MONTHYEARML23320A1122024-01-18018 January 2024 NRC to Fws, Concurrence with Endangered Species Act Determinations for North Anna Power Station, Units 1 and 2, Subsequent License Renewal, Issuance of Draft Supplemental Environmental Impact Statement, and Opportunity for Public Comment ML23355A2722023-12-21021 December 2023 NRR E-mail Capture - Schedule Revision for Emergency Preparedness Staff Augmentation Times License Amendment Request ML23318A1172023-11-13013 November 2023 NRR E-mail Capture - Formal Issuance of RAIs for North Anna Technical Support Center (TSC) License Amendment Request (LAR) (L-2023-LLA-0006) ML23312A2962023-11-0808 November 2023 Email - Surry Relief Request Acceptance Review Results; Surry Unit 1 and 2 IST P-3 P-4 Pumps ML23312A2022023-11-0808 November 2023 Relief Request Acceptance Review Results; IST Impracticality P-1 P-2 RHR Containment Pumps ML23283A3262023-10-10010 October 2023 Update Acceptance Review Status Surry TS Change Apply RG 1.97, Rev 3 Instrumentation to Lhsi ML23257A2092023-09-14014 September 2023 NRR E-mail Capture - Formal Issuance of 2nd Round RAIs for Surry Units 1&2 and North Anna Units 1&2 Emergency Plans LAR ML23255A2772023-09-12012 September 2023 Acceptance of Requested Licensing Action: Surry TS Change, Lhsi Indication and Instrumentation ML23243A9862023-08-31031 August 2023 NRR E-mail Capture - Draft RAIs for EP Staff Augmentation Times LAR (L-2022-LLA-0166) ML23219A1602023-08-0707 August 2023 003 Radiation Safety Baseline Inspection Information Request ML23193A9552023-07-12012 July 2023 NRR E-mail Capture - Acceptance Review for VC Summer and Surry Relief Request (L-2023-LLR-0029) ML23187A1122023-07-0606 July 2023 TSC Relocation LAR RAIs ML23171B0522023-06-20020 June 2023 NRR E-mail Capture - RAI for Review of Appendix F to DOM-NAF-2-P (Redacted) ML23107A2212023-04-10010 April 2023 Amendment Turbine Building Wind Load Basis Reclassification License Amendment Request - State Consultation No Comment ML23075A0232023-03-15015 March 2023 NRR E-mail Capture - RAI - License Amend Req (LAR) to Revise Tech Spec (Ts) 3.6.8 Limiting Condition for Operation to Remove Refueling Water Chemical Addition Tank and Replace the Containment Sump Buffer North Anna, 1 and 2 (L-2022-LLA-0162 ML23068A0242023-03-0808 March 2023 RAI Issuance Fuel Handling Trolley LAR ML23067A2162023-03-0707 March 2023 NRR E-mail Capture - RAI for North Anna, 1 & 2, Surry 1 & 2, Millstone, 2 & 3, Request for Approval of App. F Fleet Report DOM-NAF-2-P, Qual of the Framatome ORFEO-GAIA and ORFEO-NMGRID CHF Correlations in the Dominion VIPRE-D Computer Code ML23060A0932023-03-0101 March 2023 NRR E-mail Capture - Formal Issuance of RAIs for Surry/North Anna Emergency Plans LAR ML23059A2282023-02-28028 February 2023 NRR E-mail Capture - Draft RAIs for Containment Buffer Change to Natb (L-2022-LLA-0162) ML23054A2412023-02-23023 February 2023 NRR E-mail Capture - Formal Issuance of RAIs for Surry Turbine Building Tornado Reclassification ML23039A1712023-02-0808 February 2023 NRR E-mail Capture - Acceptance Review for Technical Support Center (TSC) Relocation (L-2023-LLA-0006) ML23018A0352023-01-17017 January 2023 NRR E-mail Capture - Acceptance Review for Fleet Report Re Appendix F of DOM-NAF-2-P (L-2022-LLT-0003) ML23018A1642023-01-17017 January 2023 Formal Issuance of RAIs for Surry ISI Alternative for SG Welds, 30 Day Calendar Response Period (Email) ML22354A0352022-12-19019 December 2022 Acceptance