5/16/2012 Summary of Meeting with Pacific Gas and Electric Company to Discuss Digital Replacement of Process Protection System at Diablo Canyon Power Plant, Units 1 and 2
ML12151A258
Person / Time
Site: Diablo Canyon  
(DPR-080, DPR-082)
Issue date: 06/11/2012
From: Joseph Sebrosky
Plant Licensing Branch IV
To:
Sebrosky J
References
TAC ME7522, TAC ME7523
Download: ML12151A258 (48)


Text

\\.,,-p.R REG(j~

UNITED STATES

~.:;,"

"'0.,.

~

NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001

~

~

3.'

ca.

r;

~

.f'

~'1 ****'" ~o June 11, 2012 LICENSEE:

Pacific Gas and Electric Company FACILITY:

Diablo Canyon Power Plant, Unit Nos. 1 and 2

SUBJECT:

SUMMARY

OF MAY 16,2012, TELECONFERENCE MEETING WITH PACIFIC GAS AND ELECTRIC COMPANY ON DIGITAL REPLACEMENT OF THE PROCESS PROTECTION SYSTEM PORTION OF THE REACTOR TRIP SYSTEM AND ENGINEERED SAFETY FEATURES ACTUATION SYSTEM AT DIABLO CANYON POWER PLANT (TAC NOS. ME7522 AND ME7523)

On May 16, 2012, a Category 1 teleconference public meeting was held between the U.S. Nuclear Regulatory Commission (NRC) and representatives of Pacific Gas and Electric Company (PG&E, the licensee) at NRC Headquarters, One White Flint North, 11555 Rockville, Maryland. The purpose of the teleconference meeting was to discuss the license amendment request (LAR) submitted by PG&E on October 26, 2011, for the Digital Replacement of the Process Protection System (PPS) Portion of the Reactor Trip System and Engineered Safety Features Actuation System at Diablo Canyon Power Plant, Unit Nos. 1 and 2 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML113070457). A list of attendees is provided in Enclosure 1.

The teleconference meeting is one in a series of publicly noticed teleconference meetings to be held periodically to discuss issues associated with the NRC staff's LAR review. Preliminary issues that the NRC staff identified during the initial review, and the licensee's responses to these preliminary issues, were discussed during the teleconference meeting. The list of preliminary issues is provided in Enclosure 2.

Items 16, 17 and 22 in Enclosure 2 relate to questions associated with the PPS factory acceptance testing (FAT). The licensee provided an updated description of the PPS FAT that is provided in Enclosure 3. The NRC staff indicated that it would review the updated description and provide additional feedback at a later time.

The NRC staff and licensee confirmed that the next meeting on this topic would be held on June 13, 2012. The licensee indicated that some of the Phase 2 documents that it expected to submit by May 30,2012, would be submitted at a later time. A description of the Phase 2 documents is provided in the October 26, 2011, LAR. The October 26, 2011, LAR broke the Phase 2 documents into sets of documents that would be provided earlier in the process and those that would be provided later in the process. In the summary of a public meeting held on January 18, 2012 (ADAMS Accession No. ML120400651), the dates that were provided for the submittal of these Phase 2 documents were May 30.2012, with the remaining Phase 2 documents being supplied by December 2012. The licensee indicated that 17 of the Phase 2 documents would be provided by May 30,2012, and that 41nvensys Operations Management documents would be submitted later than expected because the Tricon design phase for the DCPP PPS replacement is still in progress. In addition, a CS Innovations document and a PPS

- 2 replacement failure mode and effects analysis document would be delayed because of ongoing work in the areas that support these documents. PG&E indicated that the target date for the submittal of these six documents has been moved from May 30,2012, to July 31,2012.

Please direct any inquiries to me at 301-415-1132 or at :;.J~=-:.:..:;,:==~~r;:.ttI!=

J h M. Sebrosky, S ior Projec Manager lant Licensing Branch IV

./

Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-275 and 50-323

Enclosures:

1. List of Attendees
2. Staff identified issues
3. Process Protection System Factory Acceptance Testing cc w/encls: Distribution via Listserv

LIST OF ATTENDEES MAY 16, 2012, TELECONFERENCE MEETING WITH PACIFIC GAS AND ELECTRIC COMPANY REGARDING DIABLO CANYON POWER PLANT DIGITAL UPGRADE DOCKET NOS. 50-273 AND 50-323 NAME Ken Schrader Scott Patterson H. Hodges Bob Lint John Hefler K. Brandt T. Quinn J. Basso W. Odess-Gillet Roman Shaffer Rich Stattel Bill Kemper Rossnyev Alvarado Joe Sebrosky Shiattin Makor Stephanie Achen Gordon Clefton ORGANIZATION Pacific Gas and Electric Pacific Gas and Electric Pacific Gas and Electric Altran Altran Altran Altran Westinghouse Westinghouse Invensysrrriconex U.S. Nuclear Regulatory Commission U.S. Nuclear Regulatory Commission U.S. Nuclear Regulatory Commission U.S. Nuclear Regulatory Commission U.S. Nuclear Regulatory Commission U.S. Nuclear Regulatory Commission Nuclear Energy Institute

May 14, 12 DCPP PPS Open Item Summary Table Page 1 of 39 No Src/RI Issue Description P&GE response:

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments 001 I

I AR (BD)

[ISG-06 Enclosure B, Item 1.3] Deterministic Nature of Software:

The Diablo Canyon Specific Application should identify the board access sequence and provide corresponding analysis associated with digital response time performance. This analysis should be of sufficient detail to enable the NRC staff to determine that the logic-cycle;

a. has been implemented in conformance with the ALS Topical Report design basis,
b. is deterministic, and
c. the response time is derived from plant safety analysis performance requirements and in full consideration of communication errors that have been observed during equipment qualification.

As stated in the LAR, information pertaining to response time performance will be submitted as a Phase 2 document. Please ensure this matter is addressed accordingly.

Open N/A 4/18/2011 - Staff i

reviewed time response calc on share point and agrees that this is the correct information to support the SE.

Requested that these calcs be docketed.

Response

received April 2, 29, 2012. Staff will review and discuss P&GE response:

ALS further if needed at Diablo Canyon PPS document 6116-00011, "ALS System Design Specification", Section 7.5, identifies the ALS board access sequence and subsequent provides an analysis associated with digital response time performance.

telecom meeting.

a. The Diablo Canyon PPS ALS system is configured in accordance with the qualification requirements of the ALS platform topical report,

Response

b. The analysis in Diablo Canyon PPS document 6116-00011, "ALS System acceptable; waiting Design Specification", Section 7, describes a logic cycle that is deterministic.
c. The requirements for the response time of the PPS processing instrumentation (from input conditioner to conditioned output signal) is on PG&E to provide the time specified as not to exceed 0.409 seconds in Section 3.2.1.10 of the "Diablo response Canyon Power Plant Units 1 & 2 Process Protection System Replacement calculation for the Functional Requirements Specification (FRS)", Revision 4 submitted as V10 Tricon PPS of the LAR In Section 1.5.8 of the "Diablo Canyon Power Replacement Plant Units 1 & 2 Process Protection System Replacement Interface architecture by Requirements Specification (IRS)", Revision 4, submitted as Attachment 8 of the LAR, the 0.409 seconds PPS processing instrumentation response time April 16, 2012.

is allocated between the ALS and Tricon as follows:

May 14, 12 DCPP PPS Open Item Summary Table Page 2 of 39 P&GE response:

Status RAI No.

RAI Issue Description Comments SrclRI INo I

(Date Sent)

Response

I (Due Date)

ALS: 175 ms for RTO processing Tricon: 200 ms Contingency: 34 ms The 0.409 seconds PPS processing instrumentation value is the same as the value that is currently allocated to PPS processing instrumentation. As long as the 0.409 second PPS processing instrumentation value is not exceeded, the total response time values assumed in the plant safety analyses contained in FSAR Table 15.1-2 will not be exceeded; 7 seconds for Overtemperature AT RT and Overpower AT RT functions, 2 seconds for High I

pressurizer pressure RT, Low pressurizer pressure RT, and Low Low SG water level RT functions, 1 second for Low reactor coolant flow RT function, 25 seconds for Low pressurizer pressure, High containment pressure, and Low steam line pressure Safety Injection initiation, 60 seconds for Low low SG water level auxiliary feedwater initiation, 18 seconds for High containment pressure, Low pressurizer pressure, and Low steam line pressure Phase A containment isolation, 48.5 seconds for High High containment pressure containment spray initiation, 7 seconds for High High containment pressure steam line isolation, 66 seconds for High High SG water level auxiliary feedwater isolation, and 8 seconds for Low steam line pressure steam line isolation.

The ALS response time will be verified as part of the FAT and the results will be I

included in the FAT summary report to be submitted by 12/31/12.

Tricon Invensys provided detailed information on the deterministic operation of the V10 Tricon in Invensys Letter No. NRC V1 0-11-001, dated January 5, 2011.

In support of the V10 Tricon safety evaluation, Invensys submitted document 9600164-731, Maximum Response Time Calculations, describing the worst-case response time for the V1 0 Tricon Qualification System. Included in document 9600164-731 are the standard equations for calculating worst-case response time of a given V10 Tricon configuration. The time response calculation for the V10 Tricon PPS Replacement architecture was submitted on April 30, 2012. The System Response Time Confirmation Report, 993754-1-818, will be submitted to the staff as part of the ISG-06 Phase 2 submittals at the completion of factory acceptance testing of the V10 Tricon Licensee PPS Replacement.

representatives

....- L-__

May 14,12 DCPP PPS Open Item Summary Table Page 3 of 39 Issue Description P&GE response:

Status RAJ No.

RAI No r SrclRI Comments (Date Sent)

Response

(Due Date) i The Tricon response time will be verified as part of the FAT and the results will stated that PG&E be included in the FAT summary report to be submitted by 12/31/12.

will provide the Tricon Time response calc's in a document submitted on the docket.

002 AR

[ISG-06 Enclosure B, Item 1.4]

N/A Open 4/23/2011 - Staff (RA)

Software Management Plan: Regulatory Guide (RG) 1.168, Revision 1, has confirmed that "Verification, Validation, Reviews and Audits for Digital Computer Software the new version of Used in Safety Systems of Nuclear Power Plants," dated February 2004 the AlS SWP is endorses IEEE (Institute of Electrical and Electronics Engineers) 1012-1998, available for review "IEEE Standard for Software Verification and Validation," and IEEE 1028 1997,"IEEE Standard for Software Reviews and Audits," with the exceptions

Response

Istated in the Regulatory Position of RG 1.168. RG 1.168 describes a method received April 2, acceptable to the NRC staff for complying with parts of the NRC's regulations 29,2012. Staff will for promoting high functional reliability and design quality in software used in review and discuss safety systems. Standard Review Plan(SRP) Table 7-1 and Appendix 7.1-A further if needed at identify Regulatory Guide 1.168 as SRP acceptance criteria for reactor trip subsequent systems (RTS) and for engineered safety features telecom meeting.

