Other: 0CAN011601, Notification of Full Compliance with NRC Order EA-12-049 Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Bdbees), 0CAN021302, Units 1 and 2 - Overall Integrated Plan in Response to March 12, 2012, Commission Order to Modify Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Order Number EA-12-049), 0CAN021405, Second Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Order EA-12-049), 0CAN021502, Fourth Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying License with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Bdbees), 0CAN021503, Fourth Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying Licenses with Regard to Reliable Spent Fuel Pool (SFP) Instrumentation (Order Number EA-12-051), 0CAN081402, Third Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Bdbees), ML13063A015, ML13241A414, ML13241A415, ML14045A156, ML14140A514, ML15016A433, ML15054A320, ML15236A340
|
MONTHYEAR0CAN021302, Units 1 and 2 - Overall Integrated Plan in Response to March 12, 2012, Commission Order to Modify Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Order Number EA-12-049)2013-02-28028 February 2013 Units 1 and 2 - Overall Integrated Plan in Response to March 12, 2012, Commission Order to Modify Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Order Number EA-12-049) Project stage: Other ML13063A0152013-02-28028 February 2013 Overall Integrated Plan in Response to March 12, 2012, Commission Order Modifying License with Regard to Reliable Spent Fuel Pool Instrumentation (Order No. EA-12-051) Project stage: Other ML13127A2352013-05-0707 May 2013 Request for Additional Information Email Overall Integrated Plan in Response to the Commission Order Modifying Licenses Project stage: RAI ML13156A3132013-06-26026 June 2013 Request for Additional Information, Overall Integrated Plan in Response to 3/12/12 Commission Order Modifying Licenses with Regard to Reliable Spent Fuel Pool Instrumentation (Order EA-12-051) Project stage: RAI 0CAN071301, Response to Request for Additional Information for Overall Integrated Plan in Response to the Commission Order Modifying Licenses with Regard to Requirements for Reliable Spent Fuel Pool Instrumentation2013-07-25025 July 2013 Response to Request for Additional Information for Overall Integrated Plan in Response to the Commission Order Modifying Licenses with Regard to Requirements for Reliable Spent Fuel Pool Instrumentation Project stage: Response to RAI ML13241A4142013-08-28028 August 2013 First Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Order Number EA-12-049) Project stage: Other ML13241A4152013-08-28028 August 2013 First Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying Licenses with Regard to Reliable Spent Fuel Pool Instrumentation (Order Number EA-12-051) Project stage: Other ML13281A5022013-10-29029 October 2013 Interim Staff Evaluation and Request for Additional Information Regarding the Overall Integrated Plan for Implementation of Order EA-12-051, Reliable Spent Fuel Pool Instrumentation Project stage: RAI ML14045A1562014-02-20020 February 2014 Mega-Tech Services, LLC Technical Evaluation Report Regarding the Overall Integrated Plan for Arkansas Nuclear One, Units 1 and 2, TAC Nos.: MF0942 and MF0943 Project stage: Other ML14007A4592014-02-25025 February 2014 Interim Staff Evaluation Relating to Overall Integrated Plan in Response to Order EA-12-049 (Mitigation Strategies) Project stage: Acceptance Review 0CAN021405, Second Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Order EA-12-049)2014-02-27027 February 2014 Second Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Order EA-12-049) Project stage: Other 1CAN041401, Request for Implementation Date Relief in Response to March 12, 2012,Commission Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Bdbees)2014-04-0808 April 2014 Request for Implementation Date Relief in Response to March 12, 2012,Commission Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Bdbees) Project stage: Request ML14114A6972014-05-20020 May 2014 Relaxation of the Schedule Requirements for Order EA-12-049 Issuance of Order to Modify Licenses with Regard to Requirements for Mitigation Strategies for Beyond Design Basis External Events Project stage: Approval ML14140A5142014-05-28028 May 2014 Update Regarding Audit Activities Associated with Order EA-12-049 (Mitigation Strategies) Project stage: Other 0CAN081402, Third Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Bdbees)2014-08-28028 August 2014 