ML110420305

From kanterella
Jump to navigation Jump to search

Entergy - Response to NRC Request for Additional Information Dated January 10, 2011, to Support the Review of Setpoint and Setpoint Tolerance Increases for Safety Relief Valves (SRV) and Spring Safety Valves (SSV)
ML110420305
Person / Time
Site: Pilgrim
Issue date: 01/31/2011
From: Rich Smith
Entergy Nuclear Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
TAC ME3543, 2.11.007
Download: ML110420305 (256)


Text

Entergy Nuclear Operations, Inc.

wm'En terg Pilgrim Nuclear Power Station 600 Rocky Hill Road Plymouth, MA 02360 Robert G. Smith, P.E.

Site Vice President January 31, 2011 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555-0001

SUBJECT:

Entergy Nuclear Operations, Inc.

Pilgrim Nuclear Power Station Docket No. 50-293 License No. DPR-35 Entergy Response to NRC Request for Additional Information dated January 10, 2011, to support the review of Setpoint and Setpoint Tolerance Increases for Safety Relief Valves (SRV) and Spring Safety valves (SSV) (TAC No. ME3543)

REFERENCE:

1. Entergy Letter No. 2.10.016, Proposed License Amendment to Technical Specifications: Revised Technical Specification for Setpoint and Setpoint Tolerances Increases for Safety Valves (SRV) and Spring Safety Valves (SSV), and Related Changes, dated March 15, 2010.
2. NRC Letter, Request for Additional Information-Pilgrim Nuclear Power Station-To Support the Review of Setpoint and Setpoint Tolerance Increases for Safety Relief Valve and Spring Safety Relief Valve, (TAC No. ME3543), dated January 10, 2011 LETTER NUMBER: 2.11.007

Dear Sir or Madam,

This letter supports Entergy's application for the Proposed License Amendment submitted by Reference 1 and dockets Entergy's response to the NRC Request for Additional Information (RAI) forwarded to Entergy by letter dated January 10, 2011.

Enclosure 1 provides the Entergy response to the NRC RAI (Reference 2). Enclosure 1 contains Attachment 1, Pilgrim calculation No. IN1 -110, Rev. 1, for ATWS Trip Level Setting and Attachment 2, Pilgrim Surveillance procedure, 8.M.1-29, Rev. 50, ATWS Trip Unit Calibration Test.

Enclosu- 1".provides re-typed Pilgrim-specific Technical Specification and co-es pages.

Enclosure 3 is Revision 2 of GEH Report, NEDC-33532P. This report was originally provided in Reference 1, and is currently revised to include revised information on the ATWS Trip Level Setting. The report contains proprietary information as defined in 10 CFR 2.390, "Public inspectic (,, exceptions, request for withholding." General Electric Hitach'>EH), as the owner of the proprietary information, has executed an Affidavit provided within the report, which identifies the information has been handled and classified as proprietary, is customarily held in confidence, and has been withheld from public disclosure. Accordingly, it is requested the proprietary information (Enclosure 3) be withheld from public disclosure in accordance with the

Entergy Nuclear Operations, Inc. Letter Number: 2.11.007 Pilgrim Nuclear Power Station Page 2 provisions of 10 CFR 2.390 and 10 CFR 9.17, "Agency records exempt from public disclosure."

A non-proprietary version of the report is provided as Enclosure 4.

The Rev.2 of GEH Report NEDC-33532P replaces all prior revisions of the report and does not change the scope of the Proposed License Amendment submitted by Reference 1; instead it provides information in response to NRC RAI (Reference 2).

Entergy's response to this RAI supports the proposed License Amendment for Setpoint and Setpoint Tolerance Increases for Safety Relief Valves (SRV) and Spring Safety Valves (SSV),

and Related Changes and the No Significant Hazards Consideration determination submitted by Reference 1.

There are no commitments made in this submittal.

If you have any questions, please call Mr. Joseph Lynch, Pilgrim Licensing Manager at 508-830-8403.

I declare under penalty of perjury that the foregoing is true and correct. Executed on the 31 dayof JIANtAAP ,2011 Sincerely, Robert Sm~I Site Vice President : Entergy Response to NRC Request for Additional Information, dated January 10, 2011 (235 pages) : Re-Typed Technical Specification and Bases Pages (14 Pages) : (Proprietary Version) GE Hitachi Nuclear Energy Report, NEDC-33532P, "Pilgrim Nuclear Power Station Safety Valve Setpoint Increase", Rev. 2, January 2011 (74 Pages) : (Non-Proprietary Version) GE Hitachi Nuclear Energy Report, NEDC-33532, "Pilgrim Nuclear Power Station Safety Valve Setpoint Increase", Rev. 2, January 2011 (71 Pages)

Entergy Nuclear Operations, Inc. Letter Number: 2.11.007 Pilgrim Nuclear Power Station Page 3 cc: Regional Administrator, Region 1 Mr. Richard Guzman, Project Manager U.S. Nuclear Regulatory Commission Plant Licensing Branch I-1 475 Allendale Road Office of Nuclear Reactor Regulation King of Prussia, PA 19406 U.S. Nuclear Regulatory Commission (W/Enclosures 1 and 2 only) One White Flint North, O-8C2 11555 Rockville Pike John Giarrusso Rockville, MD 20852 Mass Emergency Management Agency (W/ Enclosures 1, 2, 3, and 4) 400 Worcester Road Framingham, MA 01702 Senior Resident Inspector (W/ Enclosures 1 and 2 only) Pilgrim Nuclear Power Station (W/ Enclosures 1 and 2 only)

Robert Gallaghar, Acting Director Massachusetts Department of Public Health Radiation Control Program/

Schrafft Center 529 Main Street, Suite 1M2A, Charlestown, MA 02129-1121 (W/Enclosures 1 and 2 only)

ENCLOSURE 1 To Entergy Letter Number 2.11.007 ENTERGY RESPONSE TO NRC REQUEST FOR ADDITIONAL INFORMATION DATED JANUARY 10, 2011 To Support the Review of Setpoint and Setpoint Tolerance Increases for safety Relief valve and Spring Relief Valve (TAC No. ME3543)

(Total 235 pages)

Includes the following:

  • Response to NRC RAI (3 pages)

" Attachment 1: Pilgrim Calculation No. IN1-110, Rev. 1 (80 pages) and

  • Attachment 2: Pilgrim Calibration Procedure, 8.M.1-29, Rev. 50 (152 pages)

ENCLOSURE 1 to Enterpy Letter No. 2.11.007 ENTERGY RESPONSE TO NRC REQUEST FOR ADDITIONAL INFORMATION (RAI) TO SUPPORT THE REVIEW OF SETPOINT AND SETPOINT TOLERANCE INCREASES FOR SAFETY RELIEF VALVES AND SPRING SAFETY VALVES, AND RELATED CHANGES (TAC No. ME3543)

Reference:

1. Entergy Letter No. 2.10.016, Proposed License Amendment to Technical Specifications:

Revised Technical Specification for Setpoint and Setpoint Tolerances Increases for Safety Valves (SRV) and Spring Safety Valves (SSV), and Related Changes, dated March 15, 2010.

2. GE Hitachi Nuclear Energy Report, NEDC-33532P, "Pilgrim Nuclear Power Station Safety Valve Setpoint Increase," Rev. 2, January 2011 (see Enclosure 3)

NRC REQUEST FOR ADDITIONAL INFORMATION (RAI) 1:

1. Definition of 'Trip Level Setting" in TS Table 3.2-G:

Clarify what the column tile, 'Trip Level Setting," in TS Table 3.2-G, "Instrumentation that initiate Recirculation Pump Trip and Alternate Rod Insertion," represents compared to the setpoint terms listed in Figure 1 of Regulatory Guide (RG) 1.105, "Setpoints for Safety-Related Instrumentation," Revision 3, dated December 3, 1999.

Response

The term 'Trip Level Setting" in TS Table 3.2-G represents the Allowable Value (AV).

The proposed value of <1210 psig is the Allowable Value, which is also the notify Shift Manager value. It is the limiting value that the instrument setpoint may have when tested periodically, beyond which appropriate action will be required (See Response to RAI 3).

The instrument setpoint is 1203.6 +/- 1.9 psig and represents the process value at which the switch is expected to change state. The difference between the two values represents the allowable value to trip setpoint margin. The difference between the two values represents errors associated with the as-found tolerance and drift.

NRC RAI 2

2. Setpoint Calculation Methodology:

Provide documentation of the methodology used for establishing the limiting trip setpoint or normal trip setpoint and limiting acceptable values for the as-found and as-left setpoints as measured during the periodic surveillance testing. Documentation should:

  • Include calculations.
  • Indicate Analytical Limits and/or other limiting design values.
  • Indicate the source of the parameters (Tolerances) used in calculating these three setpoint values and how they comply with RG 1.105 to ensure the 95/95 confidence level is achieved and these setpoints are adequate for the surveillance test interval specified in the plant surveillance requirements.
  • As applicable, provide reference(s) to NRC approved documents related to this setpoint calculation.

RESPONSE TO RAI 2 Calculations and Analytical Limits to this Enclosure provides the calculation for ATWS RPT trip level setting, which provides analytical limits and design limiting values.

Source Parameters (Tolerances) for Setpoint Values Entergy has applied the process delineated in RG 1.105 as a means to calculate the analytical limits and design limiting values.

ATWS RPT/ARI instrumentation is not LSSS instrumentation as defined by the NRC in the Standard Technical Specification, Rev. 3, page B3.3.4.2-1 and ATWS is not assumed in the safety analysis. ATWS instrumentation is not safety-related, it is classified as "Management-Q" in accordance with NRC guidance provided for the implementation of ATWS Rule, and for the purpose of setpoint calculation, it is treated in the same manner as safety-related instrumentation.

NRC Approved Documents Related to Setpoint Calculation NRC approved Pilgrim License Amendment 151, dated April 6, 1994 (TAC Nos.M83787, M87191, and M88390) for the 24-month fuel cycle operation. Pilgrim applied for the License Amendment 151 in accordance with the guidance of NRC Generic Letter 91-04, "Changes in Technical Specification Surveillance Intervals to accommodate a 24-month Fuel Cycle". As described in the application for the License Amendment 151, Pilgrim performed setpoint calculations and drift evaluations using the guidance provided in Regulatory Guide 1.105, Rev. 2, Regulatory Position C, which specified ISA-$67.04-1982, "Setpoints for Nuclear Safety-Related Instrumentation Used in Nuclear Power Plants" for ensuring that the instrument setpoints in safety-related systems are initially within and remain within the technical specification limits.

Pilgrim setpoint calculations and drift evaluations using the ISA-$67.04-1982 practice provides for a 95/95 tolerance limit as acceptable criteria for uncertainties and forms the licensing bases for the Pilgrim setpoint methodology.

The ATWS RPT/ARI setpoint calculation is documented in Pilgrim Calculation No. IN1i-110, (Attachment 1) and follows the ISA-$67.04-1982 practice.

NRC RAI 3

3. Test Procedures:

Describe the measures to be taken to ensure that the associated instrument channels are capable of performing specified functions in accordance with applicable design requirements and associated analysis, including:

" Information on the controls employed to ensure that the as left trip setting after completion of periodic surveillance is consistent with the setpoint methodology.

  • Discussion on the plant corrective action process for restoring the channels to operable status.

RESPONSE TO RAI 3 The setpoint calculation is documented in Pilgrim Calculation No. IN1-110, Revision 1 dated January 11, 2011. Surveillance procedures are utilized to control the setpoints, record as-found values, record and control as-left values, and identify setpoint drift issues. Pilgrim staff follows procedure EN-DC-1 15, "Engineering Change" process to ensure that calculated setpoints are translated accurately from design documents and associated analysis into procedures. The station process includes the following elements.

1. Instrumentation and Control (I&C) Design personnel prepare the design documents including calculations to determine the setpoint that will ensure that the protective action occurs at the proper value.
2. The set point is implemented via an Engineering Change process, which complies with the applicable requirements of 10 CFR 50, Appendix A and B, and licensing basis requirements.
3. I&C Maintenance personnel translate the calculated calibration values into the calibration procedure, as part of the EC process. With respect to the ATWS/RPT Trip Setting Level value, Pilgrim has implemented a surveillance procedure, 8.M.1-29, "ATWS Trip Unit Calibration Test' (Attachment 2). The procedure reflects the Technical Specification Value included in TS Table 3.2.G/4.2.G, and includes the following:
  • Acceptance Criteria, based on controlled engineering documents
  • Corrective Action
  • Acceptance Verification
  • I&C Procedure Feedback Form
4. Procedure 8.M.1-29 requires that a condition report be written in accordance with Entergy procedure, EN-LI-102, "Corrective Action Process", if the technician finds an as-found value is outside the no adjust limits. The corrective action process includes operability review, reportability review, engineering evaluation, and corrective actions to restore the equipment to operable status. Condition reports are assigned to Engineers for evaluation of performance issues discovered during periodic surveillances including repetitive findings of excessive drift.

Pilgrim EN-LI-102, "Corrective Action Process" complies with the requirements of 10 CFR 50, Appendix B. The EN-LI-102 process addresses equipment and instrument operability, restoring operability, interim acceptance of degraded conditions, and compensatory measures.

Upon receipt of the approved SRV and SSV License Amendment, Pilgrim procedure 8.M.1-29 will be revised to include revised Technical Specification values and applicable attributes for the ATWS/RPT setpoint calculations and control program.

Attachment 1 to ENCLOSURE 1 To Entergy Letter No. 2.11.007 Pilgrim Calculation No. IN1-110, Rev. 1, "Setpoint Calc for PIS263-123A, B, C, and D-Reactor High Pressure ATWS" (80 pages)

[1 ANO-1 El ANO-2 El GGNS El IP-2 [E IP-3 El PLP

[] JAF [ PNPS [] RBS R vY El-w3 3] NP-GGNS-3 El NP-RBS-3 CALCULATION ()EC # 5000071989 (2) PagelI of 40 COVER PAGE (3) Design Basis Calc. [-1 YES O]NO (4) []"CALCULATION Z* EC Markup

(') Calculation No: IN1-110 (6) Revision: 1 (7)

Title:

Setpoint Calc for PIS263-123A,B,C, and D - Reactor High (") Editorial Pressure ATWS [--] YES Z NO

) System(s): 4582 (10) Review Org (Department): ICED (11) Safety Class: (12) Component/Equipment/Structure Type/Number: __________

pe/Number:

Safety / Quality Related PIS263-123A I- Augmented Quality Program PIS263-123B E] Non-Safety Related PIS263-123C PIS263-123D PT263-122A PT263-122B (13) Document Type: B4.01 PT263-122C PT263-122D (14) Keywords (Description/Topical Codes):

REVIEWS

,.4 ý Name nature/Date ('7) Name/Sign ture/Date a at esi

  • llnreri:eri Supervisor/Approva 2 o George Perry Al 9:50 Ai 1 Responsible Engineer F1 Reviewer Bruce Rancourt Comments Attached Comments Attached

Entergy CALCULATION SHEET

('~IrImbtii I in~1 Pnyicinn 1 ~-qJPT KI( 9 rf An ATTACHMENT 9.4 RECORD OF REVISION Sheet 1 of 1 Revision Record of Revision Initial issue.

0 The entire calculation has been typed in electronic format. The Analytical limit has been changed from 1205 psig to 1220 psig as a result of replacing the SRVs per EC5000071989. The setpoint and Allowable value has been revised. Incorporate DRN-06-00655 4.

+

  • 1-

+

Am Entergy CALCULATION SHEET Calculation IN1-110, Revision 1 SHEET NO. 3 of 40 TABLE OF CONTENTS I. PURPOSE / BACKGROUND ................................................................................................ 4 A. PURPOSE: ............................................................................................................................. 4 B. BACKGROUND ........................................................................................................................... 4

11. DESIGN INPUTS / ASSUM PTION S ..................... ............................................................ 4 1I REFEREN CES ...........................................................................................................................

R. 5 IV. DETAILED CALCULATION .................................................................................................. 9 A. M ETHODOLOGY ........................................................................................................................ 9 B. LOOP DIAGRAM .................... ................................................................................................ 12 C. CALCULATION ......................................................................................................................... 13 D. NOTES: ........................................................................... ...................................................... 26 V . RESULTS & CONCLUSION ....................................... ....................................................... 39 VI. ATTACHM ENT COVER PAGE ............................................................................................... 40

Entergy CALCULATION SHEET Calculation IN1-110, Revision 1 SHEET NO. 4 of 40 I. PURPOSE I BACKGROUND A. PURPOSE:

The purpose of this calculation is to determine the setpoint and allowable value (Tech Spec value) for Reactor High Pressure ATWS switches PIS263-123A, B, C, and D.

EC5000071989 is replacing the four Safety Relief Valves (SRVs) and two Spring Safety Valves (SSVs). The setpoints associated with the four SRVs, SV-203-3A, B, C, & D and two SSvs SV-203-4A and B will be increased by 40 psig. The increase in SRV setpoints results in increased maximum reactor vessel pressure during transients. AT'WS ARI and Recirculation Pump High Pressure Trip setpoint is increased by 40 psi, consistent with the increase in setpoints of the SRVs and SSVs, and will provide the same level of protection to avoid tripping both recirculation pumps during transients that include a successful reactor scram.

B. BACKGROUND The Reactor High Pressure ATWS switches PIS263-123A, B, C, & D initiate recirculation pump trip (RPT) and alternate rod insertion (ARI) when the Reactor pressure exceeds the switch setpoint. They provide a back-up method for controlling reactivity in the unlikely event that the Reactor fails to scram when required (FSAR Section 3.9.1).

1I. DESIGN INPUTS / ASSUMPTIONS

  • See Detailed Calculation Section IVfor design inputs.
  • This calculation is performed based on the methodology described in PNPS NEDWI No.

433, (Reference 4). The calculation has been prepared in accordance with U.S. Nuclear Regulatory Commission Regulatory Guide No. 1.105, (Reference 53) and Instrument Society of America Standard ISA-$67.04 Part I - 1982, (Reference 54).

" Pressure Transmitters PT263-122A, B, C, & D are calibrated using maximum no adjust limits of +/- 0.04mA (+/- 025% of span) over a range of 4 - 20 mA (Reference 15). All measuring and test equipment will be assumed to have a combined accuracy of +

0.25% or better (Reference 30).

" Master Trip Units are calibrated using maximum no adjust limits of +/- 0.02mA (+/- 0.13%

of span) over a range of 4-20 mA (Reference 9). All measuring and test equipment will be assumed to have a combined accuracy of +/- 0.13% or better (Reference 30).

  • The As-Found Tolerance (AFT) and As-Left Tolerance (ALT) is the tolerance allowed in the accuracy between calibrations of a device. The as found tolerance establishes the limit of error the device can have and still be considered functional. It is the band that

Entergy CALCULATION SHEET Calculation IN1-110, Revision 1 SHEET NO. 5 of 40 the device must be calibrated to within and remain to avoid recalibration when periodically tested. It is typically a value that is based on the accuracy of the device. The No Adjust Limits are used to determine if the technicians need to adjust the instrument.

  • Calibration of Pressure Transmitters will be assumed to be conducted at a nominal frequency of every 24 months or better. However, a frequency of 30 months is used herein to be consistent with the Tech Spec (Reference 27) definition of surveillance frequency (U), which allows a maximum extension of 25% of the specified surveillance interval.
  • Calibration of master trip units will be assumed to be conducted at a frequency of 3 months or better. However, a frequency of 4 months is used herein to be consistent with the Tech Spec (Reference 27) definition of surveillance frequency (U), which allows a maximum extension of 25% of the specified surveillance interval.
  • This calculation will convert error effects to PSIG for calculating total loop uncertainty (TLU).
  • Reactor and Turbine building normal temperatures are taken from FSAR Tables 10.9.1

& 10.9.2 (Reference 8), because the FSAR is the most recent controlled document reference source found with this information. The temperatures are assumed to be correct because they are the same as the temperatures identified in the Bechtel Design Basis Report 6498-HDBR-05 (Reference 41).

  • The readability value used for channel crosscheck of the GE master trip unit is assumed based on the readability of the Rosemount master trip unit it replaced. This assumption is justified because the replacement was made for ATWS diversity reasons and the existing loop calibration range has been maintained.
  • The determination for dynamic effects such as response time limits is addressed in the accident analysis and is not included within the scope of this calculation.

III. REFERENCES

1. Vendor Manual V-0098, Rev. 36 (Rosemount Instruction Manual 4260/4261 May 1987), "Rosemount Alphaline Model 1151AP Absolute and Model 1151GP Gage Pressure Transmitter"
2. Vendor Manual V-0242, Rev. 12, "AT'WS Analog Trip System Instruments" (GEK-83408C, Operation and Maintenance instructions, Analog Trip Unit 184C5988G100-G799)
3. PNPS Nedorandum FS&MC 91-176, October 11, 1991 "Reactor Vessel Thermal Growth Effect on Reactor Instrumentation"

Entergy CALCULATION SHEET Calculation IN1-110. Revision 1 SHEET NO. 6 of 40

4. PNPS BECo Work Instruction Number NEDWI No. 394, Rev. 3
5. PNPS Dwg. M1P612, Rev. E2, "ATWS Instrument Rack 2275 and 2276"
6. Crane Technical Paper No. 410, "Flow of Fluids through Valves, Fittings, & Pipe"
7. PNPS Procedure 2.2.80, Rev. 45, "Reactor Vessel Level, Temperature and Internal Instrumentation"
8. PNPS, FSAR, Rev. 24
9. PNPS Procedure 8.M.1-29, Rev. 50, "ATWS Trip Unit Calibration Test (High Risk)"
10. PNPS NED No.85-237, March 8, 1985, "Cable Spreading Room Environment"
11. PNPS Drawing M1 001:

a). Sh. 128, Rev. El, "Nuclear Boiler System Reference Leg from Nozzle NI5A to Penetration X28C & X82A" b). Sh. 129, Rev. El, "Nuclear Boiler System Reference Leg from Nozzle NI5B to Penetration X-29C & X-82B" c). Sh. 61A, Rev. El, "Nuclear Boiler System Instrument Line from Reactor Vessel Nozzle N-16A to Penetration X-28B" d). Sh. 65, Rev. El, "Nuclear Boiler System Instrument Line from Reactor Vessel Nozzle N-16B to Pen X-298"

12. PNPS Drawing M1002:

a). Sh. 124, Rev. EO, "Nuclear Boiler System Reference Leg to instrument Racks 2205, 2275, 2251" b). Sh. 125, Rev. E0, "Nuclear Boiler System Reference Leg to Instrument Racks 2206, 2276, & X82B" c). Sh. 15, Rev. E2, "Nuclear Boiler System Vessel Instrumentation from Penetration X-29B to Racks 2206 & 2276" d). Sh. 21, Rev. E2, "Nuclear Boiler System Piping from X-28B to C2205 and C2275"

13. PNPS P&ID M253Sh2, Rev. 29, "Nuclear Boiler Vessel Instrumentation"

Am Entergy CALCULATION SHEET Calculation IN1-110, Revision 1 SHEET NO. 7 of 40

14. BECO Elementary Diagrams (ATWS System):

a). M1Y2, Rev. E3 b). M1Y6, Rev. E6 c). M1Y7, Rev. E6 d). M1Y4,Rev.E2 e). M1Y5, Rev. E2

15. PNPS Procedure 8.M.1-30, Rev. 56, "ATWS System Calibration Test (High Risk)"
16. ENN-MS-S-009-PNP, Revision 1, "Pilgrim safety Classification site Specific Guidance and System Safety Function Sheets"
17. PNPS Dwg. M-187, Rev. 9, "Instrument Location Reactor Building Plan - El. 51'-

0"

18. PNPS Dwg. M PAI.6, Rev. 7, "Sel,, ted Item Power Supply"
19. PNPS Dwg. M! PA20, Rev. El, "Invt*

.. 'ATWS System Pane's C2277 & G2278" (Void per PDC93-26)

20. PNPS Dwg. C-1 51, Rev. 8, "Reactor Building Containment Vessel -

Requirements Drywell Plans & Sections"

21. PNPS Electronic Analog Data Sheets: (See IAS Equipment Data Base)
a. MePAl 8, Sh. 144, Rev. F=2
b. MiPA1 8DS162 1, Rev. El
c. MIPA1 8DS162 2, Rev. E!
22. PNPS P&ID M253SH1, Rev. E43, "Nuclear Boiler Vessel Instrumentation"
23. ABB Impoll Project

.'*-*tUtien, 25 226 PI 001, Rev. 2 "Data collecGtioa*nd Analysis

24. PNPS NED Procedure 3-05. Rev. 16, "Design Calculations"
25. PNPS Nedorandum FS&MC 91-176, October 11, 1991 "Reactor Vessel Thermal Growth on Reactor instrumentation"
26. Rosemount Letter from T. Layer to B. Rancourt, August 8, 1989 Rosemount Nuclear Specifications"

Ak Entergy CALCULATION SHEET Calculation IN1-110, Revision 1 SHEET NO. 8 of 40

27. PNPS Technical Specifications Rev. 287
28. ABB Impoll Quality Assurance Manual Procedur. QP 3.4, Rev. 6, "*al*ulations"
29. NRC Generic Letter (GL) 91-04, April 2, 1991 "Changes in Technical Specification Surveillance Intervals to Accommodate a 24 month Fuel Cycle
30. PNPS Procedure 1.3.36, Rev 21, "Measuring and Test Equipment"
31. ABB Impell Proejcct Instruction, 25 226 P1 002, Rev. 1,"Setpoint Calculations"
32. GE NEDO-21617-A, December, 1978, Licensing Topical Report "Analog Transmitter/Trip Unit System for Engineered Safeguards Sensor Trip Units"
33. PNPS Dwg. M292, Rev. 31, "Control & Cable Spreading Room, Intake Structure, Access Control, Warehouse & Machine Shop Air Flow Diagrams"
34. Safety Evaluation SE2279, Rev. 0, "Modification of Control Room High Efficiency Air Filtration System Heater Controls (CRH EAFSY
35. PNPS Equipment Qualification Master List (EQML), Rev. 51
36. PDC 91-047,Rev. 0, Modification to ATWS System"
37. PNPS CaIc. INI 42, Rev' 0, "ATS Reacnto-r Dom.e Pressure High and High High SetpeitS" (Replaced by this calc, INI-I 10).
38. PNPS CaIc. IN1-28, Rev, 2, Reactor Vessel Reference Leg Static Pressure
39. ASME Steam Tables, 5th Edition
40. PNPS CaIc. No. IN1-24, Rev. 0, Reactor Water Level Instrument Calibration
41. Bechtel Report 6498-HDBR-05, Rev, 1, "Design Basis Report Control Room, Cable Spreading and Computer Room Air Conditioning System", Enclosure in Bechtel Letter 17322-GBLE-91/002, Dated 6/28/91, S. Veale (Bechtel) to R.

Fairbank (PNPS).

42. PNPS Procedure No. 2.1.15, Rev. 204, "Daily Surveillance Log (Tech Specs and Regulatory Agencies)"
43. ARP-C905L, Rev. 35, "Alarm Response Procedure
44. 10CFR50.62, Anticipated Transients Without Scram"

Entergy CALCULATION SHEET Calculation IN1-110, Revision 1 SHEET NO. 9 of 40

45. PNPS S&SA Memo 93-42, 5/18/93, "ATWS Low-Low Reactor Water Level &

High Pressure Instrumentation"

46. NEDC-33532P, Revision 2, GEH "Pilgrim Nuclear Power Station Safety Valve Setpoint Increase"
47. EN-DC-1 26, Revision 3 - "Engineering Calculation Process"
48. ENN-IC-G-001, Revision 0 - Instrument Uncertainty and Setpoint Calculation Guide"
49. ENN-IC-G-003, Revision 0 - Instrument Loop Accuracy and Setpoint Calculation Methodology"
50. S&SA200, PNPS Reload Analysis Inputs Basis (OPL-3), Rev. 0
51. TDP-0087, Technical Design Procedure, OPL-3 Design Guide, Rev. 4, Appendix 110 Parameter Sensitivities.
52. E536, Revision 12, "Environmental Parameters for use in the Environmental Qualification of Electrical Equipment (per 10CFR50.49)
53. U.S. NRC Regulatory Guide 1.105, Revision 2; Instrument Setpoints for Safety Related Systems.
54. ISA Standard ISA-67.04-1982; Setpoints for Nuclear Safety Related Instrumentation.

IV. DETAILED CALCULATION A. METHODOLOGY This calculation is performed per PNPS NEDWI No. 394, (Reference 4), and NRC GL 91-04 (Reference 29). The format of this calculation has been specifically modified to meet the content requirements identified in PNPS NED Procedure 3.05 (Reference 24).

PNPS setpoint calculations and drift evaluations are performed using ISA-$67.04-1982 practice and utilize 95/95 tolerance limits as acceptable criteria for uncertainties, as discussed in the application for License Amendment 151. This methodology using ISA-

$67.04-1982 and RG 1.105, revision 2 was the basis for License Amendment 151, and forms the licensing basis for Pilgrim setpoint methodology. The NRC approved Pilgrim License Amendment 151, dated April 6, 1994 (TAC numbers M83787, M87191, and M88390 for the 24 month fuel cycle operation. Pilgrim applied for License Amendment 151 in accordance with the guidance of NRC Generic Letter 91-04. "Changes in Technical Specification Surveillance Intervals to Accommodate a 24 month Fuel Cycle".

Af Entergy CALCULATION SHEET Calculation IN1-110, Revision 1 SHEET NO. 10 of 40 As described in the application for License Amendment 151, Pilgrim performed setpoint calculations and drift evaluations using the guidance provided in Regulatory Guide 1.105, Revision 2.

This calculation utilizes <-1220 psig for high pressure ATWS upper analytical limit provided by GE in NEDC-33532P. The goal of this calculation is to maintain the existing high pressure ATWS setpoint, while accounting for loop measurement uncertainty.

The manufacturer's drift specification is used for transmitters PT263-122A, B, C, D and master trip units PIS263-123A, B, C, D because there are not enough data points for a valid statistical analysis at this time.

This calculation covers four redundant loops. Where individual loop values differ, the values are compared and the worst case value is used for conservatism. If a loop is required to function during one or more accident scenarios, then the uncertainty effects due to each accident are calculated and compared and the single worst accident scenario is used in calculating total loop uncertainty. The individual switch safety function determines if the loop must function during an accident scenario. This loop is not required to function during an accident scenario. Note 17 provides a tabulation of the error terms for normal operation.

Pma is calculated for normal operation. This equipment is not required to function during accident scenarios (Reference 45). The normal operation Pma is due to temperature variations inside the drywell and Reactor building which affect the density of the reference leg column of water as well as static offset due to the difference between the actual condensate pot elevation and that used in scaling calculation IN 1-28 (Reference 38). Maximum and minimum Reactor building temperatures during normal operation were obtained from Reference 8. Maximum and minimum Drywell temperatures (Reference 52).

All errors identified in this calculation are individually evaluated to determine whether they are random or biases. In the context of instrument uncertainty, it is accepted within the industry that random uncertainties are those uncertainties that a manufacturer specifies as having a +/- magnitude. Random uncertainties are combined using the root sum of the squares (RSS) technique in accordance with NEDWI 394. Biases are expressed with either a + or - sign and are added together separately according to sign.

Individual component error terms which contain both a bias and a random value (for example, -0.95 +/- 0.5 psig) may be split up so that the random part (+/-0.5) is combined with other component error terms by the RSS method and the biases (-0.95) added to other component bias terms of the same sign. Both random and bias terms are added together to determine Total Loop Uncertainty (TLU). A random or bias term can also be further classified as being dependent or independent. Two error terms are classified as dependent if they posses a significant correlation, for whatever cause, known or unknown. Instrument proximity or physical connections alone do not cause dependency,

Entergy CALCULATION SHEET

(-nir" Intinn Kmi -.1 inl Paiicinn 1 q4.JIZ=T MC 11 M An because the sign of the error term is determined solely by that instrument's measured response to the stimulus (temperature, pressure, etc.). Dependent errors are summed algebraically to form independent errors.

Aft Entergy CALCULATION SHEET Calculation IN1-110, Revision 1 SHEET NO. 12 of 40 B. LOOP DIAGRAM LOOP DIAGRAM PiS263-123A, B,

___REFERENCES M253 SH. i M1Y6 & M1Y7 M1 P612 M187 M1001 SH. 128 & 61A CONDENSING MI 001 SH. 129 & 65 POT 12AEN M1002 SH. 124 &21 M1002 SH. 125 & 15 REFERENCE LEG 74'-3* EL.

51'-0 EL.

RX. BLDG.

VARIABLE LEG i I 2275 PT PIS L CONDENSING POT NUMBER LOCATION NUMBER LOCATION I 1322 12A PT263-122A C2275 PIS263-123A C22787 $P 227 128 PT26Z3-122B C2276 P1S263-123B 02278 2277 PIS263-123C C2277 PmRetire.

12A PT263-122C C2275 Pumps Trip L -- Io.-- and Aft.

12B PT263-122D C2276 PIS263-123D C2278 Rod Insertion

CALCULATION SHEET

- Entergy NIl A Ifl P~,kir~n I .*I-II::I::T kin 1* nf 1R Calculation No IKI1-110 Revision 1 SHEET NO 13 of 18 C. CALCULATION FORM 1 INSTRUMENT DATA A) PT263-122A, B, C.& D B)PIS263-123A, B, C, & D TITLE DESCRIPTION I REFERENCE REMARKS REMARKS VALUE __

The A) and B) used on this form INSTRUMENT A) PT263-122A,B,C,D are meant to distinguish NUMBER M253SH1 between the transmitter and B) PIS263-123A,B,C,D Master Trip Unit.