Westinghouse/AlS 6116-00000 Diablo Canyon PPS Management Plan, (Westinghouse Figure 2-2, shows the Verification and Validation (V&V) organization 4/12/12) Response reporting to the Project Manager. This is inconsistent with the information acceptable; the described in the AlS Management Plan for the generic system platform, staff received the where the V&Vorganization is independent form the Project Manager. This revised W/AlS is also inconsistent with the criteria of RG 1.168 and will need to be PPS MP on April 2, reconciled during the LAR and AlS l TR reviews.

2012 and will review for consistency with P&GE response:

RG 1.168.

AlS

May 14, 12 DCPP PPS Open Item Summary Table Page 4 of 39 No SrclRI Issue Description P&GE response:

The PPS Replacement LAR referenced Westinghouse document 6116 00000 Diablo Canyon PPS Management Plan, dated July 25, 2011, that was based on CSI document 6002-00003 ALS Verification and Validation Plan.

Revision 4. CS Innovations subsequently submitted a revised V&V plan.

"6002-00003 ALS Verification and Validation Plan", Revision 5, on November 11, 2011, that revised the required V&V organization structure such that the management of the verification personnel is separate and independent of the management of the development personnel. The Westinghouse 6116-00000 Diablo Canyon PPS Management Plan was revised to require a V&V organization structure in which the management of the verification personnel is separate and independent of the management of the development personnel. PG&E submitted the revised Westinghouse 6116-00000 Diablo Canyon PPS Management Plan, Revision 1, document on April 2, 2012.

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments 3

AR (RA)

[ISG-06 Enclosure B, Item 1.9]

Software V&V Plan: The ALS V&V plan states that Project Manager of the supplier is responsible for providing directions during implementation of V&V activities. Also, the organization chart in the Diablo Canyon PPS Management Plan shows the IW manager reporting to the PM.

The ALS V&V plan described in ISG-6 matrix for the ALS platform and the Diablo Canyon PPS Management Plan do not provide sufficient information about the activities to be performed during V&V. For example, the ALS V&V Plan states that for project specific systems, V&V activities are determined on a project by project basis and are described in the project Management Plan, in this case, 6116-00000, "Diablo Canyon PPS Management Plan."

However, the 6116-00000 Diablo Canyon PPS Management Plan states:

"See the ALS V&V Plan for more information and the interface between the IV&V team and the PPS Replacement project team."

The Triconex V&V plan states that the Engineering Project Plan defines the scope for V&V activities. As mentioned before, the Triconex EPP is not listed in the I SG-6 matrix.

These items will need further clarification during the LAR review to demonstrate compliance with Regulatory Guide (RG) 1.168, Revision 1, "Verification, Validation, Reviews and Audits for Digital Computer Software Open N/A

Response

received April 2, 29, 2012. Staff will review and discuss further if needed at subsequent telecom meeting.

Status: Fig. 3 of the PPSSWP (Pg.

16/46) indicates sufficient organizational independence between the Nuclear Delivery (Design)

Organization and the IV&V

I May 14,12 DCPP PPS Open Item Summary Table Page 50f39 No SrciR/ I Issue Description P&GE response:

Status RA/ No.

RA/

Comments i

(Date Sent)

Response

(Due Date)

Used in Safety Systems of Nuclear Power Plants,"

P&GE response:

ALS The Westinghouse 6116-00000 Diablo Canyon PPS Management Plan was revised to include details on how the IV&V team has an independent organizational reporting structure from the design and implementation team; the Scottsdale Operations Director and the ALS Platform & Systems Director report to different Westinghouse Vice Presidents. The IW Manager and Scottsdale Operations Director both report to the same Westinghouse Vice President, but via independent reporting structures.

Description of 6116-00000 Diablo Canyon PPS Management Plan V&V was also revised to add information on the activities being performed for the V&V.

PG&E submitted the revised Westinghouse 6116-00000 Diablo Canyon PPS Management Plan that includes the above changes on April 2, 2012.

Organization.

Fig. 3 of the PPS PMP (993754-1 905) (pg. 22/81) also denotes the DCPP PPS project organization, and provides sufficient independence between the NO and IV&V Organizations.

Close the Invensys part of the 01.

Tricon The organizational structure of Invensys Operations Management comprises, in part, Engineering and Nuclear Delivery. Each of these organizations plays a specific role in the V10 Tricon application project life cycle. Invensys Engineering is responsible for designing and maintaining the V10 Tricon platform, and Nuclear Delivery is responsible for working with nuclear customers on safety-related V10 Tricon system integration projects.

Invensys Engineering department procedures require "Engineering Project Plans (EPP)," whereas Nuclear Delivery department procedures require "Project Plans." fnvensys Engineering is not directly involved in system integration, but Nuclear Delivery may consult with Engineering on technical issues related to the V10 Tricon platform.

The NRC applied ISG-06 to the V1 0 Tricon safety evaluation. Invensys submitted a number of documents pertaining to the design of the V1 0 Tricon lplatform as well as process ~n~dJ)rocedure document~ governing Invensys W/ALS response acceptable; (Westinghouse 4/12/12) the staff received the revised W/ALS PPS MP on April 2, 2012 and will review for consistency with RG 1.168.

I

May 14, 12 ocpp PPS Open Item Summary Table Page 6 of 39 No SrclR/

Issue Description P&GE response:

Status RAJ No.

RA/

Comments (Date Sent)

Response

(Due Date)

Status: Fig. 3 of the related documents are preceded with document number 9600164. The Engineering activities, including the EPP. In most cases, these platform-PPS SWP (Pg.

platform-level documents reviewed by the staff during the V1 0 Tricon safety 16/46) indicates evaluation will not be resubmitted by Nuclear Delivery during application-sufficient specific system integration projects.

organizational independence In support of the PG&E LAR for the DCPP PPS Replacement, Invensys between the Nuclear Delivery is required to submit the application design documents as Nuclear Delivery defined in ISG-06. These project documents are preceded by document (Design) number 993754. The Phase 1 submittal under Invensys Project Letter Organization and 993754-026T, dated October 26, 2011, contained, in part, the following:

the IV&V PPS Replacement Project Management Plan (PMP), 993754-1-905. "Project Organization.

Management Plan" was used to more closely match BTP 7-14 with regard to "management plans"; and Fig. 3 of the PPS PPS Replacement Software Verification and Validation Plan (SWP),

PMP (993754-1 993754-1-802.

905) (pg. 22/81) also denotes the The PMP describes the PPS Replacement Project management activities DCPP PPS project within the Invensys scope of supply. The guidance documents BTP 7-14 and NUREG/CR-6101 were used as input during development of the PMP.

organization, and provides sufficient I

With regard to compliance with RG 1.168, the PPS Replacement PMP and independence SWP both describe the organizational structure and interfaces of the PPS between the NO Replacement Project. The documents describe the Nuclear Oelivery (NO) and IV&V design team structure and responsibilities, the Nuclear Independent Organizations.

I Verification and Validation (IV&V) team structure and responsibilities, the interfaces between NO and Nuclear IV&V, lines of reporting, and degree of independence between NO and Nuclear IV&V. In addition, the PMP Close the Invensys describes organizational boundaries between Invensys and the other part of the 01.

I external entities involved in the PPS Replacement project: PG&E, Altran, Westinghouse, and Invensys suppliers. The combination of the PMP and SWP demonstrate compliance of the Invensys organization with RG 1.168.

I

May 14, 12 DCPP PPS Open Item Summary Table Page 7 of 39 No 4

I I SrciR/

AR (RA)

Issue Description P&GE response:

IISG-06 Enclosure B, Item 1.10]

Software Configuration Management Plan: The LAR includes PG&E CF2.1D2, "Software Configuration Management for Plant Operations and Operations Support," in Attachment 12. However, the document provided in 2 only provides a guideline for preparing Software Configuration Management (SCM) and SQA plans. Though it is understood that the licensee will not perform development of software, PGE personnel will become responsible for maintaining configuration control over software upon delivery from the vendor.

The staff requires the actual plan to be used by the licensee for maintaining configuration control over PPS software in order to evaluate against the acceptance criteria of the SRP. For example, the ALS Configuration Management (CM) Plan (6002-00002) describes initial design activities related to ALS generic boards. This plan does describe the configuration management activities to be used for the development and application of the ALS platform for the Diablo Canyon PPS System. The staff requires that configuration management for this design be described in the DCPP project specific plan. These items will need further clarification during the LAR review to demonstrate compliance with BTP-14.

Status Open RA/ No.

(Date Sent)

N/A RA/

Response

(Due Date)

Comments (Westinghouse 4 12-12) Response received April 2 29, 2012. Staff will review the PG&E SyCMP procedure when it arrives on May 31,2012.

P&GE response:

PG&E will develop a SyCMP procedure to address configuration control after shipment of equipment from the vendor and will submit the document by May 31,2012.

5 May 14, 12 DCPP PPS Open Item Summary Table Page 8 of 39 No SrcIRl Issue Description P&GE response:

[ISG-06 Enclosure B, Item 1.11]

(RA)

AR Software Test Plan: The V10 platform documents identified in ISG6 matrix state that the interface between the NGIO (Next Generation Input Output)

Core Software and 10-specific software will not be tested. It is not clear when and how this interface will be tested, and why this test is not part of the software unit testing and integration testing activities.

Further, the 993754-1-813 Diablo Canyon Triconex PPS Validation Test Plan states that the DCPP's TSAP will not be loaded on the system; instead Triconex will use another TSAP for the validation test. It is not clear why the DCPP's TSAP will not be used for the validation test or when the DCPP's TSAP will be loaded on the system and validated for the Diablo Canyon PPS System. These items will need further clarification during the LAR review to demonstrate compliance with BTP-14.

P&GE response:

Tricon The next-generation input/output (I/O) modules qualified for the V1 0 Tricon are the 3721 N 4-20 mA, 32-point analog input (AI) module, and the 3625N 24 Vdc, 32-point digital output (~O) module. Technical data on these two modules was provided to the NRC in support of the V10 Tricon safety evaluation. Configuration and functional testing is performed when the I/O modules (hardware and embedded core firmware) are manufactured. From the factory the I/O modules are shipped to Invensys Nuclear Delivery for use in nuclear system integration projects, i.e., application specific configurations.