Third Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Bdbees) Project stage: Other ML15016A4332015-01-16016 January 2015 Commitment Change Notification for NRC Order EA-12-049 Project stage: Other 0CAN021503, Fourth Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying Licenses with Regard to Reliable Spent Fuel Pool (SFP) Instrumentation (Order Number EA-12-051)2015-02-24024 February 2015 Fourth Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying Licenses with Regard to Reliable Spent Fuel Pool (SFP) Instrumentation (Order Number EA-12-051) Project stage: Other 0CAN021502, Fourth Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying License with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Bdbees)2015-02-24024 February 2015 Fourth Six-Month Status Report in Response to March 12, 2012, Commission Order Modifying License with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Bdbees) Project stage: Other ML15054A3202015-03-0909 March 2015 Plan for the Onsite Audit Regarding Implementation of Mitigating Strategies and Reliable Spent Fuel Pool Instrumentation Related to Orders EA-12-049 and EA-12-051 Project stage: Other ML15236A3402015-09-0101 September 2015 Report for the Audit Regarding Implementation of Mitigating Strategies and Reliable Spent Fuel Pool Instrumentation Related to Orders EA-12-049 and EA-12-051 Project stage: Other 0CAN011601, Notification of Full Compliance with NRC Order EA-12-049 Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Bdbees)2016-01-12012 January 2016 Notification of Full Compliance with NRC Order EA-12-049 Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis External Events (Bdbees) Project stage: Other 2014-02-27
[Table View] |
|
---|
Category:Letter
MONTHYEARML24295A1202024-10-21021 October 2024 Relief Request ANO2-RR-24-001, Half-Nozzle Repair of Reactor Vessel Closure Head Penetration 71 ML24185A2602024-10-0404 October 2024 Issuance of Amendment No. 335 to Revise Typographical Errors in Technical Specifications IR 05000368/20253012024-09-0909 September 2024 Notification of NRC Initial Operator Licensing Examination 05000368/2025301 ML24255A8642024-09-0606 September 2024 Rscc Wire & Cable LLC Dba Marmon Industrial Energy & Infrastructure - Part 21 Retraction of Final Notification IR 05000313/20240112024-09-0505 September 2024 Comprehensive Engineering Team Inspection Report 05000313/2024011 and 05000368/2024011 ML24239A3972024-08-23023 August 2024 Rssc Wire & Cable LLC Dba Marmon - Part 21 Final Notification - 57243-EN 57243 IR 05000313/20240052024-08-21021 August 2024 Updated Inspection Plan for Arkansas Nuclear One – Units 1 and 2 (Report 05000313/2024005, 05000368/2024005) ML24198A0722024-08-21021 August 2024 Correction to Issuance of Amendment No. 333 Revision to Technical Specifications to Adopt TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 4b ML24220A2642024-08-20020 August 2024 Entergy Operations, Inc. - Entergy Fleet Project Manager Assignment ML24185A1522024-08-13013 August 2024 Issuance of Amendment Nos. 334, 235, and 215, Respectively, to Revise TSs to Adopt TSTF-205 IR 05000313/20240022024-08-0606 August 2024 Integrated Inspection Report 05000313/2024002 and 05000368/2024002 ML24208A0962024-07-25025 July 2024 57243-EN 57243 - Rssc Wire & Cable LLC, Dba Marmon - Part 21 Notification 05000313/LER-2024-001, Source Range Nuclear Instrument Failure Resulting in Condition Prohibited by Technical Specifications2024-07-0101 July 2024 Source Range Nuclear Instrument Failure Resulting in Condition Prohibited by Technical Specifications ML24101A1792024-06-25025 June 2024 Issuance of Amendment No. 333 Revision to Technical Specifications to Adopt TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 4b ML24143A0632024-05-22022 May 2024 Notification of Inspection (NRC Inspection Report 05000368/2024003) and Request for Information IR 05000313/20240012024-05-0808 May 2024 Integrated Inspection Report 05000313/2024001 and 05000368/2024001 ML24128A2472024-05-0808 May 2024 Project Manager Assignment ML24017A2982024-04-18018 April 2024 Summary of Regulatory Audit Regarding the License Amendment Request to Revise Technical Specifications to Adopt TSTF 505, Revision 2, Provide Risk-Informed Extended Completion Times RITSTF Initiative 4b ML24107A0282024-04-17017 April 2024 Notification of Comprehensive Engineering Team Inspection (05000313/2024011 and 05000368/2024011) and Request for Information ML24086A5412024-04-10010 April 2024 Authorization of