SERVICE DESCRIPTION Reactor High Pressure ATWvS M253SH1 N/A QUALITY A) Q Locations:

PNPS Q-List A) C2275 & C2276 CATEGORY B) MQCl B) C2277 & C2278 ENVIROMENTAL NIA EQML N/A GENERAL QUALIFICATION INFORMATION SAFETY FUNCTION N/A N/A See Note 1 (IF APPLICABLE)

TECHNICAL SPECIFICATION s 1210 psig Tech Spec Table 3.2.G (IF APPLICABLE)

MANUFACTURER A) Rosemount A) M1PA1-8SH 144 Old Data sheets B) GE B) M1PA1-8DS162-1&2 See IAS for info A) 1151GP9E22uuw03B MODEL A) M1PA1-8SH144 Old Data sheets NUMBER B) 184C5988GI12 B) M1PA1-8DS162-1&2 See IAS for info

CALCULATION SHEET Entergy f, a Icu 1a 4:on KIo. IKII

- I 1n 0  ; :

. evson 4 CIUMM-rKIfN

. 4A 0C40 FORM 1 INSTRUMENT DATA A) PT263-122A, B, C,&D B) PIS263-123A, B, C, &D TITLE DESCRIPTION I REFERENCE REMARKS VALUE ANALYTICAL LIMIT (AL) 1220 psig Note 3 N/A ALLOWABLE < 1210 psig This calculation, Form 3 N/A VALUE (AV)

TRIP 1203.57 psig increasing This calculation, Form 3 N/A SETPOINT RESET 1173.57 psig decreasing See note 15 INSTRUMENT SETPOINT DATA NORMAL OPERATION 1045 psig See Note 2 UPPER LIMIT (NUL)

NORMAL OPERATION N/A N/A N/A LOWER LIMIT (NLL)

PROCESS A) 15 to 1515 psig A) 8.M.1-30 CALIBRATED N/A RANGE B) 0 to 1500 psig B) 8.M.1-29 OPERATING MARGIN (OM) 158.6 psig This calculation, Form 3 N/A NOTE: Adequate Operating Margin is required between the setpoint and the Normal Operating Upper or Lower Limit, as applicable, to avoid inadvertent trips due to process noise, transients and measurement uncertainties.

CALCULATION SHEET Entergy IK11-l In I QWC:C:T kin lrýf IQ FORM 1 INSTRUMENT DATA A) PT263-122A, B, C,& D B) PIS263-123A, B, C, &D TITLE DESCRIPTION I REFERENCE REMARKS I_ _ _VALUE _

0 to 500 psig LRL ADJUSTABLE 0 to 3000 psig URL LRL = lower range limit RANGE Vendor Manual V-0098 URL = Upper range limit INPUT SIGNAL M1Y6, MIY7 FROM PT263-122A, B, C, & D M253SH1 N/A INSTRUMENT SETPOINT INPUT SIGNAL DATA CALIBRATED 4 to 20 ma dc M1PA1-8SH144 Span = 16 ma (CONT.) RANGE OUTPUT Relays K2A,B,C & D M1Y6 SIGNAL TO Relays K5A,B,C,& D M1Y7 OUTPUT SIGNAL Contact Position M1Y6 CALIBRATION Change M1Y7 N/A RANGE SETPOINT A) 24 MONTHS A) 8.M.1-30 CALIBRATION This calculation Design Inputs FREQUENCY B) 3 MONTHS B) 8.M.1-29 and assumptions (NOMINAL)

CALCULATION SHEET Entergy KI IKII I-In 0  : ouc' Me%(' 4&- C4

%,icuUaionII oV. IN I IS., flV~v nI L I- I NS. J 0 IQ FORM I INSTRUMENT DATA A) PT263-122A, 8, C, &0 B) PIS263-123A, B, C, &D TITLE DESCRIPTION REFERENCE REMARKS VALUE TEMPERATURE N/A N/A Te included in Ste EFFECT (Te)

RADIATION See Note 1 EFFECT (Re) N/A N/A See 10CFR50.62 ENVIRONMENTAL STEAM / CHEMICAL ALLOWANCE (EA) SPRAY EFFECT N/A M253SH1 Only applicable to components FORM 3 STEP I (SlCe) located in the Drywell PRESSURIZATION (EXTERNAL N/A EQML N/A EFFECT) (Pe)

SEISMIC EFFECT N/A EQML See 10CFR5O.62 (Se)

CABLE LEAKAGE (CI) N/A N/A N/A CIRCUIT LEAKAGE ALLOWANCE (LA) TERMINAL BLOCK Loop does not have terminal FORM 3 STEP 2 LEAKAGE (TI) N/A MIY6, M1Y7 blocks located in harsh environments PENETRATION N/A M1Y6, M1Y7 No drywell penetrations LEAKAGE (PI)

CALCULATION SHEET Entergy

('.~Ir~,I~itinn Nn NI-I 10 P~~,i~inn I .*HFI::T NN 17 nf 1R FORM 1 INSTRUMENT DATA A) PT263-122A, B. C,& D B) PIS263-123A, B, C,& D TITLE DESCRIPTION I REFERENCE REMARKS VALUE SPLICE LEAKAGE N/A N/A See Note 1 (SI)

CIRCUIT LEAKAGE ALLOWANCE (LA)

(CONTINUED) SEALING DEVICE LEAKAGE (DI) N/A N/A See Note 1 PROCESS MEASUREMENT N/A See Notes 1 and 7 PROCESS ACCURACY (Pma)

ALLOWANCE (PA)

FORM 3 STEP 3 PRIMARY ELEMENT N/A N/A No Primary Element ACCURACY (Pea)

SENSOR +/- 0.25% Span V-0098 CALIBRATION = +/-0.25% (1500 psig) PNPS Procedure 1.3.36 Sca = Sa CALIBRATION ACCURACY (Sca) + 3.75 psig ALLOWANCE (CA)

FORM 3 STEP 4 RACK EQUIPMENT = +/- 0.13% FS Attachment 1 CALIBRATION = +/- 0.13%(1500 psig) PNPS Procedure 1.3.36 Rca = Rea ACCURACY (Rca) = :1.95 psig

CALCULATION SHEET Entergy r~l^,,t~i:^ I M .1^

14 n4 ^,^^

L.,alu~aLdblo Imo. IN PU.rVisIio

,1 I o t- I INS.. IO U0 10o FORM 1 INSTRUMENT DATA A) PT263-122A, B,C, & D B) PIS263-123A, B, C.& D TITLE DESCRIPTION I REFERENCE REMARKS REMARKS VALUE __

= +/- 0.13% Full Scale RACK EQUIPMENT Assume random and

= +/-0.0013 (1500 psig) Attachment 1 ACCURACY (Rea) independent

= +/-1.95 psig RACK TEMPERATURE EFFECTS (Rte) t 4.66 psig Attachment 3 See Note Master Trip9 Unit only RACK EQUIPMENT ALLOWANCE (RA)

FORM 3 STEP 5 RACK POWER SUPPLY EFFECTS N/A Attachments 1 and 2 See Note 8 (Rps)

RACK EQUIPMENT MISCELLANEOUS N/A N/A N/A EFFECTS (Rme)

CALCULATION SHEET Entergy

ý  : ; I c1Ucm-Kr-  % -int 4 *4a a Icuia.: on ki 1KII

o. - 11A , m evson 0 FORM 1 INSTRUMENT DATA A) PT263-122A, B, C, & D B) PIS263-123A, B,C, & D TITLE DESCRIPTION REFERENCE REMARKS I_ VALUE

= +/- 0.25% Span SENSOR BASIC

= 0.0025 (1500 psig) V-0098 N/A ACCURACY (Sa)

= +/- 3.75 psig SENSOR STATIC PRESSURE SPAN N/A N/A Not a Differential Pressure SHIFT (Ssps) Transmitter SENSOR STATIC SENSOR PRESSURE ZERO N/A N/A Not a Differential Pressure ALLOWANCE (SA) SHIFT (Sspz) Transmitter FORM 3 STEP 6 SENSOR Vendor Manual V-0098 TEMPERATURE +/- 10.13 psig FSAR Tables See Note 10 EFFECTS (Ste) 10.9.1 and 10.9.2 SENSOR POWER SUPPLY EFFECTS +/- 0.375 psig Vendor Manual V-0098 See Note 11 (Spse)

SENSOR MISCELLANEOUS N/A N/A N/A EFFECTS (Sme)

CALCULATION SHEET Entergy r\I,~ NI-I IA P ,i~in 1 cR.FFTN 9iA?3nfl1R FORM I INSTRUMENT DATA A) PT263-122A, B, C, & D B) PIS263-123A, B, C, & D TITLE DESCRIPTION I REFERENCE REMARKS VALUE SENSOR DRIFT Attachment 6 DRIFT (Sd) Vendor Manual V-0098 ALLOWANCE (DA)

FORM 3 STEP 7 = + 0.10% Full Scale for 1 RACK EQUPMENT month Assume random and DRIFT (Red) + 0.0010 (1500) psig)(4) Attachment 2

=+ 6.00 psig for 4 months independent

+/-0.04 ma/16ma =

+/-0.0025 SENSOR TOLERANCE +/-(0.0025)(1500 psig) PNPS Procedure 8.M.1-30 PNPS NO ADJUST limits not to TOLERANCE (St) =+/- 3.75 psig exceed this value ALLOWANCE (TA) NOTE:

FORM 3 STEP 8 +/-(0.0025)16ma=+/-0.04 ma

+/-0.02ma/16ma= +/-0.0013 RACK EQUIPMENT (+/-0.0013)1500 psig PNPS NO ADJUST limits not to TOLERANCE (Ret) =+/-1.88 psig PNPS Procedure 8.M.1-29 NO ADJs lmn NOTE: exceed this value

______________1(0.001 3)16ma=+/-0.02 ma I___________ I___________I____

CALCULATION SHEET Entergy Calculation No. IN1-110, Revision 1 SHEET NO. 21 of 18 Calculated Limits and Setpoint Relationship (Figure 2)

ATWS Pressure Limit 1500 psig 1500 psig ANALYTICAL LIMIT (Transient Analysis Value)

Wý 14 - 1220 psig 1210 psig TECH SPEC ALLOWABLE VALUE (Trip Level Setting - T.S. 3.2.G) TLU = 16.43 As found / As left tolerance 1203.6 psig .--

Calculated Field Setpoi No Adjust limit = t 1.9 psig 1173.6 psig . . . ~1 RESET VALUE Process Normal Operation 1045 psig Upper Limit (NUL)

Normal Operating Pressure 1035 psig 1035 psig

Date 5/14/02 CALCULATION SHEET AE-Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 22 of 40 FORM 3: CALCULATION SHEET

1. Environmental Allowance (EA)

EA= +/-+(Te)2 + (Re) 2 + (S/Ce) 2 + (Pe) 2 + (Se) 2 2 2 2 + (N/A) 2 EA=++/-(N/A)2 + (N/A) + (N/A) + (N/A) N/A

2. Circuit Leakage Allowance (LA)

LA= CI+TI+PI+SI+Dl LA= NIA N/A

3. Process Allowance (PA)

PA= +I1(Pma)2 + (Pea) 2 + (Pte) 2 PA= +/- 1(0)2 + (N/A)2 + (N/A) 2 0 psig

4. Calibration Allowance (CA) 2 + (Rca) 2 CA7- +/-_(Sca)

CA= +/-*(3.75)2 +(1.95)2 +/- 4.23 psig

5. Rack Equipment Allowance (RA)

RA= + -(Rea)2 + (Rte) 2 + (Rps) 2+ (RPne) 2 RA- + V(1.95)2 +(4.66)2 +(N/,)

2 +(N/A) 2 +/- 5.05 psig

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 23 of 40 FORM 3: CALCULATION SHEET

6. Sensor Allowance (SA) 2 SA= +/-V(Sa)2 +(Ssps+Sspz) 2 +(Ste) 2 +(Spse) 2 +(Sme)

SA= +-*(3.75)2 +(N/A+N/A) 2 +(10.13)2 +(0.375)2 +(N/A) 2 +/--10.81 psig

7. Drift Allowance (DA)

DA= + (Sd)2 + (Red) 2 DA= +IV(7.5)2 + (6.00)2 _9.60 psig

8. Tolerance Allowance (TA)

TA= + F(St)2 + (Ret)2 TA= +"(3.75)2 +(1.88)2Y 4.19 psig

9. Total Loop Uncertainty Allowance (TLU) 2 2 2 TLU = LA +/-+V(EA) 2 +(PA) +(CA) +(RA) + (SA)2 + (DA) 2 + (TA) 2 TLU = N/A +/-V (N/A)2 +(0)2 +(4.23)- +(5.05)2 +(10.81)2 +(9.60)2 +(4.19)2 TLU = +/- 16.43 psig

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 24 of 40

10. TRIP SETPOINT (Tsp) in Process Units - FOR INCREASING SETPOINT Tsp = AL - TLU Tsp = 1220- 16.43 = 1203.57 psig
11. ALLOWABLE VALUE (AV) in Process Units for increasing setpoint A V = TSp + /(Re t)2 + (Re d) since this is the only portion of the loop being tested AV = 1203.57 + /(1.88)2 +(6.0O)2 AV = 1203.57 + 6.29 AV = 1209.86 psig
12. OPEREATING MARGIN (OM) for increasing setpoint OM = TSp - NUL OM = 1203.57 - 1045 = 158.57 psig
13. TRIP SETPOINT (TSp) IN PROCESS UNITS for increasing setpoint TSs = TSp modified by the factors accounting for conversion from process units to signal units.

TSp = 1203. 57 psig TSs = [(1203.57 / 1500)

  • 16] + 4 ma TSs = 16.84 madc

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 25 of 40 PARAMETER DESCRIPTION ABBREVIATIONNALUE

  • COMMENTS ATWS Pressure Limit I 1500 psig ANALYTICAL LIMIT AL =1220 psig Environmental Allowance TEMPERATURE EFFECT Te = NIA (EA) RADIATION EFFECT Re = Ni/A STEAM/CHEM SPRAY EFFECT S/Ce = NiA PRESSURIZATION (EXT.) EFFECT Pe = N/A SEISMIC EFFECT Se = N/A T Circuit Leakage Allowance CABLE LEAKAGE CI = N/A o (WA) TERMINAL BLOCK LEAKAGE TI = N/A T PENETRATION LEAKAGE PI = N/A A SPLICE LEAKAGE SI = N/A L SEALING DEVICE LEAKAGE DI = N/A L Process Allowance (PA) PROCESS MEASUREMENT Pma =0 psig 0 ACCURACY 0 PRIMARY ELEMENT ACCURACY Pea = N/A P

U Calibration Allowance (CA) SENSOR CALIBRATION ACCURACY Sca = +/- 3.75 psig N RACK EQUIPMENT Rca = +/- 1.95 psig C CALIBRATION ACCURACY E

R Rack Equipment Allowance RACK EQUIPMENT ACCURACY Rea = +/- 1.95 psig T (RA) RACK TEMPERATURE EFFECT Rte = +/- 4.66 psig A RACK POWER SUPPLY EFFECT Rps = N/A I RACK EQUIPMENT Rme = N/A N MISCELLANEOUS EFFECT T

Y SENSOR BASIC ACCURACY Sa = + 3.75 psig SENSOR STATIC PRESSURE SPAN Ssps = N/A SHIFT Sspz = N/A Sensor Allowance (LA) SENSOR STATIC PRESSURE ZERO Ste = +/- 10.13 psig SHIFT Spse = +/- 0.375psig SENSOR TEMPERATURE EFFECTS Sme = N/A SENSOR POWER SUPPLY EFFECTS SENSOR MISCELLANEOUS EFFECTS ALLOWABLE VALUE AV= 1210 psig Drift Allowance (DA) SENSOR DRIFT Sd = +/- 7.5 psig RACK EQUIPMENT DRIFT Red = +/- 6.00 psig Tolerance Allowance (TA) SENSOR TOLERANCE St= +/- 3.75 psig RACK EQUIPMENT TOLERANCE Ret= +/- 1.88 psig TRIP SETPOINT TSp = 1203.57 psig RV 1173.57 psig RESET VALUE OPERATING MARGIN OM = psig NORMAL OPERATION UPPER LIMIT NUL= 1045 psig NORMAL OPERATING BAND NORMAL OPERATION LOWER LIMIT NLL = 1035

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 26 of 40 D. NOTES:

1. This equipment is not listed on the PNPS EQML and does not perform a safety function (See 10CFR50.62 - Reference 44). It initiates recirculation pump trip (RPT) and alternate rod insertion (ARI), which is a back-up method of reactivity control at reactor high pressure. This equipment is only required to function during anticipated operational occurrences. At PNPS this equipment is classified MQCI.
2. A value of 1045 psig will be used for the normal operation upper limit (NUL).
3. The ATWS recirculation pump trip setpoint is selected to trip the pumps during the initial reactor pressure transient following a failure of the control rods to insert. The selected trip set point is low enough to ensure that the ASME pressure limit for emergency events of 1500 psig is not exceeded. Note 2 to Table 3-3 "Key Equipment Parameters" in NEDC-33532P describes that the ATWS transient analysis uses a trip setpoint of 1220 psig, which is the analytical limit shown on Figure 2. The results of the worst case ATWS pressurization events are tabulated in Table 3-4 "Summary of Key ODYN Parameters for ATWS Calculation" and the worst case peak vessel pressure is 1478 psig. The analysis of 1220 psig is demonstrated to be adequate because the peak vessel pressure results from the transient analysis described in Section 3 of NEDC-33532P is below 1500 psig.

0 An analysis reactor steam dome pressure setpoint of 1220 psig is used for the ATWS Recirculation Pump Trip (RPT) function. Starting with Reload 18 Cycle 19 this analysis setpoint is specified for transient analysis that assumes a successful reactor scram performed for Reload Licensing Analysis (RLA) [Reference 50] and ATWS analysis

[Reference 46]. The previous analysis setpoint was 1180 psig which corresponded with the Technical Specification allowable value upper limit. The value of 1220 psig is referred to as the "Trip Level Setting" in Tech Spec 3.2.G.

  • A lower analysis setpoint limit is not specified for the ATWS Recirculation Pump Trip (RPT) function:

0 Inadvertent trip of the recirculation pumps during a transient event that includes a successful scram is an operational inconvenience not a safety concern. The operational inconvenience arises due to the loss of forced circulation to sweep cold water from the reactor vessel bottom head. Reactor water level is manually raised to improve core flow by natural circulation and control thermal stratification in the bottom head.

0 The loss of both recirculation pumps is an evaluated transient that is non-limiting with respect to fuel thermal limits. As indicated by GEH in the OPL-3 Design Guide for RLA transient analysis inputs, increases in the RPT setpoint have minimal effect on peak pressure and causes negligible change in critical power ratio [Reference51].

4. In accordance with PNPS Procedure 1.3.36, measurement and test equipment utilized for calibration shall be equal to or better than the device being calibrated. The

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 27 of 40 manufacturer's stated accuracy is +/- 0.25% span (Reference 1) for the transmitter and +

0.13% span for the master trip unit (Att. 1 & 3).

5. This calculation supports a 24 month fuel cycle.
6. The no adjust limits and reset will be based on the existing settings utilized. These values are shown in PNPS Procedures 8.M.1-30 and 8.M.1-29.
7. Evaluation of Reference Leg Temperature Variations on Reactor Vessel Pressure Measurement.

The distance from the bottom of the Reactor vessel to the bottom of the inside of the pipe from the Reactor vessel to the condensing pot for each train is calculated below.

Note, this should correspond to the water level in the condensing pot, hcp.

"A" Train Level "B" Train Level Reference 83' 9.3125" 83' 9.375" M1001 Sh. 128, Top of Pipe (1005.3125") (1005.375") M1001 Sh. 129 Reactor Zero Elevation 37' 11 1/4"(-455.25") 37' 11 1/4" (-455.25") M23 Internal diameter 2" Sch. 80 Pipe + -2.157" -2.157" M1001 Sh. 128 Wall Thickness Actual Cold 547.91" 547.97" hc;p Per FS&MC memo 91-176 (Reference 25), thermal growth is 7.3 x 10-6 in/in/°F and the cold distance of the upper tap is 547". Assuming a cold temperature of 60°F:

Al = eelongation = total thermal growth of vessel = 3.993 x 10-3" (T-600 F)

Using T = Tsat (1035 psig) = 546 0F, Al = eelongation 1.96" According to PNPS calculations IN1-28 (Reference 38), IN1-24 (Reference 40), drawings M253 Sh. 1 (Reference 13), M1001 Sh. 128 & 129 (Reference 11), the following elevations relative to the bottom of the Reactor vessel were assumed to exist at calibration:

hop CAL ASSUMED = 548.5" ("A" & "B' Train) eoffset = hcp ACTUAL COLD - hcp CAL ASSUMED ecp = eoffset + eelongation = hcpACTUAL COLD - hcpCAL ASSUMED + Al

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 28 of 40

= (547.91 - 548.5)" + 1.96" = - 0.59"+ 1.96" = 1.37" (A Train)

= (547.97-548.5)" + 1.96" = -0.53"+ 1.96"= 1.43" (B Train)

From Reference 38 & 40, the reference leg penetration of the Drywell is at 534.375" for Train A and 535.75" for Train B. As depicted on drawing MIP-612 (Reference 5) and PNPS calculation INI-028 (Reference 38), the pressure transmitters are at 176.79" above reactor vessel zero (52.67' - 37' 11.25"). Therefore the height of the reference leg in the Drywell and in the Reactor Building is:

Train error in hcp (ecp) Height in DW, hDw Height in RB, hRB A +1.37" 14.125" 357.585"

+1.43" 12.75" 358.96" Per PNPS calculation INI-24 (Reference 40), PNPS FSAR (Reference 8), and ASME Steam Tables (Reference 39) the density of the fluid in the drywell and in the reactor building reference leg due to different ambient temperatures:

Ref. Highest Ref. Highest Location Temp's Temp's Lowest Temp's Temp DensityDest Lowest Temp Density lyDensity Drywell 1387F 148 0F 1250 F 61.6523 61.4818 61.8104 Reactor Building 80°F 105°F 60° F 62.422 62.1118 62.5783 Substituting these values into the following equation for the static head pressure on the transmitter:

PStatic Head = hgw*Pow +/- hRB *PRB where hDw = height of water column in drywell hRB = height of water column in reactor building PRB = density of water in drywell portion of reference leg PRB = density of water in reactor building portion of reference leg

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. INI-110 Revision 1 SHEET NO. 29 of 40 Normal Operation PStatic Head(Ret Temp) = [14.125 (61.652) + 357.585 (62.422)]*[1 ft3 / 1728 in3 ]

= 13.42 PSIG (Train "A")

= [12.75 (61.652) + 358.96 (62.422)]*[lft3/1728 in3]

= 13.42 PSIG (Train "B")

PStatic Head(Lowest Temp)_. [14.125 (61.8104) + 357.585 (62.5783)] * [lft3/1728 in3]

= 13.45 PSIG (Train "A")

= (12.75 (61.8104) + 358.96 (62.5783)] * [1 ft/1 728 in3]

= 13.46 PSIG (Train "B")

PStatic Head(Highest Temp) = [14.125 (61.4818) + 357.585 (62.1118)] * (1ft3 / 178 in 3]

= 13.36 PSIG (Train "A")

= [12.75 (61.4818) + 358.96 (62.1118)] * [1 ft3/1 728 in3]

= 13.36 PSIG (Train "B")

Maximum error equals difference between lowest pressure calculated above and the +13.4 PSIG correction factor from PNPS calculation INI1-28 (Reference 38).

Pma = (13.36 - 13.4) / 1200*100% = -0.003% Span and can he neglected.

8. Rack Power Supply Effects (Rps):

Attachments 1 & 2 specify the performance parameters applicable to the GE master trip units.

Among these parameters are the supply voltage requirements for power to the units. It is assumed that if the input voltage is maintained within the design requirements of the trip units there will be no adverse affect on the performance specifications.

The master trip unit requires a supply voltage of 21.2 to 29.1 Vdc as described in Attachment

1. The ATWS power supplies are fed from two sources; 115 Vac distribution panels Y3 & Y4 and 125 Vdc distribution panels D36 & D37 (Reference 14). The outputs from D36 and D37 are converted to AC by voltage inverters prior to feeding the ATWS power supplies.The voltages throughout the ATWS trip circuits will remain within the equipment specifications and therefore no adverse performance from any ATWS equipment can be attributed to abnormal variations in supply voltages.

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 30 of 40

9. Rack Temperature Effects (Rte):

The temperature effect for the GE master trip unit trip output which provides the reactor high pressure ARI/RPT is listed in the GE proposal dated 9/30/91 (Attachment 3). This error is +/-

0.2% of full scale assuming the error is random for an internal cabinet temperature change from 113.5 0 F to 142.5°F. The corresponding external cabinet temperature is 76 0 F to 105 0 F.

PNPS FSAR Tables 10.9.1 & 10.9.2 list the minimum and maximum temperatures at the cabinet location (Reactor Building - 51 foot elevation) as 60OF to 105'F. Therefore; Rte = (+/-0.2%) (1500 psig) [(105'F - 60°F)/(105°F - 76°F] = _ 4.66 psig

10. Sensor Temperature Effect (St):

PT263-122A, B, C, & D are located on instrument racks C2275 & C2276, Rx bldg elevation 51' (Reference drawings M253 & M187).

Area temperature range: 60°F to 105'F (winter & summer design temperatures from FSAR tables 10.9.1 & 10.92)

Using V-0098 and proportioning the Ste at the pressure transmitter upper & lower range limits (URL & LRL):

SteURL = +/- 1% span per 100'F = +/- (0.01) (3000 psig) / 100°F = + 30.0 psig / 100°F SteLRL = + 3.5% span per 100'F = +/- (0.035) (500 psig) / 100°F + 17.5 psig / 100°F.

Therefore at the calibrated span of 1500 psig: (1500 - 500) psig / (3000 -500) psig = 0.4 psig Ste = +/- [(0.4) (30.0 - 17.5) psig/100°F] + +/- 17.5 psig / 100°F = +/- 22.5 psig/100°F Adjusting for temp. range: (+/- 22.5 psig/100°F) (105'F - 60'F) = +/-10.13 psig

11. Sensor Power Supply Effects (Spse):

Note 8 details the review of the voltage regulation for the ATWS trip circuits. The review confirms the GE master trip units have a supply voltage within required limits. These trip units provide supply voltage to the Rosemount transmitters, PT263-122A, B, C, and D. From Reference 1, Spse = (+/-0.005%) (1500 psig) (28v - 23v) = +/- 0.375 psig

12. Sensor Drift (Sd)

Reference 1 gives stability (drift) for model 1151G transmitters as +/-0.25% of URL for six months. Per Attachment 6, there will be no additional drift for at least two years after the first

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 31 of 40 two days of operation/setting. Therefore, the value given in Reference 1 will be used to calculate Sd over the full calibration cycle:

Sd = +/-0.25% of URL = (+/-0.0025) (3000 psig) = +/- 7.5 psig

13. For actual values implemented at PNPS, see Figure 1.
14. A review of Reference 15 shows that the inaccuracy due to static pressure in the reference leg (from Reference 38) is accounted for in the calibration of the transmitters except for one minor calibration error. This term, CR, is the difference between the desired setpoint and the actual setpoint at which the trip will occur. This actual setpoint is determined by substituting the calibrated high setpoint in the transmitter calibration formula. The calibrated setpoint is 16.84 mA per Note 15 of this calculation. Convert this to the actual pressure the transmitter senses at the trip as follows; The ratio of mA to psig is obtained from Reference 15:

[(Actual Tsp + static Head)- 15) psig / (16.84 - 4.02) mA] = [(1510 - 15) psig / (19.97 - 4.02) mA]

Therefore, Actual Tsp = 1216.62 psig, which is 1203.22 psig + 13.4 psig static head (from Reference 38).

CR = Tsp - Actual Tsp = 1203.57 psig - 1203.22 psig = 0.35 psig This is a conservative error, i.e. the switch will trip before Reactor pressure reaches 1203.57 psig. Therefore this will not be included in TLU.

15. Calculated Reset Value & Trip Setpoint (Tsp):

Trip Setpoint:

Calibrated range: 0 to 1500 psig. span = 1500 psig Signal range: 4 mA to 20 mA, span = 16mA Tsp= 1203.57 psig Then:

Tss = [(1203.57 psig/1500 psig) (16 mA)] + 4 mA = 16.84 mA With no adjust limits (+/-0.02 mA): 16.82 mA to 16.86 mA (per Reference 9)

Reset Value:

Per Reference 21 & 36 the reset differential will be set at 0.32mA +/- .016mA (0.32mA/16mA) = 2% of span = (0.02) 1500 psig = 30 psig Therefore Reset Value = Tsp - 30 psig = 1203.57 psig - 30 psig = 1173.57 psig

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 32 of 40 Convert to signal units:

16mA (1173.57 psig/1 500 psig) + 4mA = 16.52 mA which corresponds to a no adjust limit of +/-0.16mA (16.36mA to 16.68mA):

This reset value (RV) is acceptable because (1) reset occurs at 2% span, which falls within the manufacturer's specification of 0.5% to 20% of the input span and (2) reset occurs before the process normal operation limit is reached. See Figure 1.

16. Channel Cross Check Channel cross check criteria is intended to be used by PNPS operators to determine when a channel may be malfunctioning based on a comparison of its indicated value for a plant parameter versus the value displayed by the other channels displaying the same parameter. It is intended that this comparison will be performed during plant normal operation.
1. Methodology A. Total Loop Uncertainty for Cross Check The TLU used for cross check purposes is defined as:

2 2 2 2 2 TLUCROSSCHECK = j(PA)2 + (CA) +(RA) + (SA) + (DA) +(TA) where:

PA = Pea 2 2 CA2 = Sca + Rca Note: Rca includes the readability of the meter (1/2 minimum gradation)

RA 2= Rea 2 + Rte [N.O.] 2 + Ma2 Note: Rte [N.O.] is the error due to temperature difference between calibration and Normal Operation temperature. Ma is the master trip unit analog meter accuracy.

2 SA2 = Sa 2 + (Ssps + Sspz) + Ste[N.O.] 2 Note: Ste[N.O.] is the error due to temperature difference between calibration and Normal Operation temperature.

DA 2 = Sd2 + Red2

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. INI-110 Revision 1 SHEET NO. 33 of 40 2 2 TA 2 =St + Ret Note: Ret is the "As Leff' setting tolerance of the meter indication.

The following terms from the equation for TLU in NEDWI 394 are not considered for the following reasons:

EA and its constituent terms Te, Re, S/Ce, Pe, and Se are not considered since these errors are associated with Post Accident conditions and the cross check is performed only during Normal Operation. Similar reasoning is why LA and its constituents Cl, TI, PI, SI, and DI are not considered.

The process measurement accuracy, Pma constituent of PA is not considered since it would equally affect all channels.

The sensor and rack power supply affects Spse and Rps, and are not considered because minor voltage variations on the 120 Vac buses are well within the regulation capability of the individual sensor and rack power supplies. Also, a severe degraded voltage condition is not considered, because this is not a normal plant operating condition.

For differential pressure transmitters in pressurized applications, the static pressure span and zero error terms, Ssps and Sspz, consist only of the random portion of the error. They account for the uncertainty in the correction actually applied and are still applicable.

B. Development of Channel Cross Check Criteria The purpose of this section is to discuss the derivation of the channel cross check methodology to be used at the Pilgrim Nuclear Power Station (PNPS). The purpose of the cross check process is to detect when a channel's performance begins to deviate from within analyzed bounds and is performed by comparing an individual channel's indication against some criteria.

An ideal test would be to compare the channel indication against the actual value of the parameter being monitored. In this case the criteria would be that "the difference between the indicated and the actual value must be less than the uncertainty established for the channel indication".

However, the actual value of a parameter is never known with absolute certainty. From a statistical standpoint, reduced uncertainty in the value of a parameter can be achieved by making a series of repeated independent measurements.

From Section 2, "Fundamental Considerations", of ASME PTC 19.1 - 1985 (Reference 64),

"Part 1 Measurement Uncertainty", if a series of independent measurements (readings) are made, then the mean value of the series is given by

Date 5/14102 CALCULATION SHEET AC O Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 34 of 40 (i= (Xi)! N)

From the same document, the uncertainty associated with the mean value of a series of independent readings is related to the uncertainty in each of the measurements in the series used to calculate the mean value. This uncertainty is given by SS se ries S Mepan -- _____N Where Seriep - N and si = uncertainty associated with the ith measurement.

If the measurement uncertainties are the same (all Si = Smeasurement) then Sseries - SMeasurement and Swean=Sseries = S mcas..ement This indicates that if you are estimating the actual value of a parameter by averaging several measurements, then the uncertainty in your estimate decreases as the number of measurements in the average increases.

If one were to compare the indication of a single channel with the mean indication of several channels monitoring the same parameter, what would be an appropriate comparison criteria?

The criteria proposed is that "the difference between the indication of a single channel and the mean indication of several channels monitoring the same parameter must be less than the uncertainty established for the channel indication plus the uncertainty established for the mean value". Mathematically, the criteria is expressed as follows:

Re adhig ...... - t Re a .. nels Ch.,, Channel + SAean Reaic ...... -,

-(__N ReadingChanli~, NTha..... ,i ......., + S Channell*Nchmk Re t - .d"6ane < S hne ,, , t

Date 5/14/02 CALCULATION SHEET t 0AL Entergy Calculation No. INI-110 Revision 1 SHEET NO. 35 of 40 The criteria is based on the fact that the first uncertainty is that of the reading being compared and the second uncertainty is that of the standard being compared against. In the limiting case of N = 1, i.e. comparing two readings to each other, the criteria states that the difference must be less than twice the established channel indication uncertainty. In the limiting case of N approaching infinity the uncertainty associated with the mean value approaches zero and the criteria reverts to the ideal case above.

Using the above equation and substituting TLU Cross Check for SChannel and simplifying yields:

Channeli Re ading - A verage ChanneliReadingl < (~I+ -ýN )TL UCo~s Check Tabulated below are values for QI+ I )

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 36 of 40 N

(No. of channels) TLU Cross check Multiplier (M) 2 1.707 3 1.577 4 1.500 7 1.378 8 1.354 The current PNPS Channel Cross Check procedure is performed by comparing two readings to each other, which is the limiting case of N=1 described above. Therefore, the calculation presented in Part 2 will consider both the Cross Check between Channels (limiting case of N=1) and the Cross Check against the average.

C. Application of Cross Check Criteria Round off the calculated cross check value to the nearest readable value. Compare the calculated value of the cross check criteria to the existing value taken from PNPS Procedures.

Ifthe existing value is larger than the calculated value, coordinate with PNPS ICED to evaluate reducing the existing cross check criteria to the calculated value. If not, use the existing value.