Because the module hardware and embedded core firmware are within the scope of the V10 Tricon safety evaluation, the verification and validation of the embedded core firmware will not be repeated as part of application-specific system integration projects.

Status Closed RAI No.

(Date Sent)

N/A RAI

Response

(Due Date)

Comments

Response

received April 2, 29,2012. Staff will review and discuss further if needed at subsequent telecom meeting.

Tricon Next Generation Input Output (NGIO)

Core software is tested and qualified as a platform component. As such, it does not need to be separately tested during the application development process.

TSAP is a Test Specimen Application Program used for purposes of platform qualification.

. There are certain design items that must be done with TriStation 1131 (TS1131), such as specifying which 110 module is installed in a particular

May 14, 12 DCPP PPS Open Item Summary Table Page 9 of 39 No SrclRI Issue Description P&GE response:

Status RA No.

(Dale Sent)

RAI I Response (Due Date)

Comments physical slot of the Tricon chassis, resulting in each module having a unique hardware address in the system. Also, TS1131 is used to specify which application program parameters (Le., program variable tagnames) are assigned to a particular point on a given 1/0 module. The design items configured in TS1131 will be within the scope of validation activities conducted by Invensys Nuclear IV&V for application-specific system integration projects. The necessary collateral (system build documents, configuration tables, test procedures, test results, etc.) will be submitted to the NRC to support the staff's technical review of the PPS Replacement LAR in accordance with ISG-06.

The Phase 1 submittal under Invensys Project Letter 993754-026T, dated October 26, 2011, contained, in part, the Validation Test Plan (VTP), 993754 1-813. This document describes the scope, approach, and resources of the testing activities that are required for validation testing of the V1 0 Tricon portion of the PPS Replacement. including:

Preparing for and conducting system integration tests Defining technical inputs to validation planning Defining the test tools and environment necessary for system validation testing Scheduling (and resource loading of the schedule)

Section 1.3.2 of the VTP describes the Hardware Validation Test activities and Section 1.3.3 of the VTP describes the V10 Tricon portion of the Factory Acceptance Test activities for the V10 Tricon portion of the PPS Replacement. Details on the application program are proprietary and need to be provided to the staff separately.

Invensys stated that The Diablo Canyon Application will be loaded onto plant system hardware during FAT.

Staff re-examined Invensys doc.

"Validation Test Plan (VTP),

993754-1-813,"

Section 1.3.2 of the VTP that describes the Hardware Validation Test activities and Section 1.3.3 of the VTP and determined that the application program TSAP will be used for the FAT (Section 5.1.5 FAT)

Close this portion of the 01.

May 14, 12 DCPP PPS Open Item Summary Table Page 10 of 39 No SrclRI Issue Description P&GE response:

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments 6

AR (SM)

[ISG-06 Enclosure 8, Item 1.14]

Equipment Qualification Testing Plans - The LAR Sections 4.6,4.10.2.4 and 4.11.1.2 provide little information on the plant specific application environmental factors. The Tricon V10 Safety Evaluation, ML11298A246, Section 6.2 lists 19 application specific actions Items (ASAl's) that the licensee should address for plant specific applications. The licensee should address each of these for Tricon portion of the PPS replacement. Similar information for the ALS portion of the PPS replacement will also be required.

Closed Develop a generic RAI to provide a response to ASAls for both platforms when the SERs are issued.

Response

received April 2, 29,2012. Staff will review and discuss further if needed at subsequent telecom meeting.

Staff agreed that PG&E should submit a separate P&GE response:

ALS PG&E will respond to ALS ASAI's when they are available.

RAI#XX submittal (LAR amendment) to Tricon address the ASAls for both platforms.

IN PROGRESS. All of the Application Specific Action Items will be it is not necessary addressed by March 21 2012.

to delineate exactly

May 14, 12 No I SrclRI 7

I AR (BK)

DCPP PPS Open Item Summary Table Issue Description IP&GE response:

[ISG-06 Enclosure B, Item 1.16]

Design Analysis Reports: The LAR does not appear to comply with the SRP (ISG-04) regarding the connectivity of the Maintenance Work Station to the PPS. The TriStation V10 platform relies on software to effect the disconnection of the TriStation's capability to modify the safety system software. Based on the information provided in the L TR, the NRC staff determined that the Tricon V10 platform does not comply with the NRC guidance provided in ISG-04, Highly Integrated Control Rooms-Communications Issues, (ADAMS Accession No. ML083310185), Staff Position 1, Point 10, hence the DCPP PPS configuration does not fully comply with this guidance.

In order for the NRC staff to accept this keyswitch function as an acceptable deviation to this staff position, the staff will have to evaluate the DCPP PPS specific system communications control configuration--including the operation of the keyswitch, the software affected by the keyswitch, and any testing performed on failures of the hardware and software associated with the keyswitch. The status of the ALS platform on this matter is unclear at this time and will be resolved as the ALS L TR review is completed.

Moreover, the Tricon V10 system Operational Mode Change (OMC) keyswitch does change operational modes of the 3008N MPs and enables the TriStation 1131 PC to change parameters, software algorithms, etc, related to the application program of the safety channel without the channel or division being in bypass or in trip. As stated in Section 3.1.3.2 of the Tricon V10 SER, the TriStation 1131 PC should not normally be connected while the Tricon V10 is operational and performing safety critical functions.

However, it is physically possible for the TriStation PC to be connected at all times, and this should be strictly controlled via administrative controls (e.g.,

place the respective channel out of service while changing the software, parameters, etc). The LAR does not mention any administrative controls Status Open RAI No.

(Date Sent)

N/A RAI

Response

(Due Date)

Page 11 of 39 Comments what will be done for each ASAI in this 01 matrix.

(Westinghouse 4 12-12) Response received April 2, 29, 2012. Staff reviewed this item and still need additional information to close this item. The staff will need to review this item further during an NRC audit at the Invensys facility.

All the items noted below will be the scope of the audit.

3/21/12 update: it was agreed that PG&E/lnvensys and PG&ElWestinghou se/CSI would provide a report (LAR supplement) to explain how these two issues i

May 14,12

-IVo SrclRl DCPP PPS Open Item Summary Table Issue Description P&GE response:

such as this to control the operation of the OMC (operational mode change) keyswitch. Furthermore, in order to leave the non-safety TriStation 1131 PC attached to the SR Tricon V10 system while the key switch is in the RUN position, a detailed FMEA of the TriStation 1131 PC system will be required to ascertain the potential effects this non-safety PC may have on the execution of the safety application program/operability of the channel or division. These issues must be addressed in order for the NRC staff to determine that the DCPP PPS complies with the NRC Staff Guidance provided in Staff Position 1, Point 11. The status of the ALS platform on this point is unclear at this time.

P&GE response:

Tricon The OMC keyswitch controls only the mode of the V1 0 Tricon 3008N MPs.

In RUN position the 3008N MPs ignore* all commands from external devices, whether WRITE commands from external operator interfaces or program-related commands from TS1131.

Status RAI No.

(Date Sent)

RA/

Response

(Due Date)

Page 12 of 39 Comments will be resolved and submit to NRC Date to be provided TBD.

Waiting for the V10 Tricon portion of the PPS Replacement Failure Modes and Effects Analysis, an I SG-06 Phase 2 document to be submitted to NRC in May 2012.

The keyswitch is a four-position, three-ganged switch so that the three Main Processor (MP) modules can monitor the position of the switch independently. The Operating System Executive (ETSX) executing on the MP application processor monitors the position of the keyswitch. The three MPs vote the position of the keyswitch. The voted position of the keyswitch is available as a read-only system variable that can be monitored by the TSAP. This allows alarming the keyswitch position when it is taken out of the RUN position. TS1131 messages to and from the Tricon (Le., ETSX executing on the MPs) are of a defined format. TS1131 messages for control program (Le., TSAP) changes - whether download of new control programs or modification of the executing control program - are uniquely identifiable.

Such messages are received by ETSX and appropriate response provided depending upon, among other things, the position of the keyswitch. When a request from TS1131 is received by ETSX to download a new control program or modify the executing control program, ETSX accepts or rejects the request based on the voted keyswitch position. If the keyswitch is in RUN, all such messages are rejected. If the keyswitch is in PROGRAM, the Tricon is considered out of service and ETSX runsJhrough the sequence of

--~

3/21/12 Update:

PG&Ellnvensys needs to provide a technical explanation of how the MP3008N processor actually ignores all commands when in RUN-address the items in the 01.

4/4/12 Update:

Need to explain how this message format works to reject messages

May 14, 12 DCPP PPS Open Item Summary Table Page 13 of 39

-~-

No SrclRI Issue Description P&GE response:

Status RA/ No.

(Date Sent)

--~

RA/

Response

(Due Date)

Comments steps to download the new or modified control program, as appropriate.

Multiple hardware and software failures would have to occur on the V1 0 Tricon (in combination with human-performance errors in the control room and at the computer with T81131 installed) in order for the application program to be inadvertently reprogrammed. Therefore, there is no credible single failure on the V1 0 Tricon that would allow the safety-related application program to be inadvertently programmed, e.g., as a result of unexpected operation of the connected computer with T81131 installed on it.

The above conclusion will be confirmed (for the V10 Tricon portion of the PP8 Replacement) in the Failure Modes and Effects Analysis, an 18G-06 Phase 2 document planned for submittal to NRC in May 2012. Additionally, Invensys Operations Management will support the staff's review of the hardware and software associated with the OMC keyswitch by making all of the technical data available for audit.

  • T81131 contains function blocks that allow WRITE-access to a limited set of parameters programmed into the application software, but only for a limited duration after which the capability is disabled until WRITE-access is re-enabled. However, without these function blocks programmed into the application program neither the application program nor application program parameters can be modified with the OMC keyswitch in the RUN position.

PG&E Administrative controls on use of keyswitch will be provided with commitment to include in procedures in response.

Note, T81131 is not used to change setpoints and protection set is inoperable when keyswitch is not in RUN position.

from the Tristation when in RUN??

Graphs and visual presentation of these concepts would be helpful.

This issue will also have to be addressed for the AL8 platform.

PG&Ellnvensys needs to provide a technical explanation of how the MP300BN processor actually ignores all commands when in RUN-address the items in the 01.

B AR (R8)

[18G-06 Enclosure B, Item 1.21]

8etpoint Methodology: The NRC staff understands that a summary of 8P (setpoint) Calculations will be provided in Phase 2, however, section 4.1 0.3.B Closed

~--

N/A Discussed at 4/1BI2011 CC.