Request for Alternative ANO1-ISI-037 Regarding Extension of Reactor Vessel Inservice Inspection Interval IR 05000313/20244022024-04-0808 April 2024 Security Baseline Inspection Report 05000313/2024402 and 05000368/2024402 (Full Report) IR 05000313/20244042024-04-0808 April 2024 Information Request for the Cybersecurity Baseline Inspection, Notification to Perform Inspection (05000313/2024404 and 05000368/2024404) ML24089A2262024-03-29029 March 2024 Entergy Response to Regulatory Issue Summary 2024-01, Preparation and Scheduling of Operator Licensing Exams ML24075A1712024-03-15015 March 2024 Nuclear Onsite Property Damage Insurance (10 CFR 50.54(w)(3)) ML24031A6442024-03-14014 March 2024 Issuance of Amendment No. 282 to Modify Technical Specification 3.3.1, Reactor Pressure System (RPS) Instrumentation, Turbine Trip Function on Low Control Oil Pressure ML24074A2892024-03-14014 March 2024 Proof of Financial Protection (10 CFR 140.15) ML24102A1342024-03-12012 March 2024 AN1-2024-03 Post Exam Submittal IR 05000313/20230062024-02-28028 February 2024 Annual Assessment Letter for Arkansas Nuclear One- Units 1 and 2 Report 05000313/2023006 and 05000368/2023006 IR 05000313/20230042024-02-0808 February 2024 Integrated Inspection Report 05000313/2023004 and 05000368/2023004 and Independent Spent Fuel Storage Installation Inspection Report 07200013/2023002 ML24012A0502024-02-0202 February 2024 Exemption from Select Requirements of 10 CFR Part 73 (EPID L-2023-LLE-0054 (Security Notifications, Reports, and Recordkeeping and Suspicious Activity Reporting)) ML23326A0392024-01-24024 January 2024 Issuance of Amendment No. 281 Revision to Technical Specifications to Adopt TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative 4b ML24017A1582024-01-17017 January 2024 Submittal of Emergency Plan Revision 50 IR 05000313/20234202024-01-10010 January 2024 Security Baseline Inspection Report 05000313/2023420 and 05000368/2023420 IR 05000313/20234022024-01-0202 January 2024 Security Baseline Inspection Report 05000313/2023402 and 05000368/2023402 ML23354A0022023-12-21021 December 2023 Request for Withholding Information from Public Disclosure ML23349A1672023-12-21021 December 2023 Request for Withholding Information from Public Disclosure ML23348A3572023-12-14014 December 2023 Application to Revise Technical Specifications to Use Online Monitoring Methodology – Slides and Affidavit for Pre-Submittal Meeting ML23352A0292023-12-13013 December 2023 Entergy - 2024 Nuclear Energy Liability Evidence of Financial Protection ML23340A1592023-12-13013 December 2023 Entergy Operations, Inc. - Entergy Fleet Project Manager Assignment IR 05000313/20234052023-12-12012 December 2023 – Security Baseline Inspection Report 05000313/2023405 and 05000368/2023405 ML23341A0832023-12-11011 December 2023 – Material Control and Accounting Program Inspection Report 05000313/368/2023404- Cover Letter ML23305A0922023-12-0707 December 2023 – Summary of Regulatory Audit Regarding License Amendment Request to Revise Technical Specifications to Adopt TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times RITSTF Initiative 4b ML23333A1362023-11-29029 November 2023 Supplement to Request for Exemption from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation ML23275A2072023-11-28028 November 2023 Issuance of Amendment No. 280 Removal of Technical Specification Condition Allowing Two Reactor Coolant Pump Operation ML23325A1412023-11-21021 November 2023 Request for Exemption from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation IR 05000313/20230032023-11-21021 November 2023 Revised - ANO Revised Integrated Inspection Report 05000313/2023003 and 05000368/2023003 and Independent Spent Fuel Storage Installation Inspection Report 07200013/ 2023001 ML23324A0172023-11-16016 November 2023 Submittal of Amendment 31 to Safety Analysis Report ML23313A0962023-11-13013 November 2023 Integrated Inspection Report 05000313/2023003 and 05000368/2023003 and Independent Spent Fuel Storage Installation Inspection Report 07200013/2023001 ML23243B0452023-11-13013 November 2023 Request for Withholding Information from Public Disclosure ML23311A2082023-11-0909 November 2023 Reassignment of U.S. Nuclear Regulatory Commission Branch Chief in the Division of Operating Reactor Licensing for Plant Licensing Branch IV 2024-09-09
[Table view] |
Text
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 May 28, 2014 Vice President, Operations Arkansas Nuclear One Entergy Operations, Inc.
