Drivers and Electrical Support2. Triangular Portion Below Category IClass 1ACI 318-63 Elevation 590 Adjacent to theAISC 1963 Intersection of Column Rows Y and 5 SERVICE BUILDINGNoncategory IClass 3(a)UBC(e)SUPPORTS FOR CLASS 1 MECHANI-Category IClass 1AISC 1969CAL EQUIPMENT AND CLASS 1EELECTRICAL EQUIPMENT(c)

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-2Revision 30 Page 4 of 5STRUCTURES CLASSIFICATION RG 1.29INTREPRETATIONSEISMIC BUILDINGCLASSIFICATIONDESIGN CLASSDESIGN CODE(a) UBC-64 was utilized for seismic and wind loading design. In addition, International Building Code 2006 and ASCE 7-05were utilized for seismic and wind parameters for tower E-30A.(b) Usually this applies to the basin and not the tower framing above the basin, if the basin is a backup source of water forsafety functions.(c) The definition of Class 1E electrical equipment is provided in Subsection 8.1.1.(d) Information not located.(e) Year unknown.(f) Pultruded structure for tower E-30A was designed in accordance with Cooling Tower Institute Standard Specification 137.TURBINE BUILDING (Except as Noted)Noncategory IClass 3(a)ACI 318-63AISC 19631. Auxiliary Feedwater Pump Category IClass 1ACI 318-63 RoomAISC 19632. Electrical Penetration Category IClass 1ACI 318-63 EnclosureCONDENSATE STORAGE TANK Category IClass 1ACI 318-63 FOUNDATION PRIMARY SYSTEM MAKEUP TANK Category IClass 1ACI 318-63FOUNDATION (T-90)

SIRW TANK FOUNDATION Category IClass 1ACI 318-63 FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-2Revision 30 Page 5 of 5STRUCTURES CLASSIFICATION RG 1.29INTREPRETATIONSEISMIC BUILDINGCLASSIFICATIONDESIGN CLASSDESIGN CODE(a) UBC-64 was utilized for seismic and wind loading design. In addition, International Building Code 2006 and ASCE 7-05were utilized for seismic and wind parameters for tower E-30A.(b) Usually this applies to the basin and not the tower framing above the basin, if the basin is a backup source of water forsafety functions.(c) The definition of Class 1E electrical equipment is provided in Subsection 8.1.1.(d) Information not located.(e) Year unknown.(f) Pultruded structure for tower E-30A was designed in accordance with Cooling Tower Institute Standard Specification 137.UTILITY WATER TANK FOUNDATION Category IClass 1ACI 318-63(T-91)

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 1 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.1. Reactor Protective System Channels InputsNuclear Instrumentation Power Range Safety YesPrimary Coolant Flow YesPressurizer Pressure YesPrimary Coolant Temperatures YesSteam Generator Level YesSteam Generator Pressure Yes2. Reactor Protective System Control Devices (Including CRDM Clutches and ManualActivation) (Does Not Include Clutch Power Supplies)

Yes3. Engineered Safeguards Controls Channels InputsPressurizer Pressure YesContainment Pressure YesContainment Radiation YesRefueling Radiation NoSIRW Tank Level Yes FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 2 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.4. Engineered Safeguards Control Devices (for Activation of)HPSI Pumps YesLPSI Pumps YesContainment Spray Pumps YesCharging Pumps NoLetdown Control Valves YesValve Between Auxiliary Spray Line and Charging YesValve Between the Charging Pumps and the HPSI System YesMotor Operated Valves in the SI System YesValves for Safety Injection Recirculation YesContainment Isolation Valves YesComponent Cooling Water Pumps YesComponent Cooling Water Valves YesService Water Pumps YesService Water Valves YesContainment Recirculation Air Cooler FansMix (e)Emergency Generators Yes FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 3 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.5. Engineered Safeguards Controls InstrumentationHPSI Flow to Primary Coolant System YesSafety Injection Tank Level (Passive Injection)

NoSafety Injection Tank Pressure (Passive Injection)

NoService Water Break Detectors (in Containment)