Identify the cross check value in Section V, Results and Conclusions.

2. Calculation TLUCoSSHC =( + (CA)U+_()2+ (SA) 2 + (DA) 2 + (TA) 2 where:

(PA) = N/A (CA)= +/- 25.35 psig, 2

where CA 2 = Sca 2 + Rca

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 37 of 40 and Sca = +/-3.75 psig Rca =J(RCaFo,0 n)f + (Re adability)2 = 25.08 psig where: RcaForml = +/-1.95 psig (See Form 1)

Readability = 25 psig (See Assumptions, Section 11) 2 2 2 2 (RA) = +/- 45.28 psig, where RA = Rea + Rte + Ma Rte = +/-4.66 psig (See Form 1)

Rea = +/- 1.95 psig (See Form 1)

Ma =+3% of Full Scale (Attachment 1) = +/- (0.03)(1500 psig) = _ 45 psig 2 2 2 (SA) = +/-1 0.80 psig, where SA = Sa + (Ssps + Sspz) + Ste 2

Sa =+/- 3.75 psig (See Form 1, Sht. 7)

Ssps=N/A (See Form 1)

Sspz= N/A (See Form 1)

Ste = +/- 10.13 psig (See Note 10)

(DA) = +/- 9.60 psig (See Form 3, sht. 2)

(TA) = +/- 4.19 psig (See Form 3, sht. 2) Since there is no meter adjustment possible, the setting tolerance for the master trip unit and the setting tolerance for the sensor will be used to calculate TA. Therefore, TLUCROSSCIIECK = +

(N/A)2+(25.35)2 +(45.28)2+00.8)2 +(9.60)2+(4.19)2 TLU CROSS CHECK = 54.03 psig TLUC,.oss checkM -= TLU -7shk where N = number of channels Case 1: Comparison to an Average of the Four Channels:

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 38 of 40 TL Us ch ek Ma, -54.03psig - 27.02 psig v/i.

From section B, all channel readings must satisfy the relationship:

Channeli Reading- Average ChannelReading < TL UC,.,,Chck ,*iean + TL Uco.,.SCheck Which after substituting 27.02 psig and 54.03 psig for TLUcross check mean and TLUcross Check IChannel i Re ading - Average Channel Re adingI < 27.02psig + 54.03 psig = 81.05 psig 81.05 psig will be rounded off to the nearest 10 psig, therefore, will equal 80 psig. Per PNPS Procedure 2.1.15 (Ref 42), the existing cross check value is 90 psig.

Case 2: Comparison between Two Channels:

lChanneli Re ading- Channel j Re adingl < 54.06 psig + 54.06 psig = 108.12psig TL Us checkMean - 54.06 psig = 54.06 psig lChannel i Re ading- Channel j Re adingl < 54.06psig + 54.06 psig = 108.12psig Since the calculated value is larger than the existing value in reference 42, the existing value is conservative and will be used.

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 39 of 40 V. RESULTS & CONCLUSION Plant Impact Instrument Parameter PT263-122A, B,C,D PIS263-123A, B, C, D Surveillance Interval 24 Months 3 Months Combined Measurement and +/-0.25% of Span +0.13% of Span or psig or mA Test Equipment +3.75 +/-0.02 No Adjust Limits +/-0.04 mA +/-0.02 mA SETPOINT DATA Field Trip Setpoint 1203.6 = 16.84 mA Field Reset 1173.6 = 16.52 mA Notify Watch Engineer Value 1210= 16.91 mA Channel Cross Check Value 90 psig The relationship of the field setpoint to the calculated limits is shown on Figure 2.

Date 5/14/02 CALCULATION SHEET Entergy Calculation No. IN1-110 Revision 1 SHEET NO. 40 of 40 VI. ATTACHMENT COVER PAGE

1. GE Letter to David Himle, from C.C. Canham, dated 7/24/91 with GE Trip Unit Performance Specification (14 sheets)
2. Technical Description for GE Nuclear Energy Analog Trip Unit, GE Drawing 184C5988, dated 4/91 (15 sheets).
3. GE Proposal for Nuclear safety Related Trip Units - Proposal Number HK1 507DP1, dated 9/30/91 (6 sheets)
4. PSD Nedorandum Number 91-81, dated 9/25/91 (2 sheets)
5. Not Used
6. Telephone Call Record From R. Swanson (Rosemount) to B. Brousseau (PNPS) dated 8/21/91 (1 sheet)

AlTA(,JRA~ L INI-Il IN1.110 GE NUCLEAR ENERGY San Jose, California IN 14 10 July 24 1991 TO: David Himle

SUBJECT:

BECO REQUEST FOR TRIP UNIT PERFORMANCE SPECIFICATION Attached is the requested information. It is verified as accurately extracted from 22A7716 and 22A7011. Verification is contained in DRF-AOO-02406-1 Index 9.

0 C. F. Canham, Manager Plant Electronics Application Engineering 0

IN14110 GE TRIP UNIT 184C5988 PERFORMANCE SPECIFICATIONS DIMENSIONS: ( .. 969" High, 9.875" Deep, 1.188" Wide WEIGHT: L8 OZ.

MOUNTING: Irinted Circuit Card/Slide in Card File INDICATOR SCALE: S;cale/Legend to be specified by E3uyer when ordered.

nalog signal meter: +3% FS POWER SUPPLY REQUIREMENTS:

Voltage + 25VDC +/-+.SV (Qual limit = 21.2 to 29.1 v DC)

Current <260mA TRIP UNIT OUTPUT VOLTAGE/CURRENT:

Trip Output Limits > 22 VDC (Typ 24 +0.5)

Gross Failure'Limits 22 VDC Hi 100% (Adjustable)

Low 12% (Adjustable)

Trip Status Limits 0 -12 VDC Analog Output to I -5 VDC Calibrated Slave Limits Auxiliary Output Limits 1- -5 VDC Calibrated TRIP UNIT INPUT VOLTAGE/CURRENT:

Calibration Command 2!iVDC Trip Unit Input Impedance 2!i0 ohms Trip Logic Status FZ.ont-Mounted - Led Indicator Trip Unit Frequency 25 0 Hz +2.5 Hz

Response

Analog.Output to 25.0 Rz +2.5 Hz Slave Frequency Response an-KLF-3 .wp.

Ar-M .'

Auxiliary Analog output 0.8 - 8 Hz +0.8 Hz (Adjustable)

Frequency Response Trip Unit Input/Out 300 VDC Isolation Trip Unit Analog 0.15% FS

%- Output Accuracy Trip Unit Trip Point 0.13% FS Repeatability (Accuracy)

Electromagnetic 0.5-60 BHz at 5.0 VP/P

- Susceptibility 60 MHz to 85 MHz at 3.5 VP/P 85 MHz to 100 MHz at 2.5 VP/P Operating Temperature <115 0F Normal <1450F Max.

- Limits Relative Humidity Limits <50% Normal --90% Max.

Seismic Qualification Profile The Required Response Spectrum is provided in Attachments 12 and t3. These spectra represent the minimum floor acceleration spectra to be applied to the MTU and STU (Slave Trip Unit) enclosure (cabinets only). The seismic exposure levels for both Operating Basis XEarthquake (OBE) and Safe Shutdown Earthquake (SSE) for a cabinet containing the trip units are also contained in Attachments #2 and 13. The figures do not include amplification from the floor to the trip unit mounting locations.

The seismic exposure levels to which the trip units may be exposed during plant life are dependent on the seismic levels at their mounting locations. Attachments 14 thru 19 show the trip unit seismic qualification levels. These figures do not include any margin.

The trip units required seismic testing using multifrequency test inputs. The Test Response Spectra (TRS) at the cabinet assembly base were to exceed the service conditions of Attachments 12 and

13. This assured that the trip units in their mounting locations experienced actual seismic levels in excess of their specified service condition. The trip units were to be subjected to five OBEs and one SSE in two orientations. The Required Response Spectra (RRS), Attachment i10 and #11, used during seismic testing as input into the cabinet containing installed aged trip units exceeded the service conditions of Attachments 12 and 13 by at least 21%.

an-KLF-3 .wp

Ma~ster Trip Unit (Current Input) Block Di1agram 1111INAh life" FAIL IAI m P1.1 0A0 NOR~

01-6 I

03 el JIAuK i 1PI illk Miff £?LM AAIOI RDIINIIII MAL Ia -t fueli tini bti ATTACHr~npirr -~4n

REQUIRED RESlA3NSE SPECTRUM 0 . 01 C0:ITIIOL fhi0ILtfirs VALUES S10104I ARE I'M4 HASS IPOIN7 NO. 4 IIOMl2OflTAI.

ODEqATIjN BASIS EL. 164 rT. EARtIIQUAKE 14ULTIPLY BY 1.6

-DAHPN11 RATIA' 0.05n. 0.0 i.WPo:ISE A(q.rLERATIO'4 .t )., o.03, 0.05 FOR DESMr4 BASIS EAlIZI'(UAKE Nn,'M* ,LIZIM* PATIO 1.111 ii

'.005 rnh ATTACHMENT # 2 4n m

Lo r)

0 m

r* its Imb m

I C2

-4

.4tJ~ 0 I

,03 I' 05 U'

11~

.so

9 REQUIRED RESPONSE R0 SPECTRUM VALUES SIKAMf ARE FOR -

/ONiAOL BUILDING r$PF.ATIN* DASIS SS POINT NO. 4 VERTICAL tAhiAlmKEt RAWIPLY by t.6 EL. 164 .FT.

0A1PItN RATIO 0.00. 0.01ao .O2, .0201,OOS roR OESl. BASIS t11"fUA. ER RESPONSE ACCELERATIO,'t 04KLIZ14G RATIO 1.00 ATTACHMENT # 3 62 m

z fyi 0 /.005 Ix Sm I"

CI m.4 i .

LI 4 t,

INI-110 NUCLEAR ENERGY f"EMERAL ELECT~iG 0 A-rr.14 BUSINESS OPERATIONS 0

0, z) 0:

II IIIL 0

0

-I C

11 C

C I 0; FREQUEIICY (Hz)

TRIP UNIT SSE VERTICAL QUALIFICATION CURVE

, - . a  %-o~ a a a a

&ý %a a iJ INIA 10 NUCLEAR ENERGY GENERAL ) ELECTRIC BUSINESS OPERATIONS 714 C067 ir 0 r- ILt

.1 I-cz~

-J C

Ic 0

I -4 0

FREQUENCY (Hz)

TRIP UNIT OBE VERTICAL QUALIFICATION CURVE

NUCLEAR ENERGY GENERAL ELECTRIC INI. 10ios BUSINESS OPERATIONS r c~l 114 LU

-J 0

0 0

FREQUENCY CKz)

TRIP UNIT SSE Y-DIRECTION QUALIFICATION CURVE

aimwfit-m -

A-%, a & 0A--kab A-r-IIN44I10 NUCLEAR ENERGY GENERAL ELECTRIC C-A G i 4 9 , Z 6 -

BUSINESS OPERATIONS pAcc-:10cf-1'4 0

0 IIII 0;

x 0

09 0.

0 0

-,J 0

0 I I II 0

0 IIII

-E 0 0 I 0 0

FREQUENCY (Hz)

TRIP UNIT SSE X-OIRECTION QUALIFICATION CURYE

A-TTa I INI-11lO NUCLEAR ENERGY GENERAL ELECTRIC -- to =.cJ BUSINESS OPERATIONS 0

Oi a:

-J 0

0~

0 0

0 I 6 FEQUENCY (Hz)

-d TRIP UNIT 0BE. Y-DIRECTION QUALIFICATION CURVE

INI1410i krrn.I NUCLEAR ENERGY GENERALO. ELECTRIC - A.I6Q A zzc

9FvZtt r~~(5 BUSINESS OPERATIONS

?V&r"=

0 0

0 0

0*

0 0o 0O 0 0 0

I,--

,-J 0

C4 0 IIIIn 0

0 0 0.

1 -4 O 0 FREQUENCY (Hz)

TRtP UNIT OBE X-DIRECTION QUALIFICATION CURVE

  1. dUJ;LEARt ENERlGY GE14ER A LQELECTIRI C NI11lO

'~-r ouslNESS OPERATtO"*-

ATTACHMEINT # 10 o

MCEt "4 am

- 4 WV. -

d - -p-m

-, -4

-, -4

-4

=-~--~-~-- -~ - I -~

- -~

-4I NE!

L 0 "W moc 5mrk-m_

zh .1 16 A .. Jf I -- =

t -4 l ~ -ii: ~ -

77ý

-F I- 4jýb tJ ,- . ý -:4 .1 -.1 f A - 4 -AI 3 P ---L i4 i i-4 iupm, .

A i -

-..- - ----- 3 7--! :gz

  • bAJ
  • - A* I r '94 .

0 A -- -4 - 4:*--- ----

I A.- -a. I .-- - - -

-- -t -4 40 -- -4

-~ --. ~ ft- zj t.aJ z i

I.

I. bI C

q ci AMMELETIOH (g)

CAB INET QU&IFICATION SEISHIC OeE/SSE LEYELS - YERTICAL

.-TT. INI-110 iUCLEAR ENERGY GEEI*3ERALQ ELECTRIC w MI'tNES. OPE RATIONS ATTACHMENT # 11 I

I=j ~ ~

~zja~ 4jL*~I~ .E~7ISiA

~~*:~M ~ =V. +/--.~-

____ ____,.,___ EE L u _- -

  • --*.** 0

-~-4 - ~ ii.

4 -~ - - ..-

~j~j u~ L 2 1  %~I4~2 ~ AU- ~4~ 4 4 4W' r~

-- A I -i - ýý

.1 1 ~

.4 II- I .4. 4

-- j .!-'-J 1Aim-b IQ- I Z M. 0 ;::r,-- ..-*-_.

= ---_

.-

  • f_-_ * *=4 '* . 4..ke-..

Pl . .. .1-:*

~--- I

'A-i,- -- 4-i no I t  : ° i I

= L*:"

m m

0

~1,4 d ~ p-I-.-

l* ' 1'.d "l 4-. *'4 ~ 4 .I.J S rA t~1' 4 L

-3it ;i~"

=

1=*==

L -it P--.i'* P 3,

i Iq 0 Q Q 0- C i0 Cii AC*ELERATION (g)

CABINET QUALIFICATION SEISMIC OBE/SSE LEVELS EoIL.ZONTAL

NI k oNýOa.,2 IN1.110 GE N4UCLEAR ENERGY 175 Curtner Avenue GE-N'E-901-001-0491 San Jose, CA 95125 DRF-AOO-02406-1(5).

Class I, April 1991 TECEICAL DESCRIFMION FOR GE NUCLEAR ENRGY ANALOG TRIP UNIT GE Dwg 1 184C5988 PREPAREDl BY: , 9- - - 77

/. 6-) P~ Date:_________

PLiip F. GaZber.

Technical Project Engineer Electrical Design Engineering VEIFITED BY: -~4 Date:__ __

Clark F. -Canhaz Xanaqer Plant Electronics Apl1ication Engineering REVIEWED BY William R. Marklein, Manager Electrical Design Zngineering 0

Page 1

A-T' 2-IN1-110 GE-NE-901-00I-0 4 91 IKPORTPAT NOTICE REGARDING CONTENTS OF TIS REPORT Please Read Carefully The only undertaking .of the General Electric Company (GE) respecting information in this document is contained in the conzract (or purchase order) between the Customer and GE, and nothing contained in this document shall be construed as changing the contract (or purchase order). The use of this information by anyone other than the Customer, or for any purpose other than that for which it is intended under such contract (or purchase order) is not authorized; and with respect to any unauthorized use, GE makes no representation or warranty, and assumes rjo liability as to the completeness, accuracy, or usefulness of the information contained in this document, or that its use may not infringe privately owned rights.

Page 2

GE-NE-901-001- 049 1 INI1-110 Contents Page I. Background on. Master Trip Unit (MTU) and Slave Trip Unit (STU) -c-- A4 II. Functional Block Diagram of the MTWI O q *

  • 4 III. HTU Calibration............ . ... 5 IV. Transmitter Loop Resistance . . 7 V. Performance Specifications . 7 VI. Seismic Qualification S VI-. Physical Characteristics .... . 9 VIII. Terminal Arrangement 9 IX. List of Existing Legend/Scale Configuration 9 X. Pricing. . ................... ... 12 Attachment 1 1 13 Attachment 1 2 ......... ............... .. 14 Page 3

A-TT. INI-110 GE-lfE-901-ool- 0491 I. BACKGROUND ON MASTER TRIP UNIT- (MTU) AND SLAVE TRIP UNIT (STU)

The base number for the GE Trip Unit is 184C5988GXXX, where the three X's will be replaced with a three digit number, such as 184C5988GI12.

Master Trip Units belong tot.the Group 100, 200, 400, 500, or 600. Trip Units series. Slave Trip Units are the Group 300 and 700 series.

TRIP UNIT GROUPS APPLICATION INPUT RESET GROUP FILTER DIFFERENTIAL (Hz)()

4-20 ma DC Current Input MTU 250 0.5 - 20 GI00 100-ohm Platinum RTD MTU 250 0.5 - 20 G200 Slave Trip Unit 250 0.5 - 20 G300 Voltage Input MTU 250 0.5 - 20 G400 4-20 =a Carrent Input MTU 1 0.5 - 20 G500 S 4-20 ma Current Input MTU 250 0.5 - 50 G600 Slave Trip Unit 250 0.5 - 50 G700 The MTU receives its input' signals from analog transmitters, typically Rosemount 1150 series. When- the input signal reaches a predetermined value (the setpoint), the HTU changes the state of its trip output. The MTU visually indicates the magnitude of the process parameter monitored with a meter on its front panel. The HTU provide 1 to 5 Vdc output signals, linearly related to the input signal. One output is for driving Slave Trip Units (STU), the other for driving auxiliary analog devices (recorders, meters, etc.).

It should be noted that the GE Trip Units are a direct "plug-in" compatible unit with the Rosemount unit, and no additional accessory hardware and/or components such as card files, calibration units, readout assemblies, card extenders, etc.

are required.

II. FUNCTIONAL BLOCK DIAGRAM OF THE MASTER TRIP UNIT Refer to Attachment No. 1.

Page 4

GE-W7-Qn1_001_0491 A-i-r. !II. F.ASTER TRIP UNIT CALIBRATION AND GROSS FAILURZ SETPOINTS Each MTU provides gross failure detection circuitry which detects when the input signal has deviated beyond the normal 4-20 ma process range. The MTU provides high. and low, adjustable gross failure limits. The gross failure output will be low and the gross failure indicator off until the input signal exceeds either gross failure limit; then, the gross failure output will latch high and the gross failure indicator will illuminate and latch.

The High Gross Failure Setpoint is adjustable from approxi-mately 20 to 40 milliamps. The Low Gross Failure Setpoint is adjustable from approximately 0.4 to 4.0 ma. A momentary contact pushbutton resets the gross failure indicator when illuminated and latched, if the input signal has returned to its normal range. The momentary contact pushbutton also resets the gross failure -output when latched, only if the input signal has returned to its normal range, and the trip unit is not in the calibration mode.

When the input signal is disconnected from the MTU, and the

-TU is not in the calibration mode, the gros's failure output latches high, and the gross failure indicator illuminbtes.

Terminals 8 and 9 are shorted together on the printed circuit (PC) card. This feature is used as part of a continuity loop to detect a "card-out-of-file" condition.

The front-mounted TRIP status indicator, which illuminates when the input -signal reaches (or exceeds) the setpoint, is labeled TRIP. The front-mounted GROSS, FAILURE status indicator which illuminates when either gross failure limit is exceeded is labeled GROSS FAILURE.

The GE units are plug-in compatible replacements with the Rosemount units and basically utilize similar calibration requirements. There are slight differences in the Gross Fail and Trip Setpoint Hysteresis setpoints. It should be noted that even though the differences are slight, it may require a "note" correction to the. Surveillance & 'Operational Test Procedures or Calibration Procedures to account for slight differences in the reset points.

Page 5 I

GE-NE-901-001-04 91 A** 2- = INI-110 a .N.p 1PA&C5 £SLcbF Is GROSS FAILURE LED (RED) OPEAION MODE GEi1 ROSEK tT SO & 7310 CAL 1. LED 'OFF' if: 1. LED 'ON' but not LGFS < INPUT < HGF-S. latched if:

LGFS < INPUT < HGFS.

2. LED 'ON' & latched if: 2. LED 'ON' 6 latched INPUT < LGFS or INPUT > iff:

HGFS. Can be turned 'OFF' INPUT < LGFS or if input retuined to INPUT > HGFS.

within gross fail limits Cannot be turned

& RESET. Permits checking 'OFF'. Cannot check GROSS FAIL setpoints GROSS FAIL setpoints using CAL UNIT &- READOUT with TU in cardfile.

ASSEMBLY with TU in cardfile.

NOT 1. LED 'OFF' if: 1. SAME AS GE.

IN LGFS < INPUT < HGFS.

CAL

2. LED 'ON' & latched if: 2. SAME AS GE.

INPUT < LGFS or INPUT >

HGFS. Can be turned 'OFF' if input returned to within gross fail limits

& RESET.

GE TRIP UNIT STATUS LED (BI-COLOR GREEN/RED) OPERATION GE Ij ROSEMOUNT 510 & 710 CAL Illuminates RED independent Not provided.

of INPUT NOT 1. Illuminates GREEN if: Not provided IN, LGFS < INPUT < HGFS.

CAL

2. Illuminates & latches RED if:

INPUT < LGFS or INPUT >

HGFS.

Illuminates GREEN when INPUT returns to within GROSS FAIL limits &

RESET.

Page 6

GE-KE-901-0 - 1 A4-T. -z_ 0 1 0 4 9

-ar e. -' IN -110

-IV. MAXIMUM ALLOWABLE TRANSMIaTTER LOOP RESISTANCE Total transmitter loop resistance between the +25 Vdc (nominal) power supply and signal common (excluding the resistance of the transmitter and the wiring to and from the MTU to the transmitter) is to be less than 330 ohms.

The loop is powered by -"the MTU from an external +25 Vdc (nominal) power supply which is connected as input power to the MTU.

V. PERFORMANCE SPECIFICATIONS FOR 18-MONTH. DRIFT AND THE EFFECTS OF TM-PERATURE, SEISMIC VIBRATION, AND RADIATION ON THE ACCURACY OF TEE TRIP UNIT Performance specifications for 18-month drift for the YTU would be strictly from empirical data, and does not exist at this time.

Drift is expressed in Percent Full Scale (%FS) of calibrated span for a one month interval.

The MTU meets or exceeds the design drift values* listed as follows:

Normal: 0.10% FS

. Abnormal (1 Day/Year): 0.20% FS Design Basis Earthquake (DBE)

(LOCA-HELB 180 Days): 0.10%FS where LOCA = Loss of Coolant Accident HELB = High Energy Line Break The desicn drift value is defined as the amount the output, test jack value, or setpoint deviates from the value it was set at during calibration and the value at which it is found or trips at the end of one month under the identical operational and environmental conditions of the preceeding calibration.

Page 7

GE-NE-901-001-0 4 9 1

~A~Z f'~

~INI -10; The maximum environmental conditions to which the trip units may be exposed during plant life are as fol'lows:

MAXIMUM ENVIRONMENTAL CONDITIONS LPAPAHETER NORMAL ~ ABoRM~L DEBE/POST DBEE DURATION 40 years 1 day/year 180 days TEMP "F 76.0 for Room 40(rmin)/105(max) 76.0 for Room Ambient for Room Ambient Ambient 113.5 Cabinet 77.5(min)/142.5(max) 113.5 Cabinet Internal for Cabinet Internal Internal HUMIDITY 50 90 50

%RH PRESSURE ATM ATM ATM RADIATION 2.5 x 102 Rads N/A 2.5 X-102 Rads total integrated total integrated dose dose

  • Includes a 37.5 -F cabinet temperature rise based on test data from the cabinet qualification program.

VI. SEISMIC QUALIFICATION OF THE GE TRIP UNIT AND ROSEHOUNT CARD FILE CONTAINING GE TRIP UNITS OR BOTH GE AND ROSEMOUNT TRIP UNITS The GE Analog Trip Units have been seismically a'.ialified zo generic, bounding seismic exposure levels. Durinc qualification tests, the Test Response Spectra exceeded the Required Response Spectra. This assured the Trip Units at their mounting locations in the test cabinet experienced seismic levels in excess of their specified service condition.

The Trip Units were operational during OBE and SSE tests.

They were subjected to at least five OBEs and on SSEs in two orientations.

Seismic qualification and adequacy evaluations of specific mounting and service conditions can be performed by analysis and upon request.

Page 8

GE-NE-901--001-04o9 A-M 1 AINI1-10 VII. PHYSICAL DIMENSIONS AND WEIGHT Dimensions of the trip units are 6.969 inches high by 1.188 inches wide by 9.875 inches deep.

The weight is 18.0 oz.

VIII TERMINAL ASSIGHMENT AND GROUNDING -AND SHIELDING REQUIRfEMENTS See Attachment T 2.

IX. LIST OF EXISTING LEGEND/SCALE CONFIGURATIONS GE Master Trip Unit Model' 184C5988GXXX XXX Input Type 'Meter Range I Legend jType Div I100 4-20 MA NO SCALE 101 4-2.0 MA 0 TO 1200 PSIG LINEAR" 60 4-20 MA 0 TO 35 PSIG LINEAR 70 10211 103 4-20 MA 0 TO 250 PSIG j LINEAR .50 104 , 4-20 MA -150 TO +60 INCHES WC LINEAR 42 105 4--20 MA II 0 TO +60 INCHES WC LINEAR 60 106 4-20 MA 800 TO 1200 PSIG LINEAR 40 107' 4-20 MA 0 TO +80 INCHES H0 LINEAR 40 108 4-20 MA 30 TO 40 PSI IN Hg OTHER VAC 109 4-20 MA 0 TO +50 INCHES WC LINEAR 50 110 4-20 MA 200 TO 500 INCHES WC LINEAR 60 111 4-20 MA 0 TO 10 PSIG LINEAR 50 112 4-20 MA 0 TO 1500 PSIG LINEAR 75 113 4-20 MA 0 TO 30 INCHES LINEAR 60 114 4-20 MA 0 TO 100 INCHES WC LINEAR 50 115 4-20 MA NO SCALE

-116 4-20 MA 0 TO 30 INCHES Hg LM R 60

__ __ VAC Page 9

-'--NE-901-001-0491 IhecrtT2Z INI-110 GE Master Trip Unit Modell 184C5988GXXX xxx Input TypeJ Meter Range Legend Type DijvI 117 4-20 MA. -500 TO 0 INCHES WC LINEAR So TO_5"00 _ _ _ _ _ _ _ _ _

118 4-20 MA -200 TO 0 INCHES WC LINEAR 40 TO 200

.119 4-20 MA 0 TO !so PSI LINEAR 75 120. 4-20 KA 0 TO 50 PERCENT LINEAR .50 121 4-2o MA 0 TO 300 PSIG LINEAR 05 122 4-20 MA 0 TO 100 PERCENT LINEAR 50 123 4-20 MA -3.1 TO 49.6 INCHES ABOVE LINEAR 13 263 FT 10 IN.

124 4-20 MA -2.2 TO 50.6 INCHES ABOVE LINEAR 14 263 FT 10 IN 125 4-20 MA 0 TO 210 INCHES LINEAR 42 200 RTD 3 WIRE NO SCALE PLATINUM 201 RTD 3 WIRE 50 TO 350 "F LINEAR 60 PLATINUM 202 RTD 3 WIRE 0 TO 250 F LINEAR 50 PLATINUM 203 204 205 400 1-5 VDC NO SCALE _ _ __

NO DIFFERENTIAL 401 1-5 VDC 0 TO 300 F LINEAR 60 DIFFERENTIAL DIFFERENTIAL

...402 403 404 405 500 4-20 MA NO SCALE Page 10 I -

GE-NTE-901-ool-0 4 9 1 Ae- 2 IN1-1 10 GE Master Trip Unit Model 184CS988GXXX XXX Input Type Meter Range Legend Type DliDv 501 4-20 74A -300 TO +300 INCHES WC LINEAR 60 502 4-20 MA 10 TO 50 INCHES WC LINEAR 50 503 4-20 MA 0 TO 1200 PSIG LINEAR 60 504 4-20 MA 0 TO 500 PSIG LINEAR 50 505 4-20 MA 0 TO 150n. PSID LINEAR 75 506 4-20 MA NO SCALE.

507 4-20 MA NO SCALE 508 4-20 MA NO SCALE .

509 4-20 MA -NO SCALE 510 4-20 MA NO SCALE 600 .4-20 MA NO SCALE 602 4-20 MA O0TO 50 INCHES WC LINEAR 50 f606 4-20 MA 800 TO 1200 PSIG LINEAR _40 Page 11

GE-NE- 901-001-04 91 A-rr. 2 INI-110 X. PRICING AND DELIVERY Prices for both MTU's and SLU's are given below. Order quantities of 8 or greater for any particular group (e.g.

184C5988G112) qualify for the volume prices shown below.

Quantity ?Master Trip Unit Slave Trip Unit 1 - 7 S 12,390 each -$ 10,970 each 8 $ 11,151 each $ 9,873 each 16 - 49 $ 9,912 each $ 8,776 each ANY QUANTITY ABOVE QUANTITY 49 WILL BE CONSIDERED A BULK PURCHASE. A SEPARATE PRICING LIST HAS BEEN SUPPLIED TO TEE BWR OWNERS' GROUP FOR THIS BULK PURCHASE.

Scheduling is approximately 26 weeks from date of order.

Orders above auantity 49 may require special scheduling.

Page 12

I-'

I 4 9'1 J.dInju l *ufl

,I-?. vin~lf vo W-14 i'r IvrI$u IV411040) pa11QIsinuollvlll

'h'yss 93W)VIIII It I

1111 t0) I Itoll Iici imm

)AVIS O0 AUt, I UW11110 )

CD fdloJS 0 SnIvII rC V

ci' S 4 11 d WASI~l41WIWDOi 0 SHUR 31M

])WN t- S$1 t who,,l l.*

51041(a

  • IOl '(- Is SSON1 01,14 Ao1. +--- ..... ..

iAll )+llJ *AI I.

0

ATTACHMENT #2 INI-110 GE-NE-901-C01-ArilZ Table 3-1. Trip Unit Terminal Assignments Master and Slave Trip Units Terminal Bars T3l through T312 NOTE: Although calibrate command and calibration current signals are T

routed to all Trip Units, they are used only by Master rip Units-TERMINAL SIG'*AL PO.ACATURI l.S 1 Chassis Ground Should be grounded to the relay rack external to the Card File.

2 +25V Pover 3 25V Pover Return This ground is the return for all loads except the analog-to-Slave and auxiliarT analog outputs. Power return must be bussed back to the power supply separate from the signal return.

Si-Al %Ce:ut= This ground is tbhe return for the analog-to-Slave and auxiliary analog outputs, transmitter current, and sIall currents used to generate reference voltages in each Master Trip Unit. Signal return must be bussed back to the pover supply separate from the power retura.

5 T.I p Srzrus 0 to 12 Vdc logic level to the Readout Asaembly in the Calibration Unit. It latches the trip current display after a trip action.

6 Calibrate Coemand 25 Vdc signal from the Calibration Unit (Master Trip Units) which opens the transmitter signal loop and closes the calibration current loop. It also causes a gross failure indication/output on the Master Trip Unit.

Calibration Current 7 Input of total calibration current froc T

(?aster rip Units) the Calibration Unit.

8 Card Out Alarm Terminals 8 and 9 are shorted together or the printed circuit board for the Card 9 Card Out Alarm Out Alazz systea..

I-Psge 14

ATTACHMENT 0 2 (CONTINUED) GE-'NE-9 0 1- 0 0 1

.-9_5 INI-110 GEIK-83408B Table 3-1. Trip Unit Terminal Asuignmencs (Continued)

T EM.MNAL SIGNAL WO CIA'TURE EXARJS 10 Cross Failure Output Drive for external relays wvhch signals that preset high or loy transmitter signal limits have been exceeded, or a-Trip Unit is being calibrated.

ii Trip Output Drive for external relays which operates when the trip point is bypassed through.

0Oco 10 Vdc (calibrated from 1 to 5 Vdc)

I 12 Analog-output-to-Slave Po.Aster Trip Units vith Analog Output) analog signal proportional to trans-hitter current.

supply by signal Bussed back to power return.

I Analog Input 0 to 10 Vdc (calibrated from 1 to 5 Vdc)

(Slave Trip Units) analog signal from Master Trip Unit with Analog Output Slave Trip Unit coupars-tots use this signal to detersiue the trip output state.

13 Vot used 14 4 to 20 mA Trant-. 23 to 24 Vdc nomual excitation to hitter Zxcitation remote transmitter.

15 4 to 20 M Trazt- Trana---irter current input to Master Trip

=itter Returzi Unit. Current is fed through a 250-ohn resistor.

16 Auxiliary Analog 0 to 10 Vdc (calibrated from 1 to 5 Vdc)

Output (Master analog signal proportional to trans-Trip Vnits with sitter current for driving external Analog Output) recorders, controllers, etc. Bussed back to paver supply by signal return.

.. The signal In capable of driving resis-tive loads from 1,500 ohns and up.

0.

Pago 15

0C 1- 0A 6& 1 Q Q 6 1IN I -1l i P September 30, 1991 C:. I10 NL91.O1z Mr. J. Delani Boston Edison Company Purchasing Department 800 .Boylston Street Boston. MA 02199

SUBJECT:

PROPOSAL FOR NUCLEAR SAFETY RELATED TRIP UNITS -

PROPOSAL NO. HK15070P1

REFERENCE:

Boston Edison Company Purchase Order No. NST014526 Oear Mr. Delani:

In response to -the 'referenced purchase order for equipment and qualification documentation for subject trip units. GE Muclear Energy (GE) is pleased to provide this proposal to Boston Edison Company (BECo).

1.0 SCOPE OF SUPPLY The proposad scope of supply includes the hardware and associated services to provide the safety related and qualified trip units.