Requested that

May 14,12 DCPP PPS Open Item Summary Table Page 14 of 39 No SrclRI Issue Description P&GE response:

Status of the LAR also states that PGE plans to submit a separate LAR to adopt TSTF 493. The NRC cannot accept this dependency on an unapproved

-future licensing action. The staff therefore expects the licensee to submit a summary of setpoint calculations which includes a discussion of the methods used for determining as-found and as-left tolerances. This submittal should satisfy all of the informational requirements set forth in ISG6 section 0.9.4.3.8 without a condition of TSTF 493 LAR approval P&GE response:

The evaluation of the setpoints for the PPS replacement will need to be performed by Westinghouse in two phases in order to provide sufficient documentation to support 95/95 setpoint values for the setpoints. This is because the NRC staff has been requesting additional information and additional data and analysis to demonstrate that the uncertainties used in the setpoint calculation have been based on a statistically sufficient quantity of sample data to bound the assumed values (to justify the confidence level of the calculation is appropriate) during recent Westinghouse projects involving setpoints. Significant information is required from the transmitter and RTO vendors, that has never been obtained before, to support development of calculations that can support 95/95 setpoint values.

The first phase of the evaluation of the setpoints will include evaluation of the PPS replacement set points for the Tricon and ALS architecture using expected bounding uncertainty values. A setpoint summary evaluation which includes a discussion of the methods used for determining the as-found and as-left tolerances will be submitted by May 31, 2012. This is a change to the commitment 31 in Attachment 1 to the Enclosure to the PPS Replacement LAR. The setpoint information associated with the PPS replacement is being submitted independently of the LAR for TSTF-493 and does not rely on a TSTF-493 licensing action.

The second phase of the evaluation of the setpoints will include development of Westinghouse calculations of the PPS replacement setpoin~s for the I RAI No.

(Date Sent)

RAI I Response (Due Date)

Comments PGE add to the response a statement that the setpoint changes associated with this modification will be submitted for evaluation independently with no reliance on TSTF 439 licensing action.

(Westinghouse 4 12-12) Response received April 2, 29,2012. PG&E's commitment to provide summary calc's by May 31, 2012 and not revise these set points via a TSTF-439 LAR addresses this 01.

Close this 01.

3/7/12 update:

-PG&E stated that all setpoints determinations will be addressed as part of this LAR,

May 14, 12 ocpp PPS Open Item Summary Table Page 15 of 39 No SrclRI Issue Description P&GE response:

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments Tricon and AlS architecture using sufficient information from vendors to substantiate that the setpoints are 95/95 values. The Westinghouse calculations will be completed by December 31,2012 and will be available for inspection by NRC staff in Washington DC with support provided by Westinghouse setpoint group personnel. The NRC staff inspection of Westinghouse calculations in Washington DC has been performed for another recent utility project involving setpoints.

Closed N/A and NOT submitted as a TSTF-493 licensing action.

3/21112 update:

The staff may chose to review the Westinghouse calculations at the Westinghouse office in Washington DC.

However, if the safety finding is dependent on these calculations, then the setpoint calculations will be required to be submitted on the docket per NRC licensing procedures (Westinghouse 4 12-12) Response received April 2, 29,2012. The PG&E response to 9

AR (BK) l TR Safety Conclusion Scope and Applicability - Many important sections of the DCPP PPS LAR refer the reader to the AlS licensing topical report (lTR) to demonstrate compliance of the system with various Clauses of IEEE 603 1991, IEEE 7-4.3.2-203, and ISG-04. However, many important sections of the AlS l TR state that compliance with various Clauses of these IEEE Stds and ISG-04 are application specific and refer the reader to an application specific license amendment submittal (Le., the DCPP PPS LAR in this case).

The staff has not yet had time to evaluate all the LAR information in detail and compare this information with that provided in the AlS l TR to ensure there is no missing information. However, PG&E and its contractors are encouraged to review these two licensing submittals promptly to verify that this item address the 01. Close this

01.