Email TSC Relocations LAR ML22349A2102022-12-15015 December 2022 Formal 43-day Request for Additional Information Issuance for Surry Turbine Building License Amendment Request ML23058A1442022-12-0909 December 2022 Record of Surry Verbal Relief Request Authorization - V-01 Mechanical Agitation Vavle 1-SI-241 ML22342B1472022-12-0808 December 2022 NRR E-mail Capture - Acceptance Review for LAR Re NAPS Post LOCA Buffer Change (L-2022-LLA-0162) ML22342A1002022-12-0707 December 2022 Relief Request Acceptance Review Results; Surry ISI Alternative, Prz and SG Welds and Nozzles ML22335A4842022-12-0101 December 2022 NRR E-mail Capture - Acceptance Review for LAR North Anna Power Station - Units 1 and 2 and Surry Power Station - Units 1 and 2 Emergency Plan Staff Augmentation Times (L-2022-LLA-0166) ML22277A7252022-10-0303 October 2022 Additions to Turbine Bldg Wind Load Audit ML22256A3032022-09-13013 September 2022 Change in Completion Hours Estimate Amendment Turb Bldg. Loading Basis Change LAR ML22256A2312022-09-13013 September 2022 Acceptance Email TS Change for New Fuel Framatome Agora and SFP Criticality Review ML22242A0452022-08-23023 August 2022 NRR E-mail Capture - Dominion GL 04-02 Response Draft RAIs (L-2017-LRC-0000) ML22224A1442022-08-11011 August 2022 Acceptance Email TS Change AFW Cross Connect AOT LAR ML22223A1182022-08-0404 August 2022 2022004 - Plant Surry RP Inspection - Document Request Letter E-mail ML22200A1032022-07-19019 July 2022 Acceptance of Requested Licensing Action: Surry Risk-Informed Approach for Tornado Classification of the Fuel Handling Trolley Support Structure ML22193A0052022-07-11011 July 2022 Acceptance of Requested Licensing Action: Admin Changes to Technical Specifications ML22174A3552022-06-23023 June 2022 NRR E-mail Capture - Acceptance Review for Dominion Fleet LAR to Implement TSTF-554 (L-2022-LLA-0078) ML22161B0052022-06-0909 June 2022 Acceptance Email TSTF 547 LAR ML22137A1622022-05-17017 May 2022 Acceptance of Requested Licensing Action Amendment Turb Bldg. Loading Basis Change License Amendment Request ML22110A2052022-04-19019 April 2022 Formal Issuance of RAIs for Post LOCA Buffer Change LAR ML22104A0252022-04-14014 April 2022 NRR E-mail Capture - Dominion Presentation Slides for April 21, 2022 Public Meeting on Emergency Preparedness Submittal for the North Anna Power Station and the Surry Power Station ML22083A2102022-03-24024 March 2022 NRR E-mail Capture - Draft RAI - Relief Request N2-14-LMT-003 Fourth Ten Year Inservice Inspection Interval ML22077A0542022-03-18018 March 2022 Change in Engineering Hours Estimate Surry Ph Buffer LAR Acceptance ML22032A0962022-02-0101 February 2022 002 Radiation Safety Baseline Inspection Information Request ML22018A0272022-01-18018 January 2022 2022 All RFI Responses - Exercise and Program Inspections - Revl ML22012A0572022-01-11011 January 2022 Issuance of RAIs for Surry Unit 1, Spring 2021 Steam Generator Tube Inspection ML22007A2672022-01-0707 January 2022 NRR E-mail Capture - North Anna, Unit 2, ASME Section XI Inservice Inspection Program Relief Request N2-14-LMT-003 Fourth Interval Third Period Limited Examinations (L-2021-LLR-0088) ML21340A1642021-12-0606 December 2021 Acceptance of Requested Licensing Action Amendment ML21335A0812021-12-0101 December 2021 NRR E-mail Capture - Acceptance Review for OMN-28 Request Alternative to ISTC-3700, Position Verification Testing (L-2021-LLR-0086) 2024-01-18
[Table view] |
Text
SC1.