No6. Safe Shutdown and Auxiliary Feedwater Instruments Yes7. Safe Shutdown and Auxiliary Feedwater Control Devices (Activating Circuits)Power Operated Relief Valves YesShutdown Cooling Isolation Valves YesTurbine-Driven Auxiliary Feedwater Pump YesMotor-Driven Auxiliary Feedwater Pumps YesPressurizer Heaters NoAtmospheric Dump Valves NoAFW Control Valves Yes8. AFW Automatic Initiation, Isolation and FOGG Control Devices (Including AFWPumps Suction Pressure)

Yes FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 4 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.9. Primary Coolant Overpressurization Control DevicesPressurizer Pressure Channels YesPCS Overpressurization Protection Devices YesShutdown Cooling Isolation Valves Controls Yes10. Reactor Vessel Gas Vent Isolation Valves Controls Yes11. Engineered Safeguards Pump Rooms and Radwaste Area Radiation Monitors No12. Control Room Ventilation, Instrumentation and Controls (See Table 9-14)

Yes(c)

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 5 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.13. Other Safety-Related Display SystemsSubcooled Margin Monitor YesContainment Pressure YesContainment Water Level YesContainment Temperature NoWide-Range Steam Generator Level YesContainment Hydrogen Monitor NoHigh-Range Containment Gamma Radiation Monitor YesReactor Vessel Level Monitoring System YesCore Exit Thermocouples (16 of 43)

Yes14. Local Instrumentation (Refer to Plant Safety Classification (Q-List) for Details)Transmitters (Inputs to Reactor Protective System)Mix(d)Level, Pressure, etc, Switches (Inputs to Reactor Protective System)Mix(d)Transmitters (Inputs to Engineered Safeguards and Containment Isolation)Mix(d)Level, Pressure, etc, Switches (Inputs to Engineered Safeguards and CI)Mix(d)Transmitters (Inputs to Reactor Shutdown and Decay Heat Removal)Mix(d)Level, Pressure, etc, Switches (Inputs to Reactor Shutdown and DHR)Mix(d)

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 6 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.15. Valve ActuatorsPrimary Coolant Power Operated Relief Valves Actuators YesPrimary Coolant PORV Block Valves Actuators YesInterconnecting Valve (Actuators) Required To Perform Safety Injection Function YesInterconnecting Valve (Actuators) Required To Perform Recirculating Function YesInterconnecting Valve (Actuators) Required To Perform Spray and Spray Test Function YesInterconnecting Valve (Actuators) Required To Perform Letdown, Charging and Supply of SIRW Tank Functions NoInterconnecting Valve (Actuators) Required To Perform Boric Acid Storage and Supply Function NoInterconnecting Valves (Actuators) Required To Perform Demineralizer Function NoAuxiliary Pressurizer Spray Valve Actuators NoInterconnecting Valve (Actuators) Required To Perform Residual Heat Removal Function (Shutdown Cooling)