1448 S.R. 333 Russellville, AR 72802
SUBJECT:
ARKANSAS NUCLEAR ONE, UNITS 1 AND 2- UPDATE REGARDING AUDIT ACTIVITIES ASSOCIATED WITH ORDER EA-12-049 (MITIGATION STRATEGIES) (TAG NOS. MF0942 AND MF0943)
Dear Sir or Madam:
By letter dated March 12, 2012 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML12054A735), the U.S. Nuclear Regulatory Commission (NRC) ordered Entergy Operations, Inc. (Entergy, the licensee) to take certain actions at Arkansas Nuclear One, Units 1 (AN0-1) and 2 (AN0-2), associated with the Fukushima Near-Term Task Force Recommendations. Order EA-12-049 directed that actions be taken by licensees to develop and implement strategies to maintain or restore core cooling, reactor coolant system (RCS) inventory, containment cooling, and spent fuel pool cooling capabilities during beyond-design-basis external events (BDBEE).
By letter dated February 28, 2013 (ADAMS Accession No. ML13063A151), Entergy submitted an Overall Integrated Plan (OIP) for AN0-1 and AN0-2, in response to Order EA-12-049. By letters dated August 28, 2013 and February 27, 2014 (ADAMS Accession Nos. ML13241A414 and ML14059A229), Entergy submitted six-month updates to the OIP. By letter dated April 8, 2014 (ADAMS Accession No. ML14098A114), Entergy requested relief for implementing the requirements of Order EA-12-049 at AN0-1, based on modification schedules at AN0-2, to support the planned mitigation strategies for both units. The NRC staff approved the requested relief by letter dated May 20, 2014 (ADAMS Accession No. ML14114A697). The relief extends the AN0-1 full implementation date for a period of approximately eight months beyond the original required compliance date.
By letter dated February 25, 2014 (ADAMS Accession No. ML14098A114), the NRC staff issued an interim staff evaluation (ISE) for the OIP submitted by Entergy for AN0-1 and AN0-2.
The proposed Diverse and Flexible Mitigation Capability (FLEX) strategy for AN0-1 and AN0-2 includes the deployment of a portable diesel generator (FLEX DG) that will be connected to the existing plant electrical distribution system for each unit. This will allow the energizing of selected loads in the distribution system to implement the FLEX strategy, such as critical instrumentation and battery chargers. The FLEX DG will also power the AN0-2 charging pumps to provide RCS makeup for both units. The proposed use of the plant installed AN0-2 charging pumps for RCS makeup during the transition phase of the BDBEE, as opposed to portable equipment, is considered an alternative to the NRC-endorsed guidance in the Nuclear Energy Institute (NEI) document, NEI 12-06, Rev. 0, "Diverse and Flexible Coping Strategies (FLEX) Implementation Guide" dated August 21, 2012 (ADAMS Accession No. ML12242A378).