The following is included in the proposed scope of supply as requested by your refbrenced purchase order:

I Item 1- Six (6) Cla;; 1E, Master Analog Trip Units 184C5988G112 Item 2"- Sik (6) Class 1E, Master Analog Trip Units, IB4CS988GXX (A group number will be added for the required scale.)

Item 3 - Three (3) copies of Enviran=ental and Seismic Qual ification Report Item 4 - Four (4) copies of GEK-83409 (latest revision)

Item 5 - Safety Related Pr-jduct quality Certificate (PQC) for Items 1 and 2.

The master trip units will be furnished safety related and qualified to IEEE 323-1974 and IEEE 344-1975.

Z.0 EXCEPTrONS/COMMENTS 2.1 Par& 3.0 (APPLICABLE DOCUNENTS)

The provisions of Federal Regulations, IEEE and ANSI standards apply as Interpreted by GE.

r INI-1i0 Mr. J. D~elani September 30. 1991 Page 2 2.2 Para 4.2 (Analoo Ourtnut Accuracy)

Exception istaken to the requirement that under normal operating codititbns*,analog output accuracy shall be within +/- 0.15% from 85 F to 11 F and +/- 0.3SO. of span per 100HF temperature change

-Gvr r*efeeotC eendfinrs.

The trip units will be furnished qualified to the following design requi rements:

4-20 n-A 0.15% of full scale to 113.5 O0 and HTU Slave and 0.2S% of full Scale from 113.5 F to 142.5 F Auxiliary Analog (includes 37.5 F cabinet temperature rise)

Out~pi;ts-2.3 Pare 4.3 (Trio Point Rgpoeaab1litv)

Exception is taken to the requirament that under normal operating condition3, Haster Trip Unit tri8 point r 8 peatabillty shall be w-thin ý/- 0.13% of span from 85 F to 115 F and +/- O.20% of span per 100 F temperature change over reference conditlons.

The trip units will be furnished qualified to the following dasiSn requirements for accuracy (trip polnt repcatability);

4-20 M 0.13% of full scale to 113.5 '9 and MTU Setpoint 0.20% of full Acale from 113.5 F to 14Z.5 F

- (includes 37.5'F cabinet temperature rtlse)7 2.4 Para 4.5 (Er.vironrental and Seismic Qualificatlon) o Environmental - exception is taken to the humidity (abnormal) and radiation requirements. The trip units will be furnished qualified to:

HJMIDITY (Normal)t go%

RADIATION: In (four years qualified life).

Qualification can be extended provided period surveillance and cal ibration 'are performed by BECo as recommended on a monthly basic.

o Seismic - exception istaken to the seismic loading candition; of Appendix A. The trip units as qualified by CC can meet the Appendix A SRRS at 3% O*eafing, not 6%.

2.5 Para 0.0 (FABRICATION REOUIREMEFTS)

Exception Is taken to the requirment that trii unit front panels shall be finished with black luster-less polyerethane paint (A"erican Coatings and Cheofcals No. 37038) "with white lettering.

=-. RV-.rl-- -- IN1.110 Mr. J. Delani P/ Or G September 30, 1991 Page 3 2.6 Para 8.0 (INSPECT[ON, EXAMiNATION AND TEST REOUrRENENTS)

Present production test practices do not Include setting and verification of set points as required by Paragraph 8.1." However,

_GE can provide this service to BECo as an option at'the additional cost indicated in Paragraph 5.5 below.

2.7 Para 9.0 (MAINTEN4ANCE) o GE will provide four (4) copies of the latest revision of the standard GEK-83408 (Operating and Maintenance Instructions.)

o GE does not reconimend any spare parts. In case of malfunction,

  • It is recommended that the trip units be returned to GE for repair 'and return or replacement.

2.8 Para 10.0 (HANOLTNG. PACKAGIG,. SHIPPrNG AND STORAGE)

BECo may audit CE documentation at mutually agreeable terms.

Instructions will not be submitted to BECo for approval.

2.9 Para 11.0 (QUAITTY ASSURANCE REOUIREMENTS) o Qpality Assurance functions will be performed under tNRC.

approved and BECo audited and accepted General Electric 8WR Quality Assurance Program as described in Licensing Topical Report NEDO.11209.

o Hold/Wlftncs points are not included in this proposal.

Requests fcr hold/witnec points will be discussed and nutually agreed upon.

a GE cannot assure access to sub-tier ,endors for audit purposes.

2.10 Para 12.0.(GUARANTEE)

Guarantee will be per term= and conditions of paragraph 7.0 below.

2.11 Para 13.0 (PROPOSAL REOUIREMENTS) 0oG cannot provide a list of subcontractors and lower tier suppliers.

. r- o BECo will be kept advised by the Personal Account Representative of the fabrication and test schedule. IWitness and hold points will be discussed and mutually agreed upon.

,j o Estimated delivery is thirty six (36)* eeks after receipt and GE acceptance of a purchase order from.BECo. Actual schedule will be established after order Is placed.

I Z A-TT. -3 * ' *-

Mr. J. Delani September 30, 1991  ? (ccF=(

Page 4 2.12 Para 16.0 (DOCU)ENTATION REOUIREMENTS) o Appendix 8. Exception is taken to these requirements. BECo may audit GE documentation at mutually agreeable terms.

o Spare Parts List. GE does not recomend any spares. We recom*nend that the trip units be returned to GE for repair and return or replacement.

o Seismic Report. Exception is taken to the requirement for submittal of Seismic Qualification Report for BECo approval.

-o Drawings. Exception Is taken to the requirement for submitting drawings.

o Instruction Manuals. CE will furnish four (4) copies of the latest revision of the standard GEK-83408 (Operating and Maintenance Instructions - latest revision.)

o Handling, Packaging, Shipping and Storage. BECo may audit GE instructions related to these activities.

o Certification. GE will provide certification as described in thisr proposal.

I 3.0 RESPONSIBILITIES 3.1 9f:

3.1.1 Identify a cognizant program manager responsible for the GE/BECo interface applicable to this program.

3.1.2 Establish a delivery schedule upon receipt and acceptance of the purchase order.

3.1.3 Supply GE scope of hardware and documentation as defined In Section 1.0.

3.1 EEn 3.2.1 Isuo a purchase order referencing this proposal and terms and conditions.

3.2.2 Designate a cognizant individual to Interface with GE on all matters applicable to this proposal.

3.2.3 Identify any plant specific licensing requirefflts as well as any state and/or local requir*ents applicable to the hardware and sarvicas offered In this proposal.

3.2.4 Obtain all licensing and regulatory agmncy approvals.-

A-M. INI-110 F.r. J. Delani September 30, 1991 Page 5 Z.2.5 Provide plant specific seismic requirements (enveloping RRS at the mounting locations).

4.0 SAFETY CLASSIFICATION/QIALITY ASSURANCE 4.1 Services shall be performed in accordance with the General Electric BWR Quality Assurance Program as described In the current NRC accepted revision of Licensing Topical Report, REDO-11209.

4.2 The proposed Trip Units are classified 'Safety Relatedo. The provisions of IOCFR50 Appendix B, and 10CFRZI, apply as interpreted by GE.

4.3 MECo access requirements for audits of GE Is not included in the proposed scope of suply and shall-be atranged upon requesL at.

mutually agreeable terms.

4.4 The adequacy and accuracy of all BECo supplied information is the responsibility of BECz.

5.0 PRICE The firm prices for the scope of supply described In Section. 1.0 are as follows:

DRAWING DESCRIPTION 01L UNTI PO!CFL TOTAL 5.1 184CS98S]l2 Master Trip Unit 6 S 12.390 $ 74,340 5.2 184C59e8GXXX Master Trip Unit 6 S 12,390 S 74,340 5.3 Environmental and 1 S 27,800 Seismic Qualification Report 5.4. ---- Operating and maln- 4 Q tmnance Manual GEK-83408 (latest revision) 5.5 Set & Verification 12 $ 1,000 $ 12.000 of Set Points TOTAL S 198._8

Mr. J. Celani September 30, 1991 . ...... -1 -

Page 6 ~

6.0o HEDULE 6.1 Estimated shipment Is 36 weeks after receipt and GE acceptance of a purchase order from BECO. Actual schedule will be established after order is placed.

6.2 Documentation identified in Paragraph 1.0 and 2.0 of this proposal will be supplied four (4) weeks after shipment of hardware.

7.0 TFRM5 AND CONDITIONJ This offering shall be in accordance with and subject to the tetrns and conditions of the "Agreement between Boston Edison Company considerinig the Sale of Spare Parts and Services for use in Nuclear Power Plants dated January 12.* 1971, as amended to date.

a.0 PROPRIFTARY INFORHATION #fT1CE This preposal document is proprietary to GE and Is furnished in confidence solely for use In considering the merits of the proposal and for no other direct or indirect use. The information contained herein is not to be distributed, in whole or part, to third parties without the prior consent of GE. If this proposal is not accepted, it is subJect to return to GE upon request.

9.0 EXPIRATiON DATE This proposal is valid for a period of ninety (90) days from date of issue, unless extended In writing by GE.

GE is pleased to be of servicQ to BEto in the supply of these trip units.

Should you have any questions regarding this proposal, please contact me or N. Lamberti on .(408) 92S-3602.

yours, Very truly Kiran Kumar Personal Account Representative PRODUCT SERVICES MATERIALS & PROCUREIHENT SERVICES N/C 853 - (408) 225-6993

/ng

NEDORANDJM, A-rA-cuIm~e~lL/ INI-I 10 CDC;" 4- -P, BSE-Co. Form X6604

  • From. /14 ~cj4-~ Date

. .. b SU'bject. .AC-t P4 W~et-'

C7C ;2a 7J Replies to: V/,4

References:

psq7 Pi 6 SA. pS 7 P 7-7~

Reply Requested: /L)o N F, 4kequested Date:

4/A Message: (Use attached sheets if required)

/1)A77//9-a.

Oistbution:

E Nuclear Engineering ManagerManager .b~Z'c R 14 Nuclear Enginee ng, Deputy

" Field Engineering Section Manager

" Design Section Manager BC, C0 Analysis Section Manager (Specify others - NED only) 7~b74-~

-A--" . q INIA110 L4-

__ -_* v_ C . __.___! o

  • La.

- L* _ _._ ,_ ...Ž. .

'D4~t. _3At7

. _. /, .

  • LsL 4,, " L.I ,

... .. ... .o. j. e*.o

, .. *L, . , 2*.£*.-.

(eJ

, t-.- I, .* . o.4,

. .. k *w * /.i . ,.*, *,,._ =* _ ,7 ._o . ... . ... ' " *",/9- * -

- -C- - , ,.

IN1-110 BOSTON AT-r-rAc-.A4&A-74 r EDISON KEDORANDWJ HAD #91-95 TO: FROI4: .3 ~~'nIDATE:

Subject:

Limits For ATHS Setpoints Replies To: 91-314 Reply Requested:

Requested Date:

Message:

(See Attached)

Di stri buti ion:

Nuclear Eptineertng Manager NAD File #91-95

  • 'elneering Section Manager R. KellIey oection Manager iD. Richard s Section Manager

A-1-n IN1-1 I 10 Attachment To HAD 91- e=R go 627--ln76 Background/Purpose-he current technical specifications for POPS specify high reactor pressu d low reactor water level setpoints for ATHS mitigation at allowable v ues e 1 to that used In the analyses of record, NEDO-25016. Analytical lues in later document, NEDC 31425. have additional margin for measur unce inty. However, this document was not reviewed and accepted BECo until cently. I&CS #91-314 requests that NAD resolve the differ ces between e documents and related issues. This nedorandum respo s to the same.

Discussion NEDC 31425 was viewed and accepted by SUDDS91-178. Th upper analytical limit for high p sure ATHS is 1220 psia (1205 psig). rrently, the lower analytical limit i 1190 psia (1175 psig). This limit s not ATWS related and has only a slight a ct on reload analyses' peak pre ures. Based on the typical sensitivity g en in GE document A63HA247. ., Sheet 30 and the margin available in the nalysis of Cycle 9, an an ytic limit of 1145 would not invalidate the curre core analysis. A valu of 1145 psig will be used in the cycle 10 reload ana sis. The analytical imit for reactor water level is -57 inches based upon a c rificatlon to HE 31425, Table A-2, as given in GE-NE-187-69-1291 (p. 4-6, 7). See also SUOD 91-177.

There are no errors associated wi these tpoints except that identified in GE letter LLC-52-91. ATHS must be uncti nal for the pressure range from 800 psig to 1205 psig. ATHS events a depressurize the reactor would be isolated at 800 psig and repressurize e to reactor power. ATHS need not be functiocal above the pressure it is s ned to actuate. The reactor water temperature range is 500OF-5706F. e a temperature in the drywell is not expected to vary significantly fr normal uring an ATHS. However, we recommend assuming a range of 10 150°F. T analytical limits are not a function of operating pressure nd temperatur NAD will provide a resoluti to S&SA memo 91-67.

Conclusion The above information rovides a response to I&S #191- 4.

EDISON -OMPJ flY- A7TAfZ0,x4e IN1.110 V -., ° .

SPILGRIM

-OStON STATION TELEPHONE CALL REC( )RD p~(~

0 TO "nL& .* Sem DATE. 9124 =.R TIME .M*

FROM -Bgr COMPANY/OFFICE SUBJECT SLOAZ!&ý Renptl (0 n*a& Go* t115 PHONE NO.

  • U,2- 4*,-1114
  • V 1ýA,,-

,es. *. AZ1"-- ýu A i Reqres '3S-4. 4 Action Required: 2tQ Copies to: Group Leader RA&P - GL (For Licensing Items) 0CC SIGNED Chrono File No: DATE 2 ILI f Subject File No: Page I of J._

BECo Form X-5104" 4

I .

I

Attachment 2 to ENCLOSURE 1 To Entergy Letter No. 2.11.007 Pilgrim Calibration Procedure, 8.M.1-29, "ATWS Trip Unit Calibration Test" Rev. 50 (152 pages)

RTYPE H6.08 PILGRIM NUCLEAR POWER STATION Procedure No. 8.M.1-29 ATWS TRIP UNIT CALIBRATION TEST Stop Think STAR Act Review CONTINUOUS USE PM DATABASE RELATED 8.M.1-29 Rev. 50

REVISION LOG REVISION 50 Date Originated 11/10 Pagqes Affected Description (Revisions 40 through 49 omitted due to MERLIN revision numbering scheme.)

10 In Step 9.0[3](b), correct component to be a PIS instead of an LIS and correct actuation pressure from 1160-1190 psig to 1170-1180 psig. (CR-PNP-2010-3540) 10,12,81 Update terminology to reflect Asset Suite implementation.

12,81 Delete reference to PNPS 1.3.34 regarding Pre-Evolution Brief.

79,149 Change Superintendent to Supervision.

REVISION 39 Date Originated 8/04 Pages Affected Description 1 Delete "High Risk" from title.

3,11,13,77,141 Add Alarm Summary Sheet Attachment.

10 Allow Maintenance Lead to perform Maintenance Management functions/responsibilities.

12,76 Add "if required" to PEB step.

15 Correct referenced Rx Bldg elevation to be 51', not -51'.

37 Add DS10C Panel C2277 to supervisory lights to be verified.

140 Add lines to record date and performer's name and statement to include applicable Attachment number.

8.M.1-29 Rev. 50 Page 2 of 152

TABLE OF CONTENTS Paae 1.0 PU R PO SE A ND SC O PE .................................................................................. 4 2 .0 R E F E R E NC E S ................................................................................................ 4 2.1 D EV ELO PM ENTA L................................................................................ 4 2.2 IMP LE ME NT ING .................................................................................... 5 3 .0 D E F INITIO NS ................................................................................................... 6 4 .0 D IS C USS IO N................................................................................................. .. 6 5.0 SPECIAL TOOLS AND EQUIPMENT ............................................................... 8 6.0 PRECAUTIONS AND LIMITATIONS ............................................................... 8 7.0 P R E R E Q UIS IT E S ............................................................................................. 9 8 .0 P R O C E D UR E ................................................................................................... 9 9.0 ACCEPTANCE CRITERIA .............................................................................. 10 10.0 CO RRECTIVE ACTIO N .................................................................................. 10 11.0 ACCEPTANCE VERIFICATION AND SIGNOFF ............................................ 10 12 .0 A TTA C HME NT S ............................................................................................... 11 ATTACHMENT 1 - ATWS TRIP UNIT CABINET C2277 CALIBRATION ................... 12 ATTACHMENT 2 - ATWS TRIP UNIT CABINET C2278 CALIBRATION ................... 81 ATTACHMENT 3 - I&C PROCEDURE FEEDBACK FORM ......................................... 151 ATTACHMENT 4 - ALARM

SUMMARY

SHEET ........................................................... 152 8.M.1-29 Rev. 50 Page 3 of 152

1.0 PURPOSE AND SCOPE This Procedure provides detailed instructions for qualified Maintenance personnel in performing functional testing and calibration of the Anticipated Transient Without Scram (ATWS) analog trip system. Performance of this Procedure partially satisfies Technical Specifications as listed on the table below.

TECHNICAL SPECIFICATIONS EQUIPMENT TESTED SURVEILLANCE REQUIREMENTS 4.2.G Minimum Test and Calibration Frequency for ATWS RPT/ARI Instrumentation Reactor High Pressure PIS-263-123A PIS-263-123B PIS-263-123C PIS-263-123D PS-263-123A-1 PS-263-123B-1 PS-263-123C-1 PS-263-123D-1 Reactor Low-Low Water Level LIS-263-121A LIS-263-121B LIS-263-121C LIS-263-121 D

2.0 REFERENCES

2.1 DEVELOPMENTAL

[1] NRCCC Item PAPR 020 (Pre-Evolution Briefing)

[2] Plant Design Changes (PDCs/FRNs/ERs/ECs)

(a) 86-102: SEP Feedwater Pump Trip Modification (b) 87-30: RPT Motor Drive Breaker (c) 91-47: Replacement of Rosemount Master Analog Trip Units 8.M.1-29 Rev. 50 Page 4 of 152

[3] Problem Reports (PRs)

(a) 93.9004, ATWS Cont. Lights DS10ADS10C De-energized (b) 95.9314.04, LIS-263-121A (ATWS) Failed During 8.M.1-29

[4] Technical Specifications (a) Table 3.2.G: Instrumentation That Initiates Recirculation Pump Trip and Alternate Rod Insertion (b) Table 4.2.G: Minimum Test and Calibration Frequency for ATWS RPT/ARI Instrumentation

[5] Vendor Manual V-0242: ATWS Analog Trip System Instruments 2.2 IMPLEMENTING

[1] P&ID M250: Control Rod Hydraulic System

[2] P&ID M253: Nuclear Boiler

[3] PNPS 1.3.34, "OperationsAdministrative Policies and Processes"

[4] PNPS Elementary Diagrams (a) M1YI: ATWS System (b) M1Y2: ATWS System-Instrument Data Sheet (c) M1Y3: ATWS System (d) M1Y4: ATWS System Power Supply (e) M1Y5: ATWS System Power Supply (f) M1Y6: ATWS System (g) M1Y7: ATWS System (h) M1Y8: ATWS System (i) M1Y9: ATWS System (j) M1Y10: ATWS System (k) M1Y11: ATWS System (I) M1Y12: ATWS System (m) M1Y13: ATWS Feedwater Pump Trip System 8.M.1-29 Rev. 50 Page 5 of 152

[5] PNPS Schematic Diagram (a) E550 Sh. 7, Reactor Water Level Loop 'A' PAM System (b) E550 Sh. 8, Reactor Water Level Loop 'B' PAM System 3.0 DEFINITIONS None 4.0 DISCUSSION

[1] Impact on Operations (a) Surveillance Summary - This Procedure calibrates the Division 1 (C2277) and Division 2 (C2278) ATWS trip units by simulating an input signal by use of a readout assembly for Reactor level and Reactor pressure, including the following:

0 Trip setpoints [Low-Low Reactor Level (-46"), High Reactor Pressure (1175 psig and 1400 psig)]

0 Proper alarm response 0 Proper relay response 0 Proper circuit supervisory light response 0 Calibration of the trip unit indicators (b) Impact

  • ATWS Division 1 will be inoperable during performance of Attachment 1.
  • ATWS Division 2 will be inoperable during performance of Attachment 2.

(c) Technical Specifications 0 Tables 3.2.G/4.2.G (d) Other

  • PNPS 1.3.34 Section 6.14 8.M.1-29 Rev. 50 Page 6 of 152

[2] The ATWS System provides for an addition of negative reactivity to the core (tripping Recirculation Pumps and letting air off Scram header) in the event of a transient (Hi-Hi Reactor pressure or Low-Low Reactor water level) without a Scram having taken place.

[3] The ATWS System is composed of four trip channels which make two trip systems.

Channels "A" and "C" compose Trip System "A" and it is housed in Panel C2277.

Channels "B" and "D" compose Trip System "B" and it is housed in Panel C2278.

NOTE Recirculation pump trip circuits are valid only when pumps are running. Lights will be off when pumps are off.

Feedwater pump trip circuits are valid only when pumps are running. Lights will not light when the pumps are off.

Neon lamps are used in these circuits to minimize the current flow through the trip coil and prevent false trip.

[4] Each trip system has three trip circuits, each trip circuit is equipped with a light system.

Two neon lamps are connected in series and are in series with a trip coil. During normal operation the trip relays are de-energized (untripped) and normal voltage across each neon lamp is approximately 66V DC.

[5] When one trip relay energizes (half-trip), the voltage across lamps connected in parallel with.closed contacts will go to approximately 0 volts DC and the lamps will turn off. This indicates tripped relay contacts have closed. Relay contacts and associated lamps are listed in Attachments 1 and 2.

[6] The indicator lights used are neon lamps which, when lit with one channel tripped, draw insufficient current to actuate the trip devices. When no channel is tripped, it is intended that none of the indicator lights be lit. However, because the voltage to maintain neon lamps lit is less than the threshold firing voltage of lamps, in some cases, both lamps in series may be lit. Therefore, when no channel is tripped, the pairs of indicator lamps may be either both lit or both off. When a channel is tripped, only one of the lights will be lit.

[7] Notify Operations that EPIC "RPV Level Validation Screen #71" will be affected during the calibration of LIS-263-121A and LIS-263-121C.

8.M.1-29 Rev. 50 Page 7 of 152

5.0 SPECIAL TOOLS AND EQUIPMENT

[1] Rosemount readout assembly and extender card

[2] Multimeter

[3] CR keys for access to Racks C2277 and C2278 6.0 PRECAUTIONS AND LIMITATIONS 6.1 PRECAUTIONS

[1] Only one master trip unit and associated slave unit(s) may be tested or calibrated at a given time.

[2] Exercise caution while performing test. Reactor Scram and inadvertent safeguard initiation could be the result of not following instructions.

[3] During the prejob brief the need for extra caution when manipulating the trip unit Calibration Selector knob (Press To Cal small knob) needs to be discussed. It is necessary to verify that the calibration unit CAL light does not light while manipulating the rotary knob. Whenever the CAL light is on, the calibration current is being supplied to the selected trip units. If care is not taken when using the trip unit Calibration Selector knob (Press To Cal small knob), the potential exists that an ATWS may be received if multiple trips occur. (PRO1.8151)

[4] The indicator lights used are neon lamps which, when lit with one channel tripped, draw insufficient current to actuate the trip devices. When no channel is tripped, it is intended that none of the indicator lights be lit. However, because the voltage to maintain neon lamps lit is less than the threshold firing voltage of lamps, in some cases, both lamps in series may be lit. Therefore, when no channel is tripped, the pairs of indicator lamps may be either both lit or both off. When a channel is tripped, only one of the lights will be lit.

[5] I&C Technicians shall use a different Rosemount readout assembly for Attachment 2 than what was used in Attachment 1.

6.2 LIMITATIONS The ATWS System is only required when the REACTOR MODE switch is in the RUN mode.

Refer to Technical Specifications Table 3.2.G for the required number of instrument channels per trip system.

8.M.1-29 Rev. 50 Page 8 of 152

7.0 PREREQUISITES

[1] No channels within the ATWS System may be in calibration, test, or alarm condition.

[2] ATWS System must be powered up.

[3] Readout assembly must be calibrated in accordance with PNPS 3.M.1-10.4, "Calibrationof Rosemount Trip Unit Readout Assembly', prior to use. After calibration, readout assembly shall not be left unattended until its usage for this Procedure is finished.

[4] Check with Radiation Protection (RP) on conditions and requirements. Initiate a Radiological Work Permit (RWP) if required.

[5] Obtain the on-shift SRO's signature for permission to begin test.

8.0 PROCEDURE

[1] One or more trip units may be skipped while performing this Procedure. After performing calibration of number of trip units desired, Return to Service steps must be performed. Upon completion of trip unit calibration, alarm(s) associated with the trip unit must be reset before proceeding to next trip unit.

[2] WHEN test is being performed with Reactor Recirculation Pumps and Reactor Feed Pumps not running, ENTER "NIP" (for "not performed") for steps which verify circuit supervisory lights become bright. (Lights are normally off when pumps are not running.)

(a) ARI circuit supervisory lights DS5A, B, C, and D are valid during all plant conditions and must operate according to Procedure.

[3] WHEN test is being performed with Reactor Recirculation Pump and Reactor Feed Pumps running, ENTER "NIP" (for "not performed") for steps which verify relay status.

(Lights changing status verifies relay status change.)

[4] PERFORM the procedural steps for ATWS Trip Unit Cabinet C2277 calibration test as written in Attachment 1.

[5] PERFORM the procedural steps for ATWS Trip Unit Cabinet C2278 calibration test as written in Attachment 2.

8.M.1-29 Rev. 50 Page 9 of 152

9.0 ACCEPTANCE CRITERIA

[1] The instrument calibration test was performed as written without discrepancies or with discrepancies evaluated as acceptable by the Shift Manager (SM) as indicated by Attachments 1 and 2 being completed with required signatures and initials, and with a second person's verification of system restorations.

[2] All channels tested satisfactorily and caused the appropriate trip relay to change state.

[3] ATWS analog trip units actuate as follows:

(a) LIS-263-121A, B, C, and D actuate at greater than 4.16mA signal (-49 inches indicator level) or greater than or equal to 77.26 inches above the top of the active fuel. [Tech Spec Table 3.2-G]

(b) PIS-263-123A, B, C, and D actuate on increasing signal between 1170 psig and 1180 psig (16.37 to 16.69V DC) in accordance with Technical Specifications requirements. [Tech Spec Table 3.2-G]

[4] Verification of relay position is not required if the Reactor Feed Pumps and Reactor Recirculation Pumps are running.

10.0 CORRECTIVE ACTION

[1] If equipment failed to perform its intended function or a discrepancy is encountered during the test, discontinue testing and immediately notify the Maintenance Supervisor and the SM. The Maintenance Supervisor and the SM must determine whether testing should be terminated, continued, or an investigation be performed.

[2] If equipment failed to perform its intended function, the appropriate corrective action document shall be initiated. The SM must be notified of the failure to allow Operations to initiate action deemed necessary in accordance with Technical Specifications.

11.0 ACCEPTANCE VERIFICATION AND SIGNOFF

[1] Maintenance Management/Lead is responsible for reviewing this Procedure to ensure all Acceptance Criteria have been satisfied prior to taking credit for test performance in the PM database.

[2] The on-shift SRO shall verify that all Acceptance Criteria were met and evaluate any discrepancies for acceptability.

[3] Maintenance Management/Lead shall review steps marked as "NIP" to verify correct component response(s) and proper data gathering.

8.M.1-29 Rev. 50 Page 10 of 152

12.0 ATTACHMENTS ATTACHMENT 1 - ATWS TRIP UNIT CABINET C2277 CALIBRATION ATTACHMENT 2 - ATWS TRIP UNIT CABINET C2278 CALIBRATION ATTACHMENT 3 - I&C PROCEDURE FEEDBACK FORM ATTACHMENT 4 - ALARM

SUMMARY

SHEET 8.M.1-29 Rev. 50 Page 11 of 152

ATTACHMENT I Sheet 1 of 69 ATWS TRIP UNIT CABINET C2277 CALIBRATION

[1] PERFORM the procedural steps for each instrument in the order they are written. For each step with a [ ], SIGNIFY completion with a check mark. For each step with a _ , ENTER initials or data as appropriate. For a step followed by a double _ , that step shall require verification with two individuals' signed initials required to signify completion. "NIP" (for "not performed") may be placed by a procedural step where performance of that step has been conditionally stated and the condition(s) has not been met.

[2] DOCUMENT in the space provided below the reason this test is being performed (CHECK one):

[ ] Routine Surveillance

[ Postwork testing for Work Order #

Other (specify)

[3] Prerequisites (a) Personnel assigned to perform this Attachment have read and understand what is required. All personnel involved must print their name and the date and sign their initials below.

Name (print) Date Initials Name (print) Date Initials Name (print) Date Initials Name (print) Date Initials (b) IF required, a Pre-Evolution Brief has been completed and attached to this surveillance.

[NRCCC Item PAPR 020]

Initials 8.M.1-29 Rev. 50 Page 12 of 152

ATTACHMENT 1 Sheet 2 of 69 (c) COORDINATE action to be taken with Operations personnel AND OBTAIN the on-shift SRO's signature as permission to begin test.

On-Shift SRO signature Date Time (d) CONFIRM with Operations that no other testing is being performed on the ATWS System.

Initials (e) PRIOR to start of testing, PROVIDE Operations with Attachment 4 (Alarm Summary Sheet).

Initials (f) VERIFY that the prejob brief discussed the need to verify that the CAL light is OFF when the Press To Cal knob (smaller knob) is pulled out.

(PRO1.8151)

Initials (g) Radiation Protection (RP) notified.

Initials (h) ATWS System is powered up.

Initials 8.M.1-29 Rev. 50 Page 13 of 152

SATTACHMENT Sheet 3 of 69 1 NOTE Readout assembly must be calibrated prior to calibration of trip unit(s). Readout assembly need not be recalibrated for continuous use for more than one trip unit; but if the readout assembly is left unattended, it must be recalibrated prior to use.

(i) IF PNPS 8.M.1-29 Attachment 2 was performed within the last 4 days, THEN RECORD the readout assembly used in PNPS 8.M.1-29 Attachment 2.

IF PNPS 8.M.1-29 Attachment 2 was NOT performed within the last 4 days, ENTER "NIP".

Initials Readout assembly for PNPS 8.M.1-29 Attachment 2 M&TE #

IF PNPS 8.M.1-29 Attachment 2 was performed within the last 4 days, THEN OBTAIN from M&TE a different readout assembly than what was used in PNPS 8.M.1-29 Attachment 2. RECORD the information from the calibration sticker for readout assembly to be used in PNPS 8.M.1-29 Attachment 1.

IF PNPS 8.M.1-29 Attachment 2 was NOT performed within the last 4 days, ENTER "N/P".

Readout assembly for PNPS 8.M.1-29 Attachment 1 M&TE #

Calibration performed by Time Date IF PNPS 8.M.1-29 Attachment 2 was NOT performed within the last 4 days, THEN OBTAIN a calibrated readout assembly from M&TE personnel AND RECORD information from the calibration sticker.

IF PNPS 8.M.1-29 Attachment 2 was performed within the last 4 days, ENTER "N//P".

Readout assembly for PNPS 8.M.1-29 Attachment 1 M&TE #

Calibration performed by Time Date 8.M.1-29 Rev. 50 Page 14 of 152

ATTACHMENT 1 Sheet 4 of 69 (1) VERIFY calibration of readout assembly was performed within the last 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> AND the readout assembly has NOT been left unattended since the calibration.

Initials (j) ESTABLISH communications between Control Room and ATWS Cabinet C2277 (Rx Bldg 51').

Initials

[4] Cabinet Power Supply Test (a) VERIFY the following power supply to ATWS logic Panel C2277 lights are ON:

(1) Power Supply PS1A Initials (2) Power Supply PS2A Initials (b) DEPRESS power supply monitoring circuit test button K37A at Panel C2277. [ ]

(c) VERIFY associated power supply light PSIA goes off.

Initials (d) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is ON.

Initials (e) RELEASE power supply test button K37A. [

(f) VERIFY power supply light PSIA comes on.

Initials (g) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (h) DEPRESS power supply monitor circuit test button K38A at Panel C2277. [ ]

(i) VERIFY associated power supply light PS2A goes off.

Initials 8.M.1-29 Rev. 50 Page 15 of 152

ATTACHMENT 1 Sheet 5 of 69 (j) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is ON.

Initials (k) RELEASE power supply test button K38A. [

(I) VERIFY power supply light PS2A comes on.

Initials (m) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials

[5] Calibration Unit: General Preparation (a) VERIFY the calibration unit is in the following condition at ATWS Cabinet C2277:

(1) Power switch is in "OFF" position. [ ]

(2) Transient Current knob is pulled out and turned fully counterclockwise. []

(3) Press To Cal knob (smaller knob) is in the "OFF" position and pushed in. [ ]

(4) Press To Cal knob (larger knob) is in the "OFF" position. [ ]

(b) TURN the Stable Current knob fully counterclockwise. [ ]

(c) PLUG IN the readout assembly with extender card to the calibration unit. [ ]

(d) TURN ON the power. [

(e) ALLOW minimum of 10 minutes warm-up time for the readout assembly. [1 8.M.1-29 Rev. 50 Page 16 of 152

ATTACHMENT I ATTACHMENT 1 Sheet 6 of 69

[6] Trip Unit Calibration (a) LIS-263-121A (1) VERIFY appropriate Prerequisites AND REVIEW appropriate Precautions and Limitations before proceeding further.

Initials CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(2) PULL OUT the Press To Cal knob (smaller knob)

AND VERIFY that the CAL light is OFF.

Initials

a. SET larger knob to slot #1 for LIS-263-121A. [
b. SET smaller knob to slot #1 for LIS-263-121A. [

(3) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (4) SELECT OR VERIFY SELECTED positive polarity with Transient Polarity Switch.