I

May 14,12 DCPP PPS Open Item Summary Table Page 16 of 39

~~~ -~-

No SrclRI Issue Description P&GE response:

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments compliance with these IEEE Stds and ISG-04 are adequately addressed within both licensing documents.

P&GE response:

PG&E and Westinghouse have reviewed the LAR 11-07 and the ALS topical report to verify information is provided to justify compliance with IEEE 603-1991, IEEE 7-4.3.2-2003, and ISG-04 in either the LAR or the ALS topical report. As a result of the review, it was identified that neither the LAR nor the ALS topical report contain a matrix that documents compliance with ISG-04 Table 5-4 for the DCPP ALS platform. PG&E will submit a matrix that documents compliance with ISG-04 Table 5-4 for the DCPP ALS platform by May 31, 2012.

~-

RS 10

'----~~

Plant Variable PPS Scope - In the Description section of the LAR, section 4.1.3, nine plant variables are defined as being required for RTS and section 4.1.4 lists seven plant variables that are required for the ESFAS. Three additional plant variables were also listed in section 4.10.3.4.

Some variables are not listed in section 4.10.3.4 as being PPS monitored plant parameters. It is therefore assumed that these parameters are provided as direct inputs to the SSPS and that the PPS is not relied upon for the completion of required reactor trip or safety functions associated with them. Please confirm that these plant parameters and associated safety functions will continue to operate independently from the PPS and that the replacement PPS will not adversely impact the system's ability to reliably perform these functions.

Closed RAI Required (RAI #X)

P&GE response:

The PPS Replacement LAR Sections 4.1.3 and 4.1.4 describe the plant variables from which RTS and ESFAS protective functions are generated.

May 14, 12 DCPP PPS Open Item Summary Table Page 17 of 39 Comments 7VoISrclRJ I Issue Description I P&GE response:

I Status I RAJ No. I RAJ (Date Sent) I Response (Due I

.. ~~

1The initiation signal outputs to the SSPS coincidence logic are generated in 1-..~--+~

the PPS or other, independent systems, or in some cases, by discrete Neutron Flux is an devices. Section 4.1.3 items 6 (RCP bus UF, UV, and breaker position, 8 input to Tricon but it (Main Turbine trip fluid pressure and stop valve position) and 9 (seismic is not listed in acceleration) are generated by discrete devices outside the PPS and provide Table 4-2 "Process direct contact inputs to the SSPS. Section 1.4 items 6 (Containment Exhaust Variable inputs to Radiation) and 7 (RT breaker position Permissive P-4) are also generated Tricon" outside the PPS and are direct contact inputs to the SSPS. The initiation signals associated with these plant parameters operate independently from Signals not the PPS. The replacement PPS will not adversely affect the reliable associated with performance of the safety functions associated with these plant parameters.

PPS functions will be designated as The three signals (Wide Range RCS Temperature and Pressure and Turbine such in the SE and Impulse Chamber Pressure) not listed in Sections 4.1.3 and 4.1.4 are they will not be monitored by the PPS per Section 4.10.3.4. The Wide Range RCS Pressure described since and Temperature signals are used to generate the LTOP function described they are not in in OCPP FSAR Section 5. The PPS uses Turbine Impulse Chamber scope.

Pressure to generate an initiation signal that is used by the SSPS coincidence logic to develop Permissive P-13 as discussed in RAI 3, below.

Neutron Flux should be added to Section 4.2 Table 4-2 as follows:

Input to Overtemperature fl Neutron Flux (Power Temperature (OTDT) RT Range, Upper & Lower)

Input to Overpower fl Temperature (OPDT) RT L...... ~___~_~_~'----_-'--__-'-__-'--__---'

11 RS Power Range NIS Function - Section 4.1.7 describes the Existing Power Closed* I RAI Range NIS Protection Functions and it states that the Power Range nuclear Required Only PPS instrumentation provides input to the OTOT, and OPOT protection channels.

  • RAI I (RAI # X)

Functions will be It is not entirely clear whether any of the described NIS protection functions will be PElrfol111ed by the PPS system. Please clarify exactly what the role of still described in the

May 14, 12 DCPP PPS Open Item Summary Table Page 18 of 39 No SrC/RI Issue Description P&GE response:

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments 12 RS the PPS system is for these NIS Protection functions.

P&GE response:

Power range analog inputs are provided by the NIS to each PPS Protection Set for use in the calculation of the Overtemperature Oelta-T and Overpower Oelta-T Setpoint in the Oelta-TlTavg channels. No other NIS signals interface with the PPS. The NIS Protection functions (RT and power range permissives) are generated independently by Nuclear Instrumentation bistable comparators. The NIS bistable outputs are sent directly to the SSPS and have no physical interface with the PPS.

Permissive Functions - Several Permissive functions are described within the LAR It is not clear to the staff whether any of these functions are to be performed by the PPS or if the PPS will only be providing input to external systems that in turn perform the permissive logic described in the LAR Section 4.1.9 states that "Settings of the bistable comparators used to develop the permissives are not affected by the PPS Replacement Project",

which implies that all of these permissive functions are performed by systems other than the PPS. However, it is still unclear if this statement applies to all permissive functions described throughout the LAR or if it applies only to those permissives relating to Pressurizer Pressure. It is also possible that the permissive functions are being performed by the existing PPS and will continue to be performed by the replacement system and therefore remain "not affected" by the PPS replacement project.

Please provide additional information for the following permissive functions to clearly define what the role of the PPS system will be for each.

P-4 Reactor Trip P-6 Intermediate Range Permissive P-7 Low Power Permissive (Bypasses low Ppzr reactor trip)

  • P-8 Loss of Flow Permissive P-9 Power Permissive P-10 Power Range Power Low Permissive P-11 Low Pressurizer Pressure SI Operational Bypass needs to be sent.

Close RAI Required (RAI #X)

SE.

May 14,12 DCPP PPS Open Item Summary Table Page 19 of 39 No SrclRI Issue Description P&GE response:

Status RA/ No.

RA/

Comments (Date Sent)

Response

(Due Date)

P-12 No-Load Low-Low T ave Temperature Permissive P-13 Turbine Low Power Permissive

  • The LAR states that "These signals are generated in the PPS" P&GE response:

Permissive function initiation signals generated within the existing PPS will continue to be performed by the replacement PPS and therefore remain "not affected" by the PPS replacement project. Permissive function initiation signals that are generated independently of the existing PPS will continue to be generated independently.

  • Permissive P6, P-B, P-9, and P-10 initiation signals are bistable comparator outputs from the independent NIS to the SSPS. There is no interface with the PPS.
  • Permissive P-4 initiation signals are direct contact inputs to the SSPS coincidence logic generated from contacts in the Reactor Trip Breakers (RTB). There is no interface with the PPS.
  • Permissive P-11, P-12, P-13, and P-14 initiation signals are generated by bistable comparator outputs generated in the PPS and sent to the SSPS.
  • Permissive P-7 is generated in the SSPS from 3 out of 4 power range NI channels (from NIS - P-10) below setpoint and 2/2 turbine impulse chamber pressure channels below setpoint (From PPS - P13).

The bistable initiation signals described above are monitored by the SSPS.

The SSPS generates the Permissive when appropriate coincidence of initiation signals is detected. No SSPS permissive or safety function coincidence logic is changed by the PPS replacement project.

Permissives P-6, P-7, P-B, P-9, P-10, and P-13 are functionally described in The NRC understands that all permissives are developed within the SSPS system.

Permissives P11 P14 use inputs provided by PPS system. All other permissives use inputs generated by external systems that are independent of the PPS.

See 13 below.

May 14,12 No SrclRI Issue Description DCPP PPS Open Item Summary Table IP&GE response:

FSAR Table 7.2-2. Permissives P-4, P-11, P-12, and P-14 are functionally described in FSAR Table 7.3-3.

The bistable comparator setpoints for the above-listed permissives are not expected to change at this time.

13 RS P12 Permissive Contradiction - The second paragraph of section 4.1.20 describes the P-12 interlock and states that "These signals are developed in the PPS". This statement is then contradicted in the third paragraph by the following statement; "These valves are not safety-related, but are interlocked with the P-12 signal from the SSPS."

In conjunction with the response to RA13, please provide a resolution for this contradiction in section 4.1.20 of the LAR.

P&GE response:

The word "signals" in the referenced Section 4.1.20 sentence, "These signals are developed... " is referring to the bistable comparator outputs which are monitored by the SSPS. The PPS does not generate the P-12 Permissive itself. The actual P-12 Permissive is generated by the SSPS when appropriate coincidence of initiation signals is detected. The SSPS output is interlocked with the valves as stated in the third paragraph of Section 4.1.20.

The LAR Section 4.1.20 is clarified by the following statement:

"... The P-12 Permissive is developed in the SSPS based on coincidence of the P-12 bistable comparator output initiation signals from the PPS...

~-

Protection System Permissives (P-11 unblock SI from ALS, P13 Turbine power permissive from Tricon, and P-14 Steam Generator Level high-high from Tricon) are generated by coincident logic in the SSPS based on Status Closed RAI No.

(Date Sent)

RAI Required (RAt #X)

RA/

Response

(Due Date)

Page 20 of 39 Comments The NRC understands that the P12 signal is generated by the SSPS using signals developed in the PPS.

May 14,12 DCPP PPS Open Item Summary Table Page 21 of 39 No SrcIR/

Issue Description P&GE response:

Status RAI No, (Date Sent)

RAI

Response

(Due Date)

Comments initiating signals (bistable outputs) from the PPS as noted in the response to 01 #12, Permissive development, including initiating signals and logic coincidence is shown in FSARU Tables 7.2-2 (RTS) and 7,3-3 (ESFAS),

The PPS does not perform coincident logic functions and does not "generate" any protection system permissives, 14 RS Section 4.1,1 SSPS contains the following statement in the last paragraph; "Information concerning the PPS status is transmitted to the control board status lamps and annunciators by way ofthe SSPS control board demultiplexer and to the PPS by way ofthe SSPS computer demultiplexer."

Closed PGE Response resolves this Open Item. Change status to Closed.

Why would the PPS status need to be transmitted to the PPS as the sentence suggests in the last phrase?

PG&E response:

The sentence in Section 4.1.1 contains a a typographical error, The sentence should read:

"Information concerning the PPS status is transmitted to the control board status lamps and annunciators by way of the SSPS control board demultiplexer and to the Plant Process Computer (PPC) by way of the SSPS computer demultiplexer."

~

As used in the Section 4,1.1. paragraph, "PPS Status" means "PPS Channel Trip Status."

May 14, 12 DCPP PPS Open Item Summary Table Page 22 of 39 No SrC/Rt Issue Description P&GE response:

Status RAt No.

(Date Sent)

RA/

Response

(Due Date)

Comments 15 (BK)

An ISG-04 compliance matrix for the DCPP PPS system was not submitted with, or referenced in, the LAR for the W/ALS platform. Instead the ISG-04 compliance section 4.8 of the LAR refers the reader to the ALS L TR for nearly all the points of ISG-04. Fig. 4.4 and 4.5 of the LAR indicate various 1E and non-1E communication pathways to and from ALS processor (e.g.,

Maintenance Work Station, plant computer, process control, port aggregator, and 4-20 ma temperature signal to Tricon processor). These are all application specific features of the PPS and the staff expects a W/CSI ALS document to be submitted, similar in scope and detail to the Invensys "PACIFIC GAS & ELECTRIC COMPANY NUCLEAR SAFETY-RELATED PROCESS PROTECTION SYSTEM REPLACEMENT DIABLO CANYON POWER PLANT DI&C-ISG-04 CONFORMANCE REPORT" Document No.

993754-1-912 Revision 0, to be submitted on the docket, which explains how the ALS portion of the PPS application conforms with the guidance of ISG

04.

Open RAI Required (RAI #X)

(Westinghouse 4-4

12) No further discussion necessary until May 31. 2012.

4/4/12 update: The draft ALS ISG-04 compliance matrix on the AL TRAN Sharepoint website is not detailed enough for the staff to use in approving the ALS portion of the PPS' communications design. Suggest PG&E review the Invensys ISG-04 Doc. Document No.

993754-1-912 (-P)

Revision 0, and provide guidance for an ALS document at the same level of detail.

PG&E response:

PG&E is developing the ISG-04 compliance matrixTable for the ALS platform and PG&E will submit the Table by July 31.2012.

May 14.12 DCPP PPS Open Item Summary Table Page 23 of 39 No 16 Src/R/

Issue Description P&GE response:

Status (BK)

Section 1.4.4 (pg. 12/38) of document 993754-1-813 Diablo Canyon Triconex Open PPS Validation Test Plan (VTM) states "The network equipment. including media converter, NetOptics Network Aggregator Tap, and gateway hub, and the MWS will not be within the test scope of this VTP. The Nuclear Delivery (NO) group will coordinate with Pacific Gas & Electric for system staging prior to turn over to Nuclear IV&V. The Nuclear IV&V group will confirm proper operation of network communications system interfaces before beginning testing addressed in this VTP." When. where, and what procedures will be used to test the network equipment??

-~~

PG&E response: Additional information on the PPS testing is being provided to the staff. The information on the PPS testing was updated on May 9 to address staff comments provided in the 4/18/22 conference call. The VTM will need to be updated based on the additional information. A date that the updated VTM will be submitted will be provided after feedback from the staff is received on the additional information on the PPS testing.

RAJ No.

(Date Sent)

RAI Required (RAI #X)

RAI

Response

(Due Date)

Comments Received two papers discussing integration test plans for PPS system. These papers were discussed at the 4/18/2011 CC.

The staff agrees that the analog RTD Signal loops may be tested separately at the Tricon FAT and at the ALS FAT to satisfy integration test requirements.

The staff expressed some concerns over the statement that 'There is no digital data connection between the Tricon and the ALS." This appears to be a misleading statement since both systems do have connections to the common MWS. Further clarification should be provided and the statement

May 14,12 DCPP PPS Open Item Summary Table Page 24 of 39 No SrclRI Issue Description P&GE response:

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments should be revised to describe the nature of the MWS connections to each system.

17 (BK)

Section 5.1.4.3, Hardware Validation Tests, (pg. 27/38) of document 993754 1-813 Diablo Canyon Triconex PPS Validation Test Plan (VTM) states that the ALS equipment will not be included in the FAT. Where, when, and what procedures will be used to fully test the Integrated PPS system (both Tricon V10 and ALS platforms together) be subjected to FAT.

Open RAI Required (RAI #X)

This issue was discussed at the 4/18/2011 CC.

PGE proposed performance of separate but overlapping tests at each factory to accomplish the integration test.

The staff has some concern over the fact that the MWS's to be installed in the plant would only be tested during the Tricon FAT. A fifth MWS to be configured the same as the plant MWS's is to be used during the ALS FAT.

One option to resolve this concern may be to credit the SAT test results in the SE.

PG&E response: Additional information on the PPS testing is being provided to the staff. The VTM will need to be updated based on the additional information. A date that the updated VTM will be submitted will be provided after feedback from the staff is received on the additional information on the PPS testing.

May 14,12 DCPP PPS Open Item Summary Table Page 25 of 39 No SrC/RI Issue Description P&GE response:

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments The current schedule for SAT (July 2013) does support this.

18 (BK)

Software Management Plan: Regulatory Guide (RG) 1.168, Revision 1, "Verification, Validation, Reviews and Audits for Digital Computer Software Used in Safety Systems of Nuclear Power Plants," dated February 2004 endorses IEEE (Institute of Electrical and Electronics Engineers) 1012-1998, "IEEE Standard for Software Verification and Validation," and IEEE 1028 Open RAI Required (RAI #X)

(Westinghouse 4/12/12) update:

The staff has reviewed the Invensys IEEE 1012 compliance 1997,"IEEE Standard for Software Reviews and Audits," with the exceptions stated in the Regulatory Position of RG 1.168. RG 1.168 describes a method acceptable to the NRC staff for complying with parts of the NRC's regulations for promoting high functional reliability and design quality in software used in safety systems. Standard Review Plan (SRP) Table 7-1 and Appendix 7.1-A identify Regulatory Guide 1.168 as SRP acceptance criteria for reactor trip systems (RTS) and for engineered safety features actuation systems (ESFAS)

The Invensys PPS Replacement Software Verification and Validation Plan (SWP), 993754-1-802 does not provide a clear explanation of how the Invensys SWP complies with IEEE 1012-1998. Please provide a cross reference table that explains how the Invensys SWP implements the criteria of IEEE 1012-1998.

Also, the Westinghouse/ALS 6116-00000 Diablo Canyon PPS Management Plan, does not provide a clear explanation of how the CSt SWP complies with IEEE 1012-1998. Please provide a cross reference table that explains how the W/CSI SWP implements the criteria of IEEE 1012-1998.

matrix on the PG&E/Altran sharepoint directory and it appears to be acceptable. The matrix appears to be comprehensive and indicates no exceptions to any clauses in IEEE 1012. No attempt was made to review/verify that where I nvensys claims compliance with any particular Clause in the Std, that the respective section in their SWPis acceptable-the

May 14,12 DCPP PPS Open Item Summary Table Page 26 of 39 No SrclRI Issue Description P&GE response:

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments PG&E response:

Westinghouse is incorporating the IEEE-1012 compliance map in the ALS V&V plan document 6116-00003 and PG&E will submit the ALS V&V plan document 6116-00003 to the staff by May 31,2012.

staff will work through this as the SWP is reviewed and evaluated for approval. Please submit the document on the docket.

This 01 will remain open pending review of the Westinghouse/CSI document.

19 RS Section 4'.1.1 of the LAR states that; "The SSPS evaluates the signals and performs RTS and ESFAS functions to mitigate Abnormal Operational Occurrences and Design Basis Events described in FSAR [26] Chapter 15. "

however, Chapter 15 of the DCPP FSAR does not use the terms Abnormal Operational Occurrence (AOO) or Design Basis Accident (DBE). Instead, the accident analysis in chapter 15 identifies conditions as follows; CONDITION I - NORMAL OPERATION AND OPERATIONAL TRANSIENTS CONDITION 11-FAULTS OF MODERATE FREQUENCY CONDITION III - INFREQUENT FAULTS Open RAI will eventuall y be required (RAI IX) 3/21/12 update:

PG&E has created a share point website for NRC to review PPS design drawings that will address this issue as well as 01 20 and 21. NRC staff will determine if they are needed to be submitted on the docket. PG&E will ensure the website is information is only applicable to this licensing action.

May 14,12 DCPP PPS Open Item Summary Table Page 27 of 39 No Src/R/

Issue Description P&GE response:

Status RA/ No.

(Date Sent)

RA/

Response

(Due Date)

Comments CONDITION IV - LIMITING FAULTS As such, the statement that AOO's and DBE's are described in the FSAR appears to be inaccurate. Please explain the correlation between the Conditions described in FSAR chapter 15 and the Abnormal Operational Occurrences, and Design Basis Events described in the LAR.