The ISE identified Open Item 3.2.1.0 regarding the RCS makeup strategy described in the licensee's first six-month update, and during the audit process, as follows:
The NRC staff has reviewed the ANO approach that uses the Unit 2 charging pump to supply makeup to the Unit 1 RCS for inventory control but has not concluded that this approach is acceptable. The staff has identified a number of concerns that need to be addressed regarding the proposed RCS inventory control strategy. Therefore, this open item tracks completion of the development of an acceptable integrated RCS makeup strategy that meets the requirements of Order EA-12-049.
The following concerns were noted in the ISE: (1) reliability of the strategy, considering operational human factors implications when using installed plant equipment and operators from one unit to respond to events at the other, or both, unit(s), (2) the feasibility and flexibility of the makeup strategy, should one unit enter an extended loss of all alternating current (ac) power (ELAP) conditions at a time offset from the other unit, (3) licensing implications of the proposed strategy for a potential circumstance where AN0-1 is in an ELAP condition and AN0-2 is not, and (4) with respect to using installed charging pumps as a proposed alternative to NEI 12-06, whether the approach provides an equivalent level of flexibility for responding to an undefined event as would be provided through conformance with NEI 12-06.
The NRC staff has considered additional information in the course of the ANO mitigating strategies audit process with regard to the concerns listed above associated with Open Item 3.2.1.0 as described below:
(1) Reliability of the strategy, considering operational human factors implications when using installed plant equipment and operators from one unit to respond to events at the other, or both, unit(s).
The licensee is installing direct connections for the FLEX DG to two separate, diverse safety related electrical switchgear, as well as a new piping cross-tie and piping tie-ins, to facilitate RCS makeup to AN0-1 from the AN0-2 charging pumps. The proposed alternate strategy relies only on the deployment of the FLEX DG and the alignment of cross-connects and cross-ties to provide RCS makeup to either or both units, as required, during a BDBEE. The pre-installed electrical connections and piping cross-ties simplify the operator actions required to initiate RCS makeup as compared to the actions associated with the installation of a large portable pump and more extensive temporary cables and piping/hoses. Therefore, the proposed alternate strategy reduces the number and complexity of operator actions to establish RCS makeup during a BDBEE.
The AN0-1 and AN0-2 control rooms are located adjacent to each other. During the audit process, after the issuance of the ISE, the NRC staff travelled to the ANO site and was able to observe the control room layout and communications to verify that the licensee's assertions regarding inter-unit communications appear to be feasible. According to the licensee, operators interface regularly with the opposite unit's control room for activities such as operating shared systems and outage activities. In addition, the operator keys for both units are common, allowing the use of keys for one unit to support the other unit for activities such as operating
locked-closed valves to implement the FLEX charging pump strategy. During the audit process the licensee stated that the necessary operator training on the inter-unit strategy would be incorporated into initial and continuing training to assure that the strategy is reliable for as long as the requirements of the order are applicable. In addition, the licensee indicated that the strategy will be guided by written instructions, thus helping to assure a low probability of human performance errors. Therefore, the NRC staff has reasonable assurance that inter-unit coordination, as described in the licensee's mitigation strategies plan, could be reliably accomplished.
(2) The feasibility and flexibility of the makeup strategy, should one unit enter ELAP conditions at a time offset from the other unit:
- The differences in reactor design between AN0-1 and AN0-2 result in the need for RCS makeup early in the BDBEE for AN0-1, but much later for AN0-2. AN0-2 has three charging pumps available for normal makeup to RCS inventory. None of the three charging pumps are credited to respond during design-basis accident conditions and one pump can be unavailable without impacting the normal function of the system per the AN0-2 Technical Requirements Manual (TRM). Early in the BDBEE one AN0-2 charging pump will be dedicated to supply RCS makeup as required to AN0-1 while the remaining 2 charging pumps are available for normal RCS makeup for AN0-2. If both units are simultaneously impacted by the BDBEE, a single charging pump can meet the RCS makeup requirements for both AN0-1 and AN0-2.