Initials (5) APPLY stable calibration current to LIS-263-121A by pushing in the smaller knob of the Press To Cal knob AND VERIFY the CAL light is ON at the calibration unit AND alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is ON. [

8.M.1-29 Rev. 50 Page 17 of 152

ATTACHMENT 1 Sheet 7 of 69 (6) VERIFY the following:

a. Circuit supervisory lights are bright.
1. DS3C at Panel C2277 [ ]
2. DS4C at Panel C2277 [ ]
3. DS5C at Panel C2277 [
4. DS10C at Panel C2277 [ ]
5. DS1 1C at Panel C2277 [

Initials

b. Circuit supervisory lights are OFF.
1. DS3A at Panel C2277 [
2. DS4A at Panel C2277 [ ]
3. DS5A at Panel C2277 [
4. DS10A at Panel C2277 [ ]
5. DS11A at Panel C2277 [ ]

Initials

c. Relays are ENERGIZED:
1. K1A at Panel C2277 Initials
2. K101A at Panel C2277 (This relay has a 9-second time delay.)

Initials

3. K4A at Panel C2277 Initials (7) VERIFY the Trip Status LED is OFF at the readout assembly. (IF required, PUSH Trip Current Display Reset.) []

8.M.1-29 Rev. 50 Page 18 of 152

ATTACHMENT 1 Sheet 8 of 69 NOTE If setpoints are found outside the No Adjust Limits, test must be continued. The required adjustment will be made at the end of the test for each trip unit.

(8) INCREASE the stable current AND RECORD the "As-Found" data for LIS-263-121A indicator.

Stable Current Reading Indicator Increasing mA Inches "As-Found" 4.32 -48 (-46 to -50) 8.0 -25 (-23 to -27) 12.0 0 (-2 to +2) 16.0 +25 (+23 to +27) 19.68 +48 (+46 to +50)

Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR Calibration Required (9) RECORD the reset point as shown latched on readout assembly. Setpoint is 4.96mA; No Adjust Limits are 4.80 to 5.12mA.

"As-Found" Reset mA Data (10) VERIFY Trip Status LED is:

a. ON at readout assembly. [I
b. OFF at Trip Unit LIS-263-121A.

Initials 8.M.1-29 Rev. 50 Page 19 of 152

ATTACHMENT 1 Sheet 9 of 69 (11) VERIFY the following:

a. Relays are DE-ENERGIZED:
1. K1 A at Panel C2277 Initials
2. K101A at Panel C2277 (This relay has a 9-second time delay.)

Initials

3. K4A at Panel C2277 Initials
b. Circuit supervisory lights become normal - not bright
1. DS3C at Panel C2277 [ 1
2. DS4C at Panel C2277 [ ]
3. DS5C at Panel C2277 [
4. DS1OC at Panel C2277 [ ]
5. DS11C at Panel C2277 [ ]

Initials

c. Circuit supervisory lights become normal - not bright
1. DS3A at Panel C2277 [ I
2. DS4A at Panel C2277 [ ]
3. DS5A at Panel C2277 [ 1
4. DS1OA at Panel C2277 [ I
5. DS11A at Panel C2277 [ I Initials 8.M.1-29 Rev. 50 Page 20 of 152

ATTACHMENT I Sheet 10 of 69 (12) PUSH the Trip Current Display Reset on the readout assembly AND VERIFY the Trip Status LED goes off. [

(13) SLOWLY DECREASE current with the Stable Current knob AND RECORD the "As-Found" data for LIS-263-121A indicator.

Stable Current Reading Indicator Decreasing mA Inches "As-Found" 19.68 +48 (+46 to +50) 16.0 +25 (+23 to +27) 12.0 0 (-2 to +2) 8.0 -25 (-23 to -27) 4.32 -48 (-46 to -50)

Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR Calibration Required (14) RECORD the trip point as shown latched on the readout assembly. Setpoint is 4.64mA (-46 inches indicator reading);

No Adjust Limits are 4.62 to 4.66mA.

"As-Found" Trip mA Data (15) VERIFY Trip Status LED is ON:

a. At readout assembly. [
b. At Trip Unit LIS-263-121A.

Initials 8.M.1-29 Rev. 50 Page 21 of 152

ATTACHMENT 1 Sheet 11 of 69 (16) VERIFY the following:

a. Relays are ENERGIZED:
1. K1A at Panel C2277 Initials
2. K101A at Panel C2277 Initials
3. K4A at Panel C2277 Initials
b. Circuit supervisory lights are OFF.
1. DS3A at Panel C2277 [ ]
2. DS4A at Panel C2277 [ ]
3. DS5A at Panel C2277 [ ]
4. DS1OA at Panel C2277 [ ]
5. DS1 1A at Panel C2277 [ ]

Initials

c. Circuit supervisory lights become bright.
1. DS3C at Panel C2277 [ ]
2. DS4C at Panel C2277 [ ]
3. DS5C at Panel C2277 [ ]
4. DS10C at Panel C2277 [
5. DS11C at Panel C2277 [

Initials 8.M.1-29 Rev. 50 Page 22 of 152

ATTACHMENT 1 Sheet 12 of 69 (17) IF trip point was less than 4.59mA

(-46.3 inches indicator reading), THEN NOTIFY SM.

SM notified? Yes [ ] No[ ]

(18) PUSH the Trip Current Display Reset AND VERIFY Trip Status LED goes off at the readout assembly. [II NOTE The trip point adjustments are located on the front of the trip unit.

(19) IF trip AND/OR indicator did NOT fall within the No Adjust Limits, CALIBRATE AND RECORD "As-Left" data.

a. LIS-263-121A "As-Left" Trip 4.64mA (4.62 to 4.66mA) mA Data
b. LIS-263-121A "As-Left" Reset 4.96mA (4.80 to 5.12mA) mA Data
c. Indicator LIS-263-121A Current Desired Reading Reading "As-Left" mA inches Inc. Dec.

4.32 -48 (-46 to -50) 8.0 -25 (-23 to -27) 12.0 0 (-2 to +2) 16.0 +25 (+23 to +27) 19.68 +48 (+46 to +50) 8.M.1-29 Rev. 50 Page 23 of 152

ATTACHMENT 1 Sheet 13 of 69 (20) TEST the Gross Failure function(s) by adjusting the stable current to approximately 18mA. [

a. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 29mA on readout assembly. [
b. Using Stable Current knob, SLOWLY INCREASE the reading until Gross Fail LED comes on. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 30.OmA; No Adjust Limits are 29.5mA to 30.5mA.

"As-Found" Gross Fail High mA Data

c. IF "As-Found" data was NOT within the No Adjust Limits, REMOVE the trip unit to adjust R39. REINSTALL trip unit to repeat testing by decreasing transient current (AND, IF required, stable current) to obtain reset AND increasing to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail High mA Data

d. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [
e. PUSH Gross Fail Reset button on Trip Unit LIS-263-121A AND VERIFY Gross Fail light is OFF. [ ]
f. CHANGE Transient Polarity switch to negative. [1
g. DECREASE the stable current to approximately 5.OmA. [
h. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 3.5mA on readout assembly. [ ]

8.M.1-29 Rev. 50 Page 24 of 152

[TTACHMENT

i. Using Stable Current knob, SLOWLY DECREASE the reading until Gross Fail LED comes on. [ I
j. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 2.5mA; No Adjust Limits are 3.0mA to 2.OmA.

"As-Found" Gross Fail Low mA Data

k. IF "As-Found" reading is NOT within No Adjust Limits, ADJUST R40.

INCREASE transient current (AND, IF required, stable current) to obtain reset AND DECREASE to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail Low mA Data

1. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [I]
m. CHANGE Transient Polarity switch to positive position. [I]

(21) TURN the Stable Current knob fully counterclockwise. [ ]

8.M.1-29 Rev. 50 Page 25 of 152

ATTACHMENT 1I Sheet 15 of 69 q

CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(22) PULL OUT the Press To Cal knob (smaller knob) AND:

a. VERIFY that the CAL light is OFF.

Initials THEN

b. PUSH the Gross Fail Reset button on Trip Unit LIS-263-121A AND VERIFY Gross Fail light is OFF.

Initials THEN

c. ROTATE the Press to Cal knob (smaller knob) to the "OFF" position, THEN PUSH the knob back in.

Initials (23) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (24) IF required, HAVE Operations reset alarm(s). I I 8.M.1-29 Rev. 50 Page 26 of 152

ATTACHMENT 1 Sheet 16 of 69 NOTE If operating conditions have to be confirmed, the reading of meter under calibration should match the reading indicated by the three other channels of the same function within the ATWS System.

(25) VERIFY circuit supervisory lights have returned to their normal status (not bright).

a. DS3C at Panel C2277 [I]
b. DS4C at Panel C2277 [I]
c. DS5C at Panel C2277 [I]
d. DS3A at Panel C2277 [I]
e. DS4A at Panel C2277 [ ]
f. DS5A at Panel C2277 [I]
g. IDS1A at Panel C2277 [I]
h. DS10C at Panel C2277 [I]
i. DS 11A at Panel C2277 [: ]
j. DS11C at Panel C2277 [ ]

Initials 8.M.1-29 Rev. 50 Page 27 of 152

Sheet17 of69 (b) LIS-263-121C (1) VERIFY appropriate Prerequisites AND REVIEW appropriate Precautions and Limitations before proceeding further.

Initials CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(2) PULL OUT the Press To Cal knob (smaller knob) AND VERIFY that the CAL light is OFF.

Initials

a. SET larger knob to slot #2 for LIS-263-121C. I ]
b. SET smaller knob to slot #2 for LIS-263-121C. [I (3) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (4) SELECT OR VERIFY SELECTED positive polarity with Transient Polarity Switch.

Initials (5) APPLY stable calibration current to LIS-263-121C by pushing in the smaller knob of the Press to Cal knob AND VERIFY the CAL light is ON at the calibration unit AND alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is ON. [I 8.M.1-29 Rev. 50 Page 28 of 152

ATTACHMENT Sheet 18 of 69 I (6) VERIFY the following:

a. Circuit supervisory lights are OFF.
1. DS3C at Panel C2277 [ ]
2. DS4C at Panel C2277 [ ]
3. DS5C at Panel C2277
4. DS1OC at Panel C2277 [ ]
5. DS11C at Panel C2277 [ ]

Initials

b. Circuit supervisory lights are bright.
1. DS3A at Panel C2277 E I
2. DS4A at Panel C2277 [ I
3. DS5A at Panel C2277 [ ]
4. DS10A at Panel C2277 [ ]
5. DS11 A at Panel C2277 [ I Initials
c. Relays are ENERGIZED:
1. K1 C at Panel C2277 Initials
2. K101C at Panel C2277 (This relay has a 9-second time delay.)

Initials

3. K4C at Panel C2277 Initials (7) VERIFY the Trip Status LED is OFF at the readout assembly (IF required, PUSH Trip Current Display Reset). []

8.M.1-29 Rev. 50 Page 29 of 152

ATTACHMENT 1 Sheet 19 of 69 NOTE If setpoints are found outside the No Adjust Limits, test must be continued. The required adjustment will be made at the end of the test for each trip unit.

(8) INCREASE the stable current AND RECORD the "As-Found" data for LIS-263-121C indicator.

Stable Current Reading Indicator Increasing mA inches "As-Found" 4.32 -48 (-46 to -50) 8.0 -25 (-23 to -27) 12.0 0 (-2 to +2) 16.0 +25 (+23 to +27) 19.68 +48 (+46 to +50)

[ ] Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR

] Calibration Required (9) RECORD the reset point as shown latched on readout assembly. Setpoint is 4.96mA; No Adjust Limits are 4.80 to 5.12mA.

"As-Found" Reset mA Data (10) VERIFY Trip Status LED is:

a. ON at readout assembly. [I
b. OFF at Trip Unit LIS-263-121C.

Initials 8.M.1-29 Rev. 50 Page 30 of 152

ATTACHMENT I Sheet 20 of 69 (11) VERIFY the following:

a. Relays are DE-ENERGIZED:
1. K1 C at Panel C2277 Initials
2. K101C at Panel C2277 (This relay has 9-second time delay.)

Initials

3. K4C at Panel C2277 Initials
b. Circuit supervisory lights become normal - not bright.
1. DS3C at Panel C2277 [ ]
2. DS4C at Panel C2277 [ ]
3. DS5C at Panel C2277 [ ]
4. DSIOC at Panel C2277 [ ]
5. DS11C at Panel C2277 [ ]

Initials

c. Circuit supervisory lights become normal - not bright.
1. DS3A at Panel C2277 [ ]
2. DS4A at Panel C2277 [ ]
3. DS5A at Panel C2277 [ ]
4. DS1OA at Panel C2277 [ ]
5. DS11A at Panel C2277 [ I Initials 8.M.1-29 Rev. 50 Page 31 of 152

ATTACHMENT 1 Sheet 21 of 69 (12) PUSH the Trip Current Display reset on the readout assembly AND VERIFY the Trip Status LED goes off. []

(13) SLOWLY DECREASE current with the Stable Current knob AND RECORD the "As-Found" data for LIS-263-121C indicator.

Stable Current Reading Indicator Decreasing mA inches "As-Found" 19.68 +48 (+46 to +50) 16.0 +25 (+23 to +27) 12.0 0 (-2 to +2) 8.0 -25 (-23 to -27) 4.32 -48 (-46 to -50)

Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR Calibration Required (14) RECORD the trip point as shown latched on the readout assembly. Setpoint is 4.64mA

(-46 inches indicator reading); No Adjust Limits are 4.62 to 4.66mA.

"As-Found" Trip mA Data (15) VERIFY Trip Status LED is ON:

a. At readout assembly. [ ]
b. At Trip Unit LIS-263-121C.

Initials 8.M.1-29 Rev. 50 Page 32 of 152

ATTACHMENT I Sheet 22 of 69 (16) VERIFY the following:

a. Relays are ENERGIZED:
1. K1iC at Panel C2277 Initials
2. K1Q01C at Panel C2277 Initials
3. K40 at Panel 02277 Initials
b. Circuit supervisory lights become bright.
1. DS3A at Panel C2277 [ ]
2. DS4A at Panel C2277 [ ]
3. DS5A at Panel 02277 [ ]
4. DS10A at Panel C2277 [ ]
5. DS1i1A at Panel 02277 [

Initials

c. Circuit supervisory lights are OFF.
1. DS3C at Panel 02277 [ ]
2. DS4C at Panel 02277 [ ]
3. DS5C at Panel 02277 [
4. DS1003 at Panel 02277 [
5. DS11C at Panel 02277 [

Initials 8.M.1-29 Rev. 50 Page 33 of 152

ATTACHMENT 1 Sheet 23 of 69 (17) IF trip point was less than 4.59 mA

(-46.3 inches indicator reading), THEN NOTIFY SM.

SM notified? Yes [ ] No[

(18) PUSH the Trip Current Display Reset AND VERIFY Trip Status LED goes off at the readout assembly. [I NOTE The trip point adjustments are located on the front of the trip unit.

(19) IF trip AND/OR indicator did NOT fall within the No Adjust Limits, THEN CALIBRATE AND RECORD "As-Left" data.

a. LIS-263-121C "As-Left" Trip 4.64mA (4.62 to 4.66mA) mA Data
b. LIS-263-121C "As-Left" Reset 4.96mA (4.80 to 5.12mA) mA Data
c. Indicator LIS-263-121C Current Desired Reading Reading "As-Left" mA inches Inc. Dec.

4.32 -48 (-46 to -50) 8.0 -25 (-23 to -27) 12.0 0 (-2 to +2) 16.0 +25 (+23 to +27) 19.68 +48 (+46 to +50) 8.M.1-29 Rev. 50 Page 34 of 152

ATTACHMENT 1 Sheet 24 of 69 (20) TEST the Gross Failure function(s) by adjusting the stable current to approximately 18mA. [ ]

a. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 29mA on readout assembly. [ I
b. Using Stable Current knob, SLOWLY INCREASE the reading until Gross Fail LED comes on. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 30.OmA; No Adjust Limits are 29.5mA to 30.5mA.

"As-Found" Gross Fail High mA Data

c. IF "As-Found" data was NOT within the No Adjust Limits, REMOVE trip unit to adjust R39. REINSTALL trip unit to repeat testing by decreasing transient current (and, if required, stable current) to obtain reset AND increasing to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail High mA Data

d. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [ ]
e. PUSH Gross Fail Reset button on Trip Unit LIS-263-121C AND VERIFY Gross Fail light is OFF. [
f. CHANGE Transient Polarity switch to negative. [
g. DECREASE the stable current to approximately 5.OmA. [ ]
h. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 3.5mA on readout assembly. [I 8.M.1-29 Rev. 50 Page 35 of 152

ATTACHMENT 1 Sheet 25 of 69 Using Stable Current knob, SLOWLY DECREASE the reading until Gross Fail LED comes on. [I

j. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 2.5mA; No Adjust Limits are 3.OmA to 2.OmA.

"As-Found" Gross Fail Low mA Data

k. IF "As-Found" reading is NOT within No Adjust Limits, ADJUST R40.

INCREASE transient current (AND, IF required, stable current) to obtain reset AND DECREASE to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail Low mA Data PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. II]

m. CHANGE Transient Polarity switch to positive position. [I (21) TURN the Stable Current knob fully counterclockwise. [I 8.M.1-29 Rev. 50 Page 36 of 152

ATTACHMENT 1 Sheet 26 of 69 I1 CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green. I (22) PULL OUT the Press To Cal knob (smaller knob) AND:
a. VERIFY that the CAL light is OFF.

Initials THEN

b. PUSH the Gross Fail Reset button on Trip Unit LIS-263-121C AND VERIFY Gross Fail light is OFF.

Initials THEN

c. ROTATE the Press To Cal knob (smaller knob) to the "OFF" position, THEN PUSH the knob back in.

Initials (23) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (24) IF required, HAVE Operations reset alarm(s). [I 8.M.1-29 Rev. 50 Page 37 of 152

ATTACHMENT 1 Sheet 27 of 69 NOTE If operating conditions have to be confirmed, the reading of meter under calibration should match the reading indicated by the three other channels of the same function within the ATWS System.

(25) VERIFY circuit supervisory lights have returned to their normal status (not bright).

a. DS3C at Panel C2277 [I]
b. DS4C at Panel C2277 [I]
c. DS5C at Panel C2277 [1]
d. DS3A at Panel C2277 [I]
e. DS4A at Panel C2277 [1]
f. DS5A at Panel C2277 [ ]
g. IDS1A at Panel C2277 [I]
h. DS1OC at Panel C2277 [I]

L IDSS11A at Panel C2277 [ ]

j. DS1 1C at Panel C2277 [ ]

Initials 8.M.1-29 Rev. 50 Page 38 of 152

ATTACHMENT 1 Sheet 28 of 69 (c) PIS-263-123A (1) VERIFY appropriate Prerequisites AND REVIEW appropriate Precautions and Limitations before proceeding further.

Initials CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

I Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(2) PULL OUT the Press To Cal knob (smaller knob) AND VERIFY that the CAL light is OFF.

Initials

a. SET larger knob to slot #3 for PIS-263-123A. [I
b. SET smaller knob to slot #3 for PIS-263-123A. I I (3) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (4) SELECT OR VERIFY SELECTED positive polarity with Transient Polarity Switch.

Initials (5) APPLY stable calibration current to PIS-263-123A by pushing in the smaller knob of the Press to Cal knob AND VERIFY the CAL light is ON at the calibration unit AND alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is ON. [I 8.M.1-29 Rev. 50 Page 39 of 152

ATTACHMENT 1 Sheet 29 of 69 (6) VERIFY the following:

a. Circuit supervisory lights are normal - not bright.
1. DS3C at Panel C2277 [ ]
2. DS4C at Panel C2277 [ ]
3. DS5C at Panel C2277 [ ]
4. DS1OC at Panel C2277 [ I
5. DS11C at Panel C2277 [ I Initials
b. Circuit supervisory lights are normal - not bright.
1. DS3A at Panel C2277 [ I
2. DS4A at Panel C2277 [ ]
3. DS5A at Panel C2277 [ 1
4. DS10A at Panel C2277 [ I
5. DS11 A at Panel C2277 [ 1 Initials
c. Relays are DE-ENERGIZED:
1. K2A at Panel C2277 Initials
2. K5A at Panel C2277 Initials (7) VERIFY the Trip Status LED is OFF at the readout assembly (IF required, PUSH Trip Current Display Reset). [

8.M.1-29 Rev. 50 Page 40 of 152

ATTACHMENT 1 Sheet 30 of 69 NOTE If setpoints are found outside the No Adjust Limits, test must be continued. The required adjustment will be made at the end of the test for each trip unit.

(8) INCREASE the stable current AND RECORD the"As-Found" data for PIS-263-123A indicator.

Stable Current Reading Indicator Increasing mA DSi-q "As-Found" 4.8 75 (30 to 120) 8.0 375 (330 to 420) 12.0 750 (705 to 795) 16.0 1125 (1080 to 1170) 19.2 1425 (1380 to 1470)

Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR

[ Calibration Required (9) RECORD the trip point as shown latched on the readout assembly. Setpoint is 16.53mA (1175 psig); No Adjust Limits are 16.51 to 16.55mA.

"As-Found" Trip mA Data (10) VERIFY Trip Status LED is ON:

a. At readout assembly. [I
b. At Trip Unit PIS-263-123A.

Initials 8.M.1-29 Rev. 50 Page 41 of 152

ATTACHMENT 1 Sheet 31 of 69 (11) VERIFY the following:

a. Relays are ENERGIZED:
1. K2A at Panel C2277 Initials
2. K5A at Panel C2277 Initials
b. Circuit supervisory lights are OFF.
1. DS3A at Panel C2277 [ ]
2. DS4A at Panel C2277 [ I
3. DS5A at Panel C2277 [ ]
4. DS1OA at Panel C2277 [ I
5. DS11A at Panel C2277 [ ]

Initials

c. Circuit supervisory lights become bright.
1. DS3C at Panel C2277 [ ]
2. DS4C at Panel C2277 [ 1
3. DS5C at Panel C2277 [
4. DS10C at Panel C2277 [ ]
5. DS11C at Panel C2277 [ ]

Initials (12) IF trip point was less than 16.48mA (1170 psig) OR greater than 16.58mA (1180 psig), THEN NOTIFY SM.

SM notified? Yes[ ] No[

8.M.1-29 Rev. 50 Page 42 of 152

ATTACHMENT 1 Sheet 32 of 69 (13) PUSH the Trip Current Display Reset on the readout assembly AND VERIFY the Trip Status LED goes off. [ ]

(14) SLOWLY DECREASE current with the Stable Current knob AND RECORD the "As-Found" data for PIS-263-123A indicator.

Stable Current Reading Indicator Decreasing mA Dsig "As-Found" 19.2 1425 (1380 to 1470) 16.0 1125 (1080 to 1170) 12.0 750 (705 to 795) 8.0 375 (330 to 420) 4.8 75 (30 to 120)

[ Data falls within Acceptance Criteria, "As-Left" same as "As-Found" a) OR

[ ] Calibration Required (15) RECORD the reset point as shown latched on readout assembly. Setpoint is 16.21mA; No Adjust Limits are 16.05 to 16.37mA.

"As-Found" Reset mA Data (16) VERIFY Trip Status LED is:

a. ON at readout assembly. [ ]
b. OFF at Trip Unit PIS-263-123A.

Initials 8.M.1-29 Rev. 50 Page 43 of 152

ATTACHMENT Sheet 33 of 69 1 (17) VERIFY the following:

a. Relays are DE-ENERGIZED:
1. K2A at Panel C2277 Initials
2. K5A at Panel C2277 Initials
b. Circuit supervisory lights become normal - not bright.
1. DS3C at Panel C2277 [ ]
2. DS4C at Panel C2277 [ I
3. DS5C at Panel C2277 [ ]
4. DS10C at Panel C2277 [ I
5. DS11C at Panel C2277 [ 1 Initials
c. Circuit supervisory lights become normal - not bright.
1. DS3A at Panel C2277 [ ]
2. DS4A at Panel C2277 [ ]
3. DS5A at Panel C2277 [ 1
4. DS10A at Panel C2277 [ ]
5. DS1 1A at Panel C2277 [ I Initials (18) PUSH the Trip Current Display Reset AND VERIFY Trip Status LED goes off at the readout assembly. []

8.M.1-29 Rev. 50 Page 44 of 152

1 34 of 69 1 AT1rACHMENT

-ACHMENT leet Shieet 34 of 69 NOTE The trip point adjustments are located on the front of the trip unit.

(19) IF trip AND/OR indicator did NOT fall within the No Adjust Limits, THEN CALIBRATE AND RECORD "As-Left" data.

a. PIS-263-123A "As-Left" Trip 16.53mA (16.51 to 16.55mA) mA Data
b. PIS-263-123A "As-Left" Reset 16.21 mA (16.05 to 16.37mA) mA Data
c. Indicator PIS-263-123A Current Desired Reading Reading "As-Left" mA inches Inc. Dec.

4.8 75 (30 to 120) 8.0 375 (330 to 420) 12.0 750 (705 to 795) 16.0 1125 (1080 to 1170) 19.2 1425 (1380 to 1470) 8.M.1-29 Rev. 50 Page 45 of 152

ATTACHMENT 1 Sheet 35 of 69 (20) TEST the Gross Failure function(s) by adjusting the stable current to approximately 18mA. [ ]

a. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 29mA on readout assembly. [
b. Using Stable Current knob, SLOWLY INCREASE the reading until Gross Fail LED comes on. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 30.OmA; No Adjust Limits are 29.5mA to 30.5mA.

"As-Found" Gross Fail High mA Data

c. IF "As-Found" data was NOT within the No Adjust Limits, REMOVE the trip unit to adjust R39. REINSTALL trip unit to repeat testing by decreasing transient current (&ND, IF required, stable current) to obtain reset AND increasing to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail High mA Data

d. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [ ]
e. PUSH Gross Fail Reset buttons on Trip Units PIS-263-123A and PS-263-123A-1 AND VERIFY Gross Fail lights are OFF. [ ]
f. CHANGE Transient Polarity switch to negative. [ ]
g. DECREASE the stable current to approximately 5.OmA. [ ]
h. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 3.5mA on readout assembly. [ ]

8.M.1-29 Rev. 50 Page 46 of 152

ATTACHMENT 1 Sheet 36 of 69 Using Stable Current knob, SLOWLY DECREASE the reading until Gross Fail LED comes on. I ]

j. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 2.5mA; No Adjust Limits are 3.OmA to 2.OmA.

"As-Found" Gross Fail Low mA Data

k. IF "As-Found" reading is NOT within No Adjust Limits, ADJUST R40.

INCREASE transient current (AND, IF required, stable current) to obtain reset AND DECREASE to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail Low mA Data

1. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [I]
m. CHANGE Transient Polarity switch to positive position. [1]

(21) TURN the Stable Current knob fully counterclockwise. [I]

8.M.1-29 Rev. 50 Page 47 of 152

ATTACHMENT 1 1 Sheet 37 of 69 CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

.1 (22) PULL OUT the Press To Cal knob (smaller knob) AND:

a. VERIFY that the CAL light is OFF.

Initials THEN

b. PUSH the Gross Fail Reset button on Trip Units PIS-263-123A and PS-263-123A-1 AND VERIFY Gross Fail lights are OFF.

Initials THEN

c. ROTATE the Press To Cal knob (smaller knob) to the "OFF" position, THEN PUSH the knob back in. [I (23) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (24) IF required, HAVE Operations reset alarm(s). [I 8.M.1-29 Rev. 50 Page 48 of 152

ATTACHMENT I Sheet 38 of 69 NOTE If operating conditions have to be confirmed, the reading of meter under calibration should match the reading indicated by the three other channels of the same function within the ATWS System.

(25) VERIFY circuit supervisory lights have returned to their normal status (not bright).

a. DS3C at Panel C2277
b. DS4C at Panel C2277
c. DS5C at Panel C2277
d. DS3A at Panel C2277
e. DS4A at Panel C2277
f. DS5A at Panel C2277
g. DS10A at Panel C2277
h. DS1 1A at Panel C2277
i. DS10C at Panel C2277
j. DS11C at Panel C2277 Initials 8.M.1-29 Rev. 50 Page 49 of 152

[TTACMENT (d) PS-263-123A-1 (1) VERIFY appropriate Prerequisites AND REVIEW appropriate Precautions and Limitations before proceeding further.

Initials CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(2) PULL OUT the Press To Cal knob (smaller knob) AND VERIFY that the CAL light is OFF.

Initials

a. SET larger knob to slot #4 for PS-263-123A-1. [I
b. SET smaller knob to slot #3 for PIS-263-123A. [I (3) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (4) SELECT OR VERIFY SELECTED positive polarity with Transient Polarity Switch.

Initials (5) APPLY stable calibration current to PS-263-123A-1 by pushing in the smaller knob of the Press To Cal knob AND VERIFY the CAL light is ON at the calibration unit AND alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is ON. [I 8.M.1-29 Rev. 50 Page 50 of 152

Shet40of 69 (6) VERIFY the following:

a. Circuit supervisory lights are normal - not bright.
1. DS7A at Panel C2277 [I]
2. DS8A at Panel C2277 [I]
3. DS9A at Panel C2277 [I]

Initials

b. Circuit supervisory lights are normal - not bright.
1. DS7C at Panel C2277 [1]
2. DS8C at Panel C2277 [I]
3. DS9C at Panel C2277 Initials
c. Relay K3A at Panel C2277 is DE-ENERGIZED.

Initials (7) VERIFY the Trip Status LED is OFF at the readout assembly (IF required, PUSH Trip Current Display Reset). [I 8.M.1-29 Rev. 50 Page 51 of 152

ATTACHMENT 1 Sheet 41 of 69 NOTE If setpoints are found outside the No Adjust Limits, test must be continued. The required adjustment will be made at the end of the test for each trip unit.

(8) INCREASE the stable current until PS-263-123A-1 trips. RECORD the trip point as shown latched on the readout assembly.

Setpoint is 18.93mA (1400 psig); No Adjust Limits are 18.91 to 18.95mA.

"As-Found" Trip mA Data (9) VERIFY Trip Status LED is ON:

a. At readout assembly. [I
b. At Trip Unit PS-263-123A-1.

Initials (10) VERIFY the following:

a. Relay K3A at Panel C2277 is ENERGIZED.

Initials

b. Circuit supervisory lights are OFF.
1. DS7A at Panel C2277 ( ]
2. DS8A at Panel C2277 [I
3. DS9A at Panel C2277 [1 Initials
c. Circuit supervisory lights become bright.
1. DS7C at Panel C2277 [1]

[I]

2. DS8C at Panel C2277
3. DS9C at Panel C2277 [I]

Initials 8.M.1-29 Rev. 50 Page 52 of 152

Shet42 of 69 (11) jF trip point was greater than 18.98mA (1405 psig), THEN NOTIFY SM.

SM notified? Yes[ I No[ ]

(12) PUSH the Trip Current Display Reset on the readout assembly AND VERIFY the Trip Status LED goes off. [I (13) SLOWLY DECREASE current with the Stable Current knob until PS-263-123A-1 resets AND RECORD the reset point.

"As-Found" Reset mA Data (14) VERIFY Trip Status LED is:

a. ON at readout assembly. I I
b. OFF at Trip Unit PS-263-123A-1.

Initials 8.M.1-29 Rev. 50 Page 53 of 152

ATTACHMENT 1 Sheet 43 of 69 (15) VERIFY the following:

a. Relay K3A at Panel C2277 is DE-ENERGIZED.

Initials

b. Circuit supervisory lights become normal - not bright.
1. DS7C at Panel C2277 [I]
2. DS8C at Panel C2277 [I]
3. DS9C at Panel C2277 [1]

Initials

c. Circuit supervisory lights become normal - not bright.
1. DS7A at Panel C2277 I ]
2. DS8A at Panel C2277 [i
3. DS9A at Panel C2277 [I]

Initials (16) PUSH the Trip Current Display Reset AND VERIFY Trip Status LED goes off at the readout assembly. [I 8.M.1-29 Rev. 50 Page 54 of 152

ATTACHMENT 1 Sheet 44 of 69 NOTE The trip point adjustments are located on the front of the trip unit.

(17) IF trip did NOT fall within the No Adjust Limits, CALIBRATE AND RECORD "As-Left" data.

a. PS-263-123A-1 "As-Left" Trip 18.93mA (18.91 to 18.95mA) mA Data
b. PS-263-123A-1 "As-Left" Reset mA Data (18) TEST the Gross Failure function(s) by adjusting the stable current to approximately 18mA. [
a. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 29mA on readout assembly. [ ]
b. Using Stable Current knob, SLOWLY INCREASE the reading until Gross Fail LED comes on. RECORD Gross Fail trip as read on the readout assembly.

Setpoint is 30.OmA; No Adjust Limits are 29.5mA to 30.5mA.

"As-Found" Gross Fail High mA Data

c. IF "As-Found" data was NOT within the No Adjust Limits, REMOVE the trip unit to adjust R39. REINSTALL trip unit to repeat testing by decreasing transient current (AND, IF required, stable current) to obtain reset AND increasing to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail High mA Data

d. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [ ]

8.M.1-29 Rev. 50 Page 55 of 152

ATTACHMENT I Sheet 45 of 69

e. PUSH Gross Fail Reset buttons on Trip Units PS-263-123A-1 AND PIS-263-123A AND VERIFY Gross Fail lights are OFF. [
f. CHANGE Transient Polarity switch to negative. [ ]
g. DECREASE the stable current to approximately 5.OmA. [
h. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 3.5mA on readout assembly. [ ]

Using Stable Current knob, SLOWLY DECREASE the reading until Gross Fail LED comes on. []

j. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 2.5mA; No Adjust Limits are 3.OmA to 2.OmA.

"As-Found" Gross Fail Low mA Data

k. IF "As-Found" reading is NOT within No Adjust Limits, ADJUST R40.

INCREASE transient current (AND, IF required, stable current) to obtain reset AND DECREASE to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail Low mA Data PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. ]

m. CHANGE Transient Polarity switch to positive position.

(19) TURN the Stable Current knob fully counterclockwise.

8.M.1-29 Rev. 50 Page 56 of 152

ATTACHENiT1 Shet 6f 69 CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(20) PULL OUT the Press To Cal knob (smaller knob) AND:

a. VERIFY that the CAL light is OFF.

Initials THEN

b. PUSH the Gross Fail Reset button on Trip Units PS-263-123A-1 and PIS-263-123A AND VERIFY Gross Fail lights are OFF.

Initials THEN

c. ROTATE the Press To Cal knob (smaller knob) to the "OFF" position, THEN PUSH the knob back in.