~~~

PG&E response: The AOO's are referred to as ANS Condition I "Operational Transients" in FSAR Chapter 15 and are addressed in FSAR Chapter 15.1.

The design basis accidents are referred to as ANS Condition II "faults of moderate frequency," ANS Condition III "infrequent faults," and ANS Condition IV "limiting faults" and are addressed in FSAR Chapter 15.2, 15.3, and 15.4 respectively.

May 14,12 DCPP PPS Open Item Summary Table Page 28 of 39 No 20 21 SrclRl RS RA Issue Description P&GE response:

Status The system description provided in Section 4 of the LAR includes "functions Open performed by other protective systems at DCPP in addition to the PPS functions", In many cases, there is no explanation of what system is performing the functions described nor is there a clarification of whether the described functions are being performed by the PPS system, As an example, Section 4.1.16 describes a bypass function to support testing of the high-high containment pressure channel to meet requirements of IEEE 279 and IEEE 603. The description of this function does not however, state whether this latch feature is being implemented within the PPS system or in the SSPS.

The staff needs to have a clear understanding of the functional scope of the PPS system being modified in order to make its regulatory compliance determinations. Please provide additional information such as PPS function diagrams to help the staff distinguish PPS functions from functions performed by other external systems.

PG&E Response: PPS design drawings have been provided to the staff on the Sharepoint site.

Westinghouse/CSI document 6116-00005, "Diablo Canyon PPS System Test Open Plan," states that the ALS-102 FPGA design is changed for the DCPPS System. Further, Section 5.3.3 states: "Test as many of the ALS-102 requirements as possible,"

RAI No.

(Date Sent)

RAI will eventual!

ybe required (RAI #X)

RAI will eventual!

y be required (RAI #X)

RAI

Response

(Due Date)

Comments 3/21/12 update:

PG&E has created a share point website for NRC to review PPS design drawings that will address this issue.

NRC staff will determine if they are needed to be submitted on the docket. PG&E will ensure the website is information is only applicable to this licensing action.

3/21/12 update:

PG&E has created a share point website for NRC to review PPS design

May 14,12 DCPP PPS Open Item Summary Table Page 29 of 39 No SrclRI Issue Description P&GE response:

Status RAJ No.

(Date Sent)

RAI

Response

(Due Date)

Comments I

Please identify what document describes the design verification test for this board.

drawings that will address this issue.

NRC staff will determine if they are needed to be submitted on the docket PG&E will ensure the website is information is only applicable to this licensing action.

PG&E response: PPS design drawings have been provided to the staff on the Sharepoint site.

22 BK Follow-on 01 # 5 question pertaining to the PPS VTP:

Section 1.4.4 (pg. 12/38) states "The network equipment, including media converter, NetOptics Network Aggregator Tap, and gateway hub, and the MWS will not be within the test scope of this VTP. The Nuclear Delivery (NO) group will coordinate with Pacific Gas & Electric for system staging prior to turn over to Nuclear IV&V. The Nuclear IV&V group will confirm proper operation of network communications system interfaces before beginning testing addressed in this VTP." When, where, and what procedures will be used to test the network equipment??

Also, section 5.1.4 (3) Hardware Validation Tests states that the ALS equipment will not be included in the FAT (pg. 27/38). Where, when, and what procedures will be used to fully test the Integrated PPS system (both Tricon V10 and ALS platforms together) be subjected to FAT.

Open RAlwill be required (RAI #X)

PG&E response:

Additional information on the PPS testing is being provided to the staff. The VTP will need to be updated based on the additional information. A date that the updated VTP will be submitted will be provided after feedback from the staff is received on the additional information on the PPS testing

May 14,12 DCPP PPS Open Item Summary Table Page 30 of 39 No SrclRI Issue Description P&GE response:

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments 23 BK Section 4.2.13.1 of the LAR (page 85) states; "Figure 4-13 only shows one TCM installed in the Tricon Main Chassis (Slot 7L), the PPS replacement will utilize two TCM cards in each main chassis (Slots 7L and 7 -R). This will provide two non-safety-related communication paths to the MWS and the PPC Gateway Computer from each Protection Set to ensure continued communications if a single TCM fails.

The NetOptics Model PA-Cu/PAD-CU1 PA-CU port aggregator network tap was approved previously by NRC for a similar application in the Oconee RPS SER Section 3.1.1.4.3 [18]. The NRC staff determined that due to the electrical isolation provided by use of fiber optic cables and the data isolation provided by the Port Tap and the Maintenance and Service Interface (MSI) in the Oconee RPS, there was reasonable assurance that a fault or failure within the Oconee Gateway computer or the Operator Aid Computer will not adversely affect the ability of the Oconee RPS to accomplish its safety functions.

During the SAT PG&E will test the Protection Set communications paths illustrated in Figure 4-13 to verify that there is no inbound communications path associated with port aggregator network tap Port 1. That is, PG&E will verify that communications from Port 1 to either the TCM on Port A or the MWS on Port B of the port aggregator network tap are not permitted.

Results of this test will be documented in final System Verification and Validation Report. Port aggregator dual in-line package (DIP) switch positions will be controlled by DCPP configuration management processes."

In order for the Staff to approve the integrated configuration of the PPS, prior to shipment of the PPS equipment to DCPP site, all communications paths will require testing on or before FAT, and before completion of the SER. This testing is typically completed during or before the PPS FAT, otherwise, the SER will not be completed until after the SAT. Please provide a test scheme/procedures that satisfies all regulatory requirements prior to or during the FAT. Otherwise, if this testing will be completed during the SAT, as stated in the LAR, please provide a detailed schedule for this testing so the NRC can revise its PPS LAR Review Plan accordingly.

Open RAlwill be required (RAI #X) 1 The NetOptics Model PAO-CU has two one-way output ports but is otherwise identical in function to the PA-CU.

May 14,12 DCPP PPS Open Item Summary Table Page 31 of 39 7\\jQ.

SrclRI Issue Description P&GE response:

Status RA/ No.

(Date Sent)

RA/

Response

(Due Date)

Comments PG&E response: Additional information on the PPS testing for ALS is being provided to the staff. A date the additional information will be submitted will be provided after feedback from the staff is received on the additional information on the PPS testing for ALS.

24 RJS

a. Section 4.1.17 paragraph 3 discusses the protection functions associated with High - High Steam Generator Level or P-14. In this discussion it is stated that the SI signal initiates the same two functions (Turbine Trip and Feedwater Isolation) however, there is no mention of this in section 4.1.9 or in the discussion of the P-14 permissive. Please confirm that P-14 can be initiated by either High-High SG Level or by initiation of SL
b. This same section also states that the described latched in function serves to comply with IEEE Std. 279 Section 4.16. The replacement PPS system is not being evaluated against the criteria of IEEE 279.

Instead, IEEE 603-1991 is being used and the equivalent criteria is contained in section 5.2 of IEEE 6031991. PGE needs to understand that the criteria of IEEE 279 are not relevant to this review effort.

New Item initiated on 4/23/2012.

PG&E response:

a. Turbine Trip can be initiated by either the P-14 steam generator level protection function OR by the latched Safety Injection (SI).

Section 4.1.17 describes the Steam Generator Level High-High Protection function P-14. Upon sensing high steam generator level, the PPS generates an initiation signal to the SSPS, which generates the turbine trip signal and initiates Auxiliary Feedwater when coincidence of 2 of 33 high-high level signals in any steam generator is detected.

Section 4.1.9 describes Pressurizer Protection Functions, one of which is initiation of Safety Injection through the SSPS when coincidence 3 of 4 Pressurizer Pressure Low-Low signals from the PPS is detected. The SI actuation signal also actuates turbine trip and Auxiliary Feedwater through the SSPS, but SI is not initiated by Steam Generator Level High-High The P-14 protection function is initiated ONLY by steam Generator

25 May 14,12 DCPP PPS Open Item Summary Table Page 32 of 39 c~~~---

P&GE response:

No Src/RI Issue Description Status RAI No.

RAI Comments (Date Sent)

Response

(Due Date)

Level High-High. Through the SSPS, P-14 will trip the turbine and actuate Auxiliary Feedwater. A SI signal will also actuate Turbine trip and Auxiliary Feedwater, among other actions. Pressurizer Protection functions do not initiate P-14 and Steam Generator Level High-High P-14 does not initiate SI.

b. PG&E intended Section 4.1 to describe the existing PPS and to apply only to the existing PPS, which complies with IEEE 279-1971.

Sections 4.2 to 4.13 of the LAR apply to the PPS Replacement.

Section 4.10.2.2 describes compliance of the PPS Replacement with IEEE 603-1991 Section 5.2. PG&E understands and appreciates that IEEE-603 applies to the PPS replacement.

RJS Sections 4.1.17, and 4.1.21 state that the P-9 permissive is the "Power New Item initiated on Range at Power" function while Section 4.1.9 states that the P-10 Permissive 4/23/2012.

is also called the "Power Range at Power" function. Is it correct that both of these permissives are called "Power Range at Power" and that they perform different functions?

PG&E response:

Both P-9 and P-10 are "Power Range at Power" functions; both are active when the Power Range NI channels are at power.