YesInterconnecting Valve (Actuators) Required To Perform Quality Groups B and C Components CoolingYes Interconnecting Valve (Actuators) Required To Perform Quality Group C Service Cooling YesInterconnecting Valve (Actuators) Within Main Steam Lines From Secondary Side of the Steam Generators up to and Including the Outermost Containment Isolation Valve YesAtmospheric Dump Valve Actuator NoInterconnecting Valve (Actuators) Within Feedwater Lines Extending From the Secondary Side of the Steam Generators up to and Including the Outermost Containment Isolation Valve Yes FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 7 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.Interconnecting Valve (Actuators) Required To Supply AFW From Condensate Storage Tank to Steam Generators YesInterconnecting Valve (Actuators) Required To Supply Steam From Main Steam System to AFW Turbine-Driven Pump YesInterconnecting Valve (Actuators) That Form an Extension of the Containment Boundary up to and Including the Outermost Containment Isolation Valve for the Containment Purge SystemYesContainment Cooling Dampers Actuators YesInterconnecting Valves (Actuators) of the Reactor Coolant Pressure Boundary That Penetrate the Containment up to and Including the Outermost Containment Isolation Valve YesInterconnecting Valves (Actuators) of Quality Group B, C or D System That Penetrate the Containment From the First Isolation Valve Inside Con- tainment up to and Including the Outermost Containment Isolation Valve Yes FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 8 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.16. Instrument and Control PanelsControl Room Panel (C02) - Primary Process and Reactor YesControl Room Panel (C03) - Containment Isolation and Miscellaneous YesControl Room Panel (C06) - Reactor Protective System YesControl Room Panel (C08) - Service Water and Comp CoolingPartial(c)Control Room Panel (C09) - Turbine Interface Panel NoControl Room Panel (C11) - Radiation and Turbine MonPartial(c)Control Room Panel (C12) - Feedwater, Primary Process, NIPartial(c)Control Room Panel (C13) - DBA, Shutdown and Miscellaneous YesLocal Control Panel (C15) - Rod Drive Controls NoLocal Control Panel (C17) - Charging Pump A Speed Control NoControl Room Panel (C27) -T Power and RPS CalibrationPartial (c)Local Control Panel (C33) - Engineered Safeguards Auxiliary YesLocal Control Panel (C35) - Air Compressor Controls NoLocal Control Panel (C36) - Motor-Driven Fire Pump Control NoLocal Control Panel (C37) - Diesel-Driven Fire Pump Control NoLocal Control Panel (C40) - Radwaste Controls NoLocal Control Panel (C41) - Refueling Disconnect NoLocal Control Panel (C101) - Radwaste System Sample NoLocal Control Panel (C103) - Auxiliary Building Gas Analyzer NoControl Room Panel (C106) - Cooling Tower Controls No FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTSTABLE 5.2-5Revision 30Page 9 of 9INSTRUMENTATION AND CONTROL/COMPONENT CLASSIFICATION(a)

Safety Class 1E(b)(a) Safety Class 1E components are Seismic Category I per Regulatory Guide 1.29.(b) Refer to Chapter 8 definition.(c) These components have a mix of Class 1E and Nonclass 1E circuits per Plant safety classification (Q-List).(d) These components may or may not be Class 1E according to the Plant safety classification (Q-List).(e) Instrumentation and controls on containment cooling fans V-1A, V-2A, V-3A, and V-4A are safety class 1E. Certaininstrumentation and controls on containment cooling fans V-1B, V-2B, V-3B, and V-4B are safety class 1E.Control Room Panel (C115) - Radwaste Addition Rad Mon NoControl Room Panel (C125) - H&V Controls NoControl Room Panel (C126) - Circulating Water and Iodine RemovalPartialLocal Control Panel (C150) - Auxiliary Shutdown Controls YesLocal Control Panel (C207) - Rad Monitoring Controls (FW Purity)

NoControl Room Panel (C11A ) - Control Room HVAC Yes(c)Local Control Panel (C253) - Plant Process Computer - SOE Node NoLocal Control Panel (C269) - Plant Process Computer - Communication Hub No17. Post-Accident Monitoring Equipment per Regulatory Guide 1.97 (See Appendix 7C)(c)

FSAR CHAPTER 5 - DESIGN OF STRUCTURES, SYSTEMS AND COMPONENTS TABLE 5.4-1Revision 30Page 1 of 1SAFETY-RELATED EQUIPMENT THAT REQUIRES PROTECTION FROMFLOODING DUE TO FAILURES OF NONCLASS 1 SYSTEMSElevation of Description LocationSupporting FloorAuxiliary Feedwater PumpsTurbine Bldg 571'-0"BatteriesAuxiliary Bldg 607'-6"Containment Spray PumpsAuxiliary Bldg 570'-0"Emergency Diesel GeneratorsAuxiliary Bldg 590'-0"480 V Load CentersAuxiliary Bldg 607'-6"480 V Motor Control CentersAuxiliary Bldg 607'-6"Safety Injection PumpsAuxiliary Bldg 570'-0"Service Water PumpsIntake Structure 590'-0"2,400 V SwitchgearAuxiliary Bldg 607'-6"