Initials (21) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (22) IF required, HAVE Operations reset alarm(s). [I 8.M.1-29 Rev. 50 Page 57 of 152

ATTACHMENT 1 Sheet 47 of 69 I NOTE If operating conditions have to be confirmed, the reading of meter under calibration should match the reading indicated by the three other channels of the same function within the ATWS System.

(23) VERIFY circuit supervisory lights have returned to their normal status (not bright).

a. DS7C at Panel C2277 [I
b. DS8C at Panel C2277 [I
c. DS9C at Panel C2277 [1
d. DS7A at Panel C2277 r
e. DS8A at Panel C2277 [I
f. DS9A at Panel C2277 1]

Initials 8.M.1-29 Rev. 50 Page 58 of 152

ATTACHMENT 1 Sheet 48 of 69 I (e) PIS-263-123C (1) VERIFY appropriate Prerequisites AND REVIEW appropriate Precautions and Limitations before proceeding further.

Initials CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(2) PULL OUT the Press To Cal knob (smaller knob) AND VERIFY that the CAL light is OFF.

Initials

a. SET larger knob to slot #5 for PIS-263-123C. [I
b. SET smaller knob to slot #5 for PIS-263-123C. I ]

(3) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (4) SELECT OR VERIFY SELECTED positive polarity with Transient Polarity Switch.

Initials (5) APPLY stable calibration current to PIS-263-123C by pushing in the smaller knob of the Press To Cal knob AND VERIFY the CAL light is ON at the calibration unit AND alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is ON. [I 8.M.1-29 Rev. 50 Page 59 of 152

SATTACHMENT Sheet 49 of 69 1 (6) VERIFY the following:

a. Circuit supervisory lights are normal - not bright.
1. DS3C at Panel C2277 [ ]
2. DS4C at Panel C2277 [ ]
3. DS5C at Panel C2277 [ ]
4. DS10C at Panel C2277 [ I
5. DS11C at Panel C2277 [ I Initials
b. Circuit supervisory lights are normal - not bright.
1. DS3A at Panel C2277
2. DS4A at Panel C2277 [ ]
3. DS5A at Panel C2277
4. DS10A at Panel C2277
5. DS1 1A at Panel C2277 [ ]

Initials

c. Relays are DE-ENERGIZED:
1. K2C at Panel C2277 Initials
2. K5C at Panel C2277 Initials (7) VERIFY the Trip Status LED is OFF at the readout assembly (jf required, PUSH Trip Current Display Reset). []

8.M.1-29 Rev. 50 Page 60 of 152

[ATTACHMET1 Shee 50of 69 NOTE If setpoints are found outside the No Adjust Limits, test must be continued. The required adjustment will be made at the end of the test for each trip unit.

(8) INCREASE the stable current AND RECORD the "As-Found" data for PIS-263-123C indicator.

Stable Current Reading Indicator Increasing mA psici "As-Found" 4.8 75 (30 to 120) 8.0 375 (330 to 420) 12.0 750 (705 to 795) 16.0 1125 (1080 to 1170) 19.2 1425 (1380 to 1470)

Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR

[ Calibration Required (9) RECORD the trip point as shown latched on the readout assembly. Setpoint is 16.53mA (1175 psig); No Adjust Limits are 16.51 to 16.55mA.

"As-Found" Trip mA Data (10) VERIFY Trip Status LED is ON:

a. At readout assembly. [I
b. At Trip Unit PIS-263-123C.

Initials 8.M.1-29 Rev. 50 Page 61 of 152

ATTACHMENT 1 Sheet 51 of 69 (11) VERIFY the following:

a. Relays are ENERGIZED:
1. K2C at Panel C2277 Initials
2. K5C at Panel C2277 Initials
b. Circuit supervisory lights are bright.
1. DS3A at Panel C2277 [ ]
2. DS4A at Panel C2277 [
3. DS5A at Panel C2277 [ ]
4. DS10A at Panel C2277 [ ]
5. DS1 1A at Panel C2277 Initials
c. Circuit supervisory lights are OFF.
1. DS3C at Panel C2277 [
2. DS4C at Panel C2277 [ ]
3. DS5C at Panel C2277 [ ]
4. DS1OC at Panel C2277 [
5. DS11C at Panel C2277 [ ]

Initials (12) IF trip point was less than 16.48mA (1170 psig) OR greater than 16.58mA (1180 psig), THEN NOTIFY SM.

SM notified? Yes[ ] No[

(13) PUSH the Trip Current Display Reset on the readout assembly AND VERIFY the Trip Status LED goes off. [1 8.M.1-29 Rev. 50 Page 62 of 152

ATTACHMENT 1 Sheet 52 of 69 (14) SLOWLY DECREASE current with the Stable Current knob AND RECORD the "As-Found" data for PIS-263-123C indicator.

Stable Current Reading Indicator Decreasing mA DSia "As-Found" 19.2 1425 (1380 to 1470) 16.0 1125 (1080 to 1170) 12.0 750 (705 to 795) 8.0 375 (330 to 420) 4.8 75 (30 to 120)

Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR

[ ] Calibration Required (15) RECORD the reset point as shown latched on readout assembly. Setpoint is 16.21 mA; No Adjust Limits are 16.05 to 16.37mA.

"As-Found" Reset mA Data (16) VERIFY Trip Status LED is:

a. ON at readout assembly. [
b. OFF at Trip Unit PIS-263-123C.

Initials 8.M.1-29 Rev. 50 Page 63 of 152

ATTACHMENT Sheet 53 of 69 1 (17) VERIFY the following:

a. Relays are DE-ENERGIZED
1. K2C at Panel C2277 Initials
2. K5C at Panel C2277 Initials
b. Circuit supervisory lights become normal - not bright.
1. DS3C at Panel C2277 [
2. DS4C at Panel C2277 [ ]
3. DS5C at Panel C2277 [ ]
4. DS10C at Panel C2277 [
5. DS11C at Panel C2277 [

Initials

c. Circuit supervisory lights become normal - not bright.
1. DS3A at Panel C2277 [
2. DS4A at Panel C2277 [ ]
3. DS5A at Panel C2277 [ ]
4. DS10A at Panel C2277 [
5. DS1 1A at Panel C2277 [

Initials (18) PUSH the Trip Current Display Reset AND VERIFY Trip Status LED goes off at the readout assembly. [ I 8.M.1-29 Rev. 50 Page 64 of 152

ATTACHMENT 1 Sheet 54 of 69 NOTE The trip point adjustments are located on the front of the trip unit.

(19) IF trip AND/OR indicator did NOT fall within the No Adjust Limits, THEN CALIBRATE AND RECORD "As-Left" data.

a. PIS-263-123C "As-Left" Trip 16.53 mA (16.51 to 16.55mA) mA Data
b. PIS-263-123C "As-Left" Reset 16.21 mA (16.05 to 16.37mA) mA Data
c. Indicator PIS-263-123C Current Desired Reading Reading "As-Left" mA 7si1 Inc. Dec.

4.8 75 (30 to 120) 8.0 375 (330 to 420) 12.0 750 (705 to 795) 16.0 1125 (1050 to 1170) 19.2 1425 (1380 to 1470) 8.M.1-29 Rev. 50 Page 65 of 152

ATTACHMENT 1 Sheet 55 of 69 (20) TEST the Gross Failure function(s) by adjusting the stable current to approximately 18 mA. [

a. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 29mA on readout assembly. [
b. Using Stable Current knob, SLOWLY INCREASE the reading until Gross Fail LED comes on. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 30.OmA; No Adjust Limits are 29.5mA to 30.5mA.

"As-Found" Gross Fail High mA Data

c. IF "As-Found" data was NOT within the No Adjust Limits, REMOVE the trip unit to adjust R39. REINSTALL trip unit to repeat testing by decreasing transient current (AND, IF required, stable current) to obtain reset AND increasing to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail High mA Data

d. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE.
e. PUSH Gross Fail Reset buttons on Trip Units PIS-263-123C and PS-263-123C-1 AND VERIFY Gross Fail lights are OFF.
f. CHANGE Transient Polarity switch to negative.
g. DECREASE the stable current to approximately 5.OmA. [
h. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 3.5mA on readout assembly. [

8.M.1-29 Rev. 50 Page 66 of 152

ATTACHMENT 1 Sheet 56 of 69 Using Stable Current knob, SLOWLY DECREASE the reading until Gross Fail LED comes on. [I

j. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 2.5mA; No Adjust Limits are 3.OmA to 2.OmA.

"As-Found" Gross Fail Low mA Data

k. IF "As-Found" reading is NOT within No Adjust Limits, ADJUST R40. INCREASE transient current (AND, IF required, stable current) to obtain reset AND DECREASE to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail Low mA Data PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [

m. CHANGE Transient Polarity switch to positive position. [I (21) TURN the Stable Current knob fully counterclockwise. I I 8.M.1-29 Rev. 50 Page 67 of 152

ATTACMENT CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(22) PULL OUT the Press To Cal knob (smaller knob) AND:

a. VERIFY that the CAL light is OFF.

Initials THEN

b. PUSH Gross Fail Reset buttons on Trip Units PIS-263-123C and PS-263-123C-1 AND VERIFY Gross Fail lights are OFF.

Initials THEN

c. ROTATE the Press To Cal knob (smaller knob) to the "OFF" position, THEN PUSH the knob back in. [I (23) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (24) IF required, HAVE Operations reset alarm(s). [I 8.M.1-29 Rev. 50 Page 68 of 152

ATTACHMENT 1 Sheet 58 of 69 NOTE If operating conditions have to be confirmed, the reading of meter under calibration should match the reading indicated by the three other channels of the same function within the ATWS System.

(25) VERIFY circuit supervisory lights have returned to their normal status (not bright).

a. DS3C at Panel C2277
b. DS4C at Panel C2277
c. DS5C at Panel C2277
d. DS3A at Panel C2277
e. DS4A at Panel C2277
f. DS5A at Panel C2277
g. IDS1A at Panel C2277
h. DS11 A at Panel C2277
i. DS10C at Panel C2277
j. DS11C at Panel C2277 Initials 8.M.1-29 Rev. 50 Page 69 of 152

ATTACHMENT 1 Sheet 59 of 69 (f) PS-263-123C-1 (1) VERIFY appropriate Prerequisites AND REVIEW appropriate Precautions and Limitations before proceeding further.

Initials q I CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

I (2) PULL OUT the Press To Cal knob (smaller knob) AND VERIFY that the CAL light is OFF.

Initials

a. SET larger knob to slot #6 for PS-263-123C-1. I]
b. SET smaller knob to slot #5 for PIS-263-123C. [I (3) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (4) SELECT OR VERIFY SELECTED positive polarity with Transient Polarity Switch.

Initials (5) APPLY stable calibration current to PS-263-123C-1 by pushing in the smaller knob of the Press To Cal knob AND VERIFY the CAL light is ON at the calibration unit AND alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is ON. [I 8.M.1-29 Rev. 50 Page 70 of 152

ATTACHMENT 1 Sheet 60 of 69 (6) VERIFY the following:

a. Circuit supervisory lights are normal - not bright.
1. DS7C at Panel C2277 [1]
2. DS8C at Panel C2277 [I]
3. DS9C at Panel C2277 [I]

Initials

b. Circuit supervisory lights are normal - not bright.
1. DS7A at Panel C2277 I]
2. DS8A at Panel C2277 [In
3. DS9A at Panel C2277 [: ]

Initials

c. Relay K3C at Panel C2277 is DE-ENERGIZED.

Initials (7) VERIFY the Trip Status LED is OFF at the readout assembly (IF required, PUSH Trip Current Display Reset). [I 8.M.1-29 Rev. 50 Page 71 of 152

[het61 of69 NOTE If setpoints are found outside the No Adjust Limits, test must be continued. The required adjustment will be made at the end of the test for each trip unit.

(8) INCREASE the stable current until PS-263-123C-1 trips. RECORD the trip point as shown latched on the readout assembly. Setpoint is 18.93mA (1400 psig); No Adjust Limits are 18.91 to 18.95mA.

"As-Found" Trip mA Data (9) VERIFY Trip Status LED is ON:

a. At readout assembly. I I
b. At Trip Unit PS-263-123C-1.

Initials 8.M.1-29 Rev. 50 Page 72 of 152

ATTACHMENT 1 Sheet 62 of 69 (10) VERIFY the following:

a. Relay K3C at Panel C2277 is ENERGIZED.

Initials

b. Circuit supervisory lights become bright.
1. DS7A at Panel C2277 [I]
2. DS8A at Panel C2277 [I]
3. DS9A at Panel C2277 [ ]

Initials

c. Circuit supervisory lights are OFF.
1. DS7C at Panel C2277 [I]
2. DS8C at Panel C2277 [I]
3. DS9C at Panel C2277 [I]

Initials (11) IF trip point was greater than 18.98mA (1405 psig), THEN NOTIFY SM.

SM notified? Yes[ ] No[ ]

(12) PUSH the Trip Current Display Reset on the readout assembly AND VERIFY the Trip Status LED goes off. I I (13) SLOWLY DECREASE current with the Stable Current knob until PS-263-123C-1 resets AND RECORD the reset point.

"As-Found" Reset mA Data 8.M.1-29 Rev. 50 Page 73 of 152

ATTACHMENT 1 Sheet 63 of 69 (14) VERIFY Trip Status LED is:

a. ON at readout assembly. [I
b. OFF at Trip Unit PS-263-123C-1.

Initials (15) VERIFY the following:

a. Relay K3C at Panel C2277 is DE-ENERGIZED.

Initials

b. Circuit supervisory lights become normal - not bright.
1. DS7C at Panel C2277 [I]
2. DS8C at Panel C2277
3. DS9C at Panel C2277 [1]

Initials

c. Circuit supervisory lights become normal - not bright.
1. DS7A at Panel C2277 [I]
2. DS8A at Panel C2277 [I]
3. DS9A at Panel C2277 [I]

Initials (16) PUSH the Trip Current Display Reset AND VERIFY Trip Status LED goes OFF at the readout assembly. [I 8.M.1-29 Rev. 50 Page 74 of 152

[heet64 o 6 NOTE The trip point adjustments are located on the front of the trip unit.

(17) IF trip did NOT fall within the No Adjust Limits, CALIBRATE AND RECORD "As-Left" data.

a. PS-263-123C-1 "As-Left" Trip 18.93mA (18.91 to 18.95mA) mA Data
b. PS-263-123C-1 "As-Left" Reset mA Data (18) TEST the Gross Failure function(s) by adjusting the stable current to approximately 18mA. [
a. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 29mA on readout assembly. [
b. Using Stable Current knob, SLOWLY INCREASE the reading until Gross Fail LED comes on. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 30.OmA; No Adjust Limits are 29.5mA to 30.5mA.

"As-Found" Gross Fail High mA Data

c. IF "As-Found" data was NOT within the No Adjust Limits, REMOVE the trip unit to adjust R39. REINSTALL trip unit to repeat testing by decreasing transient current (AND, IF required, stable current) to obtain reset AND increasing to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail High mA Data 8.M.1-29 Rev. 50 Page 75 of 152

ATTACHMENT 1 Sheet 65 of 69

d. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE.
e. PUSH Gross Fail Reset buttons on Trip Units PS-263-123C-1, PIS-263-123C AND VERIFY Gross Fail lights are OFF.
f. CHANGE Transient Polarity switch to negative. [ ]
g. DECREASE the stable current to approximately 5.OmA. [
h. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 3.5mA on readout assembly.

Using Stable Current knob, SLOWLY DECREASE the reading until Gross Fail LED comes on.

j. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 2.5mA; No Adjust Limits are 3.OmA to 2.OmA.

"As-Found" Gross Fail Low mA Data

k. IF "As-Found" reading is NOT within No Adjust Limits, ADJUST R40.

INCREASE transient current (AND, IF required, stable current) to obtain reset AND DECREASE to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail Low mA Data PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE.

m. CHANGE Transient Polarity switch to positive position. ]

8.M.1-29 Rev. 50 Page 76 of 152

[TTACHMENT (19) TURN the Stable Current knob fully counterclockwise. I ]

CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(20) PULL OUT the Press To Cal knob (smaller knob) AND:

a. VERIFY that the CAL light is OFF.

Initials THEN

b. PUSH Gross Fail Reset buttons on Trip Units PS-263-123C-1 and PIS-263-123C AND VERIFY Gross Fail lights are OFF.

Initials THEN

c. ROTATE the Press To Cal knob (smaller knob) to the OFF position, THEN PUSH the knob back in.

Initials (21) VERIFY alarm "DIVISION ONE PANEL TROUBLE" (C905L-B5) is CLEAR.

Initials (22) IF required, HAVE Operations reset alarm(s). [ I 8.M.1-29 Rev. 50 Page 77 of 152

ATTACHMENT 1 Sheet 67 of 69 NOTE If operating conditions have to be confirmed, the reading of meter under calibration should match the reading indicated by the three other channels of the same function within the ATWS System.

(23) VERIFY circuit supervisory lights have returned to their normal status (not bright).

a. DS7C at Panel C2277 [
b. DS8C at Panel C2277 [ ]
c. DS9C at Panel C2277 [
d. DS7A at Panel C2277 [ ]
e. DS8A at Panel C2277 [
f. DS9A at Panel C2277 [ ]

Initials

[7] Return to Service (a) ROTATE the Press To Cal knob (larger knob) to "OFF" position. [ ]

(b) TURN OFF power to the calibration unit. [

(c) VERIFY the CAL light is OFF at the calibration unit. [

(d) PUSH the Gross Fail Reset buttons. [ ]

(e) VERIFY the following:

(1) Gross Fail Lights are OFF at Cabinet C2277.

Initials Verifier (2) 125V DC power light is ON.

Initials Verifier (f) PULL OUT readout assembly with extender card from Cabinet C2277.

Initials Verifier 8.M.1-29 Rev. 50 Page 78 of 152

ATTACHMENT 1 Sheet 68 of 69

[8] NOTIFY the on-shift SRO that test is complete. [1]

[9] COMPLETE documentation AND UPDATE Maintenance records. [I]

[10] RECORD test equipment used:

M&TE # Due Date

[11] FILL OUT the I&C Procedure Feedback Form (Attachment 3)

AND FORWARD to I&C Supervision.

Initials 8.M.1-29 Rev. 50 Page 79 of 152

ATTACHMENT 1 Sheet 69 of 69 Discrepancies noted during surveillance performance:

Notes:

Date Completed:

Acceptance Criteria of Section 9.0 of the base document were met.

Maintenance Management _ Date On-Shift SRO Date Time Acceptance Criteria of Section 9.0 of the base document were not met. Notify the on-shift SRO.

Discrepancies:

Action taken:

Maint Management Date Time 8.M.1-29 Rev. 50 Page 80 of 152

ATTACHMENT 2 Sheet 1 of 70 ATWS TRIP UNIT CABINET C2278 CALIBRATION

[1] PERFORM the procedural steps for each instrument in the order they are written. For each step with a [ ], SIGNIFY completion with a check mark. For each step with a _ , ENTER initials or data as appropriate. For a step followed by a double _ , that step shall require verification with two individuals' signed initials required to signify completion. "NIP" (for "not performed") may be placed by a procedural step where performance of that step has been conditionally stated and the condition(s) has not been met.

[2] DOCUMENT in the space provided below the reason this test is being performed (CHECK one):

Routine Surveillance Postwork testing for Work Order #

[ Other (specify)

[3] Prerequisites (a) Personnel assigned to perform this Attachment have read and understand what is required. All personnel involved must print their name and the date and sign their initials below.

Name (print) Date Initials Name (print) Date Initials Name (print) Date Initials Name (print) Date Initials (b) IF required, a Pre-Evolution Brief has been completed and attached to this surveillance.

[NRCCC Item PAPR 020]

Initials 8.M.1-29 Rev. 50 Page 81 of 152

ATTACHENT 2 Sheet 2 f 70 (c) COORDINATE action to be taken with Operations personnel AND OBTAIN the on-shift SRO's signature as permission to begin test.

On-Shift SRO signature Date Time (d) CONFIRM with Operations that no other testing is being performed on the ATWS System.

Initials (e) PRIOR to start of testing, PROVIDE Operations with Attachment 4 (Alarm Summary Sheet).

Initials (f) VERIFY that the prejob brief discussed the need to verify that the CAL light is OFF when the Press to Cal knob (smaller knob) is pulled out. (PRO1.8151)

Initials (g) Radiation Protection (RP) notified.

Initials (h) ATWS System is powered up.

Initials 8.M.1-29 Rev. 50 Page 82 of 152

ATTACHMENT 2 Sheet 3 of 70 NOTE Readout assembly must be calibrated prior to calibration of trip unit(s). Readout assembly need not be recalibrated for continuous use for more than one trip unit; but if the readout assembly is left unattended, it must be recalibrated prior to use.

(i) IF PNPS 8.M.1-29 Attachment 1 was performed within the last 4 days, THEN RECORD the readout assembly used in PNPS 8.M.1-29 Attachment 1.

IF PNPS 8.M.1-29 Attachment 1 was NOT performed within the last 4 days, ENTER "NIP".

Initials Readout assembly for PNPS 8.M.1-29 Attachment 1 M&TE #

IF PNPS 8.M.1-29 Attachment 1 was performed within the last 4 days, THEN OBTAIN from M&TE a different readout assembly than what was used in PNPS 8.M.1-29 Attachment 1. RECORD the information from the calibration sticker for readout assembly to be used in PNPS 8.M.1-29 Attachment 2.

IF PNPS 8.M.1-29 Attachment 1 was NOT performed within the last 4 days, ENTER "N/P".

Readout assembly for PNPS 8.M.1-29 Attachment 2 M&TE #

Calibration performed by Time Date IF PNPS 8.M.1-29 Attachment 1 was NOT performed within the last 4 days, THEN OBTAIN a calibrated readout assembly from M&TE personnel AND RECORD information from the calibration sticker.

IF PNPS 8.M.1-29 Attachment 1 was performed within the last 4 days, ENTER "N//P".

Readout assembly for PNPS 8.M.1-29 Attachment 2 M&TE #

Calibration performed by Time Date 8.M.1-29 Rev. 50 Page 83 of 152

ATTACHMENT 2 Sheet 4 of 70 (1) VERIFY calibration of readout assembly was performed within last 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> AND the readout assembly has not been left unattended since calibration.

Initials (j) ESTABLISH communications between Control Room and ATWS Cabinet C2278 (Rx Bldg 51').

Initials

[4] Cabinet Power Supply Test (a) VERIFY the following power supply to ATWS logic Panel C2278 lights are ON:

(1) Power Supply PS1 B Initials (2) Power Supply PS2B_

Initials (b) DEPRESS power supply monitoring circuit test button K37B at Panel C2278. [ I (c) VERIFY associated power supply light PS1B goes off.

Initials (d) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is ON.

Initials (e) RELEASE power supply test button K37B. [

(f) VERIFY power supply light PS1 B comes on.

Initials (g) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (h) DEPRESS power supply monitor circuit test button K38B at Panel C2278. [

(i) VERIFY associated power supply light PS2B goes off.

Initials 8.M.1-29 Rev. 50 Page 84 of 152

ATTACHMENT 2 Sheet 5 of 70 (j) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is ON.

Initials (k) RELEASE power supply test button K38B. [ ]

(I) VERIFY power supply light PS2B comes on.

Initials (m) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials

[5] Calibration Unit: General Preparation (a) VERIFY the calibration unit is in the following condition at ATWS Cabinet C2278:

(1) Power switch is in the "OFF" position. [

(2) Transient Current knob is pulled out and turned fully counterclockwise. []

(3) Press To Cal knob (smaller knob) is in the "OFF" position and pushed in. [

(4) Press To Cal knob (larger knob) is in the "OFF" position.

(b) TURN the Stable Current knob fully counterclockwise. [ ]

(c) PLUG the readout assembly with extender card into the calibration unit. [ ]

(d) TURN ON the power. [

(e) ALLOW minimum of 10 minutes warm-up time for the readout assembly. [ ]

8.M.1-29 Rev. 50 Page 85 of 152

ATTACHMENT 2 Sheet 6 of 70

[6] Trip Unit Calibration (a) LIS-263-121B (1) VERIFY appropriate Prerequisites AND REVIEW appropriate Precautions and Limitations before proceeding further.

Initials CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND 113. The unit status indicating light remains green.

LI (2) PULL OUT the Press To Cal knob (smaller knob) AND VERIFY that the CAL light is OFF.

Initials

a. SET larger knob to slot #1 for LIS-263-121B. [I
b. SET smaller knob to slot #1 for LIS-263-121B. [I (3) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (4) SELECT OR VERIFY SELECTED positive polarity with Transient Polarity Switch.

Initials 8.M.1-29 Rev. 50 Page 86 of 152

ATTACHMENT 2 Sheet 7 of 70 (5) APPLY stable calibration current to LIS-263-121B by pushing in the smaller knob of the Press To Cal knob AND VERIFY the CAL light is ON at the calibration unit AND alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is ON. [

(6) VERIFY the following:

a. Circuit supervisory lights are bright.
1. DS3D at Panel C2278 [ ]
2. DS4D at Panel C2278 [ I
3. DS5D at Panel C2278 [ ]
4. DS10D at Panel C2278 [ ]
5. DS11D at Panel C2278 [ I Initials
b. Circuit supervisory lights are OFF.
1. DS3B at Panel C2278 [ I
2. DS4B at Panel C2278 [ ]
3. DS5B at Panel C2278 [ ]
4. DS10B at Panel C2278 [ ]
5. DS11B at Panel C2278 [ ]

Initials 8.M.1-29 Rev. 50 Page 87 of 152

ATTACHMENT 2 Sheet 8 of 70

c. Relays are ENERGIZED:
1. K1B at Panel C2278 Initials
2. K1 01 B at Panel C2278 (This relay has a 9-second time delay)

Initials

3. K4B at Panel C2278 Initials (7) VERIFY the Trip Status LED is OFF at the readout assembly (IF required, PUSH Trip Current Display Reset). [I NOTE If setpoints are found outside the No Adjust Limits, test must be continued. The required adjustment will be made at the end of the test for each trip unit.

(8) INCREASE the stable current AND RECORD the "As-Found" data for LIS-263-121B indicator.

Stable Current Reading Indicator Increasing mA inches "As-Found" 4.32 -48 (-46 to -50) 8.0 -25 (-23 to -27) 12.0 0 (-2 to +2) 16.0 +25 (+23 to +27) 19.68 +48 (+46 to +50)

Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR Calibration Required 8.M.1-29 Rev. 50 Page 88 of 152

ATTACHMENT 2 Sheet 9 of 70 (9) RECORD the reset point as shown latched on readout assembly. Setpoint is 4.96mA; No Adjust Limits are 4.80 to 5.12mA.

"As-Found" Reset mA Data (10) VERIFY Trip Status LED is:

a. ON at readout assembly. [ ]
b. OFF at Trip Unit LIS-263-121B.

Initials (11) VERIFY the following:

a. Relays are DE-ENERGIZED.
1. K1 B at Panel C2278 Initials
2. K101B at Panel C2278 (This relay has a 9-second time delay.)

Initials

3. K4B at Panel C2278 Initials
b. Circuit supervisory lights become normal - not bright.
1. DS3D at Panel C2278 [
2. DS4D at Panel C2278 [ ]
3. DS5D at Panel C2278 [ ]
4. DS10D at Panel C2278 [
5. DS 1D at Panel C2278 [

Initials 8.M.1-29 Rev. 50 Page 89 of 152

ATTACHMENT 2 Sheet 10 of 70

c. Circuit supervisory lights become normal - not bright.
1. DS3B at Panel C2278 [ I
2. DS4B at Panel C2278 [ I
3. DS5B at Panel C2278 [ ]
4. DS10B at Panel C2278 [I]
5. DS11B at Panel C2278 [1]

Initials (12) PUSH the Trip Current Display Reset on the readout assembly AND VERIFY the Trip Status LED goes off. [ I (13) SLOWLY DECREASE current with the Stable Current knob AND RECORD the "As-Found" data for LIS-263-121B indicator.

Stable Current Reading Indicator Decreasing mA inches "As-Found" 19.68 +48 (+46 to +50) 16.0 +25 (+23 to +27) 12.0 0 (-2 to +2) 8.0 -25 (-23 to -27) 4.32 -48 (-46 to -50)

] Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR

[I ] Calibration Required 8.M.1-29 Rev. 50 Page 90 of 152

ATTACHMENT 2 Sheet 11 of 70 (14) RECORD the trip point as shown latched on the readout assembly. Setpoint is 4.64mA

(-46 inches indicator reading); No Adjust Limits are 4.62 to 4.66mA.

"As-Found" Trip mA Data (15) VERIFY Trip Status LED is ON:

a. At readout assembly. [ I
b. At Trip Unit LIS-263-121B.

Initials 8.M.1-29 Rev. 50 Page 91 of 152

ATTACHMENT 2 Sheet 12 of 70 (16) VERIFY the following:

a. Relays are ENERGIZED:
1. K1 B at Panel C2278 Initials
2. K101B at Panel C2278 (This relay has a 9-second time delay.)

Initials

3. K4B at Panel C2278 Initials
b. Circuit supervisory lights are OFF.
1. DS3B at Panel C2278 [ ]
2. DS4B at Panel C2278 [ ]
3. DS5B at Panel C2278 [ ]
4. DS10B at Panel C2278 [ ]
5. DS1 1B at Panel C2278 [ ]

Initials

c. Circuit supervisory lights become bright.
1. DS3D at Panel C2278 [ ]
2. DS4D at Panel C2278 [ ]
3. DS5D at Panel C2278 [ ]
4. DS10D at Panel C2278 [
5. DS11D at Panel C2278 [ ]

Initials 8.M.1-29 Rev. 50 Page 92 of 152

ATTACHMENT 2 Sheet 13 of 70 (17) IF trip point was less than 4.59mA

(-46.3 inches indicator reading), THEN NOTIFY the SM.

SM notified? Yes[ ] No[ ]

(18) PUSH the Trip Current Display Reset AND VERIFY Trip Status LED goes off at the readout assembly. [I NOTE The trip point adjustments are located on the front of the trip unit.

(19) IF trip AND/OR indicator did NOT fall within the No Adjust Limits, THEN CALIBRATE AND RECORD "As-Left" data.

a. LIS-263-121B "As-Left" Trip 4.64mA (4.62 to 4.66mA) mA Data
b. LIS-263-121 B "As-Left" Reset 4.96mA (4.80 to 5.12mA) mA Data
c. Indicator LIS-263-121B Current Desired Reading Reading "As-Left" mA inches Inc. Dec.

4.32 -48 (-46 to -50) 8.0 -25 (-23 to -27) 12.0 0 (-2 to +2) 16.0 +25 (+23 to +27) 19.68 +48 (+46 to +50) 8.M.1-29 Rev. 50 Page 93 of 152

SATTACHMENT Sheet 14 of 70 2 (20) TEST the Gross Failure function(s) by adjusting the stable current to approximately 18mA. [

a. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 29mA on readout assembly. [
b. Using Stable Current knob, SLOWLY INCREASE the reading until Gross Fail LED comes on. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 30.OmA; No Adjust Limits are 29.5mA to 30.5mA.

"As-Found" Gross Fail High mA Data

c. IF "As-Found" data was NOT within the No Adjust Limits, REMOVE the trip unit to adjust R39. REINSTALL trip unit to repeat testing by decreasing transient current (AND, IF required, stable current) to obtain reset AND increasing to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail High mA Data

d. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [ ]
e. PUSH Gross Fail Reset buttons on Trip Unit LIS-263-121B AND VERIFY Gross Fail light is OFF. [
f. CHANGE Transient Polarity switch to negative.
g. DECREASE the stable current to approximately 5.OmA. [
h. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 3.5mA on readout assembly. [

8.M.1-29 Rev. 50 Page 94 of 152

ATTACHMENT 2 Sheet 15 of 70 Using Stable Current knob, SLOWLY DECREASE the reading until Gross Fail LED comes on. I ]

RECORD Gross Fail trip as read on the readout assembly. Setpoint is 2.5mA; No Adjust Limits are 3.OmA to 2.OmA.

"As-Found" Gross Fail Low mA Data

k. IF "As-Found" reading is NOT within No Adjust Limits, ADJUST R40.

INCREASE transient current (AND, IF required, stable current) to obtain reset AND DECREASE to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail Low mA Data PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [I]

m. CHANGE Transient Polarity switch to positive position.

(21) TURN the Stable Current knob fully counterclockwise. [I]

8.M.1-29 Rev. 50 Page 95 of 152

ATTACHMENT 2 Sheet 16 of 70 q

CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(22) PULL OUT the Press To Cal knob (smaller knob) AND:

a. VERIFY that the CAL light is OFF.

Initials THEN

b. PUSH Gross Fail Reset button on Trip Unit LIS-263-121B AND VERIFY Gross Fail light is OFF.

Initials THEN

c. ROTATE the Press To Cal knob (smaller knob) to the "OFF" position, THEN PUSH the knob back in.

Initials (23) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (24) IF required, HAVE Operations reset alarm(s). [I 8.M.1-29 Rev. 50 Page 96 of 152

Shet17 of70 NOTE If operating conditions have to be confirmed, the reading of meter under calibration should match the reading indicated by the three other channels of the same function within the ATWS System.

(25) VERIFY circuit supervisory lights have returned to their normal status (not bright).

a. DS3B at Panel C2278
b. DS4B at Panel C2278
c. DS5B at Panel C2278
d. DS3D at Panel C2278
e. DS4D at Panel C2278
f. DS5D at Panel C2278
g. DS10B at Panel C2278
h. DS1 1B at Panel C2278
i. DS10D at Panel C2278
j. DS11D at Panel C2278 Initials 8.M.1-29 Rev. 50 Page 97 of 152

ATTACHMENT 2 Sheet 18 of 70 (b) LIS-263-121 D (1) VERIFY appropriate Prerequisites AND REVIEW appropriate Precautions and Limitations before proceeding further.

Initials CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(2) PULL OUT the Press To Cal knob (smaller knob) AND VERIFY that the CAL light is OFF.

Initials

a. SET larger knob to slot #2 for LIS-263-121D. [I]
b. SET smaller knob to slot #2 for LIS-263-121 D. [I]

(3) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (4) SELECT OR VERIFY SELECTED positive polarity with Transient Polarity Switch.