Permissive P-9 blocks reactor trip on turbine trip when 3 of 4 Power Range NI channels are below 50%.

Permissive P-10 is active when 2 of 4 Power Range NI channels are above 10%. Permissive P-10 is combined with Turbine Power Permissive P-13 (which is active above approximately 10% turbine load) to provide input to Permissive P-7 that allows blocking several low power reactor trips.

In effect, Permissive P-10 is the "Power Range at Power - Low" permissive" and Permissive P-9 is the Power Range at Power - High" permissive. This is consistent with the response to 01 #12, above.

May 14,12 DCPP PPS Open Item Summary Table Page 33 of 39 No P&GE response:

Status RA/ No.

Issue Description RA/

SrclR/

Comments (Date Sent)

Response

(Due Date)

I New 26 The PG&E SyOAP defines Supplier tasks that are related to assurance of RJS Item Initiated on software quality for each of the following phases of development; 4/25/2011 Project Initiation and Planning Conceptual Design Req u i rements Design Implementation Integration Test These phases do not align with the phases used in the ALS or Tricon development lifecycles. For instance, the Tricon SOAP defines the phases as Requirements, Design, Implementation, and Test (Validation). Because of this, it is not clear how assurance of task completion can be accomplished.

During which Tricon phases would those tasks listed under Integration, Initiation and Planning, and Conceptual Design be performed?

The ALS SOAP does not mention phases but the ALS Management plan defines the development phases as; Planning, Development, Manufacturing, System Test, and Installation.

Would it be possible for PGE to provide a mapping of Phases defined in the SyOAP to the Phases of the ALS and Tricon system development processes so that the staff can correctly identify and confirm performance of these QA tasks?

May 14, 12 DCPP PPS Open Item Summary Table Page 34 of 39 No SrclRI Issue Description P&GE response:

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments PG&E response:

PGE will provide a mapping of Phases defined in the SyQAP to the Phases of the ALS and Tricon system development processes. The determination of the location of the mapping information and date to be submitted is IN PROGRESS.

27 RA Software Management Plan The LAR, Attachment 3, describes the project organization, roles and responsibilities for the PPS replacement project. This document does not describe oversight activities that PG&E will perform during the PPS replacement project, as well as the interface between PG&E and Invensys and WEC/CSI, and the methodology to judge quality of the vendor effort.

Please provide this information.

New PG&E response:

Oversight activities for the project were discussed in Section 4.2.11, Appendix B Compliance, of the LAR that discusses the DCPP Quality Assurance Program and Procurement Control Program. Section 4.2.11 states PG&E will audit 10M and CSI during the manufacturing phase under the PG&E Nuclear Procurement Program and associated directives. Section 4.2.11 of the LAR also discusses inspection activities, including that the vendors manufacturing facilities and service organizations undergo a general engineering inspection and familiarization, that more formalized inspections occur as the project progresses, and that prior to shipment of the equipment, inspections occur at the vendor facilities with the purchaser to verify manufacture of the equipment to approved drawings, project documentation and perform pre-FAT assembly, hardware configuration, and if applicable, software configuration. Section 4.2.11 of the LAR also discusses that after the equipment is shipped, it is inspected to verify the delivered materials are in general compliance with the equipment purchase specification(s) and the associated shipping documents, and that additional detailed inspections

May 14,12 No SrclRI DCPP PPS Open Item Summary Table Issue Description P&GE response:

occur by the engineering and implementation organizations to verify technical details of the received equipment as part of the staging for implementation.

PG&E would like to obtain more detail from the staff during the 5/16 CC to determine how to address this open item.

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Page 35 of 39 Comments 28 RA Software Management Plan The LAR, Attachment 3, states that PG&E is responsible for the following activities in the lifecycle: project initiation and planning phase, conceptual design phase, requirements phase, installation and checkout phase, operation phase, and maintenance phase. Further, Section 3.1.10 states that PG&E will follow the activities described before for software modifications. Please explain how PG&E will perform software modifications to the Tricon and ALS platforms once the PPS replacement project is completed.

New 29 RA PG&E response:

The control of the software modifications to the Tricon and ALS platforms once the PPS replacement project is completed will be by the Process Protection System Replacement Software Configuration Management Plan, which is being submitted as part of the Phase 2 document submittal by May

30.

Software Management Plan The LAR, Attachment 3, states that the PG&E Project Manager will share the responsibility for meeting the software quality goals and for implementing the software quality management throughout the project.

Please describe what responsibilities are going to be shared and how this is going to be performed.

New

May 14,12 ocpp PPS Open Item Summary Table Page 36 of 39 No SrclRI Issue Description P&GE response:

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments PG&E response:

PG&E would like to obtain more detail from the staff during the 5/16 CC to determine how to address this open item, after discussion of item 27.

30 RA Software Development Plan Section 7 of the Invensys Nuclear System Integration Program Manual (NSIPM) requires that non-conforming procedures shall be used to control parts, components, or systems which do not conform to requirements.

Invensys documents 993754-1-906, Software Development Plan, and 993754-1-905, PPS Replacement DCPP Project Management Plan, do not identify non-confirming procedures to be followed when deviations are identified and how deviations should be corrected.

Please provide this information.

New PG&E response:

IN PROGRESS 31 RJS Software Quality Assurance Plan:

IEEE 730 2002 stipulates in section 4 that "The SQAP shall be approved by the manager of each of the organizations having responsibilities in the SQAP. The PGE SYQAP has been approved by the PGE Diablo PPS Upgrade Project Manager and the Altran Project lead; however, there are several other organizations that have responsibilities delineated in the SOAP.

The managers of these organizations have not approved the SYQAP. The following organizations are assigned roles and Responsibilities within Section 3.4 of the SYQAP. Please explain the means by which these organizations have committed to comply with the requirements stated in the SYQAP.

  • Vendor IW Projects Managers
  • EOC Design Change Package Team
  • PGE Project Engineering Team
  • OA Organization
  • Testing and Integration Team
  • V&V Organization New

32 May 14,12 No SrC/RI DCPP PPS Open Item Summary Table Issue Description P&GE response:

PG&E response:

The software quality assurance plan was discussed in Section 4.11.1.1.1 of the LAR, which did not commit to IEEE 7302002 criteria in developing the SQAP. IEEE Standard 7-4.3.2-2003 [76] Clause 5.3.1 references IEEE Std 730-1998 for guidance but does not require it to be met.

PG&E would like to obtain more detail from the staff during the 5/16 CC to determine how to address this open item Status RA/ No.

(Date Sent)

RA/

Response

(Due Date)

Page 37 of 39 Comments RJS Section 4.2.7 "Power Supply" oftheLAR describes how power is supplied to the PPS. In this description, the 480V AC vital supply is described in the following ways.

  • First it is described as back-up common bus to the 120 V distribution panels. We cannot tell if this is through a transformer or if this refers to the alternate supply to the inverters.

It is also described as a supply to an inverter.

It is then described as supply to the battery charger New From these descriptions, it is not clear to the staff how these vital power sources are configured in relation to the 120VAC panels that feed the PPS.

Would it be possible to provide a simplified diagram to show the relationship between the 125V Batteries I DC Buses, Battery Chargers, Inverters, and the 120V AC distribution Panels that supply power to the PPS, PG&E response:

The following description clarifies the 120 V vital instrument AC power supply to the pps:

2 3

Safety-related 480 VAC from vital AC motor control center (MCC) is fed to the UPS and rectified.

Rectifier output is fed to the inverter and converted to 120 VAC.

Safety related vital DC bus power is fed to UPS as immediate backup supply. The vital DC bus is backed up by the safety-related 125 VDC station battery, which is charged from vital 480 VAC.

1

May 14, 12 DCPP PPS Open Item Summary Table Page 38 of 39 No SrclRI Issue Description P&GE response:

Status RAI No.

(Date Sent)

RAI

Response

(Due Date)

Comments 4

Inverter output is fed through a static switch with integral manual bypass switch to vital instrument AG power distribution panels.

5 On loss of inverter output. the static switch will select backup regulating transformer output (120 VAG) to distribution panels.

6 The backup regulating transformer receives input from the 480 VAG supply. The backup regulating transformer may be aligned via a transfer switch to either of two 480 VAG busses; the normal supply or an alternate supply. The alternate supply circuit breaker is normally open to prevent interconnection of redundant power supplies due to a failed transfer switch. The transfer switch may not be used under load.

Refer to the attached block diagram for additional detail.

May 14,12 DCPP PPS Open Item Summary Table Page 39 of 39 Figure 1 DCPP 120 Volt Vital Instrument AC System (Simplified) 480V BUS 1 H (2H)

Transfer UPS IY14 SD11 (21)

TRY 11 (21)

To Protection Set I Legend:

AC DC SD12 (22) i TRY 12 Transfer Switch AC DC SD13 (23)

(24)

Transfer Switch Switch To Protection Set II To Protection Set IV AC To Protection Set m IY:

UPS and DC-AC Inverter PY:

120 VAC Distribution Panel SO:

125 VDC Distribution Panel TRY:

480 VAC/120 VAC Transformer and Regulator Normal Power Flow (N)

Bypass (120 VAC)/Backup (125 VDC) Power Flow Alternate Bypass Power Flow (A)

Unit 1 Component ID's are shown; Unit 2 Component ID's are in parentheses. For example, PY11 is Unit 1 Vital Instrument AC Distribution Panel 1; PY21 is Unit 2 Vital Instrument AC Distribution Panel 1.

DCPP PPS Replacement Factory Acceptance Testing (FAT)

A. Introduction An integrated FAT, with the ALS connected to the Tricon will not be performed because the ALS and Tricon FAT will be performed in different locations. The overlapping test methodology illustrated in Figure 1 and described below will ensure that all specified PPS safety function requirements for each platform are verified at the Respective FAT'.

B. Discussion The ALS and the Tricon are directly connected via the analog Reactor Coolant System temperature channels. The ALS provides Class IE signal conditioning for the Pressurizer Vapor Space temperature, Reactor Coolant System wide range temperature and narrow range RTD inputs to the Overpower Delta Temperature (OPDT) and Overtemperature Delta Temperature (OTDT) thermal trip functions due to its improved ability to process 200 Ohm RTD inputs vs. Triconex. The ALS processes the resistance (ohms) RTD input signals and transmits the temperature values to the Tricon as analog 4-20 mA signals for the respective Protection Set.

The resistance to milliamp conversion will be tested at the ALS FAT to verify that all requirements specified for converting the resistance to current are met. The Tricon FAT will test these channels by injecting the corresponding 4 to 20 mA signals into the Tricon and verifying that all requirements specified for the temperature channels are met. After the FAT, the equipment will be shipped to DCPP and then both systems will be integrated to perform the Site Acceptance Testing (SAT) which will test the analog interface directly along with others that cannot be tested at the FAT, such as the connection to the Plant Data Network (PDN) Gateway Computer.