Thompson, John /
From: Bernardo, Robert Sent: Tuesday, September 13, 2011 7:24 AM To: Thorp, John Cc: Thompson, John
Subject:
North Anna AIT and Surry Seismic instruments
- John, I assume you've seen the clearinghouse information on Surry seismic instruments. Region has a lot of questions for the licensee, such as: Will routine surveillance tests find this condition? Un-centered because of the earthquake, or some other cause? How long? What is the periodicity of the surveillance testing? When was the last surveillance done? Region didn't have any of this information on Monday, expect to hear more over the next couple of days.
FYI, brief (or at least as brief as I can be @) status of the AIT at North Anna:
I/nfor ion cund~e e notes ain preli yinform n in th s -mel *ternal co unic on of o ating exp ence The es are b -decisio and m onta ensitiv rma n There nt inee fo ist'tion out the ag Team was on site week of 8/30, worked from home offices week of 9/6, and is back on site for this week (9/12).
Status:
- No significant damage to safety related systems (including class I structures) has been identified through site walk-downs nor has equipment degradation been detected through plant performance and surveillance testing following the earthquake.
- AIT continues to be the correct level of response.
- Potential Issues, which are unresolved at this time and may be documented as URIs:
o 2H EDG Cooling Water Jacket Leak - Had to use SBO EDG when 2H EDG was secured.
Licensee (and AIT) is leaning toward this being an installation issue (gasket was replaced in 2009).
o UJ EDG Frequency Oscillations (0.5 hertz +/-, right at TS limit, EDG was operating fine, nothing to indicate that it would have failed - licensee still owes information) o Seismic Instrumentation Power Supplies and locations. Seismic instruments lost power briefly during the event and didn't alarm. Instrumentation is used to determine EAL level, as well as operability. Know that at least Surry has similar set up (see potential generic issues).
o One or more seismic instruments in containment had polarity reversed. No other information.
o Safety related instrumentation qualification. AIT has list of a variety of instrumentation (Level, DPs, etc.,) that had various anomalies (oscillations, erratic, etc) during the event. Some may be attributed to actual system response. Question is, if the instrumentation is seismically qualified, why are there erratic readings?
o The "A"AFW pump terry turbine Lube Oil level alarm switch is powered from a non-vital source.
Therefore, operators received the alarm when the site lost power. Operators didn't understand why they had the alarm. Checked the oil, verified level was OK, and started turbine without issue. This is looking like an operator knowledge/procedure issue, maybe design issue?
o Missing orifice plates from the UJ and 2J EDG Engine driven coolant pumps. Discovered when working on a mechanical seal leak on one of the pumps. Operability determination has been completed.
- Potential Generic Issues:
o Seismic instrumentation power supplies. AIT knows that at least Surry has the same issue
o Seismic monitor locations are on structures, not on the "free field" (OBE/SSE based on "Free field" acceleration levels."
o No seismic monitors on ISFSI pads.
On September 8, Dominion representatives briefed the NRC staff on Overview of the 8/23 Earthquake Response and Restart Readiness Demonstration Plan. The slides are available in ADAMS (ML11252A006). Dominion reported that:
o OBE and DBE criteria were exceeded; However, Cumulative Absolute Velocity (CAV, a concept used by the Electric Power Research Institute (EPRI) to address OBE Exceedance in EPRI NP-5930) calculations indicate that significant damage would not be expected.
o Extensive actions are underway to inspect, evaluate, test and repair, if necessary, SSCs to ensure they are capable of performing their required design basis functions. Results are confirming the CAV expectations.
o To date, no safety related SSCs have been identified that require repair.
o Long term actions are planned to improved plant seismic monitoring capability and to re-evaluate plant OBE and DBE criteria in conjunction with the resolution to Generic Issue (GI)-
199,
- RCA for the actual cause of the trip is in progress. Licensee still believes negative flux trip came in and caused trip BEFORE LOOP. Licensee evaluating a number of different scenarios which could have caused this (in both plants).
- HQ staff (NRR/DE/EMCB) has lead on Action plan/Communication plan. Still being drafted.
- Team believes they will complete all charter items by 9/16, and plan to hold exit meeting with the licensee on Friday, 9/16.
Bob Bernardo Reactor Systems Engineer US Nuclear Regulatory Commission NRR/DIRS/IOEB Mail Stop: O-7C02A 301-415-2621 Robert.Bernardo@nrc.gov 2