Initials (5) APPLY stable calibration current to LIS-263-121D by pushing in the smaller knob of the Press To Cal knob AND VERIFY the CAL light is ON at the calibration unit AND alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is ON. I I 8.M.1-29 Rev. 50 Page 98 of 152

ATTACHMENT Sheet 19 of 70 2 (6) VERIFY the following:

a. Circuit supervisory lights are bright.
1. DS3B at Panel C2278 [ ]
2. DS4B at Panel C2278 [ ]
3. DS5B at Panel C2278 [ ]
4. DS10B at Panel C2278 [ ]
5. DS11B at Panel C2278 [ ]

Initials

b. Circuit supervisory lights are OFF.
1. DS3D at Panel C2278 [ ]
2. DS4D at Panel C2278 [ ]
3. DS5D at Panel C2278 [ ]
4. DS10D at Panel C2278 [ ]
5. DS 1D at Panel C2278 [ ]

Initials

c. Relays are ENERGIZED:
1. K1 D at Panel C2278 Initials
2. K101D at Panel C2278 (This relay has a 9-second time delay.)

Initials

3. K4D at Panel C2278 Initials (7) VERIFY the Trip Status LED is OFF at the readout assembly (IF required, PUSH Trip Current Display Reset). []

8.M.1-29 Rev. 50 Page 99 of 152

ATTACHMENT 2 Sheet 20 of 70 I NOTE If setpoints are found outside the No Adjust Limits, test must be continued. The required adjustment will be made at the end of the test for each trip unit.

(8) INCREASE the stable current AND RECORD the "As-Found" data for LIS-263-121D indicator.

Stable Current Reading Indicator Increasing mA inches "As-Found" 4.32 -48 (-46 to -50) 8.0 -25 (-23 to -27) 12.0 0 (-2 to +2) 16.0 +25 (+23 to +27) 19.68 +48 (+46 to +50)

Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR Calibration Required (9) RECORD the reset point as shown latched on readout assembly. Setpoint is 4.96mA; No Adjust Limits are 4.80 to 5.12mA.

"As-Found" Reset mA Data (10) VERIFY Trip Status LED is:

a. ON at readout assembly. [ ]
b. OFF at Trip Unit LIS-263-121D.

Initials 8.M.1-29 Rev. 50 Page 100 of 152

SATTA(3HMENT Sheet 21 of 70 2 (11) VERIFY the following:

a. Relays are DE-ENERGIZED:
1. K1D at Panel C2278 Initials
2. K101D at Panel C2278 (This relay has a 9-second time delay.)

Initials

3. K4D at Panel 02278 Initials
b. Circuit supervisory lights become normal - not bright.
1. DS3B at Panel 02278 [ 1
2. DS4B at Panel 02278 [ ]
3. DS5B at Panel C2278 [ ]
4. DS10B at Panel C2278 [ ]
5. DS11B at Panel 02278 [ ]

Initials

c. Circuit supervisory lights become normal - not bright.
1. DS3D at Panel C2278 [
2. DS4D at Panel 02278
3. DS5D at Panel C2278
4. DS10D at Panel C2278 [
5. DS11D at Panel C2278 [ ]

Initials 8.M.1-29 Rev. 50 Page 101 of 152

ATTACHMENT 2 Sheet 22 of 70 (12) PUSH the Trip Current Display Reset on the readout assembly AND VERIFY the Trip Status LED goes off. []

(13) SLOWLY DECREASE current with the Stable Current knob AND RECORD the "As-Found" data for LIS-263-121 D indicator.

Stable Current Reading Indicator Decreasing mA inches "As-Found" 19.68 +48 (+46 to +50) 16.0 +25 (+23 to +27) 12.0 0 (-2 to +2) 8.0 -25 (-23 to -27) 4.32 -48 (-46 to -50)

] Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR

] Calibration Required (14) RECORD the trip point as shown latched on the readout assembly. Setpoint is 4.64mA (-46 inches indicator reading);

No Adjust Limits are 4.62 to 4.66mA.

"As-Found" Trip mA Data (15) VERIFY Trip Status LED is ON:

a. At readout assembly. [
b. At Trip Unit LIS-263-121D.

Initials 8.M.1-29 Rev. 50 Page 102 of 152

SATTACHMENT 2 Sheet 23 of 70 (16) VERIFY the following:

a. Relays are ENERGIZED:
1. K1 D at Panel C2278 Initials
2. K101D at Panel C2278 Initials
3. K4D at Panel C2278 Initials
b. Circuit supervisory lights are OFF.
1. DS3D at Panel C2278 [ ]
2. DS4D at Panel C2278 [ ]
3. DS5D at Panel 02278 [ ]
4. DS10D at Panel C2278 [ ]
5. DS 1D at Panel C2278 [ ]

Initials

c. Circuit supervisory lights become bright.
1. DS3B at Panel 02278 [ ]
2. DS4B at Panel C2278 [ ]
3. DS5B at Panel 02278 [ ]
4. DS10B at Panel 02278 [ ]
5. DS1 1B at Panel 02278 [ ]

Initials (17) IF trip point was less than 4.59mA

(-46.3 inches indicator reading), THEN NOTIFY SM.

SM notified? Yes [ ] No[

8.M.1-29 Rev. 50 Page 103 of 152

ATTACHMENT 2 Sheet 24 of 70 (18) PUSH the Trip Current Display Reset AND VERIFY Trip Status LED goes off at the readout assembly. [I NOTE The trip point adjustments are located on the front of the trip unit.

(19) IF trip ANDIOR indicator did NOT fall within the No Adjust Limits, THEN CALIBRATE AND RECORD "As-Left" data.

a. LIS-263-121D "As-Left" Trip 4.64mA (4.62 to 4.66mA) mA Data
b. LIS-263-121D "As-Left" Reset 4.96mA (4.80 to 5.12mA) mA Data
c. Indicator LIS-263-121D Current Desired Reading Reading "As-Left" mA inches Inc. Dec.

4.32 -48 (-46 to -50) 8.0 -25 (-23 to -27) 12.0 0 (-2 to +2) 16.0 +25 (+23 to +27) 19.68 +48 (+46 to +50) 8.M.1-29 Rev. 50 Page 104 of 152

ATTACHMENT 2 Sheet 25 of 70 (20) TEST the Gross Failure function(s) by adjusting the stable current to approximately 18mA. [

a. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 29mA on readout assembly. [
b. Using Stable Current knob, SLOWLY INCREASE the reading until Gross Fail LED comes on. RECORD Gross Fail trip as read on the readout assembly.

Setpoint is 30.0mA; No Adjust Limits are 29.5mA to 30.5mA.

"As-Found" Gross Fail High mA Data

c. IF "As-Found" data was NOT within the No Adjust Limits, REMOVE the trip unit to adjust R39. REINSTALL trip unit to repeat testing by decreasing transient current (AND, IF required, stable current) to obtain reset AND increasing to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail High mA Data

d. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [
e. PUSH Gross Fail Reset button on Trip Unit LIS-263-121D AND VERIFY Gross Fail light is OFF. [
f. CHANGE Transient Polarity switch to negative. [
g. DECREASE the stable current to approximately 5.OmA. [
h. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 3.5mA on readout assembly. [

8.M.1-29 Rev. 50 Page 105 of 152

ATTACHMENT 2 Sheet 26 of 70 Using Stable Current knob, SLOWLY DECREASE the reading until Gross Fail LED comes on. [ I RECORD Gross Fail trip as read on the readout assembly. Setpoint is 2.5mA; No Adjust Limits are 3.OmA to 2.OmA.

"As-Found" Gross Fail Low mA Data

k. IF "As-Found" reading is NOT within No Adjust Limits, ADJUST R40.

INCREASE transient current (AND, IF required, stable current) to obtain reset AND DECREASE to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail Low mA Data

1. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. II]
m. CHANGE Transient Polarity switch to positive position. [I (21) TURN the Stable Current knob fully counterclockwise. EI 8.M.1-29 Rev. 50 Page 106 of 152

ATTACHMENT 2 Sheet 27 of 70 CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(22) PULL OUT the Press To Cal knob (smaller knob) AND:

a. VERIFY that the CAL light is OFF.

Initials THEN

b. PUSH Gross Fail Reset button on Trip Unit LIS-263-121D AND VERIFY Gross Fail light is OFF.

Initials THEN

c. ROTATE the Press To Cal knob (smaller knob) to the "OFF" position, THEN PUSH the knob back in.

Initials (23) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (24) IF required, HAVE Operations reset alarm(s). [I 8.M.1-29 Rev. 50 Page 107 of 152

ATTACHMENT 2 Sheet 28 of 70 NOTE If operating conditions have to be confirmed, the reading of meter under calibration should match the reading indicated by the three other channels of the same function within the ATWS system.

(25) VERIFY circuit supervisory lights have returned to their normal status (not bright).

a. DS3B at Panel C2278
b. DS4B at Panel C2278
c. DS5B at Panel C2278
d. DS3D at Panel C2278
e. DS4D at Panel C2278
f. DS5D at Panel C2278
g. DS10B at Panel C2278
h. DS11B at Panel C2278
i. DS10D at Panel C2278
j. DS11D at Panel C2278 Initials 8.M.1-29 Rev. 50 Page 108 of 152

ATTACHMENT 2 Sheet 29 of 70 (c) PIS-263-123B (1) VERIFY appropriate Prerequisites AND REVIEW appropriate Precautions and Limitations before proceeding further.

Initials CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(2) PULL OUT the Press To Cal knob (smaller knob)

AND VERIFY that the CAL light is OFF.

Initials

a. SET larger knob to slot #3 for PIS-263-123B. I ]
b. SET smaller knob to slot #3 for PIS-263-123B. [I (3) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (4) SELECT OR VERIFY SELECTED positive polarity with Transient Polarity Switch.

Initials (5) APPLY stable calibration current to PIS-263-123B by pushing in the smaller knob of the Press To Cal knob AND VERIFY the CAL light is ON at the calibration unit AND alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is ON. [I 8.M.1-29 Rev. 50 Page 109 of 152

ATTACHMENT 2 Sheet 30 of 70 (6) VERIFY the following:

a. Circuit supervisory lights are normal - not bright.
1. DS3B at Panel C2278 [ I
2. DS4B at Panel C2278 [ ]
3. DS5B at Panel C2278 [ I
4. DS10B at Panel C2278 [ I
5. DS11B at Panel C2278 [ I Initials
b. Circuit supervisory lights are normal - not bright.
1. DS3D at Panel C2278 [ I
2. DS4D at Panel C2278 [ I
3. DS5D at Panel C2278 [ ]
4. DS10D at Panel C2278 [ I
5. DS11D at Panel C2278 [ ]

Initials

c. Relays are DE-ENERGIZED:
1. K2B at Panel C2278 Initials
2. K5B at Panel C2278 Initials (7) VERIFY the Trip Status LED is OFF at the readout assembly (IF required, PUSH Trip Current Display Reset). [I 8.M.1-29 Rev. 50 Page 110 of 152

ATTACHMENT 2 Sheet 31 of 70 NOTE If setpoints are found outside the No Adjust Limits, test must be continued. The required adjustment will be made at the end of the test for each trip unit.

(8) INCREASE the stable current AND RECORD the "As-Found" data for PIS-263-123B indicator.

Stable Current Reading Indicator Increasing mA [Sig "As-Found" 4.8 75 (30 to 120) 8.0 375 (330 to 420) 12.0 750 (705 to 795) 16.0 1125 (1080 to 1170) 19.2 1425 (1380 to 1470)

Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR Calibration Required (9) RECORD the trip point as shown latched on the readout assembly. Setpoint is 16.53mA (1175 psig); No Adjust Limits are 16.51 to 16.55mA.

"As-Found" Trip mA Data (10) VERIFY Trip Status LED is ON:

a. At readout assembly. [1
b. At Trip Unit PIS-263-123B.

Initials 8.M.1-29 Rev. 50 Page 111 of 152

ATTACHMENT Sheet 32 of 70 2 (11) VERIFY the following:

a. Relays are ENERGIZED:
1. K2B at Panel C2278 Initials
2. K5B at Panel C2278 Initials
b. Circuit supervisory lights are OFF.
1. DS3B at Panel C2278 [ ]
2. DS4B at Panel C2278 [ ]
3. DS5B at Panel C2278 [ I
4. DS10B at Panel 02278 [ I
5. DS1 1B at Panel 02278 [ I Initials
c. Circuit supervisory lights become bright.
1. DS3D at Panel C2278 [ I
2. DS4D at Panel 02278
3. DS5D at Panel 02278 [ I
4. DS10D at Panel C2278 [ I
5. DS11D at Panel 02278 [ I Initials (12) IF trip point was less than 16.48mA (1170 psig) OR greater than 16.58mA (1180 psig), THEN NOTIFY SM.

SM notified? Yes[ ] No[ ]

8.M.1-29 Rev. 50 Page 112 of 152

ATTACHMENT 2 Sheet 33 of 70 (13) PUSH the Trip Current Display Reset on the readout assembly AND VERIFY the Trip Status LED goes off. []

(14) SLOWLY DECREASE current with the Stable Current knob AND RECORD the "As-Found" data for PIS-263-123B indicator.

Stable Current Reading Indicator Decreasing mA psigq "As-Found" 19.2 1425 (1380 to 1470) 16.0 1125 (1080 to 1170) 12.0 750 (705 to 795) 8.0 375 (330 to 420) 4.8 75 (30 to 120)

Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR

] Calibration Required (15) RECORD the reset point as shown latched on readout assembly. Setpoint is 16.21mA; No Adjust Limits are 16.05 to 16.37mA.

"As-Found" Reset mA Data (16) VERIFY Trip Status LED is:

a. ON at readout assembly. [
b. OFF at Trip Unit PIS-263-123B.

Initials 8.M.1-29 Rev. 50 Page 113 of 152

ATTACHMENT 2 Sheet 34 of 70 (17) VERIFY the following:

a. Relays are DE-ENERGIZED:
1. K2B at Panel C2278 Initials
2. K5B at Panel C2278 Initials
b. Circuit supervisory lights become normal - not bright.
1. DS3B at Panel C2278 [
2. DS4B at Panel C2278 [
3. DS5B at Panel C2278 [ ]
4. DS10B at Panel C2278 [ ]
5. DS1 1B at Panel C2278 [ ]

Initials

c. Circuit supervisory lights become normal - not bright.
1. DS3D at Panel C2278 [
2. DS4D at Panel C2278 [ ]
3. DS5D at Panel C2278 [ ]
4. DS10D at Panel C2278 [ ]
5. DS11D at Panel C2278 [ ]

Initials (18) PUSH the Trip Current Display Reset AND VERIFY Trip Status LED goes off at the readout assembly. []

8.M.1-29 Rev. 50 Page 114 of 152

ATTACHMENT 2 Sheet 35 of 70 I NOTE The trip point adjustments are located on the front of the trip unit.

(19) IF trip AND/OR indicator did NOT fall within the No Adjust Limits, THEN CALIBRATE AND RECORD "As-Left" data.

a. PIS-263-123B "As-Left" Trip 16.53mA (16.51 to 16.55mA) mA Data
b. PIS-263-123B "As-Left" Reset 16.21 mA (16.05 to 16.37mA) mA Data
c. PIS-263-123B Indicator Current Desired Reading Reading "As-Left" mA psi-q Inc. Dec.

4.8 75 (30 to 120) 8.0 375 (330 to 420) 12.0 750 (705 to 795) 16.0 1125 (1080 to 1170) 19.2 1425 (1380 to 1470) 8.M.1-29 Rev. 50 Page 115 of 152

ATTACHMENT 2 Sheet 36 of 70 (20) TEST the Gross Failure function(s) by adjusting the stable current to approximately 18mA. [ *]

a. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 29mA on readout assembly. [
b. Using Stable Current knob, SLOWLY INCREASE the reading until Gross Fail LED comes on. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 30.OmA; No Adjust Limits are 29.5mA to 30.5mA.

"As-Found" Gross Fail High mA Data

c. IF "As-Found" data was NOT within the No Adjust Limits, REMOVE the trip unit to adjust R39. REINSTALL trip unit to repeat testing by decreasing transient current (AND, IF required, stable current) to obtain reset AND increasing to repeat testing of trip point. RECORD "As-Left" Gross Fail trip value.

"As-Left" Gross Fail High mA Data

d. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. ]
e. PUSH Gross Fail Reset buttons on Trip Units PIS-263-123B, PS-263-123B-1 AND VERIFY Gross Fail lights are OFF. [
f. CHANGE Transient Polarity switch to negative. []
g. DECREASE the stable current to approximately 5.OmA. [
h. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 3.5mA on readout assembly. [

8.M.1-29 Rev. 50 Page 116 of 152

ATTACHMENT 2 Sheet 37 of 70 Using Stable Current knob, SLOWLY DECREASE the reading until Gross Fail LED comes on. [I

j. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 2.5mA; No Adjust Limits are 3.OmA to 2.OmA.

"As-Found" Gross Fail Low mA Data

k. IF "As-Found" reading is NOT within No Adjust Limits, ADJUST R40.

INCREASE transient current (AND, IF required, stable current) to obtain reset AND DECREASE to repeat testing of trip point. RECORD "As-Left" Gross Fail trip value.

"As-Left" Gross Fail Low mA Data PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [I]

m. CHANGE Transient Polarity switch to positive position. [I]

(21) TURN the Stable Current knob fully counterclockwise. [I]

8.M.1-29 Rev. 50 Page 117 of 152

ATTACHMENT 2 Sheet 38 of 70

  • 1 CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

I (22) PULL OUT the Press To Cal knob (smaller knob) AND:

a. VERIFY that the CAL light is OFF.

Initials THEN

b. PUSH Gross Fail Reset buttons on Trip Units PIS-263-123B and PS-263-1i23B-1 AND VERIFY Gross Fail lights are OFF.

Initials THEN

c. ROTATE the Press To Cal knob (smaller knob) to the "OFF" position, THEN PUSH the knob back in.

Initials (23) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (24) IF required, HAVE Operations reset alarm(s). [I 8.M.1-29 Rev. 50 Page 118 of 152

ATTACHMENT 2 Sheet 39 of 70 NOTE If operating conditions have to be confirmed, the reading of meter under calibration should match the reading indicated by the three other channels of the same function within the ATWS System.

(25) VERIFY circuit supervisory lights have returned to their normal status (not bright).

a. DS3B at Panel C2278
b. DS4B at Panel C2278
c. DS5B at Panel C2278
d. DS3D at Panel C2278
e. DS4D at Panel C2278
f. DS5D at Panel C2278
g. DS10B at Panel C2278
h. DS11B at Panel C2278
i. DS10D at Panel C2278
j. DS11D at Panel C2278 Initials 8.M.1-29 Rev. 50 Page 119 of 152

ATTACHMENT 2 Sheet 40 of 70 (d) PS-263-123B-1 (1) VERIFY appropriate Prerequisites AND REVIEW appropriate Precautions and Limitations before proceeding further.

Initials CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

h (2) PULL OUT the Press To Cal knob (smaller knob) AND VERIFY that the CAL light is OFF.

Initials

a. SET larger knob to slot #4 for PS-263-123B-1. [I I
b. SET smaller knob to slot #3 for PIS-263-123. I]

(3) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (4) SELECT OR VERIFY SELECTED positive polarity with Transient Polarity Switch.

Initials (5) APPLY stable calibration current to PS-263-123B-1 by pushing in the smaller knob of the Press To Cal knob AND VERIFY the CAL light is ON at the calibration unit AND alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is ON. [I 8.M.1-29 Rev. 50 Page 120 of 152

ATTACHMENT 2 Sheet 41 of 70 (6) VERIFY the following:

a. Circuit supervisory lights are normal - not bright.
1. DS7B at Panel C2278 El
2. DS8B at Panel C2278 [1
3. DS9B at Panel C2278 [I Initials
b. Circuit supervisory lights are normal - not bright.
1. DS7D at Panel C2278 [1]
2. DS8D at Panel C2278 [1]
3. DS9D at Panel C2278 [1]

Initials

c. Relay K3B at Panel C2278 is DE-ENERGIZED.

Initials (7) VERIFY the Trip Status LED is OFF at the readout assembly (IF required, PUSH Trip Current Display Reset). [I 8.M.1-29 Rev. 50 Page 121 of 152

ATTCHENT 2 NOTE If setpoints are found outside the No Adjust Limits, test must be continued. The required adjustment will be made at the end of the test for each trip unit.

(8) INCREASE stable current until PS-263-123B-1 trips. RECORD the trip point as shown latched on the readout assembly. Setpoint is 18.93mA (1400 psig); No Adjust Limits are 18.91 to 18.95mA.

"As-Found" Trip mA Data (9) VERIFY Trip Status LED is ON:

a. At readout assembly. [I
b. At Trip Unit PS-263-123B-1.

Initials (10) VERIFY the following:

a. Relay K3B at Panel C2278 is ENERGIZED.

Initials

b. Circuit supervisory lights are OFF.
1. DS7B at Panel C2278 [1]
2. DS8B at Panel C2278 [I]
3. DS9B at Panel C2278 [I]

Initials 8.M.1-29 Rev. 50 Page 122 of 152

ATTACHMENT 2 Sheet 43 of 70

c. Circuit supervisory lights become bright.
1. DS7D at Panel C2278 [ ]
2. DS8D at Panel C2278 [ ]
3. DS9D at Panel C2278 [ ]

Initials (11) IF trip point was greater than 18.98mA (1405 psig), THEN NOTIFY SM.

SM notified? Yes [ ] No[

(12) PUSH the Trip Current Display Reset on the readout assembly AND VERIFY the Trip Status LED goes off. [ ]

(13) SLOWLY DECREASE current with the Stable Current knob until PS-263-123B-1 resets AND RECORD the reset point.

"As-Found" Reset mA Data (14) VERIFY Trip Status LED is:

a. ON at readout assembly. [
b. OFF at Trip Unit PS-263-123B-1.

Initials 8.M.1-29 Rev. 50 Page 123 of 152

ATTACHMENT 2 Sheet 44 of 70 (15) VERIFY the following:

a. Relay K3B at Panel C2278 is DE-ENERGIZED.

Initials

b. Circuit supervisory lights become normal - not bright.
1. DS7B at Panel C2278 [i]
2. DS8B at Panel C2278 [1]
3. DS9B at Panel C2278 [I]

Initials

c. Circuit supervisory lights become normal - not bright.
1. DS7D at Panel C2278 [I]
2. DS8D at Panel C2278 [I]
3. DS9D at Panel C2278 [I]

Initials (16) PUSH the Trip Current Display Reset AND VERIFY Trip Status LED goes off at the readout assembly. [I 8.M.1-29 Rev. 50 Page 124 of 152

ATTACHMENT 2 Sheet 45 of 70 NOTE The trip point adjustments are located on the front of the trip unit.

(17) IF trip did NOT fall within the No Adjust Limits, CALIBRATE AND RECORD "As-Left" data.

a. PS-263-123B-1 "As-Left" Trip 18.93mA (18.91 to 18.95mA) mA Data
b. PS-263-123B-1 "As-Left" Reset mA Data (18) TEST the Gross Failure function(s) by adjusting the stable current to approximately 18mA. [
a. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 29mA on readout assembly. [
b. Using Stable Current knob, SLOWLY INCREASE the reading until Gross Fail LED comes on. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 30.OmA; No Adjust Limits are 29.5mA to 30.5mA.

"As-Found" Gross Fail High mA Data

c. IF "As-Found" data was NOT within the No Adjust Limits, REMOVE the trip unit to adjust R39. REINSTALL trip unit to repeat testing by decreasing transient current (AND, IF required, stable current) to obtain reset AND increasing to repeat testing of trip point. RECORD "As-Left" Gross Fail trip value.

"As-Left" Gross Fail High mA Data

d. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [

8.M.1-29 Rev. 50 Page 125 of 152

ATTACHMENT 2 Sheet 46 of 70

e. PUSH Gross Fail Reset buttons on Trip Units PS-263-123B-1 and PIS-263-123B AND VERIFY Gross Fail lights are OFF. [ ]
f. CHANGE Transient Polarity switch to negative. [
g. DECREASE the stable current to approximately 5.OmA. [
h. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 3.5mA on readout assembly. [ ]
i. Using Stable Current knob, SLOWLY DECREASE the reading until Gross Fail LED comes on. [ ]
j. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 2.5mA; No Adjust Limits are 3.OmA to 2.OmA.

"As-Found" Gross Fail Low mA Data

k. IF "As-Found" reading is NOT within No Adjust Limits, ADJUST R40.

INCREASE transient current (AND, IF required, stable current) to obtain reset AND DECREASE to repeat testing of trip point. RECORD "As-Left" Gross Fail trip value.

"As-Left" Gross Fail Low mA Data

1. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [
m. CHANGE Transient Polarity switch to positive position. [1 (19) TURN the Stable Current knob fully counterclockwise. []

8.M.1-29 Rev. 50 Page 126 of 152

[TTACHENT2 Shet 7o 7 I

CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(20) PULL OUT the Press To Cal knob (smaller knob) AND:

a. VERIFY that the CAL light is OFF.

Initials THEN

b. PUSH Gross Fail Reset buttons on Trip Units PS-263-123B-1 and PIS-263-123B AND VERIFY Gross Fail lights are OFF.

Initials THEN

c. ROTATE the Press To Cal knob (smaller knob) to the "OFF" position, THEN PUSH the knob back in.

Initials (21) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (22) IF required, HAVE Operations reset alarm(s). [I 8.M.1-29 Rev. 50 Page 127 of 152

ATTACHMENT 2 Sheet 48 of 70 NOTE If operating conditions have to be confirmed, the reading of meter under calibration should match the reading indicated by the three other channels of the same function within the ATWS System.

(23) VERIFY circuit supervisory lights have returned to their normal status (not bright).

a. DS7B at Panel C2278 El
b. DS8B at Panel C2278 [I
c. DS9B at Panel C2278 [I
d. DS7D at Panel C2278 [ ]
e. DS8D at Panel C2278 [I]
f. DS9D at Panel C2278 [I]

Initials 8.M.1-29 Rev. 50 Page 128 of 152

ATTACHMENT 2 Sheet 49 of 70 (e) PIS-263-123D (1) VERIFY appropriate Prerequisites AND REVIEW appropriate Precautions and Limitations before proceeding further.

Initials CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

LI (2) PULL OUT the Press To Cal knob (smaller knob)

AND VERIFY that the CAL light is OFF.

Initials

a. SET larger knob to slot #5 for PIS-263-123D. [I
b. SET smaller knob to slot #5 for PIS-263-123D. [I (3) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (4) SELECT OR VERIFY SELECTED positive polarity with Transient Polarity Switch.

Initials (5) APPLY stable calibration current to PIS-263-123D by pushing in the smaller knob of the Press To Cal knob AND VERIFY the CAL light is ON at the calibration unit AND alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is ON. [I 8.M.1-29 Rev. 50 Page 129 of 152

ATTACHMENT 2 Sheet 50 of 70 (6) VERIFY the following:

a. Circuit supervisory lights are normal - not bright.
1. DS3D at Panel C2278 [ ]
2. DS4D at Panel C2278 [ ]
3. DS5D at Panel C2278 [ ]
4. DS10D at Panel C2278 [ I
5. DS11 D at Panel C2278 [ I Initials
b. Circuit supervisory lights are normal - not bright.
1. DS3B at Panel C2278 [ ]
2. DS4B at Panel C2278 [ ]
3. DS5B at Panel C2278 [ ]
4. DS10B at Panel C2278 [ I
5. DS 11 B at Panel C2278 [ I Initials
c. Relays are DE-ENERGIZED:
1. K2D at Panel C2278 Initials
2. K5D at Panel C2278 Initials (7) VERIFY the Trip Status LED is OFF at the readout assembly (IF required, PUSH Trip Current Display Reset). [1 8.M.1-29 Rev. 50 Page 130 of 152

ATTACHMENT 2 Sheet 51 of 70 NOTE If setpoints are found outside the No Adjust Limits, test must be continued. The required adjustment will be made at the end of the test for each trip unit.

(8) INCREASE the stable current AND RECORD the "As-Found" data for PIS-263-123D indicator.

Stable Current Reading Indicator Increasing mA Dsic "As-Found" 4.8 75 (30 to 120) 8.0 375 (330 to 420) 12.0 750 (705 to 795) 16.0 1125 (1080 to 1170) 19.2 1425 (1380 to 1470)

[ Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR

[ Calibration Required (9) RECORD the trip point as shown latched on the readout assembly. Setpoint is 16.53mA (1175 psig); No Adjust Limits are 16.51 to 16.55mA.

"As-Found" Trip mA Data (10) VERIFY Trip Status LED is ON:

a. At readout assembly. [I
b. At Trip Unit PIS-263-123D.

Initials 8.M.1-29 Rev. 50 Page 131 of 152

ATTACHMENT 2 Sheet 52 of 70 (11) VERIFY the following:

a. Relays are ENERGIZED:
1. K2D at Panel C2278 Initials
2. K5D at Panel C2278 Initials
b. Circuit supervisory lights are OFF.
1. DS3D at Panel C2278 [ ]
2. DS4D at Panel C2278 [
3. DS5D at Panel C2278 [
4. DS10D at Panel C2278 [ ]
5. DS11 D at Panel C2278 [ ]

Initials

c. Circuit supervisory lights become bright.
1. DS3B at Panel C2278 [
2. DS4B at Panel C2278 [
3. DS5B at Panel C2278 [ ]
4. DS10B at Panel C2278 [ ]
5. DS11B at Panel C2278 [ ]

Initials (12) IF trip point was less than 16.48mA (1170 psig)

OR, greater than 16.58mA (1180 psig), THEN NOTIFY SM.

SM notified? Yes[ ] No[ ]

8.M.1-29 Rev. 50 Page 132 of 152

ATTACHMENT 2 Sheet 53 of 70 (13) PUSH the Trip Current Display Reset on the readout assembly AND VERIFY the Trip Status LED goes off. [ ]

(14) SLOWLY DECREASE current with the Stable Current knob AND RECORD the "As-Found" data for PIS-263-123D indicator.

Stable Current Reading Indicator Decreasing mA psi "As-Found" 19.2 1425 (1380 to 1470) 16.0 1125 (1080 to 1170) 12.0 750 (705 to 795) 8.0 375 (330 to 420) 4.8 75 (30 to 120)

] Data falls within Acceptance Criteria, "As-Left" same as "As-Found" OR

] Calibration Required (15) RECORD the reset point as shown latched on readout assembly. Setpoint is 16.21 mA; No Adjust Limits are 16.05 to 16.37mA.

"As-Found" Reset mA Data (16) VERIFY Trip Status LED is:

a. ON at readout assembly. [ ]
b. OFF at Trip Unit PIS-263-123D.

Initials 8.M.1-29 Rev. 50 Page 133 of 152

ATTACHMENT 2 Sheet 54 of 70 (17) VERIFY the following:

a. Relays are DE-ENERGIZED:
1. K2D at Panel C2278 Initials
2. K5D at Panel C2278 Initials
b. Circuit supervisory lights become normal - not bright.
1. DS3D at Panel C2278 [ ]
2. DS4D at Panel C2278 [ ]
3. DS5D at Panel C2278 [ ]
4. DS10D at Panel C2278 [ ]
5. DS1 1D at Panel C2278 [ ]

Initials

c. Circuit supervisory lights become normal - not bright.
1. DS3B at Panel C2278 [ ]
2. DS4B at Panel C2278 [ ]
3. DS5B at Panel C2278 [ ]
4. DS10B at Panel C2278 [ ]
5. DS11B at Panel C2278 [ ]

Initials (18) PUSH the Trip Current Display Reset AND VERIFY Trip Status LED goes off at the readout assembly. [ ]

8.M.1-29 Rev. 50 Page 134 of 152

ATTACHMENT 2 Sheet 55 of 70 NOTE The trip point adjustments are located on the front of the trip unit.

(19) IF trip AND/OR indicator did NOT fall within I

the No Adjust Limits, THEN CALIBRATE AND RECORD "As-Left" data.

a. PIS-263-123D "As-Left" Trip 16.53mA (16.51 to 16.55mA) mA Data
b. PIS-263-123D "As-Left" Reset 16.21mA (16.05 to 16.37mA) mA Data
c. Indicator PIS-263-123D Current Desired Reading Reading "As-Left" mA psiQ Inc. Dec.

4.8 75 (30 to 120) 8.0 375 (330 to 420) 12.0 750 (705 to 795) 16.0 1125 (1080 to 1170) 19.2 1425 (1380 to 1470) 8.M.1-29 Rev. 50 Page 135 of 152

ATTACHMENT 2 Sheet 56 of 70 (20) TEST the Gross Failure function(s) by adjusting the stable current to approximately 18mA.

a. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 29mA on readout assembly.
b. Using Stable Current knob, SLOWLY INCREASE the reading until Gross Fail LED comes on. RECORD Gross Fail trip as read on the readout assembly.

Setpoint is 30.OmA; No Adjust Limits are 29.5mA to 30.5mA.

"As-Found" Gross Fail High mA Data

c. IF "As-Found" data was NOT within the No Adjust Limits, REMOVE the trip unit to adjust R39. REINSTALL trip unit to repeat testing by decreasing transient current (AND, IF required, stable current) to obtain reset AND increasing to repeat testing of trip point. RECORD "As-Left" Gross Fail trip value.

"As-Left" Gross Fail High mA Data

d. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [
e. PUSH Gross Fail Reset buttons on Trip Units PIS-263-123D and PS-263-123D-1 AND VERIFY Gross Fail lights are OFF. [
f. CHANGE Transient Polarity switch to negative. []
g. DECREASE the stable current to approximately 5.OmA. [
h. PUSH INTransient Current knob AND TURN CLOCKWISE to approximately 3.5mA on readout assembly. [

8.M.1-29 Rev. 50 Page 136 of 152

ATTACHMENT 2 Sheet 57 of 70 Using Stable Current knob, SLOWLY DECREASE the reading until Gross Fail LED comes on. [I

j. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 2.5mA; No Adjust Limits are 3.OmA to 2.OmA.

"As-Found" Gross Fail Low mA Data

k. IF "As-Found" reading is NOT within No Adjust Limits, ADJUST R40.