Within each Protection Set, the ALS and the Tricon are both connected via digital communication links to the Maintenance Workstation (MWS) as shown in Figure 1; thus, the digital MWS is shared by the ALS and Tricon portions of the replacement PPS. Tricon communications with the MWS are bidirectional (read/write) using Triconex NET2 protocol via the fiberoptic media 4352AN Tricon Communications Module (TCM). As discussed in Section 3.1.2.9 of the Triconex V1 0 SER [ML1209008902], the TCM handles all Tricon communications with external devices, thus providing functional isolation. The ALS communications with the MWS are via the unidirectional TXB2 communication links from the ALS-102 board. The TXB2 communication links are electrically isolated at the ALS-102. Unidirectional communications provides functional isolation from the MWS. The unidirectional nature of the links will be verified at FAT as described below.

For each Protection Set, the ALS and the Tricon are both connected via digital communication links to the Plant Data Network (PDN) Gateway computer as shown in Figure 1. A port aggregator network tap is connected between the Tricon and the MWS via bidirectional Port A and Port B. All network traffic between Port A and Port B is reflected to unidirectional Port 1.

There is no communication path from Port 1 to either Port A or Port B. In addition to the 1 The gateway switch and gateway computer(s) shown shaded in Figure 1 were installed in the plant by a previous project. As existing installed plant equipment, these two items need not be tested explicitly at the FAT or SAT.

1

DCPP PPS Replacement Factory Acceptance Testing (FAT) functional isolation provided by the TCM, the port aggregator provides further functional isolation between the Gateway computer and the Tricon. The ALS communications with the Gateway computer are via the unidirectional TXB1 communication links from the ALS-102 boards. The TXB1 communication links are electrically isolated at the ALS-102. Unidirectional communications provides functional isolation from the Gateway computer. The unidirectional nature of the links will be verified at FAT as discussed below.

The ALS also communicates with ALS Service Unit (ASU) application software in the MWS via the bidirectional Test ALS Bus (TAB) communication link. Per the ALS Topical Report

[ML102570797], Table 5-2, Item 8, the TAB bus is used for communication of information from and to the ASU with the ALS Platform. This communication process is independent from the safety function logic. To enable the TAB bus to the ASU requires the setting of a switch which, when enabled, is alarmed locally and in the main control room... The TAB bus and its interfaces are designed such the buses are non-intrusive in that the bus cannot interfere with processing of any information or data on the Reliable ALS Bus (RAB). The FAT will verify that the TAB, when enabled, does not interfere with ALS logic processing.

Per the ALS System Design Specification 6116-00011 [ML110600695], the ALS allows for online maintenance of an operational system such as the bypassing and control of individual ALS outputs and the calibration of individual ALS 110 without affecting adjacent non-bypassed safety channels. The ALS Topical Report, Section 3.4, describes calibration of an analog input/output channel using the ASU. The ASU is used to select the channel to be calibrated and place that particular channel in BYPASS mode before the external test equipment is connected to the channel wiring on test points located on the field terminal blocks. The channel is placed in CALIBRATE mode to perform the calibration. ALS Topical Report Section 3.5 explains how specific digital output channels may also be placed in BYPASS or OVERRIDE mode from the ASU. The ALS FAT will verify that individual ALS outputs may be bypassed and controlled and individual ALS 1/0 may be calibrated without affecting adjacent non-bypassed safety channels.

For the Tricon FAT, PG&E will provide the Maintenance Workstation (MWS), port aggregator network tap, network switches, and media converters as needed to test the complete interface between the MWS and the Tricon. Each Protection Set has its own Maintenance Workstation (MWS). The MWS is not shared between or among Protection sets. The ALS Service Unit (ASU) software will be loaded on the MWS to facilitate identification of any interaction between the MWS Wonderware application, the ASU software, andlor the MWS operating system.

The Tricon FAT will be performed on all four protection sets. Each protection set will be integrated with all equipment necessary to support FAT. The functionality of the MWS will be tested during the FAT to verify requirements specified in the FRS and Tricon SRS. The FAT will verify correct two-way data communications between the Tricon and the MWS through Ports A and B of the port aggregator. The FAT will verify that there is no inbound communication path from network port aggregator tap Port 1 to either Port A or Port B.

PG&E will provide another MWS for the ALS FAT. The port aggregator is not required for the ALS. The communications from both TxB1 and TxB2 one-way RS-422 ports will be tested to verify all specified data is being transmitted correctly. The MWS Wonderware application will be running to display the read only parameters. The ASU software running on the MWS will be tested during the FAT to verify its functionality and to identify any interactions between the ALS 2

DCPP PPS Replacement Factory Acceptance Testing (FAT)

ASU software, the MWS Wonderware application, and/or the MWS operating system. The two way EIA-485 port will be tested with a mechanical switch to verify the ability to update parameters and to isolate the MWS from the ALS.

All boards of the same type in the ALS platform have the same capabilities. The boards can be configured by the user to meet the requirements of any protection set. The FAT will be performed on each protection set configuration, including power supplies, the MWS, and all associated equipment that supports the safety function for the specific protection set. That is, Protection Set 1 will be configured and tested with all the associated sensor inputs and appropriate loads on the digital and analog outputs. Upon completion of testing, the equipment will be reconfigured as Protection Set 2 and tested. The same process will be used for Protection Sets 3 and 4.

The PG&E SAT will be performed on an integrated system. The connection of the temperature channels from the ALS to the Tricon will be verified during the SAT. The SAT will verify functions and connections that cannot be tested at the FAT, prior to installation in the plant. The integrated system used for SAT will also be used to perform training and to develop and verify operational and maintenance procedures. Any application software changes from the time the equipment arrives at PG&E facilities until its installation in the plant is subject to configuration management controls.

C. FAT Plan Outline The Tricon FAT will test the safety-related functions specified in the LAR and will also test the following interfaces:

1. Safety-related 4-20 mAdc analog temperature input signals from ALS; these signals will be generated by a loop simulator or equivalent test equipment.
2. The FAT will verify bidirectional non-safety NET2 communications between Tricon TCM1 and TCM2 and the MWS through the two Ethernet media converters, and Ports A and B of the two port aggregator network taps.
3. ALS data acquisition and display and ALS Service Unit (ASU) software will be running on the MWS during the Tricon FAT to identify program conflicts and interactions.
4. The FAT will verify no inbound communication path from Port 1 of the port aggregator network tap to either Port A or Port B exists, per LAR commitment.

The ALS FAT will test the safety-related functions specified in the LAR and will also test the following interfaces:

1. Safety-related 4-20 mAdc analog temperature output signals to Tricon; these signals will be monitored by external equipment to verify conversion and scaling. The ALS analog temperature output channels will be terminated with 250 ohm resistors to simulate the Triconex FTP module. Voltage across the resistors will be measured to verify analog output function.

3

DCPP PPS Replacement Factory Acceptance Testing (FAT)

2. Unidirectional only non-safety EIA-422 communications from the ALS-102 "A" and ALS 102 "B" TXB1 channels. The TXB1 channels will be monitored during ALS FAT to verify data protocol. The test will verify no inbound communications via.the TXB1 channel to either ALS-102 "A" or "B".
3. Unidirectional only non-safety EIA-422 communications from the ALS-102 "Au and ALS 102 "B" TXB2 channels to the MWS. The TXB2 channels will be monitored during ALS FAT to verify data protocol. The test will verify no inbound communications via the TXB2 channel to either ALS-102 "A" or "B",
4. Tricon data acquisition and display and ALS Service Unit (ASU) software will be running on the MWS during the ALS FAT to identify program conflicts and interactions.
5. Bidirectional EIA-485 TAB communication between ALS Chassis "Au and Chassis "B" and ASU software running on MWS can take p[lace only if the communication links are physically connected and enabled. The test will verify there is no communication between the ALS chassis and the ASU if communications are not physically connected and enabled.

4

DCPP PPS Replacement Factory Acceptance Testing (FAT)

Figure 1 Replacement PPS Acceptance Testing with Overlap Prot Set! AlS "A*

Pro1 Set II ALS'A' Prot Ss1 !I! ALS

  • A' P(otsetIVALS~A' Prot Set I AlS 'B' Proi Set 11 ALS"B' Prot Sellil ALS '8' Prat Set IV ALS 'B~

,I

/'

100Br;ye;o\\c~pper-t).,.,..!:--.., L.....................::..:I I

IT,p of 2)

RS*422 Cu from AlS

-~~.. P::.t~*

I

~~=r:J

\\

Test ALS Bue (TAB)

~

", ",9'..... Disconnected V!,'hen not In use

\\

i

,/

'f,pfOrALS 'A' aodALS'B')

1QQB...T ICo"""r)

I' i-....l I

J

\\

11 j JRS-.SS

\\

/

Optical Fiber I

,,;I I

I I

ITCM117~k~M217R) i I I j I

(Typ of 2)

Class II I

,I,

,.,1 RS*422 Cu to Gateway Compvter I

Class U Clas~

{TXB1

  • TYP for ALS 'A' and ALS "B}

CIS6S1 I

,.. !-rl'-ni'i-r'i'nTrl'-nr'trl

. /'R~mcu,ok! i Iii............................

I I

Tnplicated

.,1 Rs-4B5 I

i I

1/0 Bus (Copper)

  • I 1

I L

I I

I I

I I I

Tnr:>>icated Optical Fiber I I

I I

I I

I L

\\ -

{TXB2 - TypforJ:lS <A":

I and!>.LS ~"i i

I Clan Il (Exoopt TAB) 4-20 mA Cla6s1 I

Analofl RTDSlgneis I,

I ALS"A' TCM1 (7L)

  • (TypfotALS'A" I

TCM2(7R)

\\

atidALS"B")

NET1 iNot Used}

I PrimaryRXM "I.

/'

AlS'8" ProlSel1 Prot S.I I Scope of I'

I Glasa! I Prot Set 1 Class II I Remol. RXM I

I

/

/

ALS ALS FAT Legend:

Scope of Tricon FAT Mull~Mode Optical Fiber RS-4221R8-485 Serial or 4*20 rnA Analog Copper 5

Meetlng Notlce I'OFFICE DORLlLPL4/PM DORLlLPL4/LA NRRIDE/EICB DORLlLPL4/BC DORLlLPL4/PM II NAME JSebrosky JBurkhardt RStattel MMarkley JSebrosky ilDATE 6/4/12 5/31/12 6/5112 6/8/12 6/11/12