Should AN0-2 enter ELAP while AN0-1 is only in a loss of all offsite power, AN0-1 would have the normally designated RCS makeup capacity available for that unit. AN0-2 has sufficient volume in the safety injection tanks to accomplish RCS cooldown without a pump injection source. During the audit process, the licensee provided an operational evaluation that showed that should either unit enter ELAP conditions at a time offset from the other unit, less limiting timing considerations would result, and thus the inter-unit strategy does not introduce a safety concern in those scenarios. The NRC staff reviewed the operational evaluation and concluded that it supports a reasonable assurance determination for the success of the overall strategy.
(3) Licensing implications of the proposed strategy for a potential circumstance where AN0-1 is in an ELAP condition and AN0-2 is not:
During the audit process, the licensee provided further information regarding the AN0-2 charging pumps. These pumps are not Technical Specification (TS) required or controlled equipment and are not credited for design-basis accident mitigation. While they are not TS-required and their flow is not credited, the diesel loading calculations conservatively assume the pumps are running for a design-basis accident. Thus, their potential use across units does not introduce a licensing conflict in a scenario where one unit is in an ELAP and the other is not.
The charging pumps are controlled in the licensee maintained AN0-2 TRM. The AN0-2 TRM requires that at least 2 charging pumps be Functional in Modes 1, 2, 3 and 4, with an allowed unavailability time of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> when only 1 charging pump is Functional. The boric acid makeup tanks, the borated water source for the charging pumps, are also controlled in the TRM and not the TSs, with similar 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> unavailability requirements
associated with a minimum volume. Therefore, designation of a charging pump to provide RCS make-up to AN0-1, with the unit in ELAP while AN0-2 is not, is consistent with the AN0-2 licensing basis.
(4} With respectto using installed charging pumps as a proposed alternative to NEI12-06, whether the approach provides an equivalent level of flexibility for responding to an undefined event as would be provided through conformance with NEI12-06:
Section 3.2.2, Guideline (13) of NEI 12-06 states that, "[r]egardless of installed coping capability, all plants will include the ability to use portable pumps to provide RPV[reactor pressure vessei]/RCS/SG[steam generator] makeup as a means to provide a diverse capability beyond installed equipment." The licensee proposes an alternative to this guidance. The licensee maintains that use of a designated AN0-2 charging pump provides sufficient flexibility in that none of the 3 charging pumps are credited for accident mitigation and modifications will be installed to accommodate a direct power connection to a FLEX DG as well as modifications to cross-connect flow between AN0-1 and AN0-2. In this way, the proposed alternative achieves the flexibility intended in the guidance and complies with the requirements of Order EA-12-049. During a site visit toANO as part of the audit process, the NRC staff was able to observe, in detail, the licensee's proposed layout for the electrical modifications that will support the charging pump strategy. This included a review of the proposed connection locations, building penetration locations, and proposed and existing equipment locations. This review provided the NRC staff with reasonable assurance that the overall strategy has an equivalent level of flexibility for responding to an undefined event as would be provided through conformance with NEt 12-06.
Based on the information resulting from the supplemental and ongoing audit of ANO's implementation of Order EA-12-049, as discussed above and in the ISE, the NRC staff concludes that the licensee has provided sufficient information to determine that there is reasonable assurance that the plan, when properly implemented, will meet the requirements of Order EA-12-049 at AN0-1 and AN0-2. This conclusion is contingent upon the successful completion of the items described in Entergy's letter dated April 8, 2014, regarding the implementation schedule for order compliance at AN0-1. Further review of ISE Open Item 3.2.1.D will continue during the remainder of the audit phase to ensure that the implementation steps continue to be developed consistent with the NRC's current understanding of the mitigating strategies plan for AN0-1 and AN0-2. If you have any questions, please contact John Hughey, Mitigating Strategies Project Manager, at 301-415-3204, or at john.hughey@nrc.gov.
Jeremy S. Bowen, Chief Mitigating Strategies Projects Branch Mitigating Strategies Directorate Office of Nuclear Reactor Regulation Docket Nos. 50-313 and 50-368 cc: Distribution via Listserv