INCREASE transient current (AND, IF required, stable current) to obtain reset AND DECREASE to repeat testing of trip point. RECORD "As-Left" Gross Fail trip value.

"As-Left" Gross Fail Low mA Data I. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [I]

m. CHANGE Transient Polarity switch to positive position. [1]

(21) TURN the Stable Current knob fully counterclockwise. [I]

8.M.1-29 Rev. 50 Page 137 of 152

ATTACHMENT 2 Sheet 58 of 70 p I I CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

I (22) PULL OUT the Press To Cal knob (smaller knob) AND:

a. VERIFY that the CAL light is OFF.

Initials THEN

b. PUSH Gross Fail Reset buttons on Trip Units PIS-263-123D and PS-263-123D-1 AND VERIFY Gross Fail lights are OFF.

Initials THEN

c. ROTATE the Press To Cal knob (smaller knob) to the "OFF" position, THEN PUSH the knob back in.

Initials (23) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (24) IF required, HAVE Operations reset alarm(s). [I 8.M.1-29 Rev. 50 Page 138 of 152

ATTACHMENT 2 Sheet 59 of 70 NOTE If operating conditions have to be confirmed, the reading of meter under calibration should match the reading indicated by the three other channels of the same function within the ATWS System.

(25) VERIFY circuit supervisory lights have returned to their normal status (not bright).

a. DS3B at Panel C2278
b. DS4B at Panel C2278
c. DS5B at Panel C2278
d. DS3D at Panel C2278
e. DS4D at Panel C2278
f. DS5D at Panel C2278
g. DS10B at Panel C2278
h. DS11B at Panel C2278
i. DS10D at Panel C2278
j. DS11D at Panel C2278 Initials 8.M.1-29 Rev. 50 Page 139 of 152

ATTACHMENT 2 Sheet 60 of 70 (f) PS-263-123D-1 (1) VERIFY appropriate Prerequisites AND REVIEW appropriate Precautions and Limitations before proceeding further.

Initials CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(2) PULL OUT the Press To Cal knob (smaller knob) AND VERIFY that the CAL light is OFF.

Initials

a. SET larger knob to slot #6 for PS-263-123D-1. [I]
b. SET smaller knob to slot #5 for PIS-263-123D. [I]

(3) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (4) SELECT OR VERIFY SELECTED positive polarity with Transient Polarity Switch.

Initials 8.M.1-29 Rev. 50 Page 140 of 152

ATTACHMENT 2 Sheet 61 of 70 (5) APPLY stable calibration current to PS-263-123D-1 by pushing in the smaller knob of the Press To Cal knob AND VERIFY the CAL light is ON at the calibration unit AND alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is ON. [

(6) VERIFY the following:

a. Circuit supervisory lights are normal - not bright.
1. DS7D at Panel C2278 [ ]
2. DS8D at Panel C2278 [ ]
3. DS9D at Panel C2278 [ I Initials
b. Circuit supervisory lights are normal - not bright.
1. DS7B at Panel C2278 [ I
2. DS8B at Panel C2278 [ I
3. DS9B at Panel C2278 [ I Initials
c. Relay K3D at Panel C2278 is DE-ENERGIZED.

Initials (7) VERIFY the Trip Status LED is OFF at the readout assembly (IF required, PUSH Trip Current Display Reset). []

8.M.1-29 Rev. 50 Page 141 of 152

ATTACHMENT 2 Sheet 62 of 70 NOTE If setpoints are found outside the No Adjust Limits, test must be continued. The required adjustment will be made at the end of the test for each trip unit.

(8) INCREASE the stable current until PS-263-123D-1 trips. RECORD the trip point as shown latched on the readout assembly. Setpoint is 18.93mA (1400 psig); No Adjust Limits are 18.91 to 18.95mA.

"As-Found" Trip mA Data (9) VERIFY Trip Status LED is ON:

a. At readout assembly. I I
b. At Trip Unit PS-263-123D-1.

Initials 8.M.1-29 Rev. 50 Page 142 of 152

ATTACHMENT 2 Sheet 63 of 70 (10) VERIFY the following:

a. Relay K3D at Panel C2278 is ENERGIZED.

Initials

b. Circuit supervisory lights are OFF.
1. DS7D at Panel C2278 [ ]
2. DS8D at Panel C2278 [ ]
3. DS9D at Panel C2278 [ ]

Initials

c. Circuit supervisory lights become bright.
1. DS7B at Panel C2278 [ ]
2. DS8B at Panel C2278 [ ]
3. DS9B at Panel C2278 [ I Initials (11) IF trip point was greater than 18.98mA (1405 psig), THEN NOTIFY SM.

SM notified? Yes [ ] No [ I (12) PUSH the Trip Current Display Reset on the readout assembly AND VERIFY the Trip Status LED goes off. [ ]

(13) SLOWLY DECREASE current with the Stable Current knob until PS-263-123D-1 resets. RECORD the reset point.

"As-Found" Reset mA Data 8.M.1-29 Rev. 50 Page 143 of 152

ATTACHMENT 2 Sheet 64 of 70 (14) VERIFY Trip Status LED is:

a. ON at readout assembly. [
b. OFF at Trip Unit PS-263-123D-1.

Initials (15) VERIFY the following:

a. Relay K3D at Panel C2278 is DE-ENERGIZED.

Initials

b. Circuit supervisory lights become normal - not bright.
1. DS7D at Panel C2278 [ ]
2. DS8D at Panel C2278 [ ]
3. DS9D at Panel 02278 [ ]

Initials

c. Circuit supervisory lights become normal - not bright.
1. DS7B at Panel 02278 [
2. DS8B at Panel C2278 [ ]
3. DS9B at Panel 02278 [

Initials (16) PUSH the Trip Current Display Reset AND VERIFY Trip Status LED goes off at the readout assembly. [ ]

8.M.1-29 Rev. 50 Page 144 of 152

ATTACHMENT 2 Sheet 65 of 70 NOTE The trip point adjustments are located on the front of the trip unit.

(17) IF trip did NOT fall within the No Adjust Limits, CALIBRATE AND RECORD "As-Left" data.

a. PS-263-123D-1 "As-Left" Trip 18.93mA (18.91 to 18.95mA) mA Data
b. PS-263-123D-1 "As-Left" Reset mA Data (18) TEST the Gross Failure function(s) by adjusting the stable current to approximately 18mA.
a. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 29mA on readout assembly.
b. Using Stable Current knob, SLOWLY INCREASE the reading until Gross Fail LED comes on. RECORD Gross Fail trip as read on the readout assembly.

Setpoint is 30.0 mA; No Adjust Limits are 29.5mA to 30.5mA.

"As-Found" Gross Fail High mA Data

c. IF "As-Found" data was NOT within the No Adjust Limits, REMOVE the trip unit to adjust R39. REINSTALL trip unit to repeat testing by decreasing transient current (AND, IF required, stable current) to obtain reset AND increasing to repeat testing of trip point. RECORD "As-Left" Gross Fail Trip value.

"As-Left" Gross Fail High mA Data 8.M.1-29 Rev. 50 Page 145 of 152

ATTACHMENT 2 Sheet 66 of 70

d. PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [ ]
e. PUSH Gross Fail Reset buttons on Trip Units PS-263-123D-1 and PIS-263-123D AND VERIFY Gross Fail lights are OFF. [ ]
f. CHANGE Transient Polarity switch to negative. [ ]
g. DECREASE the stable current to approximately 5.OmA. [ ]
h. PUSH IN Transient Current knob AND TURN CLOCKWISE to approximately 3.5mA on readout assembly. [ I Using Stable Current knob, SLOWLY DECREASE the reading until Gross Fail LED comes on. [
j. RECORD Gross Fail trip as read on the readout assembly. Setpoint is 2.5mA; No Adjust Limits are 3.OmA to 2.OmA.

"As-Found" Gross Fail Low mA Data

k. IF "As-Found" reading is NOT with No Adjust Limits, ADJUST R40.

INCREASE transient current (AND, IF required, stable current) to obtain reset AND DECREASE to repeat testing of trip point. RECORD "As-Left" Gross Fail trip value.

"As-Left" Gross Fail Low mA Data PULL OUT Transient Current knob AND TURN FULLY COUNTERCLOCKWISE. [ ]

m. CHANGE Transient Polarity switch to positive position. [

(19) TURN the Stable Current knob fully counterclockwise. [

8.M.1-29 Rev. 50 Page 146 of 152

ATTACHMENT 2 Sheet 67 of 70 I

CAUTION SELECTOR SWITCH INTERLOCK VERIFICATION (Ref. PRO1.8151)

Rotation of the trip unit Calibration Selection knob (Press To Cal small knob) through the various positions must be performed at a speed that will allow for the verification of:

1. The CAL light does not light; AND
2. No unit gross failure alarm lights actuate; AND
3. The unit status indicating light remains green.

(20) PULL OUT the Press To Cal knob (smaller knob) AND:

a. VERIFY that the CAL light is OFF.

Initials THEN

b. PUSH Gross Fail Reset buttons on Trip Units PS-263-123D-1 and PIS-263-123D AND VERIFY Gross Fail lights are OFF.

Initials THEN

c. ROTATE the Press To Cal knob (smaller knob) to the "OFF" position, THEN PUSH the knob back in.

Initials (21) VERIFY alarm "DIVISION TWO PANEL TROUBLE" (C905L-F5) is CLEAR.

Initials (22) IF required, HAVE Operations reset alarm(s). [I I 8.M.1-29 Rev. 50 Page 147 of 152

ATTACHENT NOTE If operating conditions have to be confirmed, the reading of meter under calibration should match the reading indicated by the three other channels of the same function within the ATWS System.

(23) VERIFY circuit supervisory lights have returned to their normal status (not bright).

a. DS7D at Panel C2278 [I]
b. DS8D at Panel C2278 [I]
c. DS9D at Panel C2278 [ ]
d. DS7B at Panel C2278 [I]
e. DS8B at Panel C2278 [I]
f. DS9B at Panel C2278 [1]

Initials 8.M.1-29 Rev. 50 Page 148 of 152

ATTACHMENT 2 Sheet 69 of 70

[7] Return to Service (a) ROTATE the Press To Cal knob (larger knob) to "OFF" position. [I]

(b) TURN OFF power to the calibration unit. [: ]

(c) VERIFY the CAL light is OFF at the calibration unit. [ ]

(d) PUSH the Gross Fail Reset buttons. [1 (e) VERIFY the following:

(1) Gross Fail lights are OFF at Cabinet C2278.

Initials Verifier (2) 125V DC power light is ON.

Initials Verifier (f) PULL OUT readout assembly with extender card from Cabinet C2278.

Initials Verifier

[8] NOTIFY the on-shift SRO that test is complete. [: ]

[9] COMPLETE documentation AND UPDATE Maintenance records. [1]

[10] RECORD test equipment used:

M&TE # Due Date

[11] FILL OUT the I&C Procedure Feedback Form (Attachment 3)

AND FORWARD to I&C Supervision.

Initials 8.M.1-29 Rev. 50 Page 149 of 152

ATTACHMENT 2 Sheet 70 of 70 Discrepancies noted during surveillance performance:

Notes:

Date Completed:

[II Acceptance Criteria of Section 9.0 of the base document were met.

Maintenance Manaaement I:)ate On-Shift SRO Date Time Acceptance Criteria of Section 9.0 of the base document were not met. Notify the on-shift SRO.

Discrepancies:

Action taken:

Maint Management Date Time 8.M.1-29 Rev. 50 Page 150 of 152

ATTACHMENT 3 Sheet 1 of 1 I&C PROCEDURE FEEDBACK FORM Date:

Name (print):

[1] Were there any problems found while performing this Procedure:

YES LJ NO l (a) If YES, record problem(s) in Step [3] below.

[2] Are there any enhancements that need to be made to this Procedure:

YES j NO L (a) If YES, record step(s) to be enhanced and a description of the enhancement(s) in Step [3] below. Include Attachment number if applicable.

[3] Problem/Enhancement:

8.M.1-29 Rev. 50 Page 151 of 152

ATTACHMENT 4 Sheet 1 of 1 ALARM

SUMMARY

SHEET ATTACHMENT ALARM LOCATION 1 "DIVISION ONE PANEL TROUBLE" C905L-B5 2 "DIVISION TWO PANEL TROUBLE" C905L-F5 8.M.1-29 Rev. 50 Page 152 of 152

ENCLOSURE 2 To Entergy Letter No. 2.11.007 RE-TYPED TECHNCIAL SPECIFICATION AND BASES PAGES (14 Pages)

Pilgrim License Page 3 TS Page 2-1 TS Bases Page B2-4 TS Page 3/4.2-26 TS Page 3/4.2-28 TS Page 3/4.2-29 TS Bases Page B3/4.2-6 TS Page 3/4.5-7 TS Page 3/4.5-8 TS Bases Page B3/4.5-21 TS Page 3/4.6-6 TS Page 3/4.6-7 TS Bases Page B3/4.6-7 TS Bases Page B3/4.6-8

B. Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. , are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

C. Records ENO shall keep facility operating records in accordance with the requirements of the Technical Specifications.

D. Equalizer Valve Restriction - DELETED E. Recirculation Loop Inoperable - DELETED F. Fire Protection ENO shall implement and maintain in effect all provisions of the approved fire protection program as described in the Final Safety Analysis Report for the facility and as approved in the SER dated December 21, 1978 as supplemented subject to the following provision:

ENO may make changes to the approved fire protection program without prior approval of the Commission only if those changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.

G. Physical Protection The licensee shall fully implement and maintain in effect all provisions of the Commission-approved physical security, training and qualification, and safeguards contingency plans including amendments made pursuant to provisions of the Miscellaneous Amendments and Search Requirements revisions to 10 CFR 73.55 (51 FR27817 and 27822) and to the authority of 10 CFR 50.90 and 10 CFR 50.54(p). The combined set of plans, which contain Safeguards Information protected under 10 CFR 73.21, is entitled: "Pilgrim Nuclear Power Station Physical Security, Training and Qualification, and Safeguards Contingency Plan, Revision 0" submitted by letter dated October 13, 2004, as supplemented by letter dated May 15, 2006.

Amendment 225, 226, 227, 228, 229, 230, 234, 232, 233,

2.0 SAFETY LIMITS 2.1 Safety Limits 2.1.1 With the reactor steam dome pressure < 785 psig or core flow < 10% of rated core flow:

THERMAL POWER shall be < 25% of RATED THERMAL POWER.

2.1.2 With the reactor steam dome pressure > 785 psig and core flow > 10% of rated core flow:

MINIMUM CRITICAL POWER RATIO shall be > 1.08 for two recirculation loop operation or > 1.11 for single recirculation loop operation.

2.1.3 Whenever the reactor is in the cold shutdown condition with irradiated fuel in the reactor vessel, the water level shall not be less than 12 inches above the top of the normal active fuel zone.

2.1.4 Reactor steam dome pressure shall be < 1340 psig at any time when irradiated fuel is present in the reactor vessel.

2.2 Safety Limit Violation With any Safety Limit not met within two hours the following actions shall be met:

2.2.1 Restore compliance with all Safety Limits, and 2.2.2 Insert all insertable control rods.

Amendment No. 1, 27, 412, 72, 133, 146,171, 7 -- Q a2"2 ý22 2-1

BASES:

2.0 SAFETY LIMITS (Cont)

REACTOR STEAM The Safety Limit for the reactor steam dome pressure has DOME PRESSURE been selected such that it is at a pressure below which it can (2.1.4) be shown that the integrity of the reactor coolant system is not endangered. The reactor pressure limit of 1340 psig as measured in the vessel steam dome was derived from the design pressure of the reactor vessel. The peak pressures for the piping systems connected to the reactor vessel have been recalculated based on a reactor steam dome peak pressure of 1340 psig. These peak pressures are below the lowest of the transient pressures permitted by the applicable design code: ASME Boiler and Pressure Vessel (B&PV) Code (1965 Edition, including the January 1966 Addendum) for the pressure vessel, USAS Piping Code B31.1 for the steam space piping and ASME Section III for the reactor coolant system recirculation piping. The ASME B&PV Code permits pressure transients up to 10% over the design pressure (110% x1250=1 375 psig). The USAS Piping Code and ASME Section III permit pressure transients and other occasional loads whose combined effect do not exceed stress levels based on the duration of the loads and the applicable service limit.

REFERENCES 1) "General Electric Standard Application for Reactor Fuel,"

NEDE-2401 1-P-A (through the latest approved amendment at the time the reload analyses are performed as specified in the CORE OPERATING LIMITS REPORT).

2) General Electric Thermal Analysis Basis (GETAB): Data, Correlation and Design Application, General Electric Co. BWR Systems Department, January 1977, NEDE-10958-PA and NEDO-10958-A.
3) "Methodology & Uncertainties for SLMCPR Evaluations,"

NEDC-32601-P-A (August 1999).

4) "Power Distribution Uncertainties for Safety Limit MCPR Evaluations," NEDC-32694-P-A (August 1999).
5) "GE 11 Compliance with Amendment 22 of GESTAR I1,"

NEDE-31917P (April 1991).

6) "GE 14 Compliance with Amendment 22 of GESTAR I1,"

NEDC-32868P (December 1998).

7) "Pilgrim Nuclear Power Station Safety Valve Setpoint Increase," GE Hitachi Nuclear Energy Report, NEDC-33532P, Rev. 2 (January 2011)

Revision 22&-

B2-4

PNPS TABLE 3.2.F (Cont)

SURVEILLANCE INSTRUMENTATION Minimum # of Operable Instrument Parameter Type Indication Channels Instrument # and Range Notes TI-5021-2A Suppression Chamber Indicator/

TRU-5021-1A Water Temperature Multipoint Recorder (1) (2) (3) (4))

2 30-230'F (Bulk)

TI-5022-2B Suppression Chamber TRU-5022-1 B Water Temperature Indicator/

Multipoint Recorder (1) (2) (3) (4)30-230'F (Bulk) 1 PID-5021 Drywell/Torus Diff. Indicator - .25 - +3.0 psig (1) (2) (3) (4)

Pressure 1 PID-5067A Drywell Pressure Indicator -.25 - +3.0 psig (1) (2) (3) (4)

PID-5067B Torus Pressure Indicator -1.0 - +2.0 psig 1Naive (a) Primary Safety/Relief Valve a) Acoustic monitor (5) or Position b) Thermocouple (b) Backup INalve (a) Primary Safety Valve Position a) Acoustic monitor (5) or Indicator b) Thermocouple (b) Backup LI-1001-604A Torus Water Level Indicator /Multipoint (1) (2) (3) (4) I 2 LR- 1001-604A (Wide Range) Recorder 0 - 300"H2 0 LI-1001- 604B LR-1001- 604B Torus Water Level Indicator /Multipoint (1) (2) (3) (4)

(Wide Range) Recorder 0 - 300"H2 0 Amendment No. *66,83,4723, 314.2-26

NOTES FOR TABLE 3.2.F (1) With less than the minimum number of instrument channels, restore the inoperable channel(s) within 30 days.

(2) With the instrument channel(s) providing no indication to the control room, restore the indication to the control room within seven days.

(3) If the requirements of notes (1) or (2) cannot be met, an orderly shutdown shall be initiated and the reactor shall be in the Cold Shutdown Condition within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

(4) These surveillance instruments are considered to be redundant to each other.

(5) At a minimum, the primary or backup parameter indicators shall be operable for each valve when the valves are required to be operable. With both primary and backup instrument channels inoperable either return one (1) channel to operable status within 31 days or be in a shutdown mode within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

The following instruments are associated with the safety/relief and safety valves:

Primary Backup Valve Acoustic Monitor Tail Pipe Temperature Thermocouple 203-3A ZT-203-3A TE6285 203-3B ZT-203-3B TE6286 203-3C ZT-203-3C TE6287 203-3D ZT-203-3D TE6288 203-4A ZT-203-4A TE6274-B 203-4B ZT-203-4B TE6275-B (6) Deleted.

(7) With less than the minimum number of operable instrument channels, restore the inoperable channels to operable status within 7 days or prepare and submit a special report to the Commission within 14 days of the event outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the channels to operable status.

Amendment No. 489, 83, 103, 3/4.2-28

PNPS TABLE 3.2-G INSTRUMENTATION THAT INITIATES RECIRCULATION PUMP TRIP AND ALTERNATE ROD INSERTION Minimum Number of Operable or Tripped Instrument Channels Per Trip Svstem (1) TriD Function Trio Level Settina 2 High Reactor Dome <1210 psig Pressure 2 Low-Low Reactor i t-46.3" Water Level indicated level Actions (1) There shall be two (2) operable trip systems for each function.

(a) If the minimum number of operable or tripped instrument channels for one (1) trip system cannot be met, restore the trip system to operable status within 14 days or be in at least hot shutdown within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

(b) If the minimum operability conditions (1 .a) cannot be met for both (2) trip systems, be in at least hot shutdown within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Amendment No. 42, 62,1056,1 1, 3/4.2-29

BASES:

3.2 PROTECTIVE INSTRUMENTATION (Cont)

The recirculation pump trip/alternate rod insertion systems are consistent with the "Monticello RPT/ARI" design described in NEDO-25016 (Reference 1) as referenced by the NRC as an acceptable design (Reference 2) for RPT. Reference 1 provides both system descriptions and performance analyses. The pump trip is provided to minimize reactor pressure in the highly unlikely event of a plant transient coincident with the failure of all control rods to scram. The rapid flow reduction increases core voiding providing a negative reactivity feedback. High pressure sensors and low water level sensors initiate the trip. The recirculation pump trip is only required at high reactor power levels, where the safety/relief valves have insufficient capacity to relieve the steam which continues to be generated in this unlikely postulated event. Requiring the trip to be operable only when in the RUN mode is therefore conservative. The low water level trip function includes a time delay of nine (9) seconds +/- one (1) second to avoid increasing the consequences of a postulated LOCA. This delay has an insignificant effect on ATWS consequences. Additional analysis of the ARI/RPT Setpoint for High Reactor Dome Pressure is identified in Reference 3.

Alternate rod insertion utlizes the same initiation logic and functions as RPT and provides a diverse means of initiating a reactor scram. ARI uses sensors diverse from the reactor protection system to depressurize the scram pilot air header, which in turn causes all control rods to be inserted.

References

1. NEDO-25016, "Evaluation of Anticipated Transients Without Scram for the Monticello Nuclear Generating Plant," September 1976.
2. NUREG-0460, Volume 3, December 1978.
3. "Pilgrim Nuclear Power Station Safety Valve Setpoint Increase," GE Hitachi Nuclear Energy Report, NEDC-33532P, Rev. 2, January 2011.

Drywell Temperature The drywell temperature limitations of Specification 3.2.H.1 ensure that safety related equipment will not be subjected to excess temperature. Exposure to excessive temperatures may degrade equipment and can cause loss of its operability.

The temperature elements for monitoring drywell temperature specified in Table 3.2.H were chosen on the basis of their reliability, location, and their redundancy (dual -

element RTD's). These temperature elements are the primary elements used for the PCILRT.

The "nominal instrument elevations" provided in Tables 3.2.H and 4.2.H assist personnel in locating the instruments for surveillance and maintenance purposes and define the approximate containment region to be monitored. The "nominal instrument elevations" are not intended to provide a precise instrument location.

Revision 4 B3/4.2-6

LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.5 CORE AND CONTAINMENT COOLING 4.5 CORE AND CONTAINMENT COOLING SYSTEMS SYSTEMS C. HPCI System C. HPCI System

1. The HPCI system shall be operable 1. HPCI system testing shall be as follows:

whenever there is irradiated fuel in the reactor vessel, reactor pressure a. Simulated Once/

is greater than 150 psig., and Automatic Operating reactor coolant temperature is Actuation Cycle greater than 3650F, except as Test specified in 3.5.C.2 below. Note ---------- ---

Not required to be performed until 12

2. From and after the date that the hours after reactor steam pressure and HPCI system is made or found to be flow are adequate to perform test.

inoperable for any reason, continued reactor operation is permissible only b. Pump When tested during the succeeding 14 days Operability as specified in unless such system is sooner made 3.13, verify with operable, providing that during such reactor pressure 14 days all active components of the <1035 and a 940 ADS system, the RCIC system, the psig, the HPCI LPCI system and both core spray pump can develop systems are operable. a flow rate > 4250 gpm against a

3. If the requirements of 3.5.C cannot system head be met, an orderly shutdown of the corresponding to reactor shall be initiated and the reactor pressure.

reactor shall be in the Cold Shutdown Condition within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. c. Motor Operated As Specified Valve Operability in 3.13


Note ----------

Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after reactor steam pressure and flow are adequate to perform test.

d. Flow Rate at Once/

150 psig. Operating Cycle, verify with reactor pressure 5 150 psig, the HPCI pump can develop a flow rate > 4250 gpm against a system head corresponding to reactor pressure.

Amendment No. 4735 3/4.5-7

LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.5 CORE AND CONTAINMENT COOLING 4.5 CORE AND CONTAINMENT COOLING SYSTEMS SYSTEMS D. Reactor Core Isolation Coolinq D. Reactor Core Isolation Cooling (RCIC)

(RCIC) System System

1. The RCIC system shall be operable 1. RCIC system testing shall be as follows:

whenever there is irradiated fuel in the reactor vessel, reactor pressure a. Simulated Once/

is greater than 150 psig, and reactor Automatic Operating coolant temperature is greater than Actuation Test Cycle 3650F, except as specified in 3.5.D.2 below. Note ------------------ --.------

Not required to be performed until 12

2. From and after the date that the hours after reactor steam pressure and RCIC system is made or found to be flow are adequate to perform test.

inoperable for any reason, continued reactor operation is permissible only during the succeeding 14 days b. Pump When tested as unless such system is sooner made Operability specified in operable, providing that during such 3.13, verify with 14 days the HPCIS is operable. reactor pressure <

1035 and a 940

3. If the requirements of 3.5.D cannot psig, the RCIC be met, an orderly shutdown of the pump can develop reactor shall be initiated and the a flow rate a 400 reactor shall be in the Cold gpm against a Shutdown Condition within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. system head corresponding to reactor pressure.
c. Motor Operability As Specified Valve Operability in 3.13

Note ------------------

Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after reactor steam pressure and flow are adequate to perform test.

d. Flow Rate at Once/Operability 150 psig. Cycle verify with reactor pressure 5 150 psig, the RCIC pump can develop a flow rate a 400 gpm against a system head corresponding to reactor pressure.

Amendment No.-3/ 3/4.5-8

HPCI System B 314.5.E B 3/4.5 CORE AND CONTAINMENT COOLING SYSTEMS 3/4.5.E Automatic Depressurization (ADS) System BASES BACKGROUND This specification ensures the operability of the ADS under all conditions for which the automatic or manual depressurization of the nuclear system is an essential response to station abnormalities.

The nuclear system pressure relief system provides automatic nuclear system depressurization for small breaks in the nuclear system so that the low pressure coolant injection (LPCI) and the core spray systems can operate to protect the fuel barrier.

Because the Automatic Depressurization System does not provide makeup to the reactor primary vessel, no credit is taken for the steam cooling of the core caused by the system actuation to provide further conservatism to the CSCS. Performance analysis of the Automatic Depressurization System is considered only with respect to its depressurizing effect in conjunction with LPCI or Core Spray. There are four valves provided and each has a capacity of 921,235 lb/hr at a reactor pressure of 1155 psig. I APPLICABLE The limiting conditions for operating the ADS are derived from the SAFETY Station Nuclear Safety Operational Analysis (FSAR Appendix G) and a ANALYSIS detailed functional analysis of the ADS (FSAR Section 6).

ACTIONS The allowable out of service time for one ADS valve is determined as 14 days because of the redundancy and because of HPCI operability; therefore, redundant protection for the core with a small break in the nuclear system is still available.

SURVEILLANCES The testing interval for the core and containment cooling systems is based on industry practice, quantitative reliability analysis, judgment and practicality. The core cooling systems have not been designed to be fully testable during operation. For example, complete ADS testing during power operation causes an undesirable loss-of-coolant inventory. When components are tested and found inoperable the impact on system operability is determined, and corrective action or Limiting Conditions of Operation are initiated. A simulated automatic actuation test once each cycle combined with code inservice testing of the pumps and valves Is deemed to be adequate testing of these systems. The ADS test circuit permits continued surveillance on the operable relief valves to assure that they will be available if required.

The surveillance requirements provide adequate assurance that the core and containment cooling systems will be operable when required.

Revision 2402, 269T 133/4.5-21

LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.6 PRIMARY SYSTEM BOUNDARY (Cont) 4.6 PRIMARY SYSTEM BOUNDARY (Cont)

c. With no required leakage detection systems Operable, be in Hot Shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in Cold Shutdown within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

D. Safety and Relief Valves D. Safety and Relief Valves

1. During reactor power operating conditions and prior to reactor startup 1. As specified in accordance with 3.13, from a Cold Condition, or whenever verify the safety function lift setpoints reactor coolant pressure is greater of the safety and relief valves as than 104 psig and temperature follows:

greater than 3400 F, both safety valves and the safety modes of all No. of S/R Valves Setpoint (osia)

I relief valves shall be operable. 2 Safety 4 Relief 1280 +/- 38.4 1155 +/- 34.6

2. If Specification 3.6.D.1 is not met, an orderly shutdown shall be initiated Following testing, lift setting shall be and the reactor coolant pressure within +/- 1%.

shall be below 104 psig within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. ----------------- Note -------------------

Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after reactor steam pressure and flow are adequate to perform test.

2. Once/ Operating Cycle, verify each relief valve opens when manually actuated.

Amendment No. 42, §66, 88, 133, 130, 140, 222, aar- /46-3/4.6-6

LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.6 PRIMARY SYSTEM BOUNDARY (Cont) 4.6 PRIMARY SYSTEM BOUNDARY (Cont)

E. Jet Pumps E. Jet Pumps

1. Whenever the reactor is in the Startup or Run Modes, all jet pumps shall be NOTES
1. Not required to be performed until 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> Operable. If it is determined that a jet pump is inoperable, the reactor shall be after the associated recirculation loop is in in Hot Shutdown within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. operation.
2. Not required to be performed until 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after >25% Rated Thermal Power.

Whenever there is recirculation flow with the reactor in the Startup or Run Modes, jet pump operability shall be checked daily by verifying at least one of the following criteria (1, 2, or 3) is satisfied for each operating recirculation loop:

1. Recirculation pump flow to speed ratio differs by : 5% from established patterns, and jet pump loop flow to recirculation pump speed ratio differs by s 5% from established patterns.
2. Each jet pump diffuser to lower plenum differential pressure differs by 5 20% from established patterns.
3. Each jet pump flow differs by 5 10% from established patterns.

Amendment No. 5,556, 71. 93. 133. 205. 24-, 222,3 3/'4.6-7

BASES:

3/4.6 PRIMARY SYSTEM BOUNDARY (Cont)

C. Coolant Leakage (Cont)

The 2 gpm limit for unidentified coolant leakage rate increase within any 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> period is a limit specified by the NRC in Generic Letter 88-01: "NRC Position on IGSCC in BWR Austenitic Stainless Steel Piping". This limit applies only during the RUN mode to accommodate the expected coolant leakage increase during pressurization.

The total leakage rate consists of all leakage, which flows to the drywell equipment drain sump (Identified leakage) and floor drain sump (Unidentified leakage).

In addition to the sump monitoring of coolant leakage, airborne radioactivity levels of the drywell atmosphere is monitored by the Reactor Pressure Boundary Leak Detection System. This system consists of two panels capable of monitoring the primary containment atmosphere for particulate and gaseous radioactivity as a result of coolant leaks D. Safety and Relief Valves The valve sizing analysis considered four relief/safety valves and two safety valves. The set pressures are established in accordance with the following three requirements of Section III of the ASME Code:

1. The lowest safety valve must be set to open at or below vessel design pressure and the highest safety valve be set at or below 105% of design pressure.
2. The valves must limit the reactor vessel pressure to no more than 110% of design pressure. 1
3. Protection systems directly related to the valve sizing transient must not be credited with action (i.e., an indirect scram must be assumed).

Revision 1-&, 4-7-7, 24,0 269, 2-74, B3/4.6- 7

BASES:

3/4.6 PRIMARY SYSTEM BOUNDARY (Cont)

D. Safety and Relief Valves (Cont)

A main steam line isolation with flux scram has been selected to be used as the safety valve sizing transient since this transient results in the highest peak vessel pressure of any transient when analyzed with an indirect scram. The original FSAR analysis concluded that the peak pressure transient with indirect scram would be caused by a loss of condenser vacuum (turbine trip with failure of the bypass valves to open). However, later observations have shown that the long lengths of steam lines to the turbine buffer the faster stop valve closure isolation and thereby reduce the peak pressure caused by this transient to a value below that produced by a main steam line isolation with flux scram.

Item 3 above indicates that no credit be taken for the primary scram signal generated by closure of the main steam isolation valves. Two other scram initiation signals would be generated, one due to high neutron flux and one due to high reactor pressure. Thus item 3 will be satisfied by assuming a scram due to high neutron flux.

Relieving capacity of 4 relief/safety valves in combination with 2 safety valves results in a peak pressure during the transient conditions used in the safety valve sizing analysis which is well below the pressure safety limit.

The relief/safety valve settings satisfy the Code requirements that the lowest safety valve set point be at or below the vessel design pressure range to prevent unnecessary cycling caused by minor transients. The results of postulated transients where inherent relief/safety valve actuation is required are identified or referenced in the Updated Final Safety Analysis Report.

Experience in safety valve operation shows that a testing of at least 50% of the safety valves per refueling outage is adequate to detect failures or deterioration. The tolerance value of t 3%

is in accordance with Section III of the ASME Boiler and Pressure Vessel Code. An analysis has been performed which shows that with all safety valves set 3% higher, the reactor coolant system pressure safety limit of 1375 psig is not exceeded.

The relief/safety valves have two functions; i.e., power relief or self-actuated by high pressure.

Power relief is a solenoid actuated function (Automatic Pressure Relief) in which external instrumentation signals of coincident high drywell pressure and low-low water level initiate the valves to open. This function is discussed in Specification 3.5.E. In addition, the valves can be operated manually.

Revision 446, 1-77, 269, 2-74, B3/